The interposin CTs are used for Power transformer Differential Protection circuit.

In a delta/Star
Power tranformer, the cts will be connected star and delta formation, for eliminating Zero
seqence current on star side.There will be mismatch of secondary current , to maintain
equilibrium, interposing Cts will be connected to Delta formed CTs.

But now a days for numerical relays these interposing CTs are not used and current mismatch
is offset in software settings of numerical relays.