RPU

132 kV Panther 37/3 0.000866000


Zebra 61/3.18 0.000144000
220 kV Single Moose 61/3.53 0.000126415
Twin Moose 0.000063591
Twin Moose 0.000019300
400 kV
Quad Moose 0.000009133
220 kV XLPE Cable 1000Sqmm 0.000048760
132 kV XLPE Cable 630Sqmm 0.000270000
LENGTH PARAMETERS CALCULATION
132 kV Panther 52.640 0.04558624
Zebra 38.200 0.00550080
220 kV Single Moose 0.100 0.00001264
Twin Moose 50.000 0.00317957
Twin Moose 64.700 0.00124871
400 kV
Quad Moose 50.000 0.00045665
XPU YPU
0.002303100 0.000498200
0.000822000 0.00141
0.000824900 0.00142
0.000581900 0.00198
0.000204400 0.005528000
0.000156836 0.007396512
0.000386000 0.026000000
0.001113400 0.009800000
PARAMETERS CALCULATIONS
0.12123518 0.02622525
0.03140040 0.05386200
0.00008249 0.00014200
0.02909500 0.09900000
0.01322468 0.35766160
0.00784180 0.36982560
Conductor Temperature Voltage Temperature Ampacity MVA MVA MW
Operating of Conductor for max with 10 %
in kV (Max) conductor for Max Margin for Max
temp(centi)at conductor conductor
45 deg ambient temp(cen temp(cen
ti) ti)with
0.95pf

ACSR Panther 132 75 366 84 75 79


ACSR Zebra 220 75 560 213 192 203
ACSR Moose 220 75 631 240 216 228
ACSR Twin Moose 220 75 1262 481 433 457
ACSR Twin Moose 400 75 1262 874 787 831
ACSR Quad Moose 400 75 2524 1749 1574 1661
ACSR Quad Bersimis 400 75 2928 2029 1826 1927
ACSR Quad Bersimis 765 75 2928 3880 3492 3686
Hexa Zeebra 765 75 3360 4452 4007 4229

As per transmission planning criteria


1)10.2.2 power factor was taken as 0.95 during peak load and 0.98 during light load

2)13.3 Kept a margin of 10% in Thermal Loading limits

5.3 voltage limits in KV as per CEA Transmission Planning criteria


Normal rating Emergency rating After planning margins
Nominal Max Min Max Min Max
765 800 728 800 713 785
400 420 380 420 372 412
220 245 198 245 194 240
132 145 122 145 119 142

11.6 Reactive power limits


Normal condition At Planning Stage
Q max Q min Q max Q min
Thermal 60% of P ma (-) 50% of Qma 50% of P max (-) 10% of Qmax
Nuclear 60% of P ma (-) 50% of Qma 50% of P max (-) 10% of Qmax
Hydel 48% of P ma (-) 50% of Qma 40% of P max (-) 20% of Qmax

15.2 Maximum short circuit level at any SS


Voltage level in KV Rated breaking capacity in KA
132 25 / 31.5
220 31.5 / 40
400 50 / 63
765 40 / 50

15.4 The Capacity of any substation at different voltage levels shall not normally exceedthe following limit
Voltage level in KV Maximum Capacity in MVA
765 9000
400 2000
220 500
132 250
MW MW MVA
with with with
90% 110% as 110% as
loading as upper upper
lower loading loading
limit limit limit

72 87 92
182 222 235
206 251 264
411 502 529
748 913 962
1495 1827 1923
1734 2119 2231
3317 4054 4267
3806 4652 4897

After planning margins


Min
745
388
203
125

owing limit