Selection Guide

I/O Wiring Conversion Systems


PLC-5 1771 to ControlLogix 1756
I/O Wiring Conversion Systems

What’s Inside
Topic Page
Product Selection 3
Approximate Dimensions 11
Wiring Diagrams - Digital Inputs 19
Wiring Diagrams - Digital Outputs 47
Wiring Diagrams - Analog Inputs and Outputs 77
Wiring Diagrams - High Resolution Isolated Analog 103

Summary of Changes
This publication contains new and updated information as indicated in the following table.

Topic Page
Analog Inputs and Outputs Product Selection - added new options for 1771-IL, 7
1771-OFE1 and 1771-OFE2 conversions
1771-N High Resolution Isolated Analog I/O Modules - New conversion options in 8
standard and combination

2 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Product Selection

1771 I/O to 1756 I/O Conversion Modules


I/O Conversion Modules provide a fast and efficient method for converting 1771
PLC-5 I/O to 1756 ControlLogix I/O. The I/O conversion is accomplished without
removing any field wires from the existing swing arm, virtually removing the risk of
wiring errors. The existing swing arms fit directly onto the edge connector of the
conversion modules.

The cables are pre-wired and have a connector for the conversion module on one
end and a removable terminal block (RTB) on the other end. The I/O signals are
routed through the conversion module and the cable to the appropriate terminals
on the I/O module.

The I/O Conversion System includes:


• Conversion Modules (Ex: Cat No: 1492-CM1771-LD001)
• Cables (Ex: Cat No: 1492-CONACAB005X)
• Conversion Mounting Assembly (Ex: Cat No: 1492-MUA4-A13-A17)

Conversion Modules, Cables, and Mounting Assemblies

Conversion Modules Pre-wired Cables, 25-pin Pre-wired Cables, 37-pin

Base Plate Cover Plate


The Conversion Modules are housed in a Conversion Mounting Assembly Base Plate. The Conversion Mounting Assembly Cover Plate covers and helps protect
This base plate has the same footprint and mounting holes as the 1771 chassis. There is no the Conversion Modules while providing a place to mount the new 1756 chassis. The Cover
need to drill and tap new mounting holes in the control cabinet. Plate has pre-drilled and tapped mounting holes allowing the new 1756 chassis to be
mounted in several locations – centered, right-justified or left-justified. There is no need to
drill and tap new mounting holes in the control cabinet.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 3


Product Selection

Conversion Mounting Assembly Selection


Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see table below, a complete System
Installation Manual is included with each assembly. Use the following steps to select the proper conversion mounting
assembly:

1. Determine the quantity of each type of 1771 I/O modules used in the I/O chassis to be converted.
2. From the table below:
a. Select the applicable 1492 conversion modules
b. Review the Max Slots for I/O and Chassis Width data from the table below
c. Select a 1756 I/O chassis which has enough I/O slots. Two I/O slots are required in the 1756 chassis for conversions
where one 1771 I/O module converts to two 1756 I/O modules.
d. Select the conversion mounting assembly which has enough conversion module slots.
(2) conversion module slots are required in the conversion mounting assembly for conversions where (2) 1771 I/O
modules convert to (1) 1756 I/O modules.

The combined depth of the conversion mounting assembly with the 1756 chassis mounted on top is 10.25 inches (controller
w/key) or 10.0 inches (controller w/o key). Dimension drawings are included in the System Installation Manual that ships with
the Assembly.

Chassis Dimensions and Max Slot Information


1771 Chassis 1756 Chassis Conversion Mounting Assembly
Chassis Width(2)
in (mm)
Without With Chassis Max Slots for
Max Slots Power Power Max Slots Width Conversion Chassis Width
Cat. No. for I/O Supply Supply Cat. No. for I/O in (mm) Cat. No. Modules in (mm)
1756-A4 3 10.35 (263)
1771-A1B 4 9.01 (229) 12.61 (320) 1492-MUA1B-A4-A7 4 9.01 (229)
1756-A7 6 14.49 (368)

1756-A7 6 14.49 (368)


1771-A2B 8 14.01 (356) 17.61 (447) 1492-MUA2B-A7-A10 8 14.01 (356)
1756-A10 9 19.02 (483)

1756-A10 9 19.02 (483)


1771-A3B1(1) 12 19.01 (483) 1492-MUA3B-A10-A13 12 19.01 (483)
1756-A13 12 23.15 (588)

1756-A13 12 23.15 (588)


1771-A4B 16 24.01 (610) 1492-MUA4-A13-A17 16 24.01 (610)
1756-A17 16 29.06 (738)
(1) 1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.

(2) Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left
justified, Right justified or Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.

4 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Product Selection

Digital Inputs
1. Column 1: find the Catalog Number of the 1771 Module you are converting from.
2. Column 2: find the Catalog Number of the compatible 1756 Module you are converting to. In some cases more than
one module exists. Review the matrix carefully and review the I/O module Installation Manuals to determine full
compatibility.
3. Column 3: find the Conversion Module catalog number and order quantity.
4. Column 4: find the Conversion Cable catalog number and order quantity.
1 2 3 4 5
Converting From Converting to Conversion Module Conversion Cable(3) Wiring Diagram
1771 Module(1) Qty. 1756 Module Qty. Cat. No. Order Cat. No. Order Page
1771-IA 2 1756-IA16 1 1492-CM1771-LD007 2 1492-C005005XE 1 19
1771-IA2 2 1756-IA16 1 1492-CM1771-LD007 2 1492-C005005XE 1 19
1771-IAD 1 1756-IA16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 20
1771-IAD 1 1756-IH16I 1 1492-CM1771-LD002 1 1492-CONCAB005Y 1 21
1771-IAN 1 1756-IA32 1 1492-CM1771-LD003 1 1492-CONCAB005Z 1 22
1771-IB 2 1756-IB16 1 1492-CM1771-LD007 2 1492-C005005XE 1 23
1771-IBD 1 1756-IB16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 24
1771-IBN 1 1756-IB32 1 1492-CM1771-LD003 1 1492-CONCAB005Z 1 25
1771-IC 2 1756-IC16 1 1492-CM1771-LD007 2 1492-C005005XE 1 26
1771-ICD 1 1756-IC16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 27
1771-ID 2 1756-IA16I 1 1492-CM1771-LD012 2 1492-C005005XL 1 28
1771-ID01 2 1756-IM16I 1 1492-CM1771-LD012 2 1492-C005005XL 1 29
1771-ID16 1 1756-IA16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1 30
1771-ID16 1 1756-IH16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1 31
1771-IG 2 1756-IG16 1 1492-CM1771-LA003(2) 2 1492-C005005XS 1 32
1771-IGD 1 1756-IG16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 33
1771-IH 2 1756-IC16 1 1492-CM1771-LD007 2 1492-C005005XE 1 34
1771-IM 2 1756-IM16I 1 1492-CM1771-LD007 2 1492-C005005XH 1 35
1771-IMD 1 1756-IM16I 1 1492-CM1771-LD002 1 1492-CONCAB005Y 1 36
1771-IN 2 1756-IN16 1 1492-CM1771-LD007 2 1492-C005005XE 1 37
1771-IND 1 1756-IN16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 38
1771-IND1 1 1756-IN16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 39
1771-IQ 2 1756-IB16I 1 1492-CM1771-LD007 2 1492-C005005XK 1 40
1771-IQ 2 1756-IB16I 1 1492-CM1771-LD014 2 1492-C005005XJ 1 41
1771-IQ16 1 1756-IB16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1 42
1771-IT 2 1756-IB16 1 1492-CM1771-LD007 2 1492-C005005XE 1 43
1771-IV 2 1756-IV16 1 1492-CM1771-LD014 2 1492-C005005XG 1 44
1771-IVN 1 1756-IV32 1 1492-CM1771-LD005 1 1492-CONCAB005Z 1 45
(1) To understand any issues concerning I/O module compatibility refer to the conversion module wiring diagrams and the Installation Manuals for the specific I/O modules involved (with particular attention to the
specification and wiring instructions).

(2) These 1771 Digital I/O Modules use a Swing Arm that only mounts to these Analog I/O Conversion Modules, which will therefore be used to provide for these 1771 Digital I/O conversions.
(3) The 005 in the Cat. No. indicates cable length of the 1492 cable. The recommended length of 0.5 M is listed, additional lengths are listed below.

1.0M Cable = 1492-CONCAB010_, 1.0M/1.0M Cable= 1492-C010010X_,0.5M/1.0M Cable = 1492-C005010X_,1.0M/0.5M Cable = 1492-C010005X_

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 5


Product Selection

Digital Outputs
1. Column 1: find the catalog number of the 1771Module you are converting from.
2. Column 2: find the catalog number of the compatible 1756 Module you are converting to.
In some cases more than one module exists. Review the matrix carefully and review the I/O module Installation Manuals to
determine full compatibility.
3. Column 3: find the catalog number of the Conversion Module.
4. Column 4: find the catalog number of the Conversion Cable.

1 2 3 4 5
Converting from 1771 Module(1) Converting to 1756 Module Conversion Module Conversion Cable (4)
Wiring Diagram
Cat. No. Qty. Cat. No. Qty.(2) Cat. No. (3) Order Qty. Cat. No. Order Qty. Page
1771-OA 1 1756-OA8E 1 1492-CM1771-LD014 1 1492-CONCAB005U 1 47
1771-OAD 1 1756-OA16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 48
1771-OAN 1 1756-OA16 2 1492-CM1771-LD013 1 1492-CONCAB005S3 1 49
1771-OB 2 1756-OB16D 1 1492-CM1771-LD014 2 1492-C005005XF 1 50
1771-OBD 1 1756-OB16E 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 51
1771-OBD 1 1756-OC8 2 1492-CM1771-LD008F 1 1492-CONCAB005S1 1 52
1771-OBDS 1 1756-OB16E 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 53
1771-OBN 1 1756-OB32 1 1492-CM1771-LD009F 1 1492-CONCAB005Z 1 54
1771-OC 1 1756-OC8 1 1492-CM1771-LD014 1 1492-CONCAB005V 1 55
1771-OD 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XM 1 56
1771-OD16 1 1756-OA16I 1 1492-CM1771-LD010F 1 1492-CONCAB005Y 1 57
1771-ODD 1 1756-OA16I 1 1492-CM1771-LD010F 1 1492-CONCAB005Y 1 58
1771-ODZ 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XP 1 59
1771-OG 2 1756-OG16 2 1492-CM1771-LA003 2 1492-C005005XS 1 60
1771-OGD 1 1756-OG16 2 1492-CM1771-LD006 1 1492-CONCAB005X 1 61
1771-OM 2 1756-OA16 1 1492-CM1771-LD014 2 1492-C005005XG 1 62
1771-OMD 1 1756-OA16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 63
1771-ON 1 1756-ON8 1 1492-CM1771-LD014 1 1492-CONCAB005W 1 64
1771-OND 1 1756-ON8 2 1492-CM1771-LD006 1 1492-CONCAB005S2 1 65
1771-OQ 2 1756-OB16I 1 1492-CM1771-LA004 2 1492-C005005XT 1 66
1771-OQ16 1 1756-OB16I 1 1492-CM1771-LD010F 1 1492-CONCAB005Y 1 67
1771-OR 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XR 1 68
1771-OVN 1 1756-OV16E 2 1492-CM1771-LD013 1 1492-CONCAB005S3 1 69
1771-OW 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 70
1771-OW16 1 1756-OW16I 1 1492-CM1771-LD011 1 1492-CONCAB005Y 1 71
1771-OWNA 1 1756-OW16I 2 1492-CM1771-LD013 1 1492-CONCAB005S4 1 72
1771-OY 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 73
1771-OYL 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 74
1771-OZ 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 75
1771-OZL 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 76
(1) To understand any issues concerning I/O module compatibility refer to the conversion module wiring diagrams and the Installation Manuals for the specific I/O modules involved (with particular attention to the
specification and wiring instructions).

(2) Where two is indicated, these modules need to be located directly next to each other in the 1756 chassis.

(3) An “F” at the end of the 1756 catalog number indicates that it is fused to match the functionality of the 1771 module being replaced.

(4) The 005 in the Cat. No. indicates cable length of the 1492 cable. The recommended length of 0.5 M is listed, additional lengths are listed below.

1.0M Cable = 1492-CONCAB010_, 1.0M/1.0M Cable= 1492-C010010X_0.5M/1.0M Cable = 1492-C005010X_, 1.0M/0.5M Cable = 1492-C010005X_

6 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Product Selection

Analog Inputs and Outputs


1. Column 1: find the catalog number of the 1771Module you are converting from.
2. Column 2: find the catalog number of the compatible 1756 Module you are converting to.
In some cases more than one module exists. Review the matrix carefully and review the I/O module Installation Manuals to
determine full compatibility.
3. Column 3: find the catalog number of the Conversion Module.
4. Column 4: find the catalog number of the Conversion Cable.
1 2 3 4 5
Converting from 1771 Module Converting to 1756 Module Conversion Module Conversion Cable Wiring Diagram
Cat. No. Qty. Cat. No. Description Qty. Cat. No. Order Qty. Cat. No. Order Qty. Page
Differential Current 1 1492-CM1771-LA002 1 1492-CONACAB005D 1 77
Differential Voltage 1 1492-CM1771-LA002 1 1492-CONACAB005C 1 78
1771-IFE 1 1756-IF16
Single End Current 1 1492-CM1771-LA001 1 1492-CONACAB005B 1 79
Single End Voltage 1 1492-CM1771-LA001 1 1492-CONACAB005A 1 80
Differential Current 1 1492-CM1771-LA002 1 1492-CONACAB005D 1 81
Differential Voltage 1 1492-CM1771-LA002 1 1492-CONACAB005C 1 82
1771-IFF 1 1756-IF16
Single End Current 1 1492-CM1771-LA001 1 1492-CONACAB005B 1 83
Single End Voltage 1 1492-CM1771-LA001 1 1492-CONACAB005A 1 84
Current 1 1492-CM1771-LA004 1 1492-CONACAB005K8 1 85
1756-IF8I
Voltage 1 1492-CM1771-LA004 1 1492-CONACAB005L8 1 86
1756-IF6I Current 1 1492-CM1771-LA004 1 1492-CONACAB005K 1 87
1771-IL 1
(6-ch) Voltage 1 1492-CM1771-LA004 1 1492-CONACAB005L 1 88
1756-IF6I Current 2 1492-CM1771-LA004 1 1492-CONACAB005T1 1 89
(2x 4-ch) Voltage 2 1492-CM1771-LA004 1 1492-CONACAB005T2 1 90
1756-IRT8I RTD 1 1492-CM1771-LA004 1 1492-CONACAB005F8 1 91
1771-IR 1
1756-IR6I RTD 1 1492-CM1771-LA004 1 1492-CONACAB005F 1 92
1756-IT6I2 Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G 1 93
1771-IXE 1
1756-IRT8I Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G8 1 94
1756-IT6I2 Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G 1 95
1771-IXHR 1
1756-IRT8I Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G8 1 96
1 1756-OF6VI Voltage 1 1492-CM1771-LA003 1 1492-CONACAB005E 1 97
1771-OFE1 1 1756-OF8I Voltage 1 1492-CM1771-LA003 1 1492-CONACABOO5E8V 1 98
2 1756-OF8I Voltage 1 1492-CM1771-LA003 2 1492-C005005E8V 1 99
1 1756-OF6CI Current 1 1492-CM1771-LA003 1 1492-CONACAB005E 1 100
1771-OFE2 1 1756-OF8I Current 1 1492-CM1771-LA003 1 1492-CONACABOO5E8C 1 101
2 1756-OF8I Current 1 1492-CM1771-LA003 2 1492-C005005E8C 1 102

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 7


Product Selection

1771-N High Resolution Isolated Analog I/O


Modules
The 1771-N High Resolution Analog I/O modules are designed for use with
1771-RTPs (Remote Termination Panels) and connected by a 6 or 15 foot
cable (Cat. No. 1771-NC6 or 1771-NC15). The conversion of the 1771-N Series
I/O to a 1756 ControlLogix I/O can be accomplished without the removal of
any field wires from the existing 1771-RTPs.

Simply replace the (2) existing 1771 cables with (2) of the following cables in
the table below. Each of these cables has a connector on one end that attaches directly to the existing 1771-RTP and a 1756
RTB (Removable Terminal Block) on the other end for connection to the ControlLogix I/O module.

Use the following steps to select the proper conversion cables:

1. Column 2: find the catalog number of the 1771 Digital I/O module.
2. In column 3, find the catalog number of the compatible 1756 Digital I/O module. In some cases more than one
module is required. Review the matrix and the I/O module installation manuals to determine full compatibility
3. In column 4, find the catalog numbers and descriptions of the appropriate cables.
1 2 3 4 5
Convert From: Convert To: Conversion Cable Catalog Number Wiring
I/O Description 1771 1756 Cable Description Diagram
Qty. Qty. Cable "A" Cable "B" Page
Module Module
1 1756-OF8I 1 Current (8 Ch) 1492-CONACAB020N88 103
1771-NOC 1 1756-OF8 1 Current (8 CH) 1492-CONACAB020N8 104
1 1756-OF6CI 2 Current (4/4 CH) 1492-CONACAB020N1 1492-CONACAB020N1 105
1 1756-IF8I 1 Current (8 CH) 1492-CONACAB020N38 106
1771-NIS
1 1756-IF6CIS 2 Current (4/4 CH) 1492-CONACAB020N2 1492-CONACAB020N2 107
1 1756-IF8I 1 Current (8 CH) 1492-CONACAB020N38 108
1 1756-IF6I 2 Current (4/4 CH) 1492-CONACAB020N3 1492-CONACAB020N3 109
1 1756-IF8I 1 Voltage (8 CH) 1492-CONACAB020N78 110
1771-NIV 1 1756-IF6I 2 Voltage (4/4 CH) 1492-CONACAB020N7 1492-CONACAB020N7 111
Current (A - 4 CH) /
1 1756-IF6I 2 1492-CONACAB020N3 1492-CONACAB020N7 112
Voltage (B - 4 CH)
Standard 1771-N High
Voltage (A - 4 CH) /
Resolution I/O 1 1756-IF6I 2 1492-CONACAB020N7 1492-CONACAB020N3 113
Current (B - 4 CH)
1 1756-IRT8I 1 RTD (8 CH) 1492-CONACAB020N48 114
1771-NR
1 1756-IR6I 2 RTD (4/4 CH) 1492-CONACAB020N4 1492-CONACAB020N4 115
1 1756-IRT8I 1 Thermocouple (8 CH) 1492-CONACAB020N68 116
1771-NT1
1 1756-IT6I 2 Thermocouple (4/4 CH) 1492-CONACAB020N5 1492-CONACAB020N5 117
1 1756-OF8I 1 Voltage (8 CH) 1492-CONACAB020N18 118
1771-NOV
1 1756-OF6VI 2 Voltage (4/4 CH) 1492-CONACAB020N5 1492-CONACAB020N1 119
1 1756-IF8I 1 Voltage (8 CH) 1492-CONACAB020N78 120
1771-NIV1
1 1756-IF6I 2 Voltage (4/4 CH) 1492-CONACAB020N7 1492-CONACAB020N7 121
1 1756-IRT8I 1 Thermocouple (8 CH) 1492-CONACAB020N68 122
1771-NT2
1 1756-IT6I2 2 Thermocouple (4/4 CH) 1492-CONACAB020N6 1492-CONACAB020N6 123

8 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Product Selection

1 2 3 4 5
Convert From: Convert To: Conversion Cable Catalog Number Wiring
I/O Description 1771 1756 Cable Description Diagram
Qty. Qty. Cable "A" Cable "B" Page
Module Module
1756-IRT8I RTD (4 CH) - 1492-CONACAB020N44
124
1756-IF8I Voltage (4 CH) 1492-CONACAB020N74 -
1756-IR6I RTD (4 CH) - 1492-CONACAB020N4
125
1771-NIVR 1756-IF6I Voltage (4 CH) 1492-CONACAB020N7 -
1756-IRT8I RTD (4 CH) - 1492-CONACAB020N44
126
1756-IF8I Current (4 CH) 1492-CONACAB020N34 -
1756-IR6I RTD (4 CH) - 1492-CONACAB020N4
127
Combination 1771-N 1 1756-IF6I 1 Current (4 CH) 1492-CONACAB020N3 -
High Resolution I/O 1756-IRT8I Thermocouple (4 CH) - 1492-CONACAB020N54
128
1756-IF8I Voltage (4 CH) 1492-CONACAB020N74 -
1756-IT6I Thermocouple (4 CH) - 1492-CONACAB020N5
129
1756-IF6I Voltage (4 CH) 1492-CONACAB020N7 -
1771-NIVT
1756-IRT8I Thermocouple (4 CH) - 1492-CONACAB020N54
130
1756-IF8I Current (4 CH) 1492-CONACAB020N34 -
1756-IT6I Thermocouple (4 CH) - 1492-CONACAB020N5
131
1756-IF6I Current (4 CH) 1492-CONACAB020N3 -

Specifications
Attribute Value
Dimensions (H x D x W) 300 x 111.25 x 38.1 mm (11.81 x 4.38 x 1.5 in.)
Approximate Shipping Weight 260g (0.57 lb)
Storage Temperature Storage Temperature -40...+85 °C (-40...+185 °F)
Operating Temperature Operating Temperature 0...+60 °C (+32...+140 °F)
Operating Humidity Operating Humidity 5...95% at +55 °C (+131 °F)
Nonoperating 50 g
Shock
Operating 30 g
Operational Vibration 2 g at 10...500 Hz
Agency Certifications UL Classified (UL File No. E113724)
CE Certifications Compliant for all applicable directives
Pollution Degree 2
Environmental Rating IP20

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 9


Product Selection

Notes:

10 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Approximate Dimensions
Dimensions are in. (mm).

Cat No. MUA1B-A4-A7 used with Cat No. 1756-A4


10.4
[263.6 ]
9.0 9.9
[229.6 ] [251.9 ]
2.4
[60.2 ]

5.4
[137 ] 12.5
[317.2 ]

11.1
[281.7 ]

6.1
[154 ]

Left Justified

10.4
[264.1 ]
9.1
2.4 [230.7 ]
[60.1 ]

5.4
[137 ] 11.1 12.5
[281.7 ] [317.2 ]

Right Justified

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 11


Approximate Dimensions

Cat No. MUA1B-A4-A7 used with Cat No. 1756-A7

14.6
[370.6 ]
9.9
2.4 9.0
[251.9 ]
[60.2 ] [229.6 ]

2.4 6.1
[60.2 ] [154 ]

5.4
[136.5 ]
12.5
[317.2 ]
11.1
[281.7 ]

Left Justified
14.6
[370.1 ]

4.1 9.0
[104.5 ] [229.6 ]
2.4
[60.2 ]

5.4
[137.3 ] 12.5
[317.2 ]

Centered

14.6
[370.1 ]

9.1
2.4
[231.9 ]
[60.2 ]

5.4
[137.3 ] 12.5
[317.2 ]
11.1
[281.7 ]

Right Justified

12 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Approximate Dimensions

Cat No. MUA2B-A7-A10 used with Cat No. 1756-A7


14.6
[370.1 ]
.2 14.0 .3
[5.7 ] [356.6 ] [7.8 ]

2.4
[59.7 ]

5.4 12.5
[136 ] [317.3 ]
11.1
[281.7 ]

Centered

9.9
[251.9 ]

6.1
[154 ]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 13


Approximate Dimensions

Cat No. MUA3-A10-A13 used with Cat No. 1756-A10

19.2
[486.9 ]
19.0
[483.6 ]
2.4
[60.2 ]

5.4
[137 ]
12.5
[317.3 ]
11.1
[281.7 ]

Centered

9.9
[252.3 ]

6.1
[154.4 ]

14 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Approximate Dimensions

Cat No. MUA3-A10-A13 used with Cat No. 1756-A13

.7 19.0 9.6
[18 ] [483.6 ] [243.9 ]
2.4
[60.2 ]

5.4
[137 ] 11.1 12.5
[281.7 ] [317.3 ]

5.7
[146 ]
Left Justified 23.2
[588 ]

2.4
[59.9 ]

2.2 1.9
[56.8 ] [47.4 ]

5.4
[137 ] 11.2
[285.6 ]

Centered
19.0
[483.6 ]
23.2
[588 ]

2.4
[60.2 ] 23.2
[588 ]

4.1
[103.1 ]

5.4
[137 ] 11.1
[281.7 ]

Right Justified

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 15


Approximate Dimensions

Cat No. MUA4-A13-A17 used with Cat No. 1756-A13

24.0
[610.6 ]
23.2
2.4
[588 ]
[60.2 ]

5.4
[137 ]
12.5
[316.7 ]
11.1
[281.7 ]

Centered

9.6
[243.7 ]

5.7
[145.9 ]

16 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Approximate Dimensions

Cat No. MUA4-A13-A17 used with Cat No. 1756-A17

29.1
[737.9 ]
.2 24.0 4.8
[6.2 ] [610.6 ] [121 ]

2.4 9.9
[60.1 ] [251.9 ]
12.5
[316.7 ]
6.1
[154 ]
11.1
[281.7 ]
Left Justified

29.1
[737.9 ]
3.6 24.0 1.4
2.4 [91.7 ] [610.6 ] [35.6 ]
[60.1 ]

11.1
[281.7 ]
5.4
[137 ]
12.5
[316.7 ]

Centered

29.1
[737.9 ]
5.1 24.0
.4 [130 ] [610.6 ]
60.1 ]

5.4
[137 ]
11.1
12.5
[281.7 ]
[316.7 ]

Right Justified

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 17


Approximate Dimensions

Notes:

18 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs
1771-IA, IA2 to 1756-IA16

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IA16
1 Black CABLE “A” 10
L2-0
Not used A 2 White 9
L2-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
L1 Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
IN-4
Input 5 5 8 Red/Black 6
L2 IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
L2 B 11
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
L2-1
From 1771-IA , -IA2 22 19
L2-1
23
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 8 0 3 Red
Input 9 1 4 Green
Input 10 2 5 Orange
L1 Input 11 3 6 Blue
Input 12 4 7 White/Black
Input 13 5 8 Red/Black
L2 Input 14 6 9 Green/Black

Input 15 7 10 Orange/Black

L2 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IA , -IA2 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IA16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IA, -IA2 module versus the 1756-IA16 module are as follows:
1771-IA, -IA2 1756-IA16 w/ 1492-C005005XE
a) Off-to-On Delay 24ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 24ms (+/-10ms) 8ms max (plus selectable filter)
 The 1771-IA, -IA2 module is rated 87V to 138V AC and 97V to 138V DC. The 1756-IA16 module is rated 79V to 132V AC only.
 Refer to your 1771-IA, -IA2 and 1756-IA16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-952 (Version 02)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 19


Wiring Diagrams - Digital Inputs

1771-IAD to 1756-IA16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IA16
Terminal B B
Terminal C C 1 Black 10
L2-0
Terminal D D 2 White 9
L2-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
L1 IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
Input 15 15 16 Black/Red 16
L2 IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
L2-1
20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IAD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IA16 RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The input delay times for the 1771-IAD module versus the 1756-IA16 module are as follows:
1771-IAD 1756-IA16 w/ 1492-CONCAB005X
a) Off-to-On Delay 5ms (+/-3ms) @120VAC 10ms max (plus selectable filter)
b) On-to-Off Delay 25ms (+/-5ms) 8ms max (plus selectable filter)
 The 1771-IAD module is rated 79V to 138V AC or DC. The 1756-IA16 module is rated 74V to 132V AC. If the input
source voltage is DC use a 1756-IH16l and 1492-CM1771-LD002 conversion module.
 Refer to your 1771-IAD and 1756-IA16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-925 (Version 02)]

20 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IAD to 1756-IH16I
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD002
1
Terminal A A 2 Cable
Terminal B B 3 1492-CONCAB005Y 1756-IH16I
Terminal C C 4
Terminal D D 5 Orange 2
GND-0
Input 00 00 6 Blue 1
IN-0
7 White/Black 4
GND-1
Input 01 01 8 Red/Black 3
IN-1
9 Green/Black 6
GND-2
Input 02 02 10 Orange/Black 5
IN-2
11 Blue/Black 8
GND-3
Input 03 03 12 Black/White 7
IN-3
13 Red/White 10
GND-4
Input 04 04 14 Green/White 9
IN-4
15 Blue/White 12
GND-5
Input 05 05 16 Black/Red 11
IN-5
17 White/Red 14
GND-6
Input 06 06 18 Orange/Red 13
IN-6
19 Blue/Red 16
GND-7
Input 07 07 20 Red/Green 15
IN-7
21 Orange/Green 18
GND-8
Input 10 10 22 Black/White/Red 17
IN-8
23 White/Black/Red 20
GND-9
Input 11 11 24 Red/Black/White 19
IN-9
25 Green/Black/White 22
GND-10
Input 12 12 26 Orange/Black/White 21
IN-10
27 Blue/Black/White 24
GND-11
Input 13 13 28 Black/Red/Green 23
IN-11
29 White/Red/Green 26
GND-12
Input 14 14 30 Red/Black/Green 25
IN-12
31 Green/Black/Orange 28
GND-13
Input 15 15 32 Orange/Black/Green 27
IN-13
33 Blue/White/Orange 30
GND-14
Input 16 16 34 Black/White/Orange 29
IN-14
35 White/Red/Orange 32
GND-15
Input 17 17 36 Orange/White/Blue 31
+ IN-15
37
- Terminal E E

1771-WH Swing Arm


From 1771-IAD

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IAD module versus 1756-IH16I module are as follows:
1771-IAD 1756-IH16I
a) Off-to-On Delay 3ms @120V DC 2ms (plus selectable filter)
b) On-to-Off Delay 25ms (+/-5ms) 6ms (plus selectable filter)
 The 1771-IAD module is rated 79V to 138V AC or DC. The 1756-IH16I module is rated 90V to 146V DC. If the input
spurce voltage is AC use a 1756-IA16 and 1492-CM1771-LD002 conversion module.
 Refer to your 1771-IAD and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-927 (Version 02)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 21


Wiring Diagrams - Digital Inputs

1771-IAN to 1756-IA32
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD003 1492-CONCAB005Z 1756-IA32
Common 0 10 1 Black 18
L2-0
Common 2 30 2 White 36
L2-1
3 Red
Input 00 1 4 Green 1
IN-0
Input 00 21 5 Orange 19
IN-16
Input 01 2 6 Blue 2
IN-1
Input 01 22 7 White/Black 20
IN-17
Input 02 3 8 Red/Black 3
IN-2
Input 02 23 9 Green/Black 21
IN-18
Input 03 4 10 Orange/Black 4
IN-3
Input 03 24 11 Blue/Black 22
IN-19
Input 04 5 12 Black/White 5
IN-4
Input 04 25 13 Red/White 23
IN-20
Input 05 6 14 Green/White 6
IN-5
Input 05 26 15 Blue/White 24
IN-21
Input 06 7 16 Black/Red 7
IN-6
Input 06 27 17 White/Red 25
IN-22
Input 07 8 18 Orange/Red 8
IN-7
Input 07 28 19 Blue/Red 26
IN-23
Input 10 11 20 Red/Green 9
IN-8
Input 10 31 21 Orange/Green 27
IN-24
Input 11 12 22 Black/White/Red 10
IN-9
L1 Input 11 32 23 White/Black/Red 28
IN-25
Input 12 13 24 Red/Black/White 11
IN-10
Input 12 33 25 Green/Black/White 29
IN-26
L2 Input 13 14 26 Orange/Black/White 12
IN-11
Input 13 34 27 Blue/Black/White 30
IN-27
Input 14 15 28 Black/Red/Green 13
IN-12
Input 14 35 29 White/Red/Green 31
IN-28
Input 15 16 30 Red/Black/Green 14
IN-13
Input 15 36 31 Green/Black/Orange 32
IN-29
Input 16 17 32 Orange/Black/Green 15
IN-14
Input 16 37 33 Blue/White/Orange 33
IN-30
Input 17 18 34 Black/White/Orange 16
IN-15
Input 17 38 35 White/Red/Orange 34
IN-31
Common 0 9 36 Orange/White/Blue 17
Common 1 L2-0
19 37 White/Red/Blue 35
L2-1
Common 1 20
Common 2 29
Common 3 39
Common 3 40

1771-WN Swing Arm


From 1771-IAN

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IAN module versus 1756-IA32 module are as follows:
1771-IAN 1756-IA32
a) Off-to-On Delay 10ms (+/-7ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-15ms) 8ms max (plus selectable filter)
 The 1771-IAN has 4 groups(allowing 4 seperate power supplies) and the 1756-IA32 has 2 groups.
This module/cable combination ties Groups 0 & 1 from the 1771-IAN to Group 0 on the 1756-IA32 and it ties Groups 2 & 3
from the 1771-IAN to Group 1 on the 1756-IA32. Field wiring modification must be made to accommodate this if multiple
supplies were used. If 4 supplies were used, 2 must be removed.
 Refer to your 1771-IAN and 1756-IA32 Installation Manual wiring schematics and diagrams for more details.

22 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IB to 1756-IB16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IB16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IB 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IB 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IB module versus the 1756-IB16 module are as follows:
1771-IB 1756-IB16 w/ 1492-C005005XE
a) Off-to-On Delay 24ms (+/-10ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 24ms (+/-10ms) 2ms max (plus selectable filter)
 The 1771-IB module is rated 24V DC. The 1756-IB16 module is rated 10 - 31V DC only.
 Refer to your 1771-IB and 1756-IB16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-995 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 23


Wiring Diagrams - Digital Inputs

1771-IBD to 1756-IB16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IB16
Terminal B B
Terminal C C 1 Black 10
GND-0
Terminal D D 2 White 9
GND-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
+ IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
- IN-12
Input 15 15 16 Black/Red 16
IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
GND-1
20 Red/Green 19
GND-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IBD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IB16 RTB. Recommended cable lengths of 0.5M or
1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 The input delay times for the 1771-IBD module versus the 1756-IB16 module are as follows:
1771-IBD 1756-IB16 w/ 1492-CONCAB005X
a) Off-to-On Delay 1ms 1ms (plus selectable filter)
b) On-to-Off Delay 1ms 2ms (plus selectable filter)
 Refer to your 1771-IBD and 1756-IB16 Installation Manual wiring Schematics and diagrams for more details.
[Reference Doc: 41170-926 (Version 02)]

24 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IBN to 1756-IB32
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD003 1492-CONCAB005Z 1756-IB32
dc Common 0 10 1 Black 18
GND-0
dc Common 2 30 2 White 36
GND-1
3 Red
Input 00 1 4 Green 1
IN-0
Input 00 21 5 Orange 19
IN-16
Input 01 2 6 Blue 2
IN-1
Input 01 22 7 White/Black 20
IN-17
Input 02 3 8 Red/Black 3
IN-2
Input 02 23 9 Green/Black 21
IN-18
Input 03 4 10 Orange/Black 4
IN-3
Input 03 24 11 Blue/Black 22
IN-19
Input 04 5 12 Black/White 5
IN-4
Input 04 25 13 Red/White 23
IN-20
Input 05 6 14 Green/White 6
IN-5
Input 05 26 15 Blue/White 24
IN-21
Input 06 7 16 Black/Red 7
IN-6
Input 06 27 17 White/Red 25
IN-22
Input 07 8 18 Orange/Red 8
IN-7
Input 07 28 19 Blue/Red 26
IN-23
Input 10 11 20 Red/Green 9
IN-8
Input 10 31 21 Orange/Green 27
IN-24
Input 11 12 22 Black/White/Red 10
IN-9
Input 11 32 23 White/Black/Red 28
+ IN-25
Input 12 13 24 Red/Black/White 11
IN-10
Input 12 33 25 Green/Black/White 29
- IN-26
Input 13 14 26 Orange/Black/White 12
IN-11
Input 13 34 27 Blue/Black/White 30
IN-27
Input 14 15 28 Black/Red/Green 13
IN-12
Input 14 35 29 White/Red/Green 31
IN-28
Input 15 16 30 Red/Black/Green 14
IN-13
Input 15 36 31 Green/Black/Orange 32
IN-29
Input 16 17 32 Orange/Black/Green 15
IN-14
Input 16 37 33 Blue/White/Orange 33
IN-30
Input 17 18 34 Black/White/Orange 16
IN-15
Input 17 38 35 White/Red/Orange 34
IN-31
dc Common 0 9 36 Orange/White/Blue 17
GND-0
dc Common 1 19 37 White/Red/Blue 35
GND-1
dc Common 1 20
dc Common 2 29
dc Common 3 39
dc Common 3 40

1771-WN Swing Arm


From 1771-IBN

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IBN module versus 1756-IB32 module are as follows:
1771-IBN 1756-IB32
a) Off-to-On Delay 6ms (+/-2ms) 1ms (plus selectable filter)
b) On-to-Off Delay 6ms (+/-2ms) 1ms (plus selectable filter)
 The 1771-IBN has 4 groups(allowing 4 seperate power supplies) and the 1756-IB32 has 2 groups.
This module/cable combination ties Groups 0 & 1 from the 1771-IBN to Group 0 on the 1756-IB32 and it ties Groups 2 & 3 from
the 1771-IBN to Group 1 on the 1756-IB32. Field wiring modification must be made to accommodate this if multiple supplies
were used. If 4 supplies were used, 2 must be removed.
 Refer to your 1771-IBN and 1756-IB32 Installation Manual wiring schematics and diagrams for more details.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 25


Wiring Diagrams - Digital Inputs

1771-IC to 1756-IC16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IC16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IC 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IC 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IC16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IC module versus the 1756-IC16 module are as follows:
1771-IC 1756-IC16 w/ 1492-C005005XE
a) Off-to-On Delay 12ms (+/-7ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-7ms) 4ms max (plus selectable filter)
 The 1771-IC module is rated 42 to 56V DC. The 1756-IC16 module is rated 42 to 56V DC only.
 Refer to your 1771-IC and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-996 (Version 00)]

26 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-ICD to 1756-IC16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IC16
Terminal B B
Terminal C C 1 Black 10
RTN
Terminal D D 2 White 9
RTN
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
+ IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
-- Input 15 15 16 Black/Red 16
IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
RTN
20 Red/Green 19
RTN
21
22
23
24
25

1771-WH Swing Arm


From 1771-ICD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IC16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.

 The input delay times for the 1771-ICD module versus the 1756-IC16 module are as follows:
1771-ICD 1756-IC16 w/ 1492-CONCAB005X
a) Off-to-On Delay 6ms (+/-2ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-1ms) 4ms max (plus selectable filter)

 The 1771-ICD module is rated 20V to 60V AC or DC. The 1756-IC16 module is rated 30V to 60V DC.
 Refer to your 1771-ICD and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 27


Wiring Diagrams - Digital Inputs

1771-ID to 1756-IA16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD012
1 Cable
2
3 1492-C005005XL 1756-IA16I
4
5
4
JMP0
3 6
Orange
Blue
CABLE”A” 1
L1-0
N.C. 7 White/Black 2
L2-0
N.O. 8 Red/Black 3
L1-1
2 1 9 Green/Black 4
JMP1 L2-1
4 3 10 Orange/Black 5
L1-2
N.C. 11 Blue/Black 6
L2-2
N.O. 12 Black/White 7
L1-3
2 1 13 Red/White 8
JMP2 L2-3
3 14 Green/White 9
4 L1-4
L2 L1 N.C. 15 Blue/White 10
L1-0 1 L2-4
LOAD N.O. 16 Black/Red 11
L2-0 L1-5
2 2 1 17 White/Red 12
L1-1 L2-5
3 JMP3 18
4 3 Orange/Red
L2-1 4 25 NOT USED
N.C. 19 Blue/Red
L1-2 5 26 NOT USED
N.O. 20 Red/Green
L2-2 6 2 27 NOT USED
1 21 Orange/Green
L1-3 7 JMP4 28 NOT USED
4 3 22 Black/White/Red
L2-3 8 29 NOT USED
N.C. 23 White/Black/Red
L1-4 9 30 NOT USED
N.O. 24 Red/Black/White
L2-4 10 2 1 31 NOT USED
25 Green/Black/White
L1-5 11 JMP5 32 NOT USED
4 3 26 Orange/Black/White
L2-5 12 33 NOT USED
N.C. 27 Blue/Black/White
34 NOT USED
N.O. 28 Black/Red/Green
NOT USED
35
2
4
JMP6
1
3
29
30
White/Red/Green
Red/Black/Green
CABLE”B” 36 NOT USED
13
N.C. 31 Green/Black/Orange L1-6
14
N.O. 32 Orange/Black/Green L2-6
2 1 15
33 Blue/White/Orange L1-7
JMP7 16
3 34 Black/White/Orange L2-7
1771-WD Swing Arm 4
N.C. 35 White/Red/Orange
17
18
L1-8
36 L2-8
From 1771-ID 2
N.O.
1 37
Orange/White/Blue
19
L1-9
Conversion Module 20
21
L2-9
L1-10
1492-CM1771-LD012 22
23
L2-10
L1-11
1 24 L2-11
2
3
4
5 Orange
JMP0 6
4 3 Blue
N.C. 7 White/Black
N.O. 8 Red/Black
2 1 9 Green/Black
JMP1 10
4 3 Orange/Black
N.C. 11 Blue/Black
N.O. 12 Black/White
2 1 13 Red/White
JMP2 14 Green/White
4 3
L1-6 N.C. 15 Blue/White
1
L2-6 N.O. 16 Black/Red
2 2 1 17 White/Red
L1-7 3 JMP3
4 3 18 Orange/Red
L2-7 4 N.C. 19 Blue/Red
L1-8 5
N.O. 20 Red/Green
L2-8 6 2 1 21 Orange/Green
L1-9 7 JMP4
L2-9 4 3 22 Black/White/Red
8 N.C. 23 White/Black/Red
L1-10 9
N.O. 24 Red/Black/White
L2-10 10 2 1
L2 L1 25 Green/Black/White
L1-11 11 JMP5
LOAD 4 3 26 Orange/Black/White
L2-11 12
N.C. 27 Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange
N.O. 36 Orange/White/Blue

1771-WD Swing Arm 2 1 37

From 1771-ID

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IA16I RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The input delay times for the 1771-ID module versus the 1756-IA16I module are as follows:
1771-ID 1756-IA16I w/ 1492-C005005XL
a) Off-to-On Delay 24ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 24ms (+/-10ms) 8ms max (plus selectable filter)
 The 1771-ID module had a jumper selection of N.O. and N.C. outputs. The 1756-IA16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-ID jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output
is required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-ID and 1756-IA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756
output module ratings are not exceeded. [Reference Doc: 41170-993 (Version 00)]

28 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-ID01 to 1756-IM16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1 Cable
2
3 1492-C005005XL 1756-IM16I
4
5
4
JMP0
3 6
Orange
Blue
CABLE”A” 1
L1-0
N.C. 7 White/Black 2
L2-0
N.O. 8 Red/Black 3
L1-1
2 1 9 Green/Black 4
JMP1 L2-1
4 3 10 Orange/Black 5
L1-2
N.C. 11 Blue/Black 6
L2-2
N.O. 12 Black/White 7
L1-3
2 1 13 Red/White 8
JMP2 L2-3
3 14 Green/White 9
4 L1-4
L2 L1 N.C. 15 Blue/White 10
L1-0 1 L2-4
LOAD N.O. 16 Black/Red 11
L2-0 L1-5
2 2 1 17 White/Red 12
L1-1 L2-5
3 JMP3 18
4 3 Orange/Red
L2-1 4 25 NOT USED
N.C. 19 Blue/Red
L1-2 5 26 NOT USED
N.O. 20 Red/Green
L2-2 6 2 27 NOT USED
1 21 Orange/Green
L1-3 7 JMP4 28 NOT USED
4 3 22 Black/White/Red
L2-3 8 29 NOT USED
N.C. 23 White/Black/Red
L1-4 9 30 NOT USED
N.O. 24 Red/Black/White
L2-4 10 2 1 31 NOT USED
25 Green/Black/White
L1-5 11 JMP5 32 NOT USED
4 3 26 Orange/Black/White
L2-5 12 33 NOT USED
N.C. 27 Blue/Black/White
34 NOT USED
N.O. 28 Black/Red/Green
NOT USED
35
2
4
JMP6
1
3
29
30
White/Red/Green
Red/Black/Green
CABLE”B” 36 NOT USED
13
N.C. 31 Green/Black/Orange L1-6
14
N.O. 32 Orange/Black/Green L2-6
2 1 15
33 Blue/White/Orange L1-7
JMP7 16
34 L2-7
1771-WD Swing Arm 4 3
N.C. 35
Black/White/Orange
White/Red/Orange
17 L1-8
18
From 1771-ID01 2
N.O.
1
36
37
Orange/White/Blue
19
L2-8
L1-9
20
Conversion Module 21
L2-9
L1-10
1492-CM1771-LD012 22
23
L2-10
L1-11
1 24 L2-11
2
3
4
5 Orange
JMP0 6
4 3 Blue
N.C. 7 White/Black
N.O. 8 Red/Black
2 1 9 Green/Black
JMP1 10
4 3 Orange/Black
N.C. 11 Blue/Black
N.O. 12 Black/White
2 1 13 Red/White
JMP2 14 Green/White
4 3
L1-6 N.C. 15 Blue/White
1
L2-6 N.O. 16 Black/Red
2 2 1 17 White/Red
L1-7 3 JMP3
4 3 18 Orange/Red
L2-7 4 N.C. 19 Blue/Red
L1-8 5
N.O. 20 Red/Green
L2-8 6 2 1 21 Orange/Green
L1-9 7 JMP4
L2-9 4 3 22 Black/White/Red
8 N.C. 23 White/Black/Red
L1-10 9
N.O. 24 Red/Black/White
L2-10 10 2 1
L2 L1 25 Green/Black/White
L1-11 11 JMP5
LOAD 4 3 26 Orange/Black/White
L2-11 12
N.C. 27 Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange
N.O. 36 Orange/White/Blue
2 1
1771-WD Swing Arm 37

From 1771-ID01

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IM16I RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The input delay times for the 1771-IM module versus the 1756-IM16I module are as follows:
1771-ID01 1756-IM16I w/ 1492-C005005XL
a) Off-to-On Delay 20ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-10ms) 8ms max (plus selectable filter)
 The 1771-ID01module had a jumper selection of N.O. and N.C. outputs. The 1756-IM16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-ID01 jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-ID01 and 1756-IM16I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-015 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 29


Wiring Diagrams - Digital Inputs

1771-ID16 to 1756-IA16I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD004
1
2 Cable
3 1492-CONCAB005Y 1756-IA16I
4
L2 L2-0 2 5 Orange 2
Input 0 L2-0
1 6 Blue 1
4 IN-0
L2-1 7 White/Black 4
L2-1
Input 1 3 8 Red/Black 3
L1 6 IN-1
L2-2 9 Green/Black 6
5 L2-2
Input 2 10 Orange/Black 5
IN-2
L2-3 8 11 Blue/Black 8
L2-3
Input 3 7 12 Black/White 7
IN-3
L2-4 12 13 Red/White 10
11 L2-4
Input 4 14 Green/White 9
14 IN-4
L2-5 15 Blue/White 12
13 L2-5
Input 5 16 Black/Red 11
16 IN-5
L2-6 17 White/Red 14
15 L2-6
Input 6 18 Orange/Red 13
18 IN-6
L2-7 19 Blue/Red 16
17 L2-7
Input 7 20 Red/Green 15
22 IN-7
L2-10 21 Orange/Green 18
21 L2-8
Input 10 22 Black/White/Red 17
IN-8
L2-11 24 23 White/Black/Red 20
23 L2-9
Input 11 24 Red/Black/White 19
26 IN-9
L2-12 25 Green/Black/White 22
25 L2-10
Input 12 26 Orange/Black/White 21
28 IN-10
L2-13 27 Blue/Black/White 24
L2-11
Input 13 27 28 Black/Red/Green 23
32 IN-11
L2-14 29 White/Red/Green 26
31 L2-12
Input 14 30 Red/Black/Green 25
IN-12
L2-15 34 31 Green/Black/Orange 28
L2-13
Input 15 33 32 Orange/Black/Green 27
IN-13
L2-16 36 33 Blue/White/Orange 30
L2-14
Input 16 35 34 Black/White/Orange 29
IN-14
L2-17 38 35 White/Red/Orange 32
L2-15
Input 17 37 36 Orange/White/Blue 31
IN-15
Not used 9 37
Not used 10
Not used 19
Not used 20
Not used 29
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-ID16
Conversion Module Installation and Application Considerations
 The input delay times for the 1771-ID16 module versus 1756-IA16I module are as follows:
1771-ID16 1756-IA16I
a) Off-to-On Delay 0.57ms 10ms max (plus selectable filter)
b) On-to-Off Delay 9ms or 18ms (selectable) 8ms max (plus selectable filter)
 The 1771-ID16 module is rated 74V to 138V AC and105V to 138V DC. The 1756-IA16I is rated 79V to 132V AC. If the input
source voltage is DC use a 1756-IH16I with this conversion module.
 Refer to your 1771-ID16 and 1756-IA16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-931 (Version 02)]

30 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-ID16 to 1756-IH16I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD004
1
2 Cable
3 1492-CONCAB005Y 1756-IH16I
4
L2-0 2 5 Orange 2
- GND-0
Input 0 1 6 Blue 1
IN-0
L2-1 4 7 White/Black 4
+ GND-1
Input 1 3 8 Red/Black 3
IN-1
L2-2 6 9 Green/Black 6
GND-2
Input 2 5 10 Orange/Black 5
IN-2
L2-3 8 11 Blue/Black 8
GND-3
Input 3 7 12 Black/White 7
IN-3
L2-4 12 13 Red/White 10
GND-4
Input 4 11 14 Green/White 9
IN-4
L2-5 14 15 Blue/White 12
GND-5
Input 5 13 16 Black/Red 11
IN-5
L2-6 16 17 White/Red 14
GND-6
Input 6 15 18 Orange/Red 13
IN-6
L2-7 18 19 Blue/Red 16
GND-7
Input 7 17 20 Red/Green 15
IN-7
L2-10 22 21 Orange/Green 18
GND-8
Input 10 21 22 Black/White/Red 17
IN-8
L2-11 24 23 White/Black/Red 20
GND-9
Input 11 23 24 Red/Black/White 19
IN-9
L2-12 26 25 Green/Black/White 22
GND-10
Input 12 25 26 Orange/Black/White 21
IN-10
L2-13 28 27 Blue/Black/White 24
GND-11
Input 13 27 28 Black/Red/Green 23
IN-11
L2-14 32 29 White/Red/Green 26
GND-12
Input 14 31 30 Red/Black/Green 25
IN-12
L2-15 34 31 Green/Black/Orange 28
GND-13
Input 15 33 32 Orange/Black/Green 27
IN-13
L2-16 36 33 Blue/White/Orange 30
GND-14
Input 16 35 34 Black/White/Orange 29
IN-14
L2-17 38 35 White/Red/Orange 32
GND-15
Input 17 37 36 Orange/White/Blue 31
IN-15
Not used 9 37
Not used 10
Not used 19
Not used 20
Not used 29
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-ID16

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-ID16 module versus 1756-IH16I module are as follows:
1771-ID16 1756-IH16I
a) Off-to-On Delay 0.57ms 2ms max (plus selectable filter)
b) On-to-Off Delay 9ms or 18ms (selectable) 6ms max (plus selectable filter)
 The 1771-ID16 module is rated 74V to 138V AC and105V to 138V DC. The 1756-IH16I is rated 90V to 146V DC. If the input
source voltage is AC use a 1756-IA16I with this conversion module.
 Refer to your 1771-ID16 and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-932 (Version 02)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 31


Wiring Diagrams - Digital Inputs

1771-IG to 1756-IG16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LA003 1492-C005005XS 1756-IG16
+ + DC A 13 Red/White CABLE”A” 10
+ DC -0
+ Input 0 0 25 Green/Black/White 1
Input IN-0
5V DC - Input 1 1 24 Red/Black/White 2
- Device IN-1
SUPPLY Input 2 2 23 White/Black/Red 3
IN-2
Input 3 3 22 Black/White/Red 4
IN-3
Input 4 4 21 Orange/Green 5
IN-4
Input 5 5 19 Blue/Red 6
IN-5
Input 6 6 18 Orange/Red 7
IN-6
Input 7 7 17 White/Red 8
Common IN-7
B 16 Black/Red 9
- DC -0
1 20
+ DC -1
2 11
IN-8
3 12
IN-9
4 13
IN-10
5 14
IN-11
6 15
IN-12
7 16
1771-WC Swing Arm 8 17
IN-13
IN-14
From 1771-IG 9 18
IN-15
10 19
11 - DC -1
12
14
15
20

SH

Conversion Module
1492-CM1771-LA003
+ + DC A 13 Red/White
+ Input 0 0 25 Green/Black/White
Input
5V DC - Input 1 1 24 Red/Black/White
- Device Input 2
SUPPLY 2 23 White/Black/Red
Input 3 3 22 Black/White/Red
Input 4 4 21 Orange/Green
Input 5 5 19 Blue/Red
Input 6 6 18 Orange/Red
Input 7 7 17 White/Red
Common B 16 Black/Red
1
2 CABLE”B”
3
4
5
6
7
1771-WC Swing Arm 8
From 1771-IG 9
10
11
12
14
15
20

SH

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IG16 RTB. Each cable can be either 0.5M or
1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-IG module versus the 1756-IG16 module are as follows:
1771-IG 1756-IG16 w/ 1492-C005005XS
a) Off-to-On Delay 1ms (+/-10ms) 270ms max (plus selectable filter)
b) On-to-Off Delay 1ms (+/-10ms) 390ms max (plus selectable filter)
 The 1771-IG module is rated 5V DC TTL INPUT MODULE. The 1756-IG16 module is rated 5V DC TTL INPUT MODULE only.
 Refer to your 1771-IG and 1756-IG16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41171-027 (Version 00)]

32 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IGD to 1756-IG16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-IG16
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
+ IN-2
Input 03 03 6 Blue 4
IN-3
- Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
- + IN-7
DC Input Input 08 10 11 Blue/Black 11
Device IN-8
Input 09 11 12 Black/White 12
IN-9
Input 10 12 13 Red/White 13
IN-10
Input 11 13 14 Green/White 14
IN-11
Input 12 14 15 Blue/White 15
IN-12
Input 13 15 16 Black/Red 16
IN-13
Input 14 16 17 White/Red 17
IN-14
Input 15 17 18 Orange/Red 18
IN-15
19 Blue/Red 20
DC-1+
- dc E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-IGD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IG16 RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-IGD module output current limits versus 1756-IG16 limits are as follows:
1771-IGD 1756-IG16 w/ 1492-CONCAB005X
a) Current/Point 122mA 110mA
b) Current/Module 500mA 110mA
 The 1771-IGD is rated 5V DC. The 1756-IG16 is rated 4.5V to 5.5V DC.
 Refer to your 1771-IGD and 1756-IG16 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-004 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 33


Wiring Diagrams - Digital Inputs

1771-IH to 1756-IC16
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IC16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-0 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IH 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
From 1771-IH 22
23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IC16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IH module versus the 1756-IC16 module are as follows:
1771-IH 1756-IC16 w/ 1492-C005005XE
a) Off-to-On Delay 15ms (+/-7ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 15ms (+/-7ms) 4ms max (plus selectable filter)
 The 1771-IH module is rated 24V - 48V DC. The 1756-IC16 module is rated 30V - 60V DC.
 Refer to your 1771-IH and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-997 (Version 00)]

34 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IM to 1756-IM16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XH 1756-IM16I
1 Black 2
L2-0
Not used A 2 White 4
L2-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 3
IN-1
Input 2 2 5 Orange 5
IN-2
L1 Input 3 3 6 Blue 7
IN-3
Input 4 4 7 White/Black 9
IN-4
Input 5 5 8 Red/Black 11
L2 IN-5
Input 6 6 9 Green/Black 13
IN-6
Input 7 7 10 Orange/Black 15
IN-7
L2 B 11 CABLE “A” 6
L2-0
12 8
L2-0
13 10
L2-0
14 12
L2-0
15 14
L2-0
16 16
L2-0
17
18
19
20 17
IN-8
1771-WA Swing Arm 21 19
21
IN-9
22
From 1771-IM 23 23
IN-10
IN-11
24 25
IN-12
25 27
IN-13
29
IN-14
31
IN-15
Conversion Module 18
L2-1
1492-CM1771-LD007 20
L2-1
22
1 L2-1
Black 24
Not used A 2 L2-1
White 26
3 L2-1
Input 0 0 Red 28
1 4 L2-1
Input 1 Green 30
5 Orange L2-1
Input 2 2 32
L1 6 L2-1
Input 3 3 Blue
Input 4 4 7 White/Black
Input 5 5 8 Red/Black
L2 Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

L2 B 11 CABLE “B”
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IM 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IM16I RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IM module versus the 1756-IM16I module are as follows:
1771-IM 1756-IM16I w/ 1492-C005005XH
a) Off-to-On Delay 20ms (+/-6ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 20ms (+/-6ms) 8ms max (plus selectable filter)
 The 1771-IM module is rated 220V to 240V AC. The 1756-IM16I module is rated 159 - 265V AC only.
 Refer to your 1771-IM and 1756-IM16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-990 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 35


Wiring Diagrams - Digital Inputs

1771-IMD to 1756-IM16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD002
1
Terminal A A 2 Cable
Terminal B B 3 1492-CONCAB005Y 1756-IM16I
Terminal C C 4
Terminal D D 5 Orange 2
L2-0
Input 00 00 6 Blue 1
IN-0
7 White/Black 4
L2-1
Input 01 01 8 Red/Black 3
IN-1
9 Green/Black 6
L2-2
Input 02 02 10 Orange/Black 5
IN-2
11 Blue/Black 8
L2-3
Input 03 03 12 Black/White 7
IN-3
13 Red/White 10
L2-4
Input 04 04 14 Green/White 9
IN-4
15 Blue/White 12
L2-5
Input 05 05 16 Black/Red 11
IN-5
17 White/Red 14
L2-6
Input 06 06 18 Orange/Red 13
IN-6
19 Blue/Red 16
L2-7
Input 07 07 20 Red/Green 15
IN-7
21 Orange/Green 18
L2-8
Input 10 10 22 Black/White/Red 17
IN-8
23 White/Black/Red 20
L2-9
Input 11 11 24 Red/Black/White 19
IN-9
25 Green/Black/White 22
L2-10
Input 12 12 26 Orange/Black/White 21
IN-10
27 Blue/Black/White 24
L2-11
Input 13 13 28 Black/Red/Green 23
IN-11
29 White/Red/Green 26
L2-12
Input 14 14 30 Red/Black/Green 25
IN-12
31 Green/Black/Orange 28
L2-13
Input 15 15 32 Orange/Black/Green 27
IN-13
L1 33 Blue/White/Orange 30
L2-14
Input 16 16 34 Black/White/Orange 29
IN-14
35 White/Red/Orange 32
L2 L2-15
Input 17 17 36 Orange/White/Blue 31
IN-15
37
Terminal E E

1771-WH Swing Arm


From 1771-IMD

Conversion Module Installation and Application Considerations


 The input delay times for the 1771-IMD module versus 1756-IM16I module are as follows:
1771-IMD 1756-IM16I
a) Off-to-On Delay 15ms (+/-8ms) 10ms (plus selectable filter)
b) On-to-Off Delay 172ms (+/-56ms) 8ms (plus selectable filter)
 The 1771-IMD module is rated 184V AC to 250V AC and 166V-230V DC. The 1756-IM16I module is rated 159V to 265V
AC. A1756 input module with an equivalent DC voltage range to convert the 1771-IMD is not available.
 Refer to your 1771-IMD and 1756-IM16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-928 (Version 02)]

36 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IN to 1756-IN16

WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IN16
1 Black 10
L2-0
Not used A 2 White 9
L2-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
L2-1
22 19
From 1771-IN 23
L2-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

L2 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IN 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IN16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IN module versus the 1756-IN16 module are as follows:
1771-IN 1756-IN16 w/ 1492-C005005XE
a) Off-to-On Delay 18ms (+/-10ms) 10ms max (plus selectable filter)
b) On-to-Off Delay 18ms (+/-10ms) 10ms max (plus selectable filter)
 The 1771-IN module is rated 24V AC. The 1756-IN16 module is rated 24V AC only.
 Refer to your 1771-IN and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-998 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 37


Wiring Diagrams - Digital Inputs

1771-IND to 1756-IN16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IN16
Terminal B B
Terminal C C 1 Black 10
L2-0
Terminal D D 2 White 9
L2-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
L1 IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
Input 15 15 16 Black/Red 16
L2 IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
L2-1
20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IND

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.

 The input delay times for the 1771-IND module versus the 1756-IN16 module are as follows:
1771-IND 1756-IN16 w/ 1492-CONCAB005X
a) Off-to-On Delay 35ms (+/-10ms) @24V AC 10ms max (plus selectable filter)
b) On-to-Off Delay 45ms (+/-15ms) 10ms max (plus selectable filter)

 The 1771-IND module is rated 24V AC or DC. The 1756-IN16 module is rated 10V to 30V AC.
 Refer to your 1771-IND and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-002 (Version 00)]

38 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IND1 to 1756-IN16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD001
Cable
Terminal A A 1492-CONCAB005X 1756-IN16
Terminal B B
Terminal C C 1 Black 10
L2-0
Terminal D D 2 White 9
L2-0
Input 00 00 3 Red 1
IN-0
Input 01 01 4 Green 2
IN-1
Input 02 02 5 Orange 3
IN-2
Input 03 03 6 Blue 4
IN-3
Input 04 04 7 White/Black 5
IN-4
Input 05 05 8 Red/Black 6
IN-5
Input 06 06 9 Green/Black 7
IN-6
Input 07 07 10 Orange/Black 8
IN-7
Input 10 10 11 Blue/Black 11
IN-8
Input 11 11 12 Black/White 12
IN-9
Input 12 12 13 Red/White 13
L1 IN-10
Input 13 13 14 Green/White 14
IN-11
Input 14 14 15 Blue/White 15
IN-12
Input 15 15 16 Black/Red 16
L2 IN-13
Input 16 16 17 White/Red 17
IN-14
Input 17 17 18 Orange/Red 18
IN-15
Terminal E E 19 Blue/Red 20
L2-1
20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH Swing Arm


From 1771-IND1

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.

 The input delay times for the 1771-IND1 module versus the 1756-IN16 module are as follows:
1771-IND1 1756-IN16 w/ 1492-CONCAB005X
a) Off-to-On Delay 25ms (+/-5ms) @48V AC 10ms max (plus selectable filter)
b) On-to-Off Delay 35ms (+/-10ms) 10ms max (plus selectable filter)

 The 1771-IND1 module is rated 48V AC. The 1756-IN16 module is rated 10V to 30V AC.
 Refer to your 1771-IND1 and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-003 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 39


Wiring Diagrams - Digital Inputs

1771-IQ to 1756-IB16I— Sinking


There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XK 1756-IB16I
1 Black 2
L2-0
Not used A 2 White 4
L2-0
IN 0 0 3 Red 1
IN-0
IN 1 1 4 Green 3
IN-1
IN 2 2 5 Orange 5
IN-2
+ IN 3 3 6 Blue 7
IN-3
IN 4 4 7 White/Black 9
_ IN-4
IN 5 5 8 Red/Black 11
IN-5
IN 6 6 9 Green/Black 13
IN-6
IN 7 7 10 Orange/Black 15
IN-7
L2 - 0 B 11 6
12 CABLE “A” 8
L2-0
L2-0
13 10
14 L2-0
12
L2-0
15 14
L2-0
16 16
17 L2-0
18
19
20 17
IN-8
1771-WA Swing Arm 21 19
IN-9
22 21
From 1771-IQ 23 23
IN-10
IN-11
24 25
IN-12
25 27
IN-13
29
IN-14
31
IN-15
18
L2-1
20 L2-1
22
L2-1
24
L2-1
26
L2-1
Conversion Module 28
L2-1
30
1492-CM1771-LD007 L2-1
32
L2-1
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
_ 8
Input 5 5 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

L2 - 1 B 11
12 CABLE “B”
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IQ 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16I RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IQ module versus the 1756-IB16I module are as follows:
1771-IQ 1756-IB16I w/ 1492-C005005XK
a) Off-to-On Delay 12ms (+/-14ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 12ms (+/-7ms) 4ms max (plus selectable filter)
 The 1771-IQ module is rated 5V to 30V DC. The 1756-IB16I module is rated 10V to 30V DC only.
 Refer to your 1771-IQ and 1756-IB16I Installation Manual wiring schematics and diagrams for more details.
 For Sourcing applications use 1492-CM1771-LD014. [Reference Doc: 41170-992 (Version 00)]

40 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IQ to 1756-IB16I— Sourcing


There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD0014 Cable
1492-C005005XJ 1756-IB16I
1 Black
DC+ A 2 White
GND 00 0 3 Red 2
GND-0
GND 01 1 4 Green 4
GND-1
GND 02 2 5 Orange 6
GND-2
GND 03 3 6 Blue 8
GND-3
7 White/Black 1
IN - 0
8 Red/Black 3
IN - 1
9 Green/Black 5
+ IN - 2
10 Orange/Black 7
IN - 3
11 Blue/Black 9
- IN - 4
12 Black/White 11 IN - 5
13 Red/White 13 IN - 6
14 Green/White 15 IN - 7
GND 04 4 15 Blue/White 10
LOAD GND-4
GND 05 5 16 Black/Red 12
GND-5
GND 06 6 17 White/Red 14
GND-6
GND 07 7 18 Orange/Red 16
GND-7
DC - B 19 Blue/Red 34 GND-15
20 Red/Green
CABLE”A”
21
22
23
24
1771-WA Swing Arm 25
18
GND-8
From 1771-IQ 20
OUT-9
22
OUT-10
24
Conversion Module OUT-11
17
19 IN - 8
1492-CM1771-LD0014 21 IN - 9
23 IN - 10
IN - 11
25
IN - 12
1 Black
27
IN - 13
DC + A 2 White
29
IN - 14
GND 08 0 3 Red 31
IN - 15
GND 09 1 4 Green 26
GND-12
2 5 Orange 28
GND -10 GND-13
3 6 Blue 30
GND -11 GND-14
7 White/Black
32
GND-15
8 Red/Black 33
NOT-USED
9 Green/Black 35
+ NOT-USED
10 Orange/Black 36
NOT-USED
11 Blue/Black
-
12 Black/White
13 Red/White
14 Green/White
GND -12 4 15 Blue/White
LOAD
GND -13 5 16 Black/Red
GND -14 6 17 White/Red
GND -15 7 18 Orange/Red

DC - B 19 Blue/Red
20 Red/Green CABLE”B”
21
22
23
24
1771-WA Swing Arm 25

From 1771-IQ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16I RTB. Each cable can be either 0.5M
or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-IQ module versus the 1756-IB16 module are as follows:
1771-IQ 1756-IB16I w/1492-C005005XJ
a) Off-to-On Delay 12ms (+/-14ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 12ms (+/-14ms) 4ms max (plus selectable filter)
 The 1771-IQ module is rated 5V to 30V DC. The 1756-IB16I module is rated 10V to 30V SOURCING DC only.
 Refer to your 1771-IQ and 1756-IB16I Installation Manual wiring schematics and diagrams for more details.
 For Sinking applications use 1492-CM1771-LD007. [Reference Doc: 41170-991 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 41


Wiring Diagrams - Digital Inputs

1771-IQ16 to 1756-IB16I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these consid-
erations before installation.
Conversion Module
1492-CM1771-LD004
1
2 Cable
3 1492-CONCAB005Y 1756-IB16I
Sinking Input Example
4
Gnd-0 2 5 Orange 2
- Gnd-0
Input 0 1 6 Blue 1
IN-0
Gnd-1 4 7 White/Black 4
+ Gnd-1
Input 1 3 8 Red/Black 3
IN-1
Gnd-2 6 9 Green/Black 6
Gnd-2
Input 2 5 10 Orange/Black 5
IN-2
Gnd-3 8 11 Blue/Black 8
 Input 3 7 12 Black/White 7
Gnd-3
Sourcing IN-3
Gnd-4 12 13 Red/White 10
Input Gnd-4
Input 4 11 14 Green/White 9
Example IN-4
Gnd-5 14 15 Blue/White 12
- Gnd-5
Input 5 13 16 Black/Red 11
IN-5
Gnd-6 16 17 White/Red 14
+ Gnd-6
Input 6 15 18 Orange/Red 13
IN-6
Gnd-7 18 19 Blue/Red 16
Gnd-7
Input 7 17 20 Red/Green 15
IN-7
Gnd-10 22 21 Orange/Green 18
Gnd-8
Input 10 21 22 Black/White/Red 17
IN-8
Gnd-11 24 23 White/Black/Red 20
Gnd-9
Input 11 23 24 Red/Black/White 19
IN-9
Gnd-12 26 25 Green/Black/White 22
Gnd-10
Input 12 25 26 Orange/Black/White 21
IN-10
Gnd-13 28 27 Blue/Black/White 24
Gnd-11
Input 13 27 28 Black/Red/Green 23
IN-11
Gnd-14 32 29 White/Red/Green 26
Gnd-12
Input 14 31 30 Red/Black/Green 25
IN-12
Gnd-15 34 31 Green/Black/Orange 28
Gnd-13
Input 15 33 32 Orange/Black/Green 27
IN-13
Gnd-16 36 33 Blue/White/Orange 30
Gnd-14
Input 16 35 34 Black/White/Orange 29
IN-14
Gnd-17 38 35 White/Red/Orange 32
Gnd-15
Input 17 37 36 Orange/White/Blue 31
IN-15
Not used 9 37
Not used 10
Not used 19
Not used 20
Not used 29
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-IQ16
Conversion Module Installation and Application Considerations
 The input delay times for the 1771-IQ16 module versus 1756-IB16I module are as follows:
1771-IQ16 1756-IB16I
a) Off-to-On Delay 0.57ms 1ms max (plus selectable filter)
b) On-to-Off Delay 0.57ms 4ms max (plus selectable filter)
 Both the 1771-IQ16 and 1756-IB16I allow operation with sourcing inputs. Refer to installation Instructions for details.
 Refer to your 1771-IQ16 and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-933 (Version 02)]

42 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IT to 1756-IB16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD007 1492-C005005XE 1756-IB16
1 Black 10
GND-0
Not used A 2 White 9
GND-0
Input 0 0 3 Red 1
IN-0
Input 1 1 4 Green 2
IN-1
Input 2 2 5 Orange 3
IN-2
+ Input 3 3 6 Blue 4
IN-3
Input 4 4 7 White/Black 5
- IN-4
Input 5 5 8 Red/Black 6
IN-5
Input 6 6 9 Green/Black 7
IN-6
Input 7 7 10 Orange/Black 8
IN-7
GND-1 B 11 CABLE “A”
12
13 CABLE “B” 11
14 IN-8
12
15 IN-9
13
16 IN-10
14
17 IN-11
15
18 IN-12
16
19 IN-13
17
20 IN-14
18
IN-15
1771-WA Swing Arm 21 20
GND-1
22 19
From 1771-IT 23
GND-1
24
25

Conversion Module
1492-CM1771-LD007
1 Black
Not used A 2 White
Input 0 0 3 Red
Input 1 1 4 Green
Input 2 2 5 Orange
+ Input 3 3 6 Blue
Input 4 4 7 White/Black
- Input 5 5 8 Red/Black
Input 6 6 9 Green/Black

Input 7 7 10 Orange/Black

GND-1 B 11
12
13
14
15
16
17
18
19
20
1771-WA Swing Arm 21
22
From 1771-IT 23
24
25

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16 RTB. Recommended cable
lengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
 The input delay times for the 1771-IT module versus the 1756-IB16 module are as follows:
1771-IT 1756-IB16 w/ 1492-C005005XE
a) Off-to-On Delay 0.6ms (+/-0.2ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 0.6ms (+/-0.2ms) 2ms max (plus selectable filter)
 The 1771-IT module is rated 24V DC. The 1756-IB16 module is rated 24V DC only.
 Refer to your 1771-IT and 1756-IB16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-999 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 43


Wiring Diagrams - Digital Inputs

1771-IV to 1756-IV16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014 Cable
1492-C005005XG 1756-IV16
1 Black
+DC-0 A 2 White
Cable A
INPUT 00 0 3 Red 1
IN-0
INPUT 01 1 4 Green 2
IN-1
INPUT 02 2 5 Orange 3
IN-2
INPUT 03 3 6 Blue 4
IN-3
7 White/Black 9
+DC-0
8 Red/Black 10 +DC-0
9 Green/Black
+
10 Orange/Black
11 Blue/Black
-
12 Black/White
13 Red/White
14 Green/White
INPUT 04 4 15 Blue/White 5
LOAD IN-4
INPUT 05 5 16 Black/Red 6
IN-5
INPUT 06 6 17 White/Red 7
IN-6
INPUT 07 7 18 Orange/Red 8
IN-7
-DC-0 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25 Cable B 11
IN-8
From 1771-IV 12
IN-9
13
Conversion Module 14
IN-10
IN-11
1492-CM1771-LD014 19
+DC-1
20
+DC-1

1 Black
+DC-1 A 2 White
INPUT 08 0 3 Red
INPUT 09 1 4 Green
INPUT 10 15
2 5 Orange IN-12
INPUT 11 16
3 6 Blue IN-13
17
7 White/Black IN-14
18
8 Red/Black IN-15
9 Green/Black
+
10 Orange/Black
11 Blue/Black
-
12 Black/White
13 Red/White
14 Green/White
INPUT 12 4 15 Blue/White
LOAD
INPUT 13 5 16 Black/Red
INPUT 14 6 17 White/Red
INPUT 15 7 18 Orange/Red

-DC-1 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25

From 1771-IV

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IV16 RTB. Each cable can be either 0.5M
or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-IV module versus the 1756-IV16 module are as follows:
1771-IV 1756-IV16 w/1492-C005005XG
a) Off-to-On Delay 15ms (+/-7ms) 1ms max (plus selectable filter)
b) On-to-Off Delay 15ms (+/-7ms) 2ms max (plus selectable filter)
 The 1771-IV module is rated 12 To 24V DC. The 1756-IV16 module is rated 10V To 30V DC only.
 Refer to your 1771-IV and 1756-IV16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-989 (Version 00)]

44 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Inputs

1771-IVN to 1756-IV32
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD005 1492-CONCAB005Z 1756-IV32

10-30V dc (0) 2 1 Black 18


DC-0 (+)
10-30V dc (2) 22 2 White 36
DC-1 (+)
3 Red
Input 00 3 4 Green 1
IN-0
Input 00 23 5 Orange 19
IN-16
Input 01 4 6 Blue 2
IN-1
Input 01 24 7 White/Black 20
IN-17
Input 02 5 8 Red/Black 3
IN-2
Input 02 25 9 Green/Black 21
IN-18
Input 03 6 10 Orange/Black 4
IN-3
Input 03 26 11 Blue/Black 22
IN-19
Input 04 7 12 Black/White 5
IN-4
Input 04 27 13 Red/White 23
IN-20
Input 05 8 14 Green/White 6
IN-5
Input 05 28 15 Blue/White 24
IN-21
Input 06 9 16 Black/Red 7
IN-6
Input 06 29 17 White/Red 25
IN-22
Input 07 10 18 Orange/Red 8
IN-7
Input 07 30 19 Blue/Red 26
IN-23
Input 10 13 20 Red/Green 9
IN-8
Input 10 33 21 Orange/Green 27
IN-24
Input 11 14 22 Black/White/Red 10
IN-9
Input 11 34 23 White/Black/Red 28
IN-25
- Input 12 15 24 Red/Black/White 11
IN-10
+ Input 12 35 25 Green/Black/White 29
IN-26
Input 13 16 26 Orange/Black/White 12
IN-11
Input 13 36 27 Blue/Black/White 30
IN-27
Input 14 17 28 Black/Red/Green 13
IN-12
Input 14 37 29 White/Red/Green 31
IN-28
Input 15 18 30 Red/Black/Green 14
IN-13
Input 15 38 31 Green/Black/Orange 32
IN-29
Input 16 19 32 Orange/Black/Green 15
IN-14
Input 16 39 33 Blue/White/Orange 33
IN-30
Input 17 20 34 Black/White/Orange 16
IN-15
Input 17 40 35 White/Red/Orange 34
IN-31
10-30V dc (0) 1 36 Orange/White/Blue 17
DC-0 (+)
10-30V dc (1) 11 37 White/Red/Blue 35
DC-1 (+)
10-30V dc (1) 12
10-30V dc (2) 21
10-30V dc (3) 31
10-30V dc (3) 32

1771-WN Swing Arm


From 1771-IVN
Conversion Module Installation and Application Considerations
 The input delay times for the 1771-IVN module versus 1756-IV32 module are as follows:
1771-IVN 1756-IV32
a) Off-to-On Delay 6ms (+/-2ms) 1ms (plus selectable filter)
b) On-to-Off Delay 6ms (+/-2ms) 2ms (plus selectable filter)
 The 1771-IVN has 4 groups (allowing 4 seperate power supplies) and the 1756-IV32 has 2 groups.
This module/cable combination ties Groups 0 & 1 from the 1771-IVN to Group 0 on the 1756-IV32 and it ties Groups 2 & 3
from the 1771-IVN to Group 1 on the 1756-IV32.Field wiring modification must be made to accommodate this if multiple
supplies were used. If 4 supplies were used, 2 must be removed.
 Refer to your 1771-IVN and 1756-IV32 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-934 (Version 02)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 45


Wiring Diagrams - Digital Inputs

Notes:

46 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs
1771-OA to 1756-OA8E
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014
Cable
1492-CONCAB005U 1756-OA8E

1 Black 2 Not Used


L1 A 2 White 1
L2-0
Output 00 0 3 Red 3
OUT-0
Output 01 1 4 Green 5
OUT-1
Output 02 2 5 Orange 7
OUT-2
Output 03 3 6 Blue 9
OUT-3
7 White/Black 4
L1-0
8 Red/Black 6
L1-0
9 Green/Black 8
L1 L1-0
10 Orange/Black 10
L1-0
11 Blue/Black 12
L1-1
L2 12 Black/White 14
L1-1
13 Red/White 16
L1-1
14 Green/White 18
L1-1
Output 04 4 15 Blue/White 11
LOAD OUT-4
Output 05 5 16 Black/Red 13
OUT-5
Output 06 6 17 White/Red 15
OUT-6
Output 07 7 18 Orange/Red 17
OUT-7
L2 B 19 Blue/Red 19
L2-1
20 Red/Green 20
L1-1
21
22
23
24
25

1771-WA Swing Arm


From 1771-OA

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA8E RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OA module output current limits versus 1756-OA8E limits are as follows:
1771-OA 1756-OA8E w/ 1492-CONCAB005U
a) Current/Point 1.5A 2A
b) Current/Module 6A 4A @ 60°C
c) Surge Current/Pt 4A for 8.3ms 20A for 43 ms
 The 1771-OA has eight (8) 2A, 250V fuses - 1 per output. The 1756-OA8E is electronically fused per point. Refer to the 1756 -
OA8E Installation Manual for details on electronic fusing.
 Refer to your 1771-OA and 1756-OA8E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-943 (Version 01)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 47


Wiring Diagrams - Digital Outputs

1771-OAD to 1756-OA16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
L1 A
1492-CONCAB005X 1756-OA16
L1 B
L1 C 1 Black 10
L1-0
L1 D 2 White 9
L2-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
L1 Output 02 02 5 Orange 3
OUT-2
Output 03 03 6 Blue 4
OUT-3
Output 04 04 7 White/Black 5
L2 OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
OUT-7
Output Output 10 10 11 Blue/Black 11
OUT-8
Device Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L2 L1-1
E 20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-OAD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OAD module output current limits versus 1756-OA16 limits are as follows:
1771-OAD 1756-OA16 w/ 1492-CONCAB005X
a) Current/Point 2A 0.5A
b) Current/Module 8A 4A
c) Surge Current/point 25A for 100ms 5A for 43ms
 The L2 terminal (Terminal E) on the 1771-OAD module was an optional connection, but it is required for the 1756-OA16. This
connection must be added if it was not connected.
 The 1771-OAD is rated 10V to 138V AC. The 1756-OA16 is rated 74V to 256V AC.
 Refer to your 1771-OAD and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-935 (Version 01)]

48 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OAN to 1756-OA16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD013
Cable
L1 1 1492-CONCAB005S3 1756-OA16
L1
L1 11
L2 10 1 Black 10
L2 L1-0
L2 20 2 White 9
L2-0
Output 00 2 3 Red 1
OUT-0
Output 01 3 4 Green 2
OUT-1
Output Output 02 4 5 Orange 3
OUT-2
Device Output 03 5 6 Blue 4
OUT-3

MODULE A
Output 04 6 7 White/Black 5
OUT-4
Output 05 7 8 Red/Black 6
OUT-5
Output 06 8 9 Green/Black 7
OUT-6
Output 07 9 10 Orange/Black 8
11 OUT-7
Output 10 12 Blue/Black 11
12 OUT-8
Output 11 13 Black/White 12
13 OUT-9
Output 12 14 Red/White 13
14 OUT-10
Output 13 15 Green/White 14
15 OUT-11
Output 14 16 Blue/White 15
16 OUT-12
Output 15 17 Black/Red 16
17 OUT-13
Output 16 18 White/Red 17
OUT-14
Output 17 19 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L1-1
19
L2-1
L1 21
L1 31 1756-OA16
L2 30 20 Red/Green 10 L1-0
L2 40 21 Orange/Green 9 L2-0
Output 00 22 22 Black/White/Red 1 OUT-0
Output 01 23 23 White/Black/Red 2 OUT-1
Output 02 24 24 Red/Black/White 3 OUT-2
Output 03 25 25 Green/Black/White 4 OUT-3
5

MODULE B
Output 04 26 26 Orange/Black/White OUT-4
Output 05 27 27 Blue/Black/White 6 OUT-5
Output 06 28 28 Black/Red/Green 7 OUT-6
Output 07 29 29 White/Red/Green 8 OUT-7
Output 10 32 30 Red/Black/Green 11 OUT-8
Output 11 33 31 Green/Black/Orange 12 OUT-9
Output 12 34 32 Orange/Black/Green 13 OUT-10
Output 13 35 33 Blue/White/Orange 14 OUT-11
Output 14 36 34 Black/White/Orange 15 OUT-12
Output 15 37 35 White/Red/Orange 16 OUT-13
Output 16 38 36 Orange/White/Blue 17 OUT-14
Output 17 39 37 White/Red/Blue 18 OUT-15
20 L1-1
19 L2-1
1771-WN Swing Arm
From 1771-OAN

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OAN module output current limits versus 1756-OA16 limits are as follows:
1771-OAN 1756-OA16 w/ 1492-CONCAB005S3
a) Current/Point 1A 0.5A
b) Current/Module 8A (32 pts) 2A (16 pts)
c) Surge Current/Point 10A for 25ms 5A for 43ms
 The 1771-OAN has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the 1771-OAN
together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply was used, all but
1 of the power supplies must be removed.
 The 1771-OAN did not allow connections for L2, however the 1756-OA16 requires an L2 connection for proper operation. The 1771-OAN
did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must
rewire L2 to one of these terminals.
 Refer to your 1771-OAN and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded.
 This configuration uses two (2) 1756-OA16 output modules to replace a single 1771-OAN output module. This may require the use of a
larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
[Reference Doc: 41170-942 (Version 02)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 49


Wiring Diagrams - Digital Outputs

1771-OB to 1756-OB16D

WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014 Cable
1492-C005005XF 1756-OB16D
1 Black CABLE”A”
L1 A 2 White 16
GND-0
Output 00 0 3 Red 1
OUT-0
Output 01 1 4 Green 3
OUT-1
Output 02 2 5 Orange 5
OUT-2
Output 03 3 6 Blue 7
OUT-3
7 White/Black 2
+DC-0
8 Red/Black 4
+DC-0
9 Green/Black 6
+ +DC-0
10 Orange/Black 8
+DC-0
11 Blue/Black 10
- +DC-0
12 Black/White 12
+DC-0
13 Red/White 14
+DC-0
14 Green/White
Output 04 4 15 Blue/White 9
LOAD OUT-4
Output 05 5 16 Black/Red 11
OUT-5
Output 06 6 17 White/Red 13
OUT-6
Output 07 7 18 Orange/Red 15
OUT-7
L2 B 19 Blue/Red 16
GND-0
20 Red/Green

21 NOT USED
22
23 CABLE”B”
24
32
1771-WA Swing Arm 25
17
GND-1
OUT-8
19
From 1771-OB Conversion Module 21
OUT-9
OUT-10
23
1492-CM1771-LD014 18
OUT-11
+DC-1
20
+DC-1
1 Black 22
+DC-1
L1 A 2 White 24
+DC-1
Output 00 0 3 Red 26
+DC-1
Output 01 1 4 Green 28
+DC-1
Output 02 2 5 Orange 30
25 +DC-1
Output 03 3 6 Blue
OUT-12
7 White/Black 27
OUT-13
8 Red/Black 29
OUT-14
9 Green/Black 31
+ OUT-15
10 Orange/Black 32
34 GND-1
11 Blue/Black
GND-1
- 33
12 Black/White
NOT USED
13 Red/White 35
36 NOT USED
14 Green/White
ONT USED
Output 04 4 15 Blue/White
LOAD
Output 05 5 16 Black/Red
Output 06 6 17 White/Red
Output 07 7 18 Orange/Red

L2 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25

From 1771-OB

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16D RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The 1771-OB module output current limits versus 1756-OB16D limits are as follows:
1771-OB 1756-OB16D w/ 1492-C005005XF
a) Current/Point 1.5A 2A
b) Current/Module 6A 4A @ 60°C
c) Surge Current/Point 4A for 8.3ms 4A for 10ms
 The 1771-OB has eight (8) 2A, 250V fuses - 1 per output. The 1756-OB16D is a DIAGNOSTIC MODULE. Refer to the 1756-OB16D
Installation Manual for details on diagnostics.
 Refer to your 1771-OB and 1756-OB16D Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-988 (Version 00)]

50 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OBD to 1756-OB16E

WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-OB16E
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
+ Output 02 02 5 Orange 3
OUT-2
Output 03 03 6 Blue 4
- OUT-3
Output 04 04 7 White/Black 5
OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
OUT-7
- dc Output + Output 10 10 11 Blue/Black 11
OUT-8
Device Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L2 DC-1+
E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-OBD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OBD module output current limits versus 1756-OB16E limits are as follows:
1771-OBD 1756-OB16E w/ 1492-CONCAB005X
a) Current/Point 2A 1A
b) Current/Module 8A 4A
c) Surge Current/point 4A for 10ms 2A for 10ms
 The 1771-OBD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch). The 1756-OB16E is electronically fused per
group. Refer to the 1756-OB16E Installation Manual for details on electronic fusing.
 The 1771-OBD is rated 10V to 60V DC. The 1756-OB16E is rated 10V to 31.2V DC. If the load source voltage is greater than 30V
DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
 Refer to your 1771-OBD and 1756-OB16E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-936 (Version 01)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 51


Wiring Diagrams - Digital Outputs

1771-OBD to 1756-OC8
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD008F 1492-CONCAB005S1 1756-OC8
1 Black 2 DC-0(+)
2 White 1 OUT-0
3 Red 3 OUT-1
4 Green 5 OUT-2
5 Orange 7 OUT-3
9 RTN OUT-0
6 Blue 4 DC-0(+)

MODULE A
7 White/Black 6 DC-0(+)
8 Red/Black 8 DC-0(+)
9 Green/Black 10 RTN OUT-0
DC(+) A 10 Orange/Black 12 DC-1(+)
DC(+) B 11 Blue/Black 14 DC-1(+)
DC(+) C 12 Black/White 16 DC-1(+)
DC(+) D 13 Red/White 18
+ DC-1(+)
Output 00 00 14 Green/White 11 OUT-4
Output 01 01 15 Blue/White 13 OUT-5
-
Output 02 02 16 Black/Red 15 OUT-6
Output 03 03 17 White/Red 17 OUT-7
Output 04 04 19
LOAD RTN OUT-1
Output 05 05 18 Orange/Red 20 RTN OUT-1
Output 06 06
Output 07 07 1756-OC8
Output 10 10 19 Blue/Red 2 DC-0(+)
Output 11 11 20 Red/Green 1 OUT-0
Output 12 12 21 Orange/Green 3 OUT-1
Output 13 13 22 Black/White/Red 5 OUT-2
Output 14 14 23 White/Black/Red 7 OUT-3
Output 15 15 9 RTN OUT-0

MODULE B
Output 16 16 24 Red/Black/White 4
DC-0(+)
Output 17 17 25 Green/Black/White 6
DC-0(+)
26 Orange/Black/White 8
DC(-) DC-0(+)
E 27 Blue/Black/White 10
RTN OUT-0
28 Black/Red/Green 12
DC-1(+)
29 White/Red/Green 14
DC-1(+)
30 Red/Black/Green 16
DC-1(+)
31 Green/Black/Orange 18
1771-WH, WHF, WHFB Swing Arm DC-1(+)
32 Orange/Black/Green 11
From 1771-OBD OUT-4
33 Blue/White/Orange 13
OUT-5
34 Black/White/Orange 15
OUT-6
35 White/Red/Orange 17
OUT-7
36 19
RTN OUT-1
37 White/Red/Blue 20
RTN OUT-1

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OC8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OBD module output current limits versus 1756-OC8 limits are as follows:
1771-OBD 1756-OC8 w/ 1492-CONCAB005S1
a) Current/Point 2A 2A
b) Current /Module 8A 8A
c) Surge Current /Point 4A for 10ms 4A for 10ms
 The 1771-OBD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch ). The 1756-OC8 is NOT fused ,as such a
2AG fuse clip and 10A fuse is provided on the 1492-CM1771-LD008F conversion module.
 The 1771-OBD is rated 10V to 60V DC. The 1756-OC8 is rated 30V to 60V DC. If the load source voltages is less
than 30V DC, then use 1756-OB16E with the 1492-CM1771-LD006 conversion module.
 This configuration uses two(2) 1756-OC8 output modules to replace a single 1771-OBD output module. This may require
the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for
this possibility.
 Refer to your 1771-OBD and 1756-OC8 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41170-937 (Version 01)]

52 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OBDS to 1756-OB16E
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-OB16E
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
Output 02 02 5 Orange 3
+ OUT-2
Output 03 03 6 Blue 4
OUT-3
- Output 04 04 7 White/Black 5
OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
- + OUT-7
dc Output Output 10 10 11 Blue/Black 11
Device OUT-8
Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
DC-1+
- dc E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1171-OBDS

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OB16E RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OBDS module output current limits versus 1756-OB16E limits are as follows:
1771-OBDS 1756-OB16E w/ 1492-CONCAB005X
a) Current/Point 1A 1A
b) Current/Module 8A 8A
c) Surge Current/Point 4A for 10ms 2A for 10ms
 The 1771-OBDS has a single 12A, 250V rectifier fuse (1/4 x 1-1/4 inch). The 1756-OB16E is electronically fused per
group. Refer to the 1756-OB16E Installation Manual for details on electronic fusing.
 The 1771-OBDS is rated 10V to 40V DC. The 1756-OB16E is rated 10V to 31.2V DC. If the load source voltage is greater
than 30V DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
 Refer to your 1771-OBDS and 1756-OB16E Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-005 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 53


Wiring Diagrams - Digital Outputs

1771-OBN to 1756-OB32

WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD009F 1492-CONCAB005Zc 1756-OB32
10-30V dc(0) 1
10-30V dc(1) 11 1 Black 18 DC-0(+)
10-30V dc(2) 21 2 White 36 DC-1(+)
10-30V dc(3) 31 3 Red
Output 00 2 4 Green 1 OUT-0
Output 00 22 5 Orange 19 OUT-16
Output 01 3 6 Blue 2 OUT-1
Output 01 23 7 White/Black 20 OUT-17
Output 02 4 8 Red/Black 3 OUT-2
Output 02 24 9 Green/Black 21 OUT-18
Output 03 5 10 Orange/Black 4
+ OUT-3
Output 03 25 11 Blue/Black 22 OUT-19
- Output 04 6 12 Black/White 5 OUT-4
Output 04 26 13 Red/White 23 OUT-20
Output 05 7 14 Green/White 6
LOAD OUT-5
Output 05 27 15 Blue/White 24 OUT-21
Output 06 8 16 Black/Red 7 OUT-6
Output 06 28 17 White/Red 25 OUT-22
Output 07 9 18 Orange/Red 8 OUT-7
Output 07 29 19 Blue/Red 26 OUT-23
Output 10 12 20 Red/Green 9 OUT-8
Output 10 32 21 Orange/Green 27
22
OUT-24
Output 11 13 Black/White/Red 10 OUT-9
Output 11 33 23 White/Black/Red 28 OUT-25
Output 12 14 24 Red/Black/White 11 OUT-10
Output 12 34 25 Green/Black/White 29
OUT-26
Output 13 15 26 Orange/Black/White 12
OUT-11
Output 13 35 27 Blue/Black/White 30
OUT-27
Output 14 16 28 Black/Red/Green 13
OUT-12
Output 14 36 29 White/Red/Orange 31
OUT-28
Output 15 17 30 Red/Black/Green 14
OUT-13
Output 15 37 31 Green/Black/Orange 32
OUT-29
Output 16 18 32 Orange/Black/Green 15
OUT-14
Output 16 38 33 Blue/White/Orange 33
OUT-30
Output 17 19 34 Black/White/Orange 16
OUT-15
Output 17 39 35 White/Red/Orange 34
OUT-31
Common 0 10 36 Orange/White/Blue 17
RTN OUT-0
Common 1 20 37 White/Red/Blue 35
RTN OUT-1
Common 2 30
Common 3 40

1771-WN Swing Arm


From 1771-OBN

Conversion Module Installation and Application Considerations


cThe 1771-OBN module output current limits versus 1756-OB32 limits are as follows:
1771-OBN 1756-OB32w/1492-CONCAB005Z
a) Current/Point 0.5A 0.35A @ 60˚C
b) Current/Module 8A 6A @ 60˚C
c) Surge Current/Point 2A for 10ms 1A for 10ms
d The 1771-OBN has four (4) 4A, 250V rectifier fuses. The 1756-OB32 is NOT fused, as such four (4) 2AG fuse clips and 4A
fuses are provided on the 1492-CM1771-LD009F conversion module.
e The 1492-CONAB005Z is limited to 3A per pin.
f The 1771-OBN has 4 groups (allowing 4 separate power supplies) and the 1756-OB32 has 2 groups. This module/cable
combination ties Groups 0 & 1 from the 1771-OBN to Group 0 on the 1756-OB32 and Groups 2 & 3 from the 1771-OBN to
Group 1 on the 1756-OB32. Field wiring modification must be made to accommodate this if multiple supplies were used.
If 4 supplies were used, 2 must be removed.
g Refer to your 1771-OBN and 1756-OB32 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. 41170-938 (01)

54 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OC to 1756-OC8
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014
Cable
1492-CONCAB005V 1756-OC8
1 Black 9
RTN-0
+DC A 2 White 10
RTN-0
Output 00 0 3 Red 1
OUT-0
Output 01 1 4 Green 3
OUT-1
Output 02 2 5 Orange 5
OUT-2
Output 03 3 6 Blue 7
OUT-3
7 White/Black 2
+DC-0
8 Red/Black 4
+DC-0
9 Green/Black 6
+DC +DC-0
10 Orange/Black 8
+DC-0
11 Blue/Black 12
+DC-1
-DC 12 Black/White 14
+DC-1
13 Red/White 16
+DC-1
14 Green/White 18
+DC-1
Output 04 4 15 Blue/White 11
LOAD OUT-4
Output 05 5 16 Black/Red 13
OUT-5
Output 06 6 17 White/Red 15
OUT-6
Output 07 7 18 Orange/Red 17
OUT-7
RTN B 19 Blue/Red 19
RTN-1
20 Red/Green 20
RTN-1
21
22
23
24
25

1771-WA Swing Arm


From 1771-OC

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OC8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OC module output current limits versus 1756-OC8 limits are as follows:
1771-OC 1756-OC8 w/ 1492-CONCAB005V
a) Current/Point 1.5A 2A
b) Current/Module 8A 8A @ 60°C
c) Surge Current/Point 4A for 1.0ms 4A for 10ms
 The 1771-OC has eight (8) 2A, 250V fuses - 1 per output. Refer to the 1756-OC8 Installation Manual for details.
 Refer to your 1771-OC and 1756-OC8 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded. [Reference Doc: 41171-020 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 55


Wiring Diagrams - Digital Outputs

1771-OD to 1756-OA16I

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and output module). Read and understand these considerations
before installation. In addition, refer to the current draw requirements of the existing loads for this configuration
to ensure they are within the current ratings of the 1756 output module.
CONVERSION MODULE
1492-CM1771-LD012
1
1
2 1492-C005005XM
3
4
1756-OA16I
5
4
JMP0
3 6
Orange
Blue
CABLE”A” 2
L1-0
N.C. 7 White/Black 1
L2-0
N.O. 8 Red/Black 4
L1-1
2 1 9 Green/Black 3
JMP1 L2-1
4 3 10 Orange/Black 6
L1-2
N.C. 11 Blue/Black 5
L2-2
N.O. 12 Black/White 8
L1-3
2 1 13 Red/White 7
JMP2 L2-3
3 14 Green/White 10
4 L1-4
L2 L1 N.C. 15 Blue/White 9
L1-0 1 L2-4
LOAD N.O. 16 Black/Red 12
L2-0 L1-5
2 2 1 17 White/Red 11
L1-1 L2-5
3 JMP3 18
4 3 Orange/Red
L2-1 4 25 NOT USED
N.C. 19 Blue/Red
L1-2 5 26 NOT USED
N.O. 20 Red/Green
L2-2 6 2 27 NOT USED
1 21 Orange/Green
L1-3 7 JMP4 28 NOT USED
4 3 22 Black/White/Red
L2-3 8 29 NOT USED
N.C. 23 White/Black/Red
L1-4 9 30 NOT USED
N.O. 24 Red/Black/White
L2-4 10 2 1 31 NOT USED
25 Green/Black/White
L1-5 11 JMP5 32 NOT USED
4 3 26 Orange/Black/White
L2-5 12 33 NOT USED
N.C. 27 Blue/Black/White
34 NOT USED
N.O. 28 Black/Red/Green
NOT USED
35
2
4
JMP6
1
3
29
30
White/Red/Green
Red/Black/Green
CABLE”B” 36 NOT USED
14
N.C. 31 Green/Black/Orange L1-6
13
N.O. 32 Orange/Black/Green L2-6
2 1 16
33 Blue/White/Orange L1-7
JMP7 15
3 34 Black/White/Orange L2-7
1771-WD Swing Arm 4
N.C. 35 White/Red/Orange
18 L1-8
17
From 1771-OD N.O. 36 Orange/White/Blue
20
L2-8
2 1 37 L1-9
19
L2-9
CONVERSION MODULE 22
L1-10
1492-CM1771-LD012 21
24
L2-10
L1-11
1 23 L2-11
2
3
4
5 Orange
JMP0 6
4 3 Blue
N.C. 7 White/Black
N.O. 8 Red/Black
2 1 9 Green/Black
JMP1 10
4 3 Orange/Black
N.C. 11 Blue/Black
N.O. 12 Black/White
2 1 13 Red/White
JMP2 14 Green/White
4 3
L1-6 N.C. 15 Blue/White
1
L2-6 N.O. 16 Black/Red
2 2 1 17 White/Red
L1-7 3 JMP3
4 3 18 Orange/Red
L2-7 4 N.C. 19 Blue/Red
L1-8 5
N.O. 20 Red/Green
L2-8 6 2 1 21 Orange/Green
L1-9 7 JMP4
L2-9 4 3 22 Black/White/Red
8 N.C. 23 White/Black/Red
L1-10 9
N.O. 24 Red/Black/White
L2-10 10 2 1
L2 L1 25 Green/Black/White
L1-11 11 JMP5
LOAD 4 3 26 Orange/Black/White
L2-11 12
N.C. 27 Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange
N.O. 36 Orange/White/Blue

1771-WD Swing Arm 2 1 37

From 1771-OD

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 This Bul. 1492 cable consists of 2 separate cables (cable “A” and “B”) wired to one 1756-IM16I RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
2 The 1771-OD module output resistive current limits versus 1756-OA16I limits are as follows:
(NOTE: for switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OD 1756-OA16I w/ 1492-CONCAB005XM
a) Current/Point 0.2A @ 138V AC 2A @ 240V AC
1A @ 30V DC 2A @ 30V DC
0.25A@ 125V DC 0.25A @ 125V DC
2 The 1492-COO5005XM is limited to 3A per pin.
3 The 1771-OD module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OD jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O.. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
4 Refer to your 1771-OD and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. 41170-994 (01)

56 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OD16 to 1756-OA16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD010F

NotUsed 9 1
NotUsed 10 2 Cable
NotUsed 19 3 1492-CONCAB005Y 1756-OA16I
NotUsed 20 4
L1-0 2 5 Orange 2
L1-0
Output 0 1 6 Blue 1
L1 LOAD OUT-0
L1-1 4 7 White/Black 4
L1-1
Output 1 3 8 Red/Black 3
OUT-1
L1-2 6 9 Green/Black 6
L2 L1-2
Output 2 5 10 Orange/Black 5
OUT-2
L1-3 8 11 Blue/Black 8
L1-3
Output 3 7 12 Black/White 7
OUT-3
L1-4 12 13 Red/White 10
L1-4
Output 4 11 14 Green/White 9
OUT-4
L1-5 14 15 Blue/White 12
L1-5
Output 5 13 16 Black/Red 11
OUT-5
L1-6 16 17 White/Red 14
L1-6
Output 6 15 18 Orange/Red 13
OUT-6
L1-7 18 19 Blue/Red 16
L1-7
Output 7 17 20 Red/Green 15
OUT-7
L1-8 22 21 Orange/Green 18
L1-8
Output 8 21 22 Black/White/Red 17
OUT-8
L1-9 24 23 White/Black/Red 20
L1-9
Output 9 23 24 Red/Black/White 19
OUT-9
L1-10 26 25 Green/Black/White 22
L1-10
Output 10 25 26 Orange/Black/White 21
OUT-10
L1-11 28 27 Blue/Black/White 24
L1-11
Output 11 27 28 Black/Red/Green 23
OUT-11
L1-12 32 29 White/Red/Green 26
L1-12
Output 12 31 30 Red/Black/Green 25
OUT-12
L1-13 34 31 Green/Black/Orange 28
L1-13
Output 13 33 32 Orange/Black/Green 27
OUT-13
L1-14 36 33 Blue/White/Orange 30
L1-14
Output 14 35 34 Black/White/Orange 29
OUT-14
L1-15 38 35 White/Red/Orange 32
L1-15
Output 15 37 36 Orange/White/Blue 31
OUT-15
Not used 29 37
Not used 30
Not used 39
Not used 40

1771-WN Swing Arm


From 1771-OD16

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16I RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OD16 module output current limits versus 1756-OA16I limits are as follows:
1771-OD16 1756-OA16I w/ 1492-CONCAB005Y
a) Current/Point 2A 1A
b) Current/Module 8A 4A
b) Surge Current/Point 20A for 100ms 20A for 43ms
 The 1771-OD16 has sixteen (16) 3A ,250V recifier fuses. The 1756-OA16I is NOT fused,as such sixteen (16) 2AG fuse
clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
 The 1771-OD16 is rated 74V to 138V AC and 105V to 138V DC. The 1756-OA16I is rated 74V to 265V AC. A1756 isolated
output module with an equivalent DC voltage range to convert the1771 -OD16 is not available.
 Refer to your 1771-OD16 and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756
output module rating are not exceeded. [Reference Doc: 41170-939 (Version 01)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 57


Wiring Diagrams - Digital Outputs

1771-ODD to 1756-OA16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD010F

Not Used 9 1
Not Used 10 2 Cable
Not Used 19 3 1492-CONCAB005Y 1756-OA16I
Not Used 20 4
L1-0 2 5 Orange 2
L1-0
Ouput 0 1 6 Blue 1
L1 LOAD OUT-0
L1-1 4 7 White/Black 4
L1-1
Ouput 1 3 8 Red/Black 3
OUT-1
L2 L1-2 6 9 Green/Black 6
L1-2
Ouput 2 5 10 Orange/Black 5
OUT-2
L1-3 8 11 Blue/Black 8
L1-3
Ouput 3 7 12 Black/White 7
OUT-3
L1-4 12 13 Red/White 10
L1-4
Ouput 4 11 14 Green/White 9
OUT-4
L1-5 14 15 Blue/White 12
L1-5
Ouput 5 13 16 Black/Red 11
OUT-5
L1-6 16 17 White/Red 14
L1-6
Ouput 6 15 18 Orange/Red 13
OUT-6
L1-7 18 19 Blue/Red 16
L1-7
Ouput 7 17 20 Red/Green 15
OUT-7
L1-8 22 21 Orange/Green 18
L1-8
Ouput 8 21 22 Black/White/Red 17
OUT-8
L1-9 24 23 White/Black/Red 20
L1-9
Ouput 9 23 24 Red/Black/White 19
OUT-9
L1-10 26 25 Green/Black/White 22
L1-10
Ouput 10 25 26 Orange/Black/White 21
OUT-10
L1-11 28 27 Blue/Black/White 24
L1-11
Ouput 11 27 28 Black/Red/Green 23
OUT-11
L1-12 32 29 White/Red/Green 26
L1-12
Ouput 12 31 30 Red/Black/Green 25
OUT-12
L1-13 34 31 Green/Black/Orange 28
L1-13
Ouput 13 33 32 Orange/Black/Green 27
OUT-13
L1-14 36 33 Blue/White/Orange 30
L1-14
Ouput 14 35 34 Black/White/Orange 29
OUT-14
L1-15 38 35 White/Red/Orange 32
L1-15
Ouput 15 37 36 Orange/White/Blue 31
OUT-15
Not Used 29 37
Not Used 30
Not Used 39
Not Used 40

1771-WN Swing Arm


From 1771-ODD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16I RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-ODD module output current limits versus 1756-OA16I limits are as follows:
1771-ODD 1756-OA16I w/ 1492-CONCAB005Y
a) Current/Point 2A 2A
b) Current/Module 8A 5A
c) Surge Current/Point 20A for 100ms 20A for 43ms
 The 1771-ODD has sixteen (16) 3A, 250V rectifier fuses. The 1756-OA16I is NOT fused, as such sixteen(16) 2AG fuses
and clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
 The 1771-ODD is rated 74V to 138V AC. The 1756-OA16I is rated 74V to 265V AC.
 Refer to your 1771-ODD and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756
output module ratings are not exceeded. [Reference Doc: 41171-009 (Version 00)]

58 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-ODZ to 1756-OA16I
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
IMPORTANT
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2
Cable
3
4
1492-CONCAB005Y 1492-C005005XP 1756-OA16I
JMP0
5
6
Orange
CABLE”A”
4 3 Blue 2
L1-0
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 1 L2-0
2 1 9 Green/Black 3
JMP1 L2-1
4 3 10 Orange/Black 6 L1-1
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 5
L2-2
2 1 13 Red/White 7
JMP2 L2-3
4 3 14 Green/White 10
L1-2
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 9 L2-4
+V0/1 2 2 1 17 White/Red 11 L2-5
Out-1 N.O./N.C. 3 JMP3
L2 LOAD 4 3 18 Orange/Red 14
Out-2 N.O./N.C. 4 L1-3
N.C. 19 Blue/Red 16 L1-3
+V2/3 5
N.O. 20 Red/Green 13 L2-6
Out-3 N.O./N.C. 6 2 1 21 Orange/Green 15
Out-4 N.O./N.C. 7 JMP4 L2-7
+ 4 3 22 Black/White/Red
+V4/5 8 N.C. 23 White/Black/Red
Out-5 N.O./N.C. 9
- LOAD N.O. 24 Red/Black/White
Out-6 N.O./N.C. 10 2 1 25 Green/Black/White
+V6/7 11 JMP5
4 3 26 Orange/Black/White
Out-7 N.O./N.C. 12 27
N.C. Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35
1771-WD Swing Arm N.O. 36
White/Red/Orange
Orange/White/Blue
33
34
NOT USED
NOT USED
2 1 37
From 1771-ODZ 35
36
NOT USED
NOT USED

Conversion Module
1492-CM1771-LD012
1
2
3
4
5
CABLE”B”
Orange
JMP0 6
4 3 Blue 18 L1-4
N.C. 7 White/Black 20
L1-4
N.O. 8 Red/Black 17
2 L2-8
1 9 Green/Black 19
JMP1 10 L2-9
4 3 Orange/Black 22
L1-5
N.C. 11 Blue/Black 24
L1-5
N.O. 12 Black/White 21 L2-10
2 1 13 Red/White 23
JMP2 L2-11
4 3 14 Green/White 26
L1-4
Out-0 N.O./N.C. N.C. 15 Blue/White 28
1 L1-6
L1 N.O. 16 Black/Red 25 L2-12
+V0/1 2 2 1 17 White/Red 27 L2-13
Out-1 N.O./N.C. 3 JMP3
L2 LOAD 4 3 18 Orange/Red 30
Out-2 N.O./N.C. 4 L1-7
N.C. 19 Blue/Red 32
+V2/3 5 L1-7
N.O. 20 Red/Green 29 L2-14
Out-3 N.O./N.C. 6 2 1 21 Orange/Green 31
Out-4 N.O./N.C. 7 JMP4 L2-15
+ 4 3 22 Black/White/Red
+V4/5 8 N.C. 23 White/Black/Red
Out-5 N.O./N.C. 9
- LOAD N.O. 24 Red/Black/White
Out-6 N.O./N.C. 10 2 1 25 Green/Black/White
+V6/7 11 JMP5
4 3 26 Orange/Black/White
Out-7 N.O./N.C. 12
N.C. 27 Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
N.C. 35 White/Red/Orange

1771-WD Swing Arm 2


N.O.
1
36
37
Orange/White/Blue

From 1771-ODZ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16I RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The 1771-ODZ module output resistive current limits versus 1756-OA16I limits are as follows:
1771-ODZ 1756-OA16I w/ 1492-C005005XP
a) Current/Point 2A 2A
b) Current/Module 6A 5A @ 60°C
c) Surge Current/Point 20A for 100ms 20A for 43ms
 The 1771-ODZ module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-ODZ jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-ODZ and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-016 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 59


Wiring Diagrams - Digital Outputs

1771-OG to 1756-OG16
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LA003 1492-C005005XS 1756-OG16
+ + DC A 13 Red/White CABLE”A” 10
+ DC -0
+ Output 0 0 25 Green/Black/White 1
Output OUT-0
5V DC - Output 1 1 24 Red/Black/White 2
- Device OUT-1
SUPPLY Output 2 2 23 White/Black/Red 3
OUT-2
Output 3 3 22 Black/White/Red 4
OUT-3
Output 4 4 21 Orange/Green 5
OUT-4
Output 5 5 19 Blue/Red 6
OUT-5
Output 6 6 18 Orange/Red 7
OUT-6
Output 7 7 17 White/Red 8
Common OUT-7
B 16 Black/Red 9
- DC -0
1 20
+ DC -1
2 11
OUT-8
3 12
OUT-9
4 13
OUT-10
5 14
OUT-11
6 15
OUT-12
7 16
1771-WC Swing Arm 8 17
OUT-13
OUT-14
From 1771-OG 9 18
OUT-15
10 19
11 - DC -1
12
14
15
20

SH

Conversion Module
1492-CM1771-LA003
+ + DC A 13 Red/White
+ Output 8 0 25 Green/Black/White
Output
5V DC - Output 9 1 24 Red/Black/White
- Device Output 10
SUPPLY 2 23 White/Black/Red
Output 11 3 22 Black/White/Red
Output 12 4 21 Orange/Green
Output 13 5 19 Blue/Red
Output 14 6 18 Orange/Red
Output 15 7 17 White/Red
Common B 16 Black/Red
1
2 CABLE”B”
3
4
5
6
7
1771-WC Swing Arm 8
From 1771-OG 9
10
11
12
14
15
20

SH

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OG16 RTB. Each cable can be either 0.5M or
1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The input delay times for the 1771-OG module versus the 1756-OG16 module are as follows:
1771-OG 1756-OG16 w/ 1492-C005005XS
a) Off-to-On Delay 1ms (+/-10ms) 45ms max (plus selectable filter)
b) On-to-Off Delay 1ms (+/-10ms) 145ms max (plus selectable filter)
 The 1771-OG module is rated 5V DC TTL INPUT MODULE. The 1756-OG16 module is rated 5V DC TTL INPUT MODULE only.
 Refer to your 1771-OG and 1756-OG16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41171-028 (Version 00)]

60 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OGD to 1756-OG16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006
Cable
+ dc A 1492-CONCAB005X 1756-OG16
+ dc B
+ dc C 1 Black 10
DC-0+
+ dc D 2 White 9
RTN OUT-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
Output 02 02 5 Orange 3
+ OUT-2
Output 03 03 6 Blue 4
OUT-3
- Output 04 04 7 White/Black 5
OUT-4
Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
- + OUT-7
dc Output Output 10 10 11 Blue/Black 11
Device OUT-8
Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
DC-1+
- dc E 20 Red/Green 19
RTN OUT-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1171-OGD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OG16 RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OGD module output current limits versus 1756-OG16 limits are as follows:
1771-OGD 1756-OG16 w/ 1492-CONCAB005X
a) Current/Point 1mA 24mA
b) Current/Module 310mA 384mA
 The 1771-OGD has a single 10A, 250V rectifier fuse (1/4 x 1-1/4 inch). The 1756-OG16 is electronically fused per
group. Refer to the 1756-OG16 Installation Manual for details on electronic fusing.
 The 1771-OGD is rated 10V to 60V DC. The 1756-OG16 is rated 10V to 31.2V DC.
 Refer to your 1771-OGD and 1756-OG16 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-006 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 61


Wiring Diagrams - Digital Outputs

1771-OM to 1756-OA16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014 Cable
1492-C005005XG 1756-OA16
1 Black
L1-0 A 2 White Cable “A”
OUTPUT 00 0 3 Red 1
OUT-0
OUTPUT 01 1 4 Green 2
OUT-1
OUTPUT 02 2 5 Orange 3
OUT-2
OUTPUT 03 3 6 Blue 4
OUT-3
7 White/Black 10
L1-0
8 Red/Black
L1 9 Green/Black
+
10 Orange/Black
11 Blue/Black
-
L2 12 Black/White
13 Red/White
14 Green/White
OUTPUT 04 4 15 Blue/White 5
LOAD OUT-4
OUTPUT 05 5 16 Black/Red 6
OUT-5
OUTPUT 06 6 17 White/Red 7
OUT-6
OUTPUT 07 7 18 Orange/Red 8
OUT-7
L2-0 B 19 Blue/Red 9 L2-0
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25 Cable “B”
11
OUT-8
12
From 1771-OM 13
OUT-9
OUT-10
Conversion Module 14
OUT-11
20
1492-CM1771-LD014 L1-1

1 Black
L1-1 A 2 White
INPUT 08 0 3 Red
INPUT 09 1 4 Green
INPUT 10 15
2 5 Orange OUT-12
INPUT 11 16
3 6 Blue OUT-13
17
7 White/Black OUT-14
18
8 Red/Black OUT-15
19
L1 9 Green/Black L2-1
10 Orange/Black
11 Blue/Black

L2 12 Black/White
13 Red/White
14 Green/White
INPUT 12 4 15 Blue/White
LOAD
INPUT 13 5 16 Black/Red
INPUT 14 6 17 White/Red
INPUT 15 7 18 Orange/Red
L2-1 B 19 Blue/Red
20 Red/Green

21
22
23
24
1771-WA Swing Arm 25

From 1771-OM

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16 RTB. Each cable can be either 0.5M
or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
 The 1771-OM module output current limits versus 1756-OA16 limits are as follows:
1771-OM 1756-OA16 w/ 1492-CONCAB005XG
a) Current/Point 2A 0.5 @ 60°C
b) Current/Module 6A 4A @ 60°C
c) Surge Current/Point 20A for 100ms 5A for 43ms
 The 1771-OM module is rated 220V to 240V AC. The 1756-OA16 module is rated 74V to 265V AC only.
 Refer to your 1771-OM and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded. [Reference Doc: 41171-022 (Version 00)]

62 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OMD to 1756-OA16
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD006

Cable
L1 A
1492-CONCAB005X 1756-OA16
L1 B
L1 C 1 Black 10
L1-0+
L1 D 2 White 9
L2-0
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 2
OUT-1
L1 Output 02 02 5 Orange 3
OUT-2
Output 03 03 6 Blue 4
OUT-3
Output 04 04 7 White/Black 5
OUT-4
L2 Output 05 05 8 Red/Black 6
OUT-5
Output 06 06 9 Green/Black 7
OUT-6
Output 07 07 10 Orange/Black 8
- + OUT-7
Output 10 10 11 Blue/Black 11
LOAD OUT-8
Output 11 11 12 Black/White 12
OUT-9
Output 12 12 13 Red/White 13
OUT-10
Output 13 13 14 Green/White 14
OUT-11
Output 14 14 15 Blue/White 15
OUT-12
Output 15 15 16 Black/Red 16
OUT-13
Output 16 16 17 White/Red 17
OUT-14
Output 17 17 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L1-1+
L2 E 20 Red/Green 19
L2-1
21
22
23
24
25

1771-WH, WHF, WHFB Swing Arm


From 1771-OMD

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OMD module output current limits versus 1756-OA16 limits are as follows:
1771-OMD 1756-OA16 w/ 1492-CONCAB005X
a) Current/Point 2A 0.5A
b) Current/Module 8A 4A
c) Surge Current/Point 25A for 100ms 5A for 43ms
 The 1771-OMD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch). The 1756-OA16 has a mechanical 3.15A @250V AC
slow blow fuse. Refer to the 1756-OA16 Installation Manual for details on electronic fusing.
 The 1771-OMD is rated 184V to 250V AC. The 1756-OA16 is rated 74V to 265V AC. If the load source voltage is greater than
30V DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
 Refer to your 1771-OMD and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756
output module ratings are not exceeded. [Reference Doc: 41171-007 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 63


Wiring Diagrams - Digital Outputs

1771-ON to 1756-ON8

WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD014
Cable
1492-CONCAB005W 1756-ON8
1 Black 9
NOT USED
L1 A 2 White 2
L1-0
Output 00 0 3 Red 1
OUT-0
Output 01 1 4 Green 3
OUT-1
Output 02 2 5 Orange 5
OUT-2
Output 03 3 6 Blue 7
OUT-3
7 White/Black 4
L1-0
8 Red/Black 6
L1-0
9 Green/Black 8
L1 L1-0
10 Orange/Black 10
L1-0
11 Blue/Black 12
L1-1
L2 12 Black/White 14
L1-1
13 Red/White 16
L1-1
14 Green/White 18
L1-1
Output 04 4 15 Blue/White 11
LOAD OUT-4
Output 05 5 16 Black/Red 13
OUT-5
Output 06 6 17 White/Red 15
OUT-6
Output 07 7 18 Orange/Red 17
OUT-7
L2 B 19 Blue/Red 19
NOT USED
20 Red/Green 20
L1-1
21
22
23
24
25

1771-WA Swing Arm


From 1771-ON

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-ON8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-ON module output current limits versus 1756-ON8 limits are as follows:
1771-ON 1756-ON8 w/ 1492-CONCAB005W
a) Current/Point 1.5A 2A
b) Current/Module 6A 5A @ 60°C
c) Surge Current/Point 4A for 10ms 20A for 43ms
 The 1771-ON has eight (8) 2A, 250V fuses - 1 per output. The 1756-ON8 is electronically fused per point. Refer to the 1756-ON8
Installation Manual for details on electronic fusing.
 Refer to your 1771-ON and 1756-ON8 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded. [Reference Doc: 41171-021 (Version 00)]

64 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OND to 1756-ON8
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module Cable


1492-CM1771-LD006 1492-CONCAB005S2 1756-ON8
2 L1-0
4
L1 A L1-0
6
L1 B L1-0
8
L1-0
L1 C 1 Black 10
L1-0
L1 D 2 White
9 NOT USED
Output 00 00 3 Red 1
OUT-0
Output 01 01 4 Green 3
OUT-1
L1 Output 02 02 5 Orange 5
OUT-2
Output 03 03 6 Blue 7
OUT-3
Output 04 04 7 White/Black 11
OUT-4
L2 Output 05 05 8 Red/Black 13
OUT-5
Output 06 06 9 Green/Black 15
OUT-6
Output 07 07 10 Orange/Black 17
OUT-7
Output Output 10 10 11 Blue/Black
19 NOT USED
Device Output 11 11 12 Black/White
L1-1
Output 12 12 13 Red/White 14
L1-1
Output 13 13 14 Green/White 16
L1-1
Output 14 14 15 Blue/White 18
L1-1
Output 15 15 16 Black/Red 20
L1-1
Output 16 16 17 White/Red
Output 17 17 18 Orange/Red
19 Blue/Red
L2 E 20 Red/Green 1756-ON8
21 2
22 L1-0
4
23 L1-0
6
24 L1-0
8
25 L1-0
10
L1-0
9 NOT USED
1
OUT-8
3
OUT-9
5
OUT-10
1771-WH, WHF Swing Arm 7
OUT-11
From 1771-OND 11
OUT-12
13
OUT-13
15
OUT-14
17
OUT-15
19 NOT USED
L1-1
14
L1-1
16
Conversion Module Installation and Application Considerations L1-1
18
L1-1
 This Bul. 1492 cable consists of a cable wired to two 1756-ON8 RTB. Recommended cable lengths of 20
L1-1
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OND module output current limits versus (2)1756-ON8 limits are as follows:
1771-OND 1756-ON8 w/ 1492-CONCAB005S2
a) Current/Point 2A 2A
b) Current/Module 8A 5A
c) Surge Current/Point 25A for 100ms 20A for 43ms
 The L2 terminal (Terminal E) on the 1771-ON8 module was an optional connection, but it is required for the 1756-OA16.
This connection must be added if it was not connected.
 The 1771-OND is rated 24V AC. The 1756-ON8 is rated 10V to 30V AC.
 Refer to your 1771-OND and 1756-ON8 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-008 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 65


Wiring Diagrams - Digital Outputs

1771-OQ to 1756-OB16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LA004 Cable
1492-C005005XT 1756-OB16I
Not Used
DC-1
18 18 Orange/Red Cable “A” 2
17 17 White/Red
1 DC-1
OUTPUT-0 16 16 Black/Red OUTPUT-0
LOAD DC-1 4
15 15 Blue/White DC-1
OUTPUT 1 14 14 Green/White 3
+ OUTPUT 1
OUTPUT 2 13 13 Red/White 5
OUTPUT 2
DC-2 12 12 Black/White 6
- OUTPUT 3 11 11 Blue/Black 7 DC-2
10 OUTPUT 3
LOAD DC-2 10 Orange/Black 8
DC-2
DC-3 9 9 Green/Black 10
DC-3
OUTPUT-4 8 8 Red/Black 9
OUTPUT-4
DC-3 7 7 White/Black 12
DC-3
OUTPUT 5 6 6 Blue 11
OUTPUT 5
OUTPUT 6 5 5 Orange 13
OUTPUT 6
DC-4 4 4 Green 14 DC-4
OUTPUT 7 3 3 Red 15
OUTPUT 7
DC-4 2 2 White 16
DC-4
Not Used 1 1 Black

18
1771-WF Swing Arm 17 DC-1
OUTPUT-8
20
From 1771-OQ DC-1
19
OUTPUT 9
21
OUTPUT 10
22
DC-2
Conversion Module 23
OUTPUT 11
24
1492-CM1771-LA004 Cable “B” 26
DC-2
DC-3
25
OUTPUT-12
28
Not Used 18 18 Orange/Red DC-3
27
DC-1 17 17 White/Red OUTPUT 13
29
OUTPUT-8 16 16 Black/Red OUTPUT 14
LOAD 30 DC-4
DC-1 15 15 Blue/White 31
OUTPUT 9 14 14 Green/White
OUTPUT 15
32
+ OUTPUT 10 13 13 Red/White DC-4
DC-2 12 12 Black/White
33 NOT USED
- 11 11 34 NOT USED
OUTPUT 11 Blue/Black
35 NOT USED
DC-2 10 10 Orange/Black
LOAD 36 NOT USED
DC-3 9 9 Green/Black
OUTPUT-12 8 8 Red/Black
DC-3 7 7 White/Black
OUTPUT 13 6 6 Blue

OUTPUT 14 5 5 Orange

DC-4 4 4 Green
OUTPUT 15 3 3 Red

DC-4 2 2 White
Not Used 1 1 Black

1771-WF Swing Arm


From 1771-OQ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16I RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The 1771-OQ module output resistive current limits versus 1756-OB16I limits are as follows:
1771-OQ 1756-OB16I w/ 1492-C005005XT
a) Current/Point 2.25A 2A
b) Current/Module 9A 8A
c) Surge Current/Point 4A for 10ms 4A for 10ms
 The 1771-OQ is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC.
 Refer to your 1771-OQ and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-033 (Version 00)]

66 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OQ16 to 1756-OB16I
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD010F

Not Used 9 1
Not Used 10 2 Cable
Not Used 19 3 1492-CONCAB005Y 1756-OB16I
Not Used 20 4
DC-0 2 5 Orange 2
LOAD DC-0
Ouput 0 1 6 Blue 1
+ OUT-0
DC-1 4 7 White/Black 4
DC-1
Ouput 1 3 8 Red/Black 3
OUT-1
- DC-2 6 9 Green/Black 6
DC-2
Ouput 2 5 10 Orange/Black 5
OUT-2
DC-3 8 11 Blue/Black 8
DC-3
Ouput 3 7 12 Black/White 7
OUT-3
DC-4 12 13 Red/White 10
DC-4
Ouput 4 11 14 Green/White 9
OUT-4
DC-5 14 15 Blue/White 12
DC-5
Ouput 5 13 16 Black/Red 11
OUT-5
DC-6 16 17 White/Red 14
DC-6
Ouput 6 15 18 Orange/Red 13
OUT-6
DC-7 18 19 Blue/Red 16
DC-7
Ouput 7 17 20 Red/Green 15
OUT-7
DC-8 22 21 Orange/Green 18
DC-8
Ouput 8 21 22 Black/White/Red 17
OUT-8
DC-9 24 23 White/Black/Red 20
DC-9
Ouput 9 23 24 Red/Black/White 19
OUT-9
DC-10 26 25 Green/Black/White 22
DC-10
Ouput 10 25 26 Orange/Black/White 21
OUT-10
DC-11 28 27 Blue/Black/White 24
DC-11
Ouput 11 27 28 Black/Red/Green 23
OUT-11
DC-12 32 29 White/Red/Green 26
DC-12
Ouput 12 31 30 Red/Black/Green 25
OUT-12
DC-13 34 31 Green/Black/Orange 28
DC-13
Ouput 13 33 32 Orange/Black/Green 27
OUT-13
DC-14 36 33 Blue/White/Orange 30
DC-14
Ouput 14 35 34 Black/White/Orange 29
OUT-14
DC-15 38 35 White/Red/Orange 32
DC-15
Ouput 15 37 36 Orange/White/Blue 31
OUT-15
Not Used 29 37
Not Used 30
Not Used 39
Not Used 40

1771-WN Swing Arm


From 1771-OQ16

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OB16I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 The 1771-OQ16 module output current limits versus 1756-OB16I limits are as follows:
1771-OQ16 1756-OB16I w/ 1492-CONCAB005Y
a) Current/Point 2A 2A
b) Current/Module 32A 8A
c) Surge Current/Point 4A for 10ms 4A for 10ms
 The 1771-OQ16 has sixteen (16) 3A, 250V rectifier fuses. The 1756-OB16I is NOT fused, as such sixteen(16) 2AG fuses
and clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
 The 1771-OQ16 is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC.
 Refer to your 1771-OQ16 and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. [Reference Doc: 41171-010 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 67


Wiring Diagrams - Digital Outputs

1771-OR to 1756-OB16I
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2
Cable
3
4
1492-CONCAB005Y 1492-C005005XR 1756-OA16I
5
4
JMP0
3 6
Orange
Blue CABLE ”A” 2
L2-0
N.C. 7 White/Black
N.O. 8 Red/Black 1
L1-0
2 1 9 Green/Black 3
JMP1 L1-1
4 3 10 Orange/Black 5
L1-2
N.C. 11 Blue/Black
N.O. 12 Black/White 4 L2-1
2 1 13 Red/White 6
JMP2 L2-2
4 3 14 Green/White 8
L2-3
N.C. 15 Blue/White
0-IN 1
N.O. 16 Black/Red 9
2 L1-3
0-OUT 2 1 17 White/Red 11
3 JMP3 L1-4
1-IN 3 18 Orange/Red 13
4 L1-5
1-OUT 4 N.C. 19 Blue/Red
2-IN 5 10
N.O. 20 Red/Green
L2-4
2-OUT 6 2 1 12
21 Orange/Green
L2-5
3-IN 7 JMP4 22
4 3 Black/White/Red
8 N.C.
3-OUT 23 White/Black/Red
9
4-IN N.O. 24 Red/Black/White
10 2 1 25
4-OUT Green/Black/White
L2 L1 5-IN 11 JMP5
4 3 26 Orange/Black/White
5-OUT 12 27
LOAD N.C. Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange 26 NOT USED
JMP7 34 Black/White/Orange NOT USED
4 3 27
N.C. 35 White/Red/Orange 28 NOT USED
N.O. 36 Orange/White/Blue
1771-WD Swing Arm 2 1 37
29
30
NOT USED
NOT USED
NOT USED
From 1771-OR 31
32 NOT USED
33 NOT USED
Conversion Module 34
35
NOT USED
NOT USED
1492-CM1771-LD012 36 NOT USED

1
2
3
4
5 Orange
CABLE ”B”
JMP0 6
4 3 Blue 14
L2-6
N.C. 7 White/Black
N.O. 8 Red/Black 15
L1-6
2 1 9 Green/Black 17
JMP1 L1-7
4 3 10 Orange/Black 19
L1-8
N.C. 11 Blue/Black
N.O. 12 Black/White 16 L2-7
2 1 13 Red/White 18
JMP2 L2-8
4 3 14 Green/White 20
L2-9
6-IN N.C. 15 Blue/White
1
N.O. 16 Black/Red 21
6-OUT 2 L1-9
2 1 17 White/Red 23 L1-10
L2 L1 7-IN 3 JMP3
4 3 18 Orange/Red 25
7-OUT 4 L1-11
LOAD N.C. 19 Blue/Red
8-IN 5 22
N.O. 20 Red/Green
L2-10
8-OUT 6 2 1 24
21 Orange/Green
L2-11
9-IN 7 JMP4
4 3 22 Black/White/Red
9-OUT 8 N.C. 23 White/Black/Red
10-IN 9
N.O. 24 Red/Black/White
10-OUT 10 2 1 25 Green/Black/White
11-IN 11 JMP5
4 3 26 Orange/Black/White
11-OUT 12 27
N.C. Blue/Black/White
N.O. 28 Black/Red/Green
2 1 29 White/Red/Green
JMP6 30
4 3 Red/Black/Green
N.C. 31 Green/Black/Orange
N.O. 32 Orange/Black/Green
2 1 33 Blue/White/Orange
JMP7 34 Black/White/Orange
4 3
1771-WD Swing Arm N.C. 35
36
White/Red/Orange
Orange/White/Blue
N.O.
From 1771-OR 2 1 37

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16I RTB. Each cable can be either
0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
 The 1771-OR module output resistive current limits versus 1756-OA16I limits are as follows:
1771-OR 1756-OA16I w/ 1492-C005005XR
a) Current/Point 2A 2A
b) Current/Module 6A 5A @ 60°C
c) Surge Current/Point 15A for 100ms 20A for 43ms
 The 1771-OR module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OR jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OR and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-017 (Version 00)]

68 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OVN to 1756-OV16E
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD013
Cable
L1 1
L1
L1 11
1492-CONCAB005S3 1756-OV16E
L1-0 
L2 10 1 Black 10
L2 20 2 White 9
L2 L2-0
Output 00 2 3 Red 1
OUT-0
Output 01 3 4 Green 2
OUT-1
Output Output 02 4 5 Orange 3
Device OUT-2
Output 03 5 6 Blue 4
OUT-3

MODULE A
Output 04 6 7 White/Black 5
OUT-4
Output 05 7 8 Red/Black 6
OUT-5
Output 06 8 9 Green/Black 7
OUT-6
Output 07 9 10 Orange/Black 8
OUT-7
Output 10 12 11 Blue/Black 11
OUT-8
Output 11 13 12 Black/White 12
OUT-9
Output 12 14 13 Red/White 13
OUT-10
Output 13 15 14 Green/White 14
OUT-11
Output 14 16 15 Blue/White 15
16 OUT-12
Output 15 17 Black/Red 16
17 OUT-13
Output 16 18 White/Red 17
OUT-14
Output 17 19 18 Orange/Red 18
OUT-15
19 Blue/Red 20
L1-1 
19
L2-1
L1 21
L1 31 1756-OV16E
L2 30 20 Red/Green 10
L1-0
L2 40 21 Orange/Green 9
L2-0

Output 00 22 22 Black/White/Red 1
OUT-0
Output 01 23 23 White/Black/Red 2
OUT-1
Output 02 24 24 Red/Black/White 3
OUT-2
Output 03 25 25 Green/Black/White 4
OUT-3

MODULE B
Output 04 26 26 Orange/Black/White 5
OUT-4
Output 05 27 27 Blue/Black/White 6
OUT-5
Output 06 28 28 Black/Red/Green 7
OUT-6
Output 07 29 29 White/Red/Green 8
OUT-7
Output 10 32 30 Red/Black/Green 11
OUT-8
Output 11 33 31 Green/Black/Orange 12
OUT-9
Output 12 34 32 Orange/Black/Green 13
OUT-10
35 33 Blue/White/Orange 14
Output 13 OUT-11
Output 14 36 34 Black/White/Orange 15
OUT-12
Output 15 37 35 White/Red/Orange 16
OUT-13
38 36 Orange/White/Blue 17
Output 16 OUT-14
Output 17 39 37 White/Red/Blue 18
OUT-15
20 L1-1
1771-WN Swing Arm 19 L2-1

From 1771-OVN

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OV16E RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M,
010=1.0M). See table 2 for other lengths.
 The 1771-OVN module output current limits versus 1756-OV16E limits are as follows:
1771-OVN 1756-OV16E w/ 1492-CONCAB005S3
a) Current/Point 0.5A 1A
b) Current/Module 8A (32 pts) 8A (16 pts)
c) Surge Current/Point 2A for 10ms 2A for 10ms
 The 1771-OVN has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the
1771-OVN together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply
was used, all but 1 of the power supplies must be removed.
 The 1771-OVN did not allow connections for L2, however the 1756-OV16E requires an L2 connection for proper operation. The 1771-
OVN did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must
rewire L2 to one of these terminals.
 Refer to your 1771-OVN and 1756-OV16E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded.
 This configuration uses two (2) 1756-OV16E output modules to replace a single 1771-OVN output module. This may require the use of a
larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
[Reference Doc: 41171-018 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 69


Wiring Diagrams - Digital Outputs

1771-OW to 1756-OX8I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3 1492-CONCAB005Y 1756-OX8I
4
5 Orange 2
JMP0 3 L1-0
4 6 Blue 1 OUT-0 N.C.
N.C. 7 White/Black 4 L1-0
N.O. 8 Red/Black 3
9 Green/Black
OUT-0 N.O.
2 1 6
JMP1 3 L1-1
4 10 Orange/Black 5 OUT-1 N.C.
N.C. 11 Blue/Black 8 L1-1
N.O. 12 Black/White 7
OUT-1 N.O.
2 1 13 Red/White 10 L1-2
4 JMP2 3 14 Green/White 9
OUT-2 N.C.
N.C. 15 Blue/White 12
L1 Out-0 N.O./N.C. 1 L1-2
+V0/1 2 N.O. 16 Black/Red 11
OUT-2 N.O.
3 2 1 17 White/Red 14
L2 Out-1 N.O./N.C. L1-3
LOAD 4 JMP3 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
5 N.C. 19 Blue/Red 16
+V2/3 L1-3
6 N.O. 20 Red/Green 15
Out-3 N.O./N.C. OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 L1-4
4 JMP4 3 22 Black/White/Red 17
+ +V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
LOAD N.O. 24 Red/Black/White 19
- Out-6 N.O./N.C. 10 OUT-4 N.O.
+V6/7 11
2 1 25 Green/Black/White 22 L1-5
4 JMP5 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 3 L1-6
4 30 Red/Black/Green 25 OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
OUT-6 N.O.
2 1 33 Blue/White/Orange 30
JMP7 3 L1-7
4 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32 L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
2 1 37

1771-WD Swing Arm


From 1771-OW

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OW module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OW 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 0.2A @ 138V AC 2A @ 240V AC
1A @ 30V DC 2A @ 30V DC
0.25A @ 125V DC 0.25A @ 125V DC
 The 1771-OW module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OW jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OW and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-941 (Version 01)]

70 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OW16 to 1756-OW16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD011

Output 10 (NC) 17 1
Output 11 (NC) 20 2 Cable
Output 12 (NC) 23 3 1492-CONCAB005Y 1756-OW16I
Output 13 (NC) 26 4
L1 Common 00 2 5 Orange 2
Output 00 L1-0
1 6 Blue 1
LOAD OUT-0 N.O.
Common 01 4 7 White/Black 4
L1-1
Output 01 3 8 Red/Black 3
L2 6 OUT-1 N.O.
Common 02 9 Green/Black 6
5 L1-2
Output 02 10 Orange/Black 5
OUT-2 N.O.
Common 03 8 11 Blue/Black 8
L1-3
Output 03 7 12 Black/White 7
OUT-3 N.O.
Common 04 10 13 Red/White 10
9 L1-4
Output 04 14 Green/White 9
12 OUT-4 N.O.
Common 05 15 Blue/White 12
11 L1-5
Output 05 16 Black/Red 11
14 OUT-5 N.O.
Common 06 17 White/Red 14
+ L1-6
Output 06 13 18 Orange/Red 13
- LOAD OUT-6 N.O.
Common 07 16 19 Blue/Red 16
15 L1-7
Output 07 20 Red/Green 15
19 OUT-7 N.O.
Common 10 21 Orange/Green 18
18 L1-8
Output 10 (NO) 22 Black/White/Red 17
OUT-8 N.O.
Common 11 22 23 White/Black/Red 20
21 L1-9
Output 11(NO) 24 Red/Black/White 19
25 OUT-9 N.O.
Common 12 25 Green/Black/White 22
24 L1-10
Output 12 (NO) 26 Orange/Black/White 21
28 OUT-10 N.O.
Common 13 27 Blue/Black/White 24
L1-11
Output 13 (NO) 27 28 Black/Red/Green 23
31 OUT-11 N.O.
Common 14 29 White/Red/Green 26
30 L1-12
Output 14 (NO) 30 Red/Black/Green 25
OUT-12 N.O.
Common 15 34 31 Green/Black/Orange 28
L1-13
Output 15 (NO) 33 32 Orange/Black/Green 27
OUT-13 N.O.
Common 16 37 33 Blue/White/Orange 30
L1-14
Output 16 (NO) 36 34 Black/White/Orange 29
OUT-14 N.O.
Common 17 40 35 White/Red/Orange 32
L1-15
Output 17 (NO) 39 36 Orange/White/Blue 31
OUT-15 N.O.
Output 14 (NC) 29 37
Output 15 (NC) 32
Output 16 (NC) 35
Output 17 (NC) 38

1771-WN Swing Arm


From 1771-OW16
Conversion Module Installation and Application Considerations
 The 1771-OW16 module output resistive current limits versus 1756-OW16I limits are as follows:
1771-OW16 1756-OW16I w/ 1492-CONCAB005Y
a) Current/Point 2A @ 250V AC 2A @ 240V AC
2A @ 30V DC 2A @ 30V DC
0.3A @ 150V DC 0.25A @ 125V AC
 The 1492-CONCAB005Y is limited to 3A per pin.
 The 1771-OW16 has N.O. and N.C. relay contact outputs. The 1756-OW16I has N.O. relay contact outputs only. The conver-
sion module does not convert the N.C. to N.O. contacts. If the 1771-OW16 N.C. outputs were being used, the installer must
rewire the 1771-WN swing arm and move the N.C. wires to the N.O. output terminals. In addition, the control Logix programming
will need to be changed to simulate a N.C. relay with this output.
 Refer to your 1771-OW16 and 1756-OW16I Installation Manual wiring schematics and diagrams for more details.
Ensure 1756 output module ratings are not exceeded. Reference Doc: 41170-940 (Version 01)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 71


Wiring Diagrams - Digital Outputs

1771-OWNA to 1756-OW16I
There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module
1492-CM1771-LD013
Cable
L1 L1 1 1492-CONCAB005S4 1756-OW16I
L1 11
L2
L2
10
20
1
2
Black 2
L1-0 
White
L2 L2-0
Output 00 2 3 Red 1
OUT-0
Output 01 3 4 Green 3
OUT-1
Output Output 02 4 5 Orange 5
Device OUT-2
Output 03 5 6 Blue 7
OUT-3

MODULE A
Output 04 6 7 White/Black 9
OUT-4
Output 05 7 8 Red/Black 11
OUT-5
Output 06 8 9 Green/Black 13
OUT-6
Output 07 9 10 Orange/Black 15
11 OUT-7
Output 10 12 Blue/Black 17
12 OUT-8
Output 11 13 Black/White 19
13 OUT-9
Output 12 14 Red/White 21
OUT-10
Output 13 15 14 Green/White 23
15 OUT-11
Output 14 16 Blue/White 25
16 OUT-12
Output 15 17 Black/Red 27
OUT-13
Output 16 18 17 White/Red 29
OUT-14
Output 17 19 18 Orange/Red 31
OUT-15
19 Blue/Red 4
6 L1-1
L1-1
32 
L1-1
34
L1-1
L1 21
L1 31 1756-OW16I
L2
L2
30
40
20 Red/Green 2
L1-0 
21 Orange/Green
L2-0
Output 00 22 22 Black/White/Red 1
OUT-0
Output 01 23 23 White/Black/Red 3
OUT-1
Output 02 24 24 Red/Black/White 5
OUT-2
Output 03 25 25 Green/Black/White 7
OUT-3

MODULE B
Output 04 26 26 Orange/Black/White 9
OUT-4
Output 05 27 27 Blue/Black/White 11
OUT-5
Output 06 28 28 Black/Red/Green 13
OUT-6
Output 07 29 29 White/Red/Green 15
OUT-7
Output 10 32 30 Red/Black/Green 17
OUT-8
Output 11 33 31 Green/Black/Orange 19
OUT-9
Output 12 34 32 Orange/Black/Green 21
OUT-10
35 33 Blue/White/Orange 23
Output 13 OUT-11
Output 14 36 34 Black/White/Orange 25
OUT-12
Output 15 37 35 White/Red/Orange 27
OUT-13
38 36 Orange/White/Blue 29
Output 16 OUT-14
Output 17 39 37 White/Red/Blue 31
OUT-15
4
6 L1-1
L1-1
1771-WN Swing Arm 32

L1-1
From 1771-OWNA 34
L1-1

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-OW16I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
 The 1771-OWNA module output current limits versus 1756-OW16I limits are as follows:
1771-OWNA 1756-OW16I w/ 1492-CONCAB005S4
a) Current/Point 1A 0.5A
b) Current/Module 12A (32 pts) 2A (16 pts)
 The 1771-OWNA has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the 1771 -OWNA
together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply wa s used, all but
1 of the power supplies must be removed.
 The 1771-OWNA did not allow connections for L2, however the 1756-OW16I requires an L2 connection for proper operation. The 1771-OWNA
did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must rewire L2 to
one of these terminals.
 Refer to your 1771-OWNA and 1756-OW16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module
ratings are not exceeded.
 This configuration uses two (2) 1756-OW16I output modules to replace a single 1771-OWNA output module. This may require the use of a
larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
 1756-OW16I output modules has all inputs jumpered together pins 2 through 34 even.
[Reference Doc: 41171-019 (Version 00)]

72 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OY to 1756-OX8I

There are several key application considerations and system specifications (bottom of drawing) when using
these components (conversion module, cable and output module). Read and understand these considerations
IMPORTANT before installation. In addition, refer to the current draw requirements of the existing loads for this configuration
to ensure they are within the current ratings of the 1756 output module.

Conversion Module
1492-CM1771-LD012
1
2
3 Cable 1756-OX8I
4 1492-CONCAB005Y c
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
1771-WD Swing Arm 2 1 37

From 1771-OY

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


c This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d The 1771-OY module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: for switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OY 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 138V AC 2A @ 240V AC
100mA @ 125V DC 2A @ 30V DC
0.25A @ 125V DC
e The 1771-OY module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. relay outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OY jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O.. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
f Refer to your 1771-OY and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded. 41171-011 (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 73


Wiring Diagrams - Digital Outputs

1771-OYL to 1756-OX8I

There are several key application considerations and system specifications (bottom of drawing) when using
these components (conversion module, cable and output module). Read and understand these considerations
IMPORTANT before installation. In addition, refer to the current draw requirements of the existing loads for this configuration
to ensure they are within the current ratings of the 1756 output module.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3
1492-CONCAB005Y c 1756-OX8I
4
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
2 1 37
1771-WD Swing Arm
From 1771-OYL

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


c This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d The 1771-OYL module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: for switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OYL 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 24V AC 2A @ 240V AC
100mA @ 24V DC 2A @ 30V DC
0.25A @ 125V DC
e The 1771-OYL module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. relay outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OYL jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O.. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
f Refer to your 1771-OYL and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded.
41171-012 (00)

74 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Digital Outputs

1771-OZ to 1756-OX8I
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3
4
1492-CONCAB005Y 1756-OX8I
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
2 1 37

1771-WD Swing Arm


From 1771-OZ

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OZ module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OZ 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 138V AC 2A @ 240V AC
100mA @ 138V DC 2A @ 30V DC
0.25A @ 125V DC
 The 1771-OZ module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OZ jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OZ and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-013 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 75


Wiring Diagrams - Digital Outputs

1771-OZL to 1756-OX8I
WARNING There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LD012
1
2 Cable
3
4
1492-CONCAB005Y 1756-OX8I
5 Orange 2
JMP0 L1-0
4 3 6 Blue 1
OUT-0 N.C.
N.C. 7 White/Black 4
L1-0
N.O. 8 Red/Black 3
OUT-0 N.O.
2 1 9 Green/Black 6
JMP1 L1-1
4 3 10 Orange/Black 5
OUT-1 N.C.
N.C. 11 Blue/Black 8
L1-1
N.O. 12 Black/White 7
2 1 OUT-1 N.O.
13 Red/White 10
JMP2 L1-2
4 3 14 Green/White 9
OUT-2 N.C.
Out-0 N.O./N.C. N.C. 15 Blue/White 12
1 L1-2
L1 N.O. 16 Black/Red 11
+V0/1 2 OUT-2 N.O.
2 1 17 White/Red 14
Out-1 N.O./N.C. 3 JMP3 L1-3
L2 LOAD 4 3 18 Orange/Red 13
Out-2 N.O./N.C. 4 OUT-3 N.C.
N.C. 19 Blue/Red 16
+V2/3 5 L1-3
N.O. 20 Red/Green 15
Out-3 N.O./N.C. 6 OUT-3 N.O.
2 1 21 Orange/Green 18
Out-4 N.O./N.C. 7 JMP4 L1-4
+ 4 3 22 Black/White/Red 17
+V4/5 8 OUT-4 N.C.
N.C. 23 White/Black/Red 20
Out-5 N.O./N.C. 9 L1-4
- LOAD N.O. 24 Red/Black/White 19
Out-6 N.O./N.C. 10 2 1 OUT-4 N.O.
25 Green/Black/White 22
+V6/7 11 JMP5 L1-5
4 3 26 Orange/Black/White 21
Out-7 N.O./N.C. 12 OUT-5 N.C.
N.C. 27 Blue/Black/White 24
L1-5
N.O. 28 Black/Red/Green 23
OUT-5 N.O.
2 1 29 White/Red/Green 26
JMP6 L1-6
4 3 30 Red/Black/Green 25
OUT-6 N.C.
N.C. 31 Green/Black/Orange 28
L1-6
N.O. 32 Orange/Black/Green 27
2 1 OUT-6 N.O.
33 Blue/White/Orange 30
JMP7 L1-7
4 3 34 Black/White/Orange 29
OUT-7 N.C.
N.C. 35 White/Red/Orange 32
L1-7
N.O. 36 Orange/White/Blue 31
OUT-7 N.O.
2 1 37

1771-WD Swing Arm


From 1771-OZL

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M),
010=1.0M). See table 2 for other lengths.
 The 1771-OZL module output resistive current limits versus 1756-OX8I limits are as follows:
(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions)
1771-OZL 1756-OX8I w/ 1492-CONCAB005Y
a) Current/Point 100mA @ 138V AC 2A @ 240V AC
100mA @ 138V DC 2A @ 30V DC
0.25A @ 125V DC
 The 1771-OZL module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but
selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality
of the 1771-OZL jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is
required, change the jumper from pins 1-2 to pins 3-4.
 Refer to your 1771-OZL and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41171-014 (Version 00)]

76 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs
1771-IFE to 1756-IF16 Differential Current

There are several key application considerations and system specifications (bottom of drawing) when using
WARNING
IMPORTANT these components (conversion module, cable and output module). Read and understand these considerations
before installation.

1492-CM1771-LA002
1492-CONACAB005D 1756-IF16
4-Wire Transmitter
+ + Channel 1+ 1 1 Black 2
IN-0
Power Supply Transmitter - Channel 1- 2 2 White 4
IN-1
- Channel 2+ 3 3 Red 6
IN-2
Channel 2- 4 4 Green 8
IN-3
Channel 3+ 6 5 Orange 12
IN-4
Channel 3- 7 6 Blue 14
IN-5
Channel 4+ 8 7 White/Black 16
IN-6
Channel 4- 9 8 Red/Black 18
IN-7
Not Used 5 9 10
RTN
Not Used 10 10 Orange/Black 1
iRTN-0
Not Used 15 11 Blue/Black 5
Module Common iRTN-2
20 12 11
Module Common iRTN-4
21 13 15
iRTN-6
Channel 5+ 11 14 Green/White 20
IN-8
Channel 5- 12 15 Blue/White 22
IN-9
Channel 6+ 13 16 Black/Red 24
IN-10
Channel 6- 14 17 White/Red 26
IN-11
Channel 7+ 16 18 Orange/Red 30
IN-12
Channel 7- 17 19 Blue/Red 32
IN-13
Channel 8+ 18 20 Red/Green 34
IN-14
Channel 8- 19 21 Orange/Green 36
IN-15
22 19
iRTN-8
23 23
iRTN-10
24 29
iRTN-12
1 25 33
iRTN-14
SH
1

1771-WG Swing Arm

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002
module and the 1756-IF16 [1492-CONACAB005D] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005D] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16.
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41170-946 (0)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 77


Wiring Diagrams - Analog Inputs and Outputs

1771-IFE to 1756-IF16 Differential Voltage

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

1492-CM1771-LA002
1492-CONACAB005C
1756-IF16
4-Wire Transmitter
+ + Channel 1+ 1 1 Black 2
IN-0
Power Supply Transmitter - Channel 1- 2 2 White 4
IN-1
- Channel 2+ 3 3 Red 6
IN-2
Channel 2- 4 4 Green 8
IN-3
Channel 3+ 6 5 Orange 12
IN-4
Channel 3- 7 6 Blue 14
IN-5
Channel 4+ 8 7 White/Black 16
IN-6
Channel 4- 9 8 Red/Black 18
IN-7
Not Used 5 9 10
RTN
Not Used 10 10 Orange/Black
Not Used 15 11 Blue/Black
Module Common 20 12
Module Common 21 13
Channel 5+ 11 14 Green/White 20
IN-8
Channel 5- 12 15 Blue/White 22
IN-9
Channel 6+ 13 16 Black/Red 24
IN-10
Channel 6- 14 17 White/Red 26
IN-11
Channel 7+ 16 18 Orange/Red 30
IN-12
Channel 7- 17 19 Blue/Red 32
IN-13
Channel 8+ 18 20 Red/Green 34
IN-14
Channel 8- 19 21 Orange/Green 36
IN-15
22
23
24
1 25

SH
1

1771-WG Swing Arm

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002
module and the 1756-IF16 [1492-CONACAB005C] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 This design assumes that all inputs on the1771-IFE were connected to voltage transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005C] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16.
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41170-947 (1)

78 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IFE to 1756-IF16 Single End Current

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT
WARNING
these components (conversion module, cable and input module). Read and understand these considerations
before installation.

1492-CM1771-LA001
1492-CONACAB005B 1756-IF16
Channel 1 1 1 Black 2
IN-0
Channel 2 2 2 White 4
IN-1
Channel 3 3 3 Red 6
IN-2
Channel 4 4 4 Green 8
IN-3
Channel 5 6 5 Orange 12
2-Wire Transmitter IN-4
Channel 6 7 6 Blue 14
IN-5
Channel 7 8 7 White/Black 16
IN-6
+ Transmitter Channel 8 9 8 Red/Black 18
IN-7
Power Supply - Module Common 5 9 Green/Black 10
RTN
Module Common 10 10 Orange/Black
Module Common 15 11 Blue/Black
Module Common 20 12 Black/White 28
Module Common RTN
21 13
Channel 9 11 14 Green/White 20
IN-8
Channel 10 12 15 Blue/White 22
IN-9
Channel 11 13 16 Black/Red 24
IN-10
Channel 12 14 17 White/Red 26
IN-11
Channel 13 16 18 Orange/Red 30
IN-12
Channel 14 17 19 Blue/Red 32
IN-13
Channel 15 18 20 Red/Green 34
IN-14
Channel 16 19 21 Orange/Green 36
IN-15
22
23 1
iRTN-0
24 3
iRTN-1
25 5
1 iRTN-2
7
iRTN-3
SH 9
RTN
1 11
iRTN-4
13
iRTN-5
15
iRTN-6
17
iRTN-7
1771-WG Swing Arm 19
iRTN-8
21
iRTN-9
23
iRTN-10
25
iRTN-11
27
RTN
29
iRTN-12
31
iRTN-13
33
iRTN-14
35
iRTN-15

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001
module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16. 41170-944 (1)
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 79


Wiring Diagrams - Analog Inputs and Outputs

1771-IFE to 1756-IF16 Single End Voltage

There are several key application considerations and system specifications (bottom of drawing) when using
WARNING
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

1492-CM1771-LA001
1492-CONACAB005A 1756-IF16
3-Wire Transmitter
Channel 1 1 1 Black 2
IN-0
Transmitter Channel 2 2 2 White 4
IN-1
Channel 3 3 3 Red 6
IN-2
Channel 4 4 4 Green 8
IN-3
Channel 5 6 5 Orange 12
IN-4
Channel 6 7 6 Blue 14
IN-5
Channel 7 8 7 White/Black 16
IN-6
Channel 8 9 8 Red/Black 18
+ IN-7
- Module Common 5 9 Green/Black 10
RTN
Power Supply Module Common 10 10 Orange/Black 9
RTN
Module Common 15 11 Blue/Black 27
RTN
Module Common 20 12 Black/White 28
RTN
Module Common 21 13
Channel 9 11 14 Green/White 20
IN-8
Channel 10 12 15 Blue/White 22
IN-9
Channel 11 13 16 Black/Red 24
IN-10
Channel 12 14 17 White/Red 26
IN-11
Channel 13 16 18 Orange/Red 30
IN-12
Channel 14 17 19 Blue/Red 32
IN-13
Channel 15 18 20 Red/Green 34
IN-14
Channel 16 19 21 Orange/Green 36
IN-15
22
23
24
1 25

SH
1

1771-WG Swing Arm

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001
module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 This design assumes that all inputs on the1771-IFE were connected to voltage transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16.
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41170-945 (1)

80 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IFF to 1756-IF16 Differential Current

There are several key application considerations and system specifications (bottom of drawing) when using
WARNING
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA002 Cable
1492-CONACAB005D c 1756-IF16
4-Wire Transmitter
+ + Channel 1+ 1 1 Black 2
IN-0
Power Supply Transmitter - Channel 1- 2 2 White 4
IN-1
- Channel 2+ 3 3 Red 6
IN-2
Channel 2- 4 4 Green 8
IN-3
Channel 3+ 6 5 Orange 12
IN-4
Channel 3- 7 6 Blue 14
IN-5
Channel 4+ 8 7 White/Black 16
IN-6
Channel 4- 9 8 Red/Black 18
IN-7
Not Used 5 9 10
RTN
Not Used 10 10 Orange/Black 1
iRTN-0
Not Used 15 11 Blue/Black 5
iRTN-2
Module Common 20 12 11
Module Common iRTN-4
21 13 15
iRTN-6
Channel 5+ 11 14 Green/White 20
IN-8
Channel 5- 12 15 Blue/White 22
IN-9
Channel 6+ 13 16 Black/Red 24
IN-10
Channel 6- 14 17 White/Red 26
IN-11
Channel 7+ 16 18 Orange/Red 30
IN-12
Channel 7- 17 19 Blue/Red 32
IN-13
Channel 8+ 18 20 Red/Green 34
IN-14
Channel 8- 19 21 Orange/Green 36
IN-15
22 19
iRTN-8
23 23
iRTN-10
24 29
iRTN-12
25 33
d iRTN-14
SH

1771-WG Swing Arm


From 1771-IFF

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


c This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002
module and the 1756-IF16 [1492-CONACAB005D] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
e This design assumes that all inputs on the1771-IFF were connected to current transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005D] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
f The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16.
g Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.
41171-025 (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 81


Wiring Diagrams - Analog Inputs and Outputs

1771-IFF to 1756-IF16 Differential Voltage

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module Cable


1492-CM1771-LA002 1492-CONACAB005C 1756-IF16
4-Wire Transmitter
+ + Channel 1+ 1 1 Black 2
IN-0
Power Supply Transmitter - Channel 1- 2 2 White 4
IN-1
- Channel 2+ 3 3 Red 6
IN-2
Channel 2- 4 4 Green 8
IN-3
Channel 3+ 6 5 Orange 12
IN-4
Channel 3- 7 6 Blue 14
IN-5
Channel 4+ 8 7 White/Black 16
IN-6
Channel 4- 9 8 Red/Black 18
IN-7
Not Used 5 9 10
RTN
Not Used 10 10 Orange/Black
Not Used 15 11 Blue/Black
Module Common 20 12
Module Common 21 13
Channel 5+ 11 14 Green/White 20
IN-8
Channel 5- 12 15 Blue/White 22
IN-9
Channel 6+ 13 16 Black/Red 24
IN-10
Channel 6- 14 17 White/Red 26
IN-11
Channel 7+ 16 18 Orange/Red 30
IN-12
Channel 7- 17 19 Blue/Red 32
IN-13
Channel 8+ 18 20 Red/Green 34
IN-14
Channel 8- 19 21 Orange/Green 36
IN-15
22
23
24
25
d
SH

1771-WG Swing Arm


From 1771-IFF

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS

c This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002
module and the 1756-IF16 [1492-CONACAB005C] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
e This design assumes that all inputs on the1771-IFF were connected to voltage transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005C] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
f The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16.
g Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.
41171-026 (00)

82 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IFF to 1756-IF16 Single End Current

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA001 Cable
1756-IF16
1492-CONACAB005B c
Channel 1 1 1 Black 2
IN-0
Channel 2 2 2 White 4
IN-1
Channel 3 3 3 Red 6
IN-2
Channel 4 4 4 Green 8
IN-3
Channel 5 6 5 Orange 12
2-Wire Transmitter IN-4
Channel 6 7 6 Blue 14
IN-5
Channel 7 8 7 White/Black 16
IN-6
+ Transmitter Channel 8 9 8 Red/Black 18
IN-7
Power Supply - Module Common 5 9 Green/Black 10
RTN
Module Common 10 10 Orange/Black
Module Common 15 11 Blue/Black
Module Common 20 12 Black/White 28
Module Common RTN
21 13
Channel 9 11 14 Green/White 20
IN-8
Channel 10 12 15 Blue/White 22
IN-9
Channel 11 13 16 Black/Red 24
IN-10
Channel 12 14 17 White/Red 26
IN-11
Channel 13 16 18 Orange/Red 30
IN-12
Channel 14 17 19 Blue/Red 32
IN-13
Channel 15 18 20 Red/Green 34
IN-14
Channel 16 19 21 Orange/Green 36
IN-15
22
23 1
iRTN-0
24 3
iRTN-1
25 5
iRTN-2
d 7
iRTN-3
SH 9
RTN
11
d 13
iRTN-4
iRTN-5
15
iRTN-6
17
iRTN-7
1771-WG Swing Arm 19
iRTN-8
21
From 1771-IFF 23
iRTN-9
iRTN-10
25
iRTN-11
27
RTN
29
iRTN-12
31
iRTN-13
33
iRTN-14
35
iRTN-15

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


c This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001
module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
e This design assumes that all inputs on the1771-IFF were connected to current transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
f The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16.
g Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details. 41171-023 (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 83


Wiring Diagrams - Analog Inputs and Outputs

1771-IFF to 1756-IF16 Single End Voltage

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA001 Cable
1492-CONACAB005A c 1756-IF16
3-Wire Transmitter
Channel 1 1 1 Black 2
IN-0
Transmitter Channel 2 2 2 White 4
IN-1
Channel 3 3 3 Red 6
IN-2
Channel 4 4 4 Green 8
IN-3
Channel 5 6 5 Orange 12
IN-4
Channel 6 7 6 Blue 14
IN-5
Channel 7 8 7 White/Black 16
IN-6
Channel 8 9 8 Red/Black 18
+ IN-7
- Module Common 5 9 Green/Black 10
RTN
Power Supply Module Common 10 10 Orange/Black 9
RTN
Module Common 15 11 Blue/Black 27
RTN
Module Common 20 12 Black/White 28
RTN
Module Common 21 13
Channel 9 11 14 Green/White 20
IN-8
Channel 10 12 15 Blue/White 22
IN-9
Channel 11 13 16 Black/Red 24
IN-10
Channel 12 14 17 White/Red 26
IN-11
Channel 13 16 18 Orange/Red 30
IN-12
Channel 14 17 19 Blue/Red 32
IN-13
Channel 15 18 20 Red/Green 34
IN-14
Channel 16 19 21 Orange/Green 36
IN-15
22
23
24
25
d
SH

1771-WG Swing Arm


From 1771-IFF

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS

c This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001
module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
e This design assumes that all inputs on the1771-IFF were connected to voltage transmitters. If there was a mix of current
and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16
terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
f The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please
ensure the correct input range is configured in the 1756-IF16.
g Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details. 41171-024 (00)

84 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IL to 1756-IF8I Current

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA004 Cable
1756-IF8I
1492-CONACAB005K8
4-Wire Transmitter
+ + Channel0 18 18 Orange/Red 4
Power Supply Transmitter Channel0 17 17 Iin_CH0
- White/Red 6
- 16 16
RTN_CH0
Channel1 Black/Red 3
Channel1 15 15 Iin_CH1
Blue/White 5 RTN_CH1
Channel2 14 14 Green/White 12
13
Iin_CH2
Channel2 13 Red/White 14
12 RTN_CH2
Channel3 12 Black/White 11
11 11 13 Iin_CH3
Channel3 Blue/Black
10 RTN_CH3
10 Orange/Black
9 9 Green/Black
2-Wire
Transmitter Channel4 8 8 Red/Black 20
+ Channel4 7 7 White/Black 22 Iin_CH4
6 6 Blue RTN_CH4
- Channel5 19
Channel5 5 5 Orange 21 Iin_CH5
4 RTN_CH5
Channel6 4 Red / Black 28
3 Iin_CH6
Channel6 3 White / Black 30
2 RTN_CH6
Channel7 2 Blue 27 Iin_CH7
Channel7 1 1 Orange 29 RTN_CH7

1 N.C. 23 N.C.
2 N.C. 24 N.C.
7 N.C. 25 N.C.
8 N.C. 26 N.C.
9 N.C. 31 N.C.
10 N.C. 32 N.C.
SH
15 N.C. 33 N.C.
16 N.C. 34 N.C.
17 N.C. 35 N.C.
18 N.C. 36 N.C.
1771-WF Swing Arm
From 1771-IL

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


This Bul. 1492 cable consists of a cable wired to one 1756-IF6I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004
module and the 1756-IF8I [1492-CONACAB005K8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration
in the 1756-IF8I.
Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 85


Wiring Diagrams - Analog Inputs and Outputs

1771-IL to 1756-IF8I Voltage

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA004 Cable
1756-IF8I
1492-CONACAB005L8
4-Wire Transmitter
+ + Vout_CH0 18 18 Orange/Red 2
Power Supply Transmitter RTN_CH0 17 17 6 Vout_CH0
- White/Red
- RTN_CH0
Vout_CH1 16 16 Black/Red 1
RTN_CH1 15 15 Vout_CH1
Blue/White 5 RTN_CH1
Vout_CH2 14 14 Green/White 10
RTN_CH2 13 13 Vout_CH2
Red/White 14
12 RTN_CH2
Vout_CH3 12 Black/White 9
RTN_CH3 11 11 Blue/Black 13 Vout_CH3
10 RTN_CH3
10 Orange/Black
9 9 Green/Black
Vout_CH4 8 8 Red/Black 18
7 7 Vout_CH4
RTN_CH4 White/Black 22
Vout_CH5 6 6 Blue 17 RTN_CH4
RTN_CH5 5 5 Orange
Vout_CH5
21 RTN_CH5
Vout_CH6 4 4 Red / Black 26
3 White / Black Vout_CH6
RTN_CH6 3 30
Vout_CH7 2 2 Blue RTN_CH6
25 Vout_CH7
RTN_CH7 1 1 Orange 29 RTN_CH7

3 3 N.C. 23 N.C.
4 N.C. 24 N.C.
7 N.C. 27 N.C.
8 N.C. 28 N.C.
11 N.C. 31 N.C.
12 N.C. 32 N.C.
15 N.C. 33 N.C.
SH 16 N.C. 34 N.C.
19 N.C. 35 N.C.
3 20 N.C. 36 N.C.

1771-WF Swing Arm


From 1771-IL

This Bul. 1492 cable consists of a cable wired to one 1756-IF8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004
module and the 1756-IF8I [1492-CONACAB005L8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration
in the 1756-IF8I.
Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

86 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IL to 1756-IF6I — 6-ch Current

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA004 Cable
1756-IF6I
4-Wire Transmitter
1492-CONACAB005K c
+ + Channel0 18 18 Orange/Red 3 IN-0/I
Power Supply Transmitter - Channel0 17 17 White/Red 5
RET-0
- Channel1 16 16 Black/Red 4
IN-1/I
Channel1 15 15 Blue/White 6
RET-1
Channel2 14 14 Green/White 9
IN-2/I
Channel2 13 13 Red/White 11
RET-2
Channel3 12 12 Black/White 10 IN-3/I
Channel3 11 11 Blue/Black 12
RET-3
10 10 Orange/Black 1
9 9 Green/Black IN-0/V
2-Wire 2
Channel4 8 8 Red/Black IN-1/V
Transmitter 7
+ Channel4 7 7 White/Black IN-2/V
8
6 6 Blue IN-3/V
- Channel5
Channel5 5 5 Orange
Channel6 4 4 Green
Channel6 3 3 Red 17
Channel7 2 2 White 19 IN-4/I
1 1 RET-4
Channel7 Black 18
IN-5/I
20 RET-5
15 IN-4/V
16 IN-5/V

d SH

1771-WF Swing Arm


From 1771-IL

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


c This Bul. 1492 cable consists of a cable wired to one 1756-IF6I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004
module and the 1756-IF6I [1492-CONACAB005K] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
e The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration
in the 1756-IF6I.
f Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details. 41171-030 (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 87


Wiring Diagrams - Analog Inputs and Outputs

1771-IL to 1756-IF6I — 6-ch Voltage

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANTARNING these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
1492-CM1771-LA004 Cable
1492-CONACAB005L c 1756-IF6I
2-Wire Transmitter
+ + Channel0 18 18 Orange/Red 1
Channel0 17 17 5 IN-0
Power Supply Transmitter - White/Red
- Channel1 2 RET-0
16 16 Black/Red
Channel1 15 15 IN-1
Blue/White 4
Channel2 14 14 RET-1
Green/White 7
Channel2 13 13 IN-2
Red/White 11
Channel3 12 12 RET-2
Black/White 8
Channel3 11 11 12 IN-3
Blue/Black
10 RET-3
10 Orange/Black 9
NO CONNECT
9 9 Green/Black 10
Channel4 NO CONNECT
8 8 Red/Black 15
Channel4 IN-4
7 7 White/Black 19
Channel5 RET-4
6 6 Blue 16
IN-5
Channel5 5 5 Orange 20
Channel6 RET-5
4 4 Green 3 NO CONNECT
Channel6 3 3 Red
4 NO CONNECT
Channel7 2 2 White 13 NO CONNECT
Channel7 1 1 Black 14 NO CONNECT
17 NO CONNECT
18 NO CONNECT

SH
d
d

1771-WF Swing Arm


From 1771-IL

c This Bul. 1492 cable consists of a cable wired to one 1756-IF6I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004
module and the 1756-IF6I [1492-CONACAB005L] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
e The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration
in the 1756-IF6I.
f Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41171-029 (00)

88 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IL to 1756-IF6I — (2 x 4-ch) Current

IMPORTANT

Conversion Module
1492-CM1771-LA004 Cable
1492-CONACAB005T1 1756-IF6I
4-Wire Transmitter
+ + Channel0 18 18 Orange/Red 3 IN-0/I
Power Supply Transmitter - Channel0 17 17 White/Red 5
RET-0
- Channel1 16 16 Black/Red 4
IN-1/I
Channel1 15 15 Blue/White 6
RET-1
Channel2 14 14 Green/White 9
IN-2/I
Channel2 13 13 Red/White 11
RET-2
Channel3 12 12 Black/White 10 IN-3/I
Channel3 11 11 Blue/Black 12
RET-3
10 10 Orange/Black 1
9 9 Green/Black IN-0/V
2-Wire 2
Channel4 8 8 Red/Black IN-1/V
Transmitter 7
+ Channel4 7 7 White/Black IN-2/V
8
6 6 Blue IN-3/V
- Channel5
Channel5 5 5 Orange
Channel6 4 4 Green
Channel6 3 3 Red 17
Channel7 2 2 White 19 IN-4/I
1 1 RET-4
Channel7 Black 18
IN-5/I
20 RET-5
15 IN-4/V
16 IN-5/V

 SH

1771-WF Swing Arm 1756-IF6I


From 1771-IL 3 IN-0/I
5
RET-0
4
IN-1/I
6
RET-1
9
IN-2/I
11
RET-2
10 IN-3/I
12
RET-3
1
IN-0/V
2
IN-1/V
7
IN-2/V
8
IN-3/V

17
19 IN-4/I
RET-4
18
IN-5/I
20 RET-5
15 IN-4/V
16 IN-5/V

Conversion Module Installation and Application Considerations


 This Bul. 1492 cable consists of a cable wired to two 1756-IF6I RTB. Recommended cable lengths of 0.5M or
1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the
1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T1]
provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the
conversion module grounding stud.
 The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.
 Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features
and configuration details.
 This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756
I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
[Reference Doc: 41171-032 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 89


Wiring Diagrams - Analog Inputs and Outputs

1771-IL to 1756-IF6I — (2 x 4-ch) Voltage

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
1492-CM1771-LA004 Cable
1492-CONACAB005T2c 1756-IF6I
4-Wire Transmitter
+ + Channel0 18 18 Orange/Red 1
Channel0 17 17 5 IN-0
Power Supply Transmitter - White/Red
- Channel1 2 RET-0
16 16 Black/Red
Channel1 15 15 IN-1
Blue/White 6
Channel2 14 14 RET-1
Green/White 7
Channel2 13 13 IN-2
Red/White 11
2-Wire 12 RET-2
Transmitter Channel3 12 Black/White 8
+ Channel3 11 11 12 IN-3
Blue/Black
10 RET-3
- 10 Orange/Black 9
NO CONNECT
9 9 Green/Black 10
Channel4 NO CONNECT
8 8 Red/Black 15
Channel4 IN-4
7 7 White/Black 19
Channel5 RET-4
6 6 Blue 16
IN-5
Channel5 5 5 Orange 20
Channel6 RET-5
4 4 Green 3 NO CONNECT
Channel6 3 3 Red
4 NO CONNECT
Channel7 2 2 White 13 NO CONNECT
Channel7 1 1 Black 14 NO CONNECT
17 NO CONNECT
18 NO CONNECT

SH
d 1756-IF6I
d
1 IN-0
5
2 RET-0
1771-WF Swing Arm IN-1
4
From 1771-IL RET-1
7
IN-2
11
RET-2
8
12 IN-3
RET-3
9
NO CONNECT
10
NO CONNECT
15
IN-4
19
RET-4
16
IN-5
20
RET-5
3 NO CONNECT
4 NO CONNECT
13 NO CONNECT
14 NO CONNECT
17 NO CONNECT
18 NO CONNECT

Conversion Module Installation and Application Considerations


c This Bul. 1492 cable consists of a cable wired to two 1756-IF6I RTB. Recommended cable lengths of 0.5M or
1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the
1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T2]
provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the
conversion module grounding stud.
e The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.
f Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features
and configuration details.
g This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756
I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
41171-031 (00)

90 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IR to 1756-IRT8I
There are several key application considerations and system sp cations (bottom of drawing) when using
WARNING
IMPORTANT these components (conversion module, cable and output module). Read and understand these considerations
before installation.

Cable


2-Wire RTD Channel1 - C 18 18 6 IN_0/RTD C


Channel1 - B 17 17 4 IN_0(-)/B
Channel1 - A 16 16 3 IN_0(+)A
Channel2 - C 15 15 10 IN_1/RTD C
Channel2 - B 14 14 8 IN_1(-)/B
Channel2 - A 13 13 7 IN_1(+)/A
Channel3 - C 12 12 14 IN_2/RTD C
Channel3 - B 11 11 12 IN_2(-)/B
Channel3 - A 10 10 11 IN_2(+)/A
Channel4 - C 9 9 18 IN_3/RTD C
3-Wire RTD
Channel4 - B 8 8 16 IN_3(-)/B
Channel4 - A 7 7 15 IN_3(+)/A
Channel5 - C 6 6 22 IN_4/RTD C
Channel5 - B 5 5 20 IN_4(-)/B
Channel5 - A 4 4 19 IN_4(+)/A
Channel6 - C 3 3 26 IN_5/RTD C
Channel6 - B 2 2 24 IN_5(-)/B
Channel6 - A 1 1 23 IN_5(+)/A

1 N.C. 28 N.C.
2 N.C. 29 N.C.
N.C.
 SH
5
9
N.C.
N.C.
30
31 N.C.
 13 N.C. 32 N.C.
 17 N.C. 33 N.C.
21 N.C. 34 N.C.
 25 N.C. 35 N.C.
27 N.C. 36 N.C.

Conversion Module Installation and Application Considerations


 Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used
between the 1492-CM1771-LA004 module and the 1756-IRT8I [1492-CONACAB005F8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

 Refer to your 1771-IR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 91


Wiring Diagrams - Analog Inputs and Outputs

1771-IR to 1756-IR6I

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT
WARNING
these components (conversion module, cable and input module). Read and understand these considerations
before installation.

1492-CM1771-LA004 1492-CONACAB005F
1756-IR6I

2-Wire RTD Channel1 - C 18 18 Orange/Red 5


RTN-0/C
Channel1 - B 17 17 White/Red 3
16 IN-0/B
Channel1 - A 16 Black/Red 1
IN-0/A
Channel2 - C 15 15 Blue/White 6
14 R TN-1/C
Channel2 - B 14 Green/White 4 IN-1/B
Channel2 - A 13 13 Red/White 2
IN-1/A
Channel3 - C 12 12 Black/White 11
11 RTN-2/C
Channel3 - B 11 Blue/Black 9
IN-2/B
Channel3 - A 10 10 Orange/Black 7
IN-2/A
Channel4 - C 9 9 Green/Black 12
3-Wire RTD R TN-3/C
Channel4 - B 8 8 Red/Black 10
IN-3/B
Channel4 - A 7 7 White/Black 8
IN-3/A
Channel5 - C 6 6 Blue 19
RTN-4/C
Channel5 - B 5 5 Orange 17
IN-4/B
Channel5 - A 4 4 Green 15
IN-4/A
Channel6 - C 3 3 Red 20
RTN-5/C
Channel6 - B 2 2 White 18
IN-5/B
Channel6 - A 1 1 Black 16
IN-5/A

1
SH
1

1771-WF Swing Arm

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004
module and the 1756-IR6I [1492-CONACAB005F] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 The 1771-IR input configuration was software configured, as is the 1756-IR6I. Please ensure the correct configuration
in the 1756-IR6I.
3 Refer to your 1771-IR and 1756-IR6I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41170-950 (1)

92 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IXE to 1756-IT6I2

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

1492-CM1771-LA005
Thermocouple
1492-CONACAB005G 1756-IT6I2
+ Input 1+ 18 18 Orange/Red 5
IN-0
- Input 1- 17 17 White/Red 6
RTN-0
Input 2+ 16 16 Black/Red 7
IN-1
Input 2- 15 15 Blue/White 8
RTN-1
Input 3+ 14 14 Green/White 9
IN-2
Input 3- 13 13 Red/White 10
RTN-2
Input 4+ 12 12 Black/White 11
IN-3
Input 4- 11 11 Blue/Black 12
RTN-3
10 10 Orange/Black 13
IN-4
9 9 Green/Black 14
RTN-4
Input 5+ T
8 8 Red/Black 15
IN-5
Input 5- 7 7 White/Black 16
RTN-5
6 Blue 3
Input 6+ 6 CJC+
5 Orange 4
Input 6- 5 CJC-
4 4
3 3
2 2
1 1

1 SH
1

1771-WI Swing Arm

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA005 module. The pre-wired cable used between the 1492-CM1771-LA005
module and the 1756-IT6I2 [1492-CONACAB005G] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 The 1771-IXE has 8 input channels. The 1756-IT6I2 only has 6 input channels. This module combination can only
be used to convert the signals if 6 or less channels were used on the 1771-IXE.
3 The 1771-IXE has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005]
passes this CJC signal to the 1756-IT6I2. Ensure that the 1756-IT6I2 is configured for external CJC.
4 The 1771-IXE input configuration was software configured, as is the 1756-IT6I2. Please ensure the correct configuration
in the 1756-IT6I2.
5 Refer to your 1771-IXE and 1756-IT6I2 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.
41170-951 (1)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 93


Wiring Diagrams - Analog Inputs and Outputs

1771-IXE to 1756-IRT8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module , cable and input module). Read and understand these
considerations bef ore installation.

Conversion Module
Cable
1492-CM1771-LA005 SER “B”
1492-CONACAB005G8 1756-IRT8I
Thermocouple
+ In_CH0+ 18 18 Orange/Red 3
In_CH0+
In_CH0- 17 17 White/Red 4
- In_CH0-
In_CH1+ 16 16 Black/Red 7
In_CH1+
In_CH1- 15 15 Blue/White 8
In_CH1-
In_CH2+ 14 14 Green/White 11 In_CH2+
In_CH2- 13 13 Red/White 12 In_CH2-
In_CH3+ 12 15
12 Black/White In_CH3+
In_CH3- 11 16
11 Blue/Black In_CH3-
CJC+ 10 10 Orange/Black 19 In_CH4+
CJC- 9 9 Green/Black 20 In_CH4-
In_CH4+ T
8 8 Red/Black 23 In_CH5+
In_CH4- 7 7 White/Black 24 In_CH5-
In_CH5+ 6 Blue 1 CJC+
6
In_CH5- 5 Orange 2 CJC-
5
In_CH6+ 4 27
4 Red/Black In_CH6+
In_CH6- 3 28
3 White/Black In_CH6-
In_CH7+ 2 2 Blue 31
In_CH7+
In_CH7- 1 1 Orange 32 In_CH7-

SH 5 N.C. 18 N.C.
6 N.C. 21 N.C.
9 N.C. 22 N.C.
10 N.C. 25 N.C.
13 N.C. 26 N.C.
14 N.C. 29 N.C.
17 N.C. 30 N.C.

1771-WI Swing Arm


From 1771-IXE
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B”
module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IXE has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”]
passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXE input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration
in the 1756-IRT8I.
Refer to your 1771-IXE and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

94 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-IXHR to 1756-IT6I2

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
Cable
1492-CM1771-LA005
1492-CONACAB005G c 1756-IT6I2
Thermocouple
+ Input 1+ 18 18 Orange/Red 5
IN-0
- Input 1- 17 17 White/Red 6
RTN-0
Input 2+ 16 16 Black/Red 7
IN-1
Input 2- 15 15 Blue/White 8
RTN-1
Input 3+ 14 14 Green/White 9
IN-2
Input 3- 13 13 Red/White 10
RTN-2
Input 4+ 12 12 Black/White 11
IN-3
Input 4- 11 11 Blue/Black 12
RTN-3
10 10 Orange/Black 13
IN-4
9 9 Green/Black 14
RTN-4
Input 5+ T
8 8 Red/Black 15
IN-5
Input 5- 7 7 White/Black 16
RTN-5
6 Blue 3
Input 6+ 6 CJC+
5 Orange 4
Input 6- 5 CJC-
4 4
3 3
2 2
1 1

d SH
d

1771-WI Swing Arm


From 1771-IXHR
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
c This Bul. 1492 cable consists of a cable wired to one 1756-IT6I2 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA005 module. The pre-wired cable used between the 1492-CM1771-LA005
module and the 1756-IT6I2 [1492-CONACAB005G] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
e The 1771-IXHR has 8 input channels. The 1756-IT6I2 only has 6 input channels. This module combination can only
be used to convert the signals if 6 or less channels were used on the 1771-IHER.
f The 1771-IXHR has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005]
passes this CJC signal to the 1756-IT6I2. Ensure that the 1756-IT6I2 is configured for external CJC.
g The 1771-IXHR input configuration was software configured, as is the 1756-IT6I2. Please ensure the correct configuration
in the 1756-IT6I2.
h Refer to your 1771-IXHR and 1756-IT6I2 Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41171-035 (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 95


Wiring Diagrams - Analog Inputs and Outputs

1771-IXHR to 1756-IRT8I

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and input module). Read and understand these considerations
before installation.

Conversion Module
Cable
1492-CM1771-LA005 SER “B”
1492-CONACAB005G8 1756-IRT8I
Thermocouple
+ In_CH0+ 18 18 Orange/Red 3
In_CH0+
In_CH0- 17 17 White/Red 4
- In_CH0-
In_CH1+ 16 16 Black/Red 7
In_CH1+
In_CH1- 15 15 Blue/White 8
In_CH1-
In_CH2+ 14 14 Green/White 11 In_CH2+
In_CH2- 13 13 Red/White 12
In_CH3+ In_CH2-
12 12 Black/White 15 In_CH3+
In_CH3- 11 16
11 Blue/Black In_CH3-
CJC+ 10 10 Orange/Black 19 In_CH4+
CJC- 9 9 Green/Black 20 In_CH4-
In_CH4+ T
8 8 Red/Black 23 In_CH5+
In_CH4- 7 7 White/Black 24 In_CH5-
In_CH5+ 6 Blue 1 CJC+
6
In_CH5- 5 Orange 2 CJC-
5
In_CH6+ 4 27
4 Red/Black In_CH6+
In_CH6- 3 28
3 White/Black In_CH6-
In_CH7+ 2 2 Blue 31
In_CH7+
In_CH7- 1 1 Orange 32 In_CH7-

SH 5 N.C. 18 N.C.
6 N.C. 21 N.C.
9 N.C. 22 N.C.
10 N.C. 25 N.C.
13 N.C. 26 N.C.
14 N.C. 29 N.C.
17 N.C. 30 N.C.

1771-WI Swing Arm


From 1771-IXHR
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B”
module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

The 1771-IXHR has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”]
passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXHR input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration
in the 1756-IRT8I.
Refer to your 1771-IXHR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

96 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-OFE1 to 1756-OF6VI

There are several key application considerations and system specifications (bottom of drawing) when using
IMPORTANT these components (conversion module, cable and output module). Read and understand these considerations
before installation.

1492-CM1771-LA003
1492-CONACAB005E 1756-OF6VI
+ Channel 1 Out + A 13 Red/White 1
Voltage OUT-0
- Channel 1 Out - 0 25 Green/Black/White 5
Load RTN-0
Channel 2 Out + 1 24 Red/Black/White 2
OUT-1
Channel 2 Out - 2 23 White/Black/Red 6
RTN-1
Channel 3 Out + 3 22 Black/White/Red 7
OUT-2
Channel 3 Out - 4 21 Orange/Green 11
RTN-2
Channel 4 Out + 5 19 Blue/Red 8
OUT-3
Channel 4 Out - 6 18 Orange/Red 12
RTN-3
Not Used 7 17 15
OUT-4
Not Used B 16 19
RTN-4
1 16
Not Used
2 20
Not Used
3 13
Not Used
4 14
Not Used
5
1771-WC 6
7
Swing Arm 8
9
10
11
12
14
15
1 20
SH
1

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003
module and the 1756-OF6VI [1492-CONACAB005E] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 The 1771-OFE1 analog output range was configured by jumpers, the output range for the 1756-OF6VI is software
configured. Please ensure the correct output range is configured in the 1756-OF6VI.
3 Refer to your 1771-OFE1 and 1756-OF6VI Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41170-949 (1)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 97


Wiring Diagrams - Analog Inputs and Outputs

1771-OFE1 to 1756-OF8I

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
Cable
1492-CM1771-LA003

1492-CONACAB005E8V 1756-OF8I
+ Channel 1 Out + A 13 2
Voltage OUT_0/V
- Channel 1 Out - 0 25 6
Load RTN_0
Channel 2 Out + 1 24 1
OUT_1/V
Channel 2 Out - 2 23 5
RTN_1
Channel 3 Out + 3 22 10
OUT_2/V
Channel 3 Out - 4 21 14
RTN_2
Channel 4 Out + 5 19 9
OUT_3/V
Channel 4 Out - 6 18 13
RTN_3
Not Used 7 17
Not Used B 16
1
2
3
4
5
1771-WC Swing Arm 3 N.C. 23 N.C.
6
4 N.C. 24 N.C.
From 1771-OFE1 7 25 N.C.
7 N.C.
8 8 N.C. 26 N.C.
9 11 N.C. 27 N.C.
12 N.C. 28 N.C.
10
15 N.C. 29 N.C.
11 16 N.C. 30 N.C.
12 17 N.C. 31 N.C.
14 18 N.C. 32 N.C.
15 19 N.C. 33 N.C.
20 N.C. 34 N.C.
 20 21 N.C. 35 N.C.
N.C. 36 N.C.
 SH 22




Conversion Module Installation and Application Considerations


 Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used
between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-CONACAB005E8V] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.


 Refer to your 1771-OFE1 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and

98 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-OFE1(2) to 1756-OF8I

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1756-OF8I
Conversion Module 1492-C005005E8V
1492-CM1771-LA003 Cable “A”
+ Channel 1 Out + A 13
       

2
Voltage OUT_0/V
- Channel 1 Out - 0 25 6

 
        

Load RTN_0
1 24 1
          

Channel 2 Out + OUT_1/V


2 23 5
          

Channel 2 Out - RTN_1


3 22 10
          

Channel 3 Out + OUT_2/V


4 21 14
 

    

Channel 3 Out - RTN_2


5 19 9
    

Channel 4 Out + OUT_3/V


6 18 13


    

Channel 4 Out - RTN_3


Not Used 7 17
Not Used B 16
1
2
3
4
5
6
7
1771-WC Swing Arm 8
From 1771-OFE1 9
10
11
12
14
15
20


SH

Conversion Module
1492-CM1771-LA003 Cable “B”

+ Channel 1 Out + A 13
       

18
Voltage OUT_4/V
- Channel 1 Out - 0 25 22

 
        

Load RTN_4
1 24 17
          

Channel 2 Out + OUT_5/V


2 23 21
          

Channel 2 Out - RTN_5


3 22 26
          

Channel 3 Out + OUT_6/V


4 21 30
 

    

Channel 3 Out - RTN_6


5 19 25
    

Channel 4 Out + OUT_7/V


6 18 29


    

Channel 4 Out - RTN_7


Not Used 7 17
Not Used B 16
1
2
3
4
5
6
3 N.C. 23 N.C.
7
1771-WC Swing Arm 8 4 N.C. 24 N.C.
From 1771-OFE1 9 7 N.C. 27 N.C.
10 8 N.C. 28 N.C.
11 11 N.C. 31 N.C.
12
14
12 N.C. 32 N.C.
15
15 N.C. 33 N.C.
16 N.C. 34 N.C.
20

N.C. N.C.

SH
19 35
20 N.C. 36 N.C.

Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OF8I. Each cable can be either 0.5M or 1.0M (005=0.5M,
010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.

shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used
between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-C005005E8V] provides a shield ground lug to ground the shield at the 1756 ControlLogix
chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

Refer to your 1771-OFE1 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and

DIR 10002306858 (Version 00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 99


Wiring Diagrams - Analog Inputs and Outputs

1771-OFE2 to 1756-OF6CI

There are several key application considerations and system specifications (bottom of drawing) when using
WARNING
IMPORTANT these components (conversion module, cable and output module). Read and understand these considerations
before installation.

1492-CM1771-LA003 1756-OF6CI
1492-CONACAB005E

+ Channel 1 Out + A 13 Red/White 1


Current OUT-0
- Channel 1 Out - 0 25 Green/Black/White 5
Load RTN-0
Channel 2 Out + 1 24 Red/Black/White 2
OUT-1
Channel 2 Out - 2 23 White/Black/Red 6
RTN-1
Channel 3 Out + 3 22 Black/White/Red 7
OUT-2
Channel 3 Out - 4 21 Orange/Green 11
RTN-2
Channel 4 Out + 5 19 Blue/Red 8
OUT-3
Channel 4 Out - 6 18 Orange/Red 12
RTN-3
Not Used 7 17 15
OUT-4
Not Used B 16 19
RTN-4
1 16
Not Used
2 20
Not Used
3 13
Not Used
4 14
Not Used
5
6
7
1771-WC 8
Swing Arm 9
10
11
12
14
15
1 20

SH
1

CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS


1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected
to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003
module and the 1756-OF6CI [1492-CONACAB005E] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
2 IMPORTANT: The 1771-OFE2 module required the use of an external power supply to drive the analog device. The
1756-OF6CI analog output provides the drive power to the analog device. ENSURE the external power supply is REMOVED
from the current loop before applying power to the 1756-OF6CI module or the analog output module may be damaged.
3 The 1771-OFE2 analog output ranges were factory set, the output range for the 1756-OF6CI is software configured. Please
ensure the correct output range is configured in the 1756-OF6CI.
4 The 1756-OF6CI module can drive a load up to 550 ohms with the standard pre-configured cable [1492-CONACAB005E].
If greater than a 550 ohm drive current is required, the pre-wired cable can be modified at the 1756-OF6CI terminal block
to drive up to a 1000 ohms. Refer to the 1756-OF6CI Installation Manual for modification details.
5 Refer to your 1771-OFE2 and 1756-OF6CI Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.

41170-948 (1)

100 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - Analog Inputs and Outputs

1771-OFE2 to 1756-OF8I

WARNING
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Conversion Module
Cable
1492-CM1771-LA003

1492-CONACAB005E8C 1756-OF8I
+ Channel 1 Out + A 13 4
Current OUT_0/I
- Channel 1 Out - 0 25 6
Load RTN_0
Channel 2 Out + 1 24 3
OUT_1/I
Channel 2 Out - 2 23 5
RTN_1
Channel 3 Out + 3 22 12
OUT_2/I
Channel 3 Out - 4 21 14
RTN_2
Channel 4 Out + 5 19 11
OUT_3/I
Channel 4 Out - 6 18 13
RTN_3
Not Used 7 17
Not Used B 16
1
2
3
4
5
1771-WC Swing Arm 1 N.C. 23 N.C.
6
2 N.C. 24 N.C.
From 1771-OFE2 7 N.C.
7 N.C. 25
8 8 N.C. 26 N.C.
9 9 N.C. 27 N.C.
10 N.C. 28 N.C.
10
15 N.C. 29 N.C.
11 16 N.C. 30 N.C.
12 17 N.C. 31 N.C.
14 18 N.C. 32 N.C.
15 19 N.C. 33 N.C.
20 N.C. 34 N.C.
 20 21 N.C. 35 N.C.
N.C. 36 N.C.
 SH 22




Conversion Module Installation and Application Considerations


 Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)

shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used
between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-CONACAB005E8C] provides a shield ground lug to ground the shield at the 1756
ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.


 Refer to your 1771-OFE1 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and

DIR 10002306853 (Version 00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 101


Wiring Diagrams - Analog Inputs and Outputs

1771-OFE2(2) to 1756-OF8I

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1756-OF8I
Conversion Module 1492-C005005E8C
1492-CM1771-LA003 Cable “A”
+ Channel 1 Out + A 13
       

4
Current OUT_0/I
- Channel 1 Out - 0 25 6

 
        

Load RTN_0
1 24 3
          

Channel 2 Out + OUT_1/I


2 23 5
          

Channel 2 Out - RTN_1


3 22 12
          

Channel 3 Out + OUT_2/I


4 21 14
 

    

Channel 3 Out - RTN_2


5 19 11
    

Channel 4 Out + OUT_3/I


6 18 13


    

Channel 4 Out - RTN_3


Not Used 7 17
Not Used B 16
1
2
3
4
5
6
7
1771-WC Swing Arm 8
From 1771-OFE1 9
10
11
12
14
15
20


SH

Conversion Module
1492-CM1771-LA003 Cable “B”

+ Channel 1 Out + A 13
       

20
Current OUT_4/I
- Channel 1 Out - 0 25 22

 
        

Load RTN_4
1 24 19
          

Channel 2 Out + OUT_5/I


2 23 21
          

Channel 2 Out - RTN_5


3 22 28
          

Channel 3 Out + OUT_6/I


4 21 30
 

    

Channel 3 Out - RTN_6


5 19 27
    

Channel 4 Out + OUT_7/I


6 18 29


    

Channel 4 Out - RTN_7


Not Used 7 17
Not Used B 16
1
2
3
4
5
6
1 N.C. 23 N.C.
7
1771-WC Swing Arm 8 2 N.C. 24 N.C.
From 1771-OFE1 9 7 N.C. 25 N.C.
10 8 N.C. 26 N.C.
11 15 N.C. 31 N.C.
12
14
16 N.C. 32 N.C.
15
15 N.C. 33 N.C.
16 N.C. 34 N.C.
20

N.C. N.C.

SH
17 35
18 N.C. 36 N.C.

Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OF8I. Each cable can be either 0.5M or 1.0M (005=0.5M,
010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.

shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used
between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-C005005E8C] provides a shield ground lug to ground the shield at the 1756 ControlLogix
chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.

Refer to your 1771-OFE2 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and

DIR 10002306859 (Version 00)

102 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog
Standard High Resolution I/O

1771-NOC to 1756-OF8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Modul
e
1771-RTP3 or 1771-RTP4

SH B1 1492-CONACAB020N88
W2
W3
B2
B3
Cable”B”
R8 B4 15 29 RTN_7
2 I8 B5
S8 A4
O8 A5 4 27 OUT_7/I
R7 B8 18 30 RTN_6
I7 B9
S7 A6
O7 A7 7 28 OUT_6/I
R6 B12 21 21 RTN_5
I6 B13
S6 A8
O6 A9 10 19 OUT_5/I
R5 B16 24 22 RTN_4
I5 B17
O5 A10 13 20 OUT_4/I
S5 A11

W1 A1
CR A2
CL A3 Cable”A”
R4 B12 15 13 RTN_3
I4 B13
S4 A12
O4 A13 4 11 OUT_3/I
R3 B14 18 14 RTN_2
I3 B15
S3 A14
O3 A15 7 12 OUT_2/I
R2 B16 21 5 RTN_1
I2 B17
S2 A16
O2 A17 10 3 OUT_1/I
R1 B18 24 6 RTN_0
CURRENT
LOAD I1 B19
O1 A19 13 4 OUT_0/I
S1 A18

3
1 N.C. 23 N.C.
2 N.C. 24 N.C.
7 N.C. 25 N.C.
8 N.C. 26 N.C.
9 N.C. 31 N.C.
10 N.C. 32 N.C.
15 N.C. 33 N.C.
16 N.C. 34 N.C.
17 N.C. 35 N.C.
Interface Module Installation and Application Considerations 18 N.C. 36 N.C.
Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row terminals,
of B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4.
cable does not connect to these terminals.

[Reference Doc: DIR 10002306650]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 103


Wiring Diagrams - High Resolution Isolated Analog

1771-NOC to 1756-OF8

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

6
1756-OF8
RTP3 OR RTP4
SH B1 1492-CONACAB020N8
5 W2 B2 Cable”B”
W3 B3
R8 B4 15 White/Red
2 I8 B5 16
S8 A4
O8 A5 4 Orange 19 I-OUT-3
R7 B8 18 Green 15 I-RTN
I7 B9 19
S7 A6
O7 A7 7 White/Orange 13 I-OUT-2
R6 B12 21 White/Black
I6 B13 22
S6 A8
O6 A9 10 Gray 9 I-OUT-1
R5 B16 24 Black 5 I-RTN
I5 B17 25
O5 A10 13 White 3 I-OUT-0
S5 A11

W1 A1
CR A2 1492-CONACAB020N8
CL A3 Cable”A”
R4 B12 15 White/Red 4
I4 B13
S4 A12
O4 A13 4 Orange 19 I-OUT-3
R3 B14 18 Green 15 I-RTN
I3 B15
S3 A14
O3 A15 7 White/Orange 13 I-OUT-2
R2 B16 21 White/Black
I2 B17
S2 A16
O2 A17 10 Gray 9 I-OUT-1
R1 B18 24 Black 5 I-RTN
CURRENT
LOAD I1 B19
O1 A19 13 3 I-OUT-0
S1 A18 White

CONVERSION MODULE INSTALLATION


AND APPLICATION CONSIDERATIONS
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for proper
shield grounding instructions.
4 RTN terminals are internally connected on the
1756-OF8.
5 Terminals w1, w2, w3, are spares used f or field
wire convenience. NOTE: this is only true
for modules RTP3 and RTP4. The Bul. 1492 41171-079 (00)
cable does not connect to these terminals.
6 The 1771 - NOC module provides channel to channel isolation,
the 1756-OF8 does not. A conversion from 1771-NOC to an isolated 1756-OF8
is avalible.

104 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NOC to 1756-OF6CI

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP3 or RTP4
SH B1 N/A
Cable “B”
g W2 B2 N/A 1492-CONACAB020N1c 1756-OF6CI
W3 B3 N/A
R8 B4 15 White/Red 12
d RTN-3 f
I8 B5
S8 A4
O8 A5 4 Orange 8 OUT-3
R7 B8 18 Green 11 RTN-2
I7 B9
S7 A6
O7 A7 7 White/Orange 7 OUT-2
R6 B12 21 White/Black 6 RTN-1
I6 B13
S6 A8
O6 A9 10 Gray 2 OUT-1
R5 B16 24 Black 5 RTN-0
I5 B17
O5 A10 13 White 1 OUT-0
S5 A11

W1 A1 N/A
Cable “A” 1756-OF6CI
CR A2 N/A
CL A3 N/A
1492-CONACAB020N1c
R4 B12 15 White/Red 12
RTN-3 f
I4 B13
S4 A12
O4 A13 4 Orange 8 OUT-3
R3 B14 18 Green 11 RTN-2
I3 B15
S3 A14
O3 A15 7 White/Orange 7 OUT-2
R2 B16 21 White/Black 6 RTN-1
I2 B17
S2 A16
O2 A17 10 Gray 2
+ R1 B18 24 Black 5
OUT-1
CURRENT RTN-0
LOAD I1 B19
O1 A19 13 1 OUT-0
- S1 A18 White

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-OF6CI.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for modules RTP3 and
RTP4. The Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-072 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 105


Wiring Diagrams - High Resolution Isolated Analog

1771-NIS to 1756-IF8I

WARNING
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module

c
4 SH B1 N/A 1492-CONACAB020N38
W2 B2 N/A
W3 B3 N/A CABLE “B”
R8 B4 15 29 RTN_7
2 I8 B5 16 27 IN_7/I/SRC
S8 A4
O8 A5
R7 B8 18 30 RTN_6
I7 B9 19 28 IN_6/I/SRC
S7 A6
O7 A7
R6 B12 21 21 RTN_5
I6 B13 22 19 IN_5/I/SRC
S6 A8
O6 A9
R5 B16 24 22 RTN_4
I5 B17 25 20 IN_4/I/SRC
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
CABLE “A”
CL A3 N/A
R4 B12 15 13 RTN_3
I4 B13 16 11 IN_3/I/SRC
S4 A12
O4 A13
- R3 B14 18 14
CURRENT RTN_2
24VDC I3 B15 19 12
SUPPLY LOAD IN_2/I/SRC
S3 A14
+ O3 A15
R2 B16 21 5 RTN_1
I2 B17 22 3 IN_1/I/SRC
S2 A16
O2 A17
+ 24VDC - R1 B18 24 6
CURRENT RTN_0
SUPPLY I1 B19 25 4
LOAD IN_0/I/SRC
O1 A19
S1 A18

3 1 N.C. 23 N.C.
2 N.C. 24 N.C.
7 N.C. 25 N.C.
8 N.C. 26 N.C.
9 N.C. 31 N.C.
10 N.C. 32 N.C.
15 N.C. 33 N.C.
16 N.C. 34 N.C.
Interface Module Installation and Application Considerations 17 N.C. 35 N.C.
18 N.C. 36 N.C.
c Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
d Terminals starting with A are the lower row terminals,
of B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f for module RTP4. The Bul. 1492
cable does not connect t o t hese t erminals.

DIR 10002306457 (Version 00)

106 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIS to 1756-IF6CIS

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1771-RTP4
SH B1 N/A 1492-CONACAB020N2 1756-IF6CIS
5 W2 B2 N/A Cable “B”
W3 B3 N/A 4
R7 B4 15 White/Red
12 I-RTN-7
2 I7 B5 16 Red
10 I-IN-7
S7 A4
O7 A5 4 White/Green
8 V-OUT-7
R6 B8 18 Green
11 I-RTN-6
I6 B9 19 Yellow
9 I-IN-6
S6 A6
O6 A7 7 White/Yellow
7 V-OUT-6
R5 B12 21 White/Black
6 I-RTN-5
I5 B13 22 Brown
4 I-IN-5
S5 A8
LOOP POWER O5 A9 10 White/Brown V-OUT-5
SUPPLIED INTERNALLY Black 2
R4 B16 24 5
+ I4 B17 25 Violet
I-RTN-4
CURRENT White/Violet
3 I-IN-4
LOAD O4 A10 13
1 V-OUT-4
- S4 A11

W1 A1 N/A 1492-CONACAB020N2
1756-IF6CIS
CR A2 N/A Cable “A”
CL A3 N/A
R3 B12 15 White/Red
12 I-RTN-3 4
USER SUPPLIED I3 B13 16 Red
LOOP POWER 10 I-IN-3
S3 A12
SUPPLIED INTERNALLY O3 A13 4 White/Green
+ R2 B14 18 Green
8 V-OUT-3
24VDC CURRENT 11 I-RTN-2
I2 B15 19 Yellow
SUPPLY LOAD 9 I-IN-2
- S2 A14
O2 A15 7 White/Yellow
7 V-OUT-2
R1 B16 21 White/Black
6 I-RTN-1
I1 B17 22 Brown
4 I-IN-1
S1 A16
O1 A17 10 White/Brown V-OUT-1
+ 24VDC - R0 B18 24 Black
2
5 I-RTN-0
CURRENT SUPPLY I0 B19 25 Violet
LOAD 3 I-IN-0
O0 A19 13 White/Violet
1 V-OUT-0
S0 A18

3
CONVERSION MODULE INSTALLATION
AND APPLICATION CONSIDERATIONS
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for proper
shield grounding instructions.
4 RTN terminals are internally connected on the
1756-IF6CIS.
5 Terminals w1, w2, w3, are spares used f or field
wire convenience. NOTE: this is only true
for modules RTP4. The Bul. 1492
cable does not connect to these terminals.

41171-073 (01)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 107


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV to 1756-IF8I — Current

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP3
       

SH B1 N/A 1492-CONACAB020N38
4 W2 B2 N/A
W3 B3 N/A CABLE “B”
R8 B4 15        

29 RTN_7
2 I8 B5 16     

27

IN_7/I/SRC
S8 A4
O8 A5
+ R7 B8 18     

30 RTN_6
24VDC CURRENT I7 B9 19          

28
SUPPLY LOAD

IN_6/I/SRC
- S7 A6
O7 A7
R6 B12 21 21
    

RTN_5
I6 B13 22  

19



IN_5/I/SRC
S6 A8
O6 A9
R5 B16 24    

22 RTN_4
I5 B17 25 

20 IN_4/I/SRC
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
CABLE “A”
CL A3 N/A
R4 B12 15 13
       

RTN_3
I4 B13 16 11
    

IN_3/I/SRC
S4 A12
O4 A13
R3 B14 18
    

14 RTN_2
I3 B15 19
      

  

12 IN_2/I/SRC
S3 A14
O3 A15
R2 B16 21
    

5


RTN_1
I2 B17 22
 

3



IN_1/I/SRC
S2 A16
O2 A17
+ 24VDC - R1 B18 24
   

6
CURRENT RTN_0
SUPPLY I1 B19 25 4
LOAD 

IN_0/I/SRC
O1 A19
S1 A18

3 1 N.C. 23 N.C.
2 N.C. 24 N.C.
7 N.C. 25 N.C.
8 N.C. 26 N.C.
9 N.C. 31 N.C.
10 N.C. 32 N.C.
15 N.C. 33 N.C.
16 N.C. 34 N.C.
17 N.C. 35 N.C.
Interface Module Installation and Application Considerations 18 N.C. 36 N.C.

Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)



Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306458 (Version 00)

108 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV to 1756-IF6I — Current

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1771-RTP4
SH B1 N/A 1492-CONACAB010N3 1756-IF6I
5 W2 B2 N/A
CABLE “B”
W3 B3 N/A
R8 B4 15 White/Red
4
2 12 RTN-3
I8 B5 16 Orange
10 IN-3/I
S8 A4
8 IN-3/V
O8 A5
+ R7 B8 18 Green
24VDC CURRENT 11 RTN-2
I7 B9 19 White/Orange
SUPPLY LOAD 9 IN-2/I
- S7 A6
7 IN-2/V
O7 A7
R6 B12 21 White/Black
RTN-1
6
I6 B13 22 Gray
4 IN-1/I
S6 A8
2 IN-1/V
O6 A9
R5 B16 24 White RTN-0
5
I5 B17 25 Black
3 IN-0/I
O5 A10 IN-0/V
1
S5 A11

W1 A1 N/A
CR A2 N/A
1492-CONACAB010N3 1756-IF6I
CABLE “A”
CL A3 N/A
R4 B12 15 White/Red 4
12 RTN-3
I4 B13 16 Orange
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 White/Orange
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Gray
S2 4 IN-1/I
A16
O2 2 IN-1/V
A17
+ 24VDC - R1 B18 24 White
CURRENT SUPPLY 5 RTN-0
LOAD I1 B19 25 Black
3 IN-0/I
O1 A19
1 IN-0/V
S1 A18

3
CONVERSION MODULE INSTALLATION
AND APPLICATION CONSIDERATIONS

1 Cables are available in 2.0m, or 5.0m


2 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for proper
shield grounding instructions.
4 RTN terminals are internally connected on the
1756-IF6I.
5 Terminals w1, w2, w3, are spares used f or field
wire convenience. NOTE: this is only true
for modules RTP3. The Bul. 1492
cable does not connect to these terminals.
41171-074 (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 109


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV to 1756-IF8I — Voltage

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
       

4 SH B1 N/A 1492-CONACAB020N78
W2 B2 N/A
W3 B3 N/A CABLE “B”
R8 B4 15   

29
 

RTN_7
2 I8 B5 16 

25


IN_7/V
S8 A4
O8 A5
+ R7 B8 18  


30 RTN_6
VOLTAGE I7 B9 19 

26
LOAD


IN_6/V
- S7 A6
O7 A7
R6 B12 21 21
  

   

RTN_5
I6 B13 22  

17

 

IN_5/V
S6 A8
O6 A9
R5 B16 24 

22
  

RTN_4
I5 B17 25 

18 IN_4/V
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
CABLE “A”
CL A3 N/A
R4 B12 15 13
  

 

RTN_3
I4 B13 16 9


IN_3/V
S4 A12
O4 A13
R3 B14 18
 


14 RTN_2
I3 B15 19




10 IN_2/V
S3 A14
O3 A15
R2 B16 21
  

5
   

RTN_1
I2 B17 22
 

1

 

IN_1/V
S2 A16
O2 A17
R1 B18 24 6


VOLTAGE
  

RTN_0
LOAD I1 B19 25 

2 IN_0/V
O1 A19
S1 A18

3 3 N.C. 23 N.C.
4 N.C. 24 N.C.
7 N.C. 27 N.C.
8 N.C. 28 N.C.
11 N.C. 31 N.C.
12 N.C. 32 N.C.
Interface Module Installation and Application Considerations 15 N.C. 33 N.C.
16 N.C. 34 N.C.
Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) 19 N.C. 35 N.C.
20 N.C. 36 N.C.

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
for module RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306478 (Version 00)

110 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV to 1756-IF6I — Voltage

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module 1756-IF6I


1771-RTP4 or 1771-RTP4
Cable “B”
SH B1 N/A
g 1492-CONACAB020N7c
W2 B2 N/A
W3 B3 N/A
R8 B4 15 White/Red
d 12 RTN-3 f
I8 B5 16 Red
8 IN-3V
S8 A4
O8 A5
- R7 B8 19 Green
VOLTAGE 11 RTN-2
I7 B9 18 Yellow
LOAD 7 IN-2V
S7 A6
+ O7 A7
R6 B12 22 White/Black
6 RTN-1
I6 B13 21 Brown
S6 2 IN-1V
A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0V
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
Cable “A” 1756-IF6I
CL A3 N/A
1492-CONACAB020N7c
R4 B12 15 White/Red
12 RTN-3
f
I4 B13 16 Red
8 IN-3V
S4 A12
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Brown
2 IN-1V
S2 A16
O2 A17
- R1 B18 24 Black
VOLTAGE 5 RTN-0
I1 B19 25 Violet
LOAD 1 IN-0V
O1 A19
+ S1 A18

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-IF6I.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
41171-080 Ver (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 111


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV to 1756-IF6I — Current and Voltage

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module 1756-IF6I


1771-RTP4
Cable “B”
SH B1 N/A
g 1492-CONACAB020N7c
W2 B2 N/A
W3 B3 N/A (Voltage)
R8 B4 15 White/Red
d 12 RTN-3 f
I8 B5 16 Red
8 IN-3V
S8 A4
O8 A5
- R7 B8 19 Green
VOLTAGE 11 RTN-2
I7 B9 18 Yellow
LOAD 7 IN-2V
S7 A6
+ O7 A7
R6 B12 22 White/Black
6 RTN-1
I6 B13 21 Brown
S6 2 IN-1V
A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0V
O5 A10
S5 A11
CABLE “A”
W1 A1 N/A c
CR
1492-CONACAB010N3 1756-IF6I
A2 N/A
CL A3 N/A (Current)
R4 B12 15 White/Red 4
12 RTN-3
I4 B13 16 Red
Orange
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
Green
11 RTN-2
I3 B15 19 Yellow
White/Orange
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
White/Black
I2 6 RTN-1
B17 22 Brown
Gray
S2 4 IN-1/I
A16
O2 2 IN-1/V
A17
- R1 B18 24 Black
White
CURRENT 5 RTN-0
I1 B19 25 Violet
Black
LOAD 3 IN-0/I
O1 A19
+ S1 A18
1 IN-0/V

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-IF6I.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
41171-039 Ver (00)

112 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV to 1756-IF6I — Voltage and Current

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1771-RTP4
1492-CONACAB010N3
SH B1
5 W2 B2
N/A
N/A
CABLE “B” 1756-IF6I
W3 B3 N/A (Current)
R8 B4 15 White/Red 4
2 12 RTN-3
I8 B5 16 Orange
10 IN-3/I
S8 A4
8 IN-3/V
- O8
R7
A5
B8 18 Green
CURRENT 11 RTN-2
I7 B9 19 White/Orange
LOAD 9 IN-2/I
S7 A6
7 IN-2/V
+ O7 A7
R6 B12 21 White/Black
6 RTN-1
I6 B13 22 Gray
4 IN-1/I
S6 A8
O6 2 IN-1/V
A9
R5 B16 24 White
5 RTN-0
I5 B17 25 Black
3 IN-0/I
O5 A10
1 IN-0/V
S5 A11

W1 A1 N/A 1492-CONACAB010N7
1756-IF6I
CR A2 N/A CABLE “A”
CL A3 N/A (Voltage)
R4 B12 15 White/Red
12 RTN-3 f
I4 B13 16 Orange
S4 A12 8 IN-3V
O4 A13
R3 B14 18 Green
I3 B15 19 White/Orange
11 RTN-2
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
I2 6 RTN-1
B17 22 Gray
S2 2 IN-1V
A16
O2 A17
- R1 B18 24 White
Voltage 5 RTN-0
LOAD I1 B19 25 Black
1 IN-0V
+ O1 A19
S1 A18

3
CONVERSION MODULE INSTALLATION
AND APPLICATION CONSIDERATIONS

1 Cables are available in 2.0m, or 5.0m


2 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for proper
shield grounding instructions.
4 RTN terminals are internally connected on the
1756-IF6I.
5 Terminals w1, w2, w3, are spares used f or field
wire convenience. NOTE: this is only true
for modules RTP3. The Bul. 1492
cable does not connect to these terminals.
41171-038 (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 113


Wiring Diagrams - High Resolution Isolated Analog

1771-NR to 1756-IRT8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
        

4 SH B1 N/A
1492-CONACAB020N48
W2 B2 N/A
Cable “B”
W3 B3 N/A
R8 B4 15         

2 34 IN_7/RTD C
I8 B5 16   

32 IN_7(-)/B
S8 A4
O8 A5 4     

31 IN_7(+)/A
R7 B8 18     

30 IN_6/RTD C
I7 B9 19  

 

RTD 28 IN_6(-)/B
TRANSMITTER S7 A6
O7 A7 7
          

27 IN_6(+)/A
R6 B12 21      

26 IN_5/RTD C
I6 B13 22    

S6 24 IN_5(-)/B
A8
O6 A9 10   

23 IN_5(+)/A
R5 B16 24

22 IN_4/RTD C
I5 B17 25
20 IN_4(-)/B
  
 

O5 A10 13     

19 IN_4(+)/A
S5 A11

W1 A1 N/A
CR A2 N/A
Cable “A”
CL A3 N/A
R4 B12 15
        

18 IN_3/RTD C
I4 B13 16
  

16 IN_3(-)/B
S4 A12
O4 A13 4
    

15 IN_3(+)/A
R3 B14 18
    

14 IN_2/RTD C
I3 B15 19  

 

12 IN_2(-)/B
S3 A14
O3 A15 7
          

11 IN_2(+)/A
R2 B16 21      

I2 10 IN_1/RTD C
B17 22
   

S2 8 IN_1(-)/B
A16
O2 A17 10   

7 IN_1(+)/A
R1 B18 24

6 IN_0/RTD C
I1 B19 25
  
 

RTD 4 IN_0(-)/B
TRANSMITTER O1 A19 13     

3 IN_0(+)/A
S1 A18
1 N.C. 25 N.C.
2 N.C. 29 N.C.
5 N.C. 33 N.C.
3 9 N.C. 35 N.C.
13 N.C. 36 N.C.
17 N.C.
21 N.C.

Interface Module Installation and Application Considerations


Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306848 (Version 00)

114 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NR to 1756-IR6I

There are several key application considerations and system specifications (bottom
IMPORTANT using these components (conversion module, cable and input module). Read and
considerations before installation.

1771-RTP4
SH B1 N/A
1756-IR6I
5 1492-CONACAB020N4
W2 B2 N/A
Cable “B”
W3 B3 N/A
R8 B4 15 12 RTN-3 4
White/Red
2 I8 B5 16 Red
10 IN-3/B
S8 A4
O8 A5 4 Orange
8 IN-3/A
R7 B8 18 Green
11 RTN-2
I7 B9 19 Yellow
RTD 9 IN-2/B
TRANSMITTER S7 A6
O7 A7 7 White/Orange
7 IN-2/A
R6 B12 21 White/Black
6 RTN-1
I6 B13 22 Brown
S6 4 IN-1/B
A8
O6 A9 10 Gray
2 IN-1/A
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet IN-0/B
3
O5 A10 13 White
1 IN-0/A
S5 A11

W1 A1 N/A
CR A2 N/A
1492-CONACAB020N4 1756-IR6I
Cable “A”
CL A3 N/A
R4 B12 15 12 RTN-3 4
White/Red
I4 B13 16 Red
10 IN-3/B
S4 A12
O4 A13 4 Orange 8 IN-3/A
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
9 IN-2/B
S3 A14
O3 A15 7 White/Orange
7 IN-2/A
R2 B16 21 White/Black
I2 6 RTN-1
B17 22 Brown
S2 4 IN-1/B
A16
O2 A17 10 Gray
2 IN-1/A
R1 B18 24 Black
RTN-0
5
I1 B19 25 Violet IN-0/B
RTD 3
TRANSMITTER O1 A19 13 White
1 IN-0/A
S1 A18

CONVERSION MODULE INSTALLATION


AND APPLICATION CONSIDERATIONS
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for proper
shield grounding instructions.
4 RTN terminals are internally connected on the
1756-IR6I.
5 Terminals w1, w2, w3, are spares used f or field
wire convenience. NOTE: this is only true 41171-075 (00)
for modules RTP4. The Bul. 1492
cable does not connect to these terminals.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 115


Wiring Diagrams - High Resolution Isolated Analog

1771-NT1 or -NT2 to 1756-IRT8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Interface Module
1
1771-RT41 1492-CONACAB020N68 1756-IRT8I
4 SH B1 Cable “B”
W1 A1
2 White/Red
R4 B2 15 32 IN_7(-)/B
I4 B3 16 Red
31 IN_7(+)/A
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
28 IN_6(-)/B
I3 B5 19
27 IN_6(+)/A
S3 A4
+ O3 A5

14 White/Violet
35 CJC1
Thermocouple 1 White/Grey
36 CJC1

R2 B6 21 White/Black
24 IN_5(-)/B
I2 B7 22 Brown
23 IN_5(+)/A
S2 A6
O2 A7
R1 B8 24 Black
20 IN_4(-)/B
I1 B9 25 Violet
19 IN_4(+)/A
O1 A9
S1 A8

Interface Module
1771-RT41
4 SH B1 Cable “A”
W1 A1
2 White/Red
R4 B2 15 16 IN_3(-)/B
I4 B3 16 Red
15 IN_3(+)/A
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
12 IN_2(-)/B
I3 B5 19
11 IN_2(+)/A
S3 A4
+ O3 A5

14 White/Violet
1 CJC0
Thermocouple 1 White/Grey
2 CJC0

R2 B6 21 White/Black
8 IN_1(-)/B
I2 B7 22 Brown
7 IN_1(+)/A
S2 A6
O2 A7
R1 B8 24 Black
4 IN_0(-)/B
I1 B9 25 Violet
3 IN_0(+)/A
O1 A9
S1 A8

5 N.C. 18 N.C.
3 6 N.C. 21 N.C.
9 N.C. 22 N.C.
10 N.C. 25 N.C.
13 N.C. 26 N.C.
14 N.C. 29 N.C.
17 N.C. 30 N.C.
33 N.C.
34 N.C.
Interface Module Installation and Application Considerations
Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.
This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules.
Each 1771-RTP1 and RT41 module has there own cold junction compensation thermocouple attached to the interface module.

DIR 10002306849 (Version 00)

116 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NT1 to 1756-IT6I

There are several key application considerations and system specifications (bottom
IMPORTANT using these components (conversion module, cable and input module). Read and
considerations before installation.

1771-RT41 1
1492-CONACAB020N5 1756-IT6I
4 SH B1 Cable “B”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
8 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
11 RTN-2
I3 B5 19
7 IN-2
S3 A4
+ O3 A5

White/Violet
10 CJC+
Thermocouple White/Grey
14 CJC-

R2 B6 21 White/Black
6 RTN-1
I2 B7 22 Brown
2 IN-1
S2 A6
O2 A7
R1 B8 24 Black
5 RTN-0
I1 B9 25 Violet
1 IN-0
O1 A9
S1 A8

1771-RT41 1
1492-CONACAB020N5 1756-IT6I
4 SH B1 Cable “A”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
8 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
11 RTN-2
I3 B5 19
7 IN-2
S3 A4
+ O3 A5
White/Violet
10 CJC+
Thermocouple White/Grey
14 CJC-

R2 B6 21 White/Black
6 RTN-1
I2 B7 22 Brown
2 IN-1
S2 A6
O2 A7
R1 B8 24 Black
5 RTN-0
I1 B9 25 Violet
1 IN-0
O1 A9
S1 A8

CONVERSION MODULE INSTALLATION


AND APPLICATION CONSIDERATIONS
c Cables are available in 2.0M or 5.0M.
dTerminals starting with A are the lower row of
terminals, B terminals are the upper row.
eFollow your PLC Analog User Manual for proper
shield grounding instructions. 41171-076 (01)
fTerminals W1, W2 and W3 are spares used for field wire
convenience. NOTE. This is only true for modules RT41 .
The Bul. 1492 cable does not connect to these terminals.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 117


Wiring Diagrams - High Resolution Isolated Analog

1771-NOV to 1756-OF8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
       

Interface Module
1771-RTP3 or 1771-RTP4

SH B1 1492-CONACAB020N18
W2 B2
W3 B3
Cable”B”
R8 B4 15 29 RTN_7
        

2 I8 B5
S8 A4
O8 A5 4 25 OUT_7/V
    

R7 B8 18 30 RTN_6
    

I7 B9
S7 A6
O7 A7 7 26 OUT_6/V
          

R6 B12 21
     

21 RTN_5
I6 B13
S6 A8
O6 A9 10
  

17 OUT_5/V
B16 24

R5 22 RTN_4
I5 B17
O5 A10 13 18 OUT_4/V
    

S5 A11

W1 A1
CR A2
CL A3 Cable”A”
R4 B12 15
        

13 RTN_3
I4 B13
S4 A12
O4 A13 4 9 OUT_3/V
    

R3 B14 18
    

14 RTN_2
I3 B15
S3 A14
O3 A15 7
          

10 OUT_2/V
R2 B16 21
     

5 RTN_1
I2 B17
S2 A16
O2 A17 10 1 OUT_1/V
  

- R1 B18 24

6 RTN_0
VOLTAGE
LOAD I1 B19
O1 A19 2 OUT_0/V
    

13
+ S1 A18

3
1 N.C. 23 N.C.
2 N.C. 24 N.C.
7 N.C. 25 N.C.
8 N.C. 26 N.C.
9 N.C. 31 N.C.
10 N.C. 32 N.C.
15 N.C. 33 N.C.
16 N.C. 34 N.C.
17 N.C. 35 N.C.
18 N.C. 36 N.C.
Interface Module Installation and Application Considerations
Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306686 (Version 00)

118 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NOV to 1756-OF6VI

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP3 or RTP4
SH B1 N/A
Cable “B”
g W2 B2 N/A 1492-CONACAB020N1c 1756-OF6VI
W3 B3 N/A
R8 B4 15 White/Red 12
d RTN-3 f
I8 B5
S8 A4
O8 A5 4 Orange 8 OUT-3
R7 B8 18 Green 11 RTN-2
I7 B9
S7 A6
O7 A7 7 White/Orange 7 OUT-2
R6 B12 21 White/Black 6 RTN-1
I6 B13
S6 A8
O6 A9 10 Gray 2 OUT-1
R5 B16 24 Black 5 RTN-0
I5 B17
O5 A10 13 White 1 OUT-0
S5 A11

W1 A1 N/A
Cable “A” 1756-OF6VI
CR A2 N/A
CL A3 N/A
1492-CONACAB020N1c
R4 B12 15 White/Red 12
RTN-3 f
I4 B13
S4 A12
O4 A13 4 Orange 8 OUT-3
R3 B14 18 Green 11 RTN-2
I3 B15
S3 A14
O3 A15 7 White/Orange 7 OUT-2
R2 B16 21 White/Black 6 RTN-1
I2 B17
S2 A16
O2 A17 10 Gray 2
- OUT-1
R1 B18 24 Black 5
VOLTAGE RTN-0
LOAD I1 B19
O1 A19 13 1 OUT-0
+ S1 A18 White

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-OF6VI.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for modules RTP3 and
RTP4. The Bul. 1492 cable does not connect to these terminals.
41171-081 Ver(00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 119


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV1 to 1756-IF8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
       

4 SH B1 N/A 1492-CONACAB020N78
W2 B2 N/A
W3 B3 N/A CABLE “B”
R8 B4 15   

29
 

RTN_7
2 I8 B5 16 

25


IN_7/V
S8 A4
O8 A5
- R7 B8 18  


30 RTN_6
VOLTAGE I7 B9 19 

26
LOAD


IN_6/V
S7 A6
+ O7 A7
R6 B12 21 21
  

   

RTN_5
I6 B13 22  

17

 

IN_5/V
S6 A8
O6 A9
R5 B16 24 

22
  

RTN_4
I5 B17 25 

18 IN_4/V
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
CABLE “A”
CL A3 N/A
R4 B12 15 13
  

 

RTN_3
I4 B13 16 9


IN_3/V
S4 A12
O4 A13
R3 B14 18
 


14 RTN_2
I3 B15 19




10 IN_2/V
S3 A14
O3 A15
R2 B16 21
  

5
   

RTN_1
I2 B17 22
 

1

 

IN_1/V
S2 A16
O2 A17
- R1 B18 24


6
VOLTAGE
  

RTN_0
LOAD I1 B19 25 

2 IN_0/V
O1 A19
+ S1 A18

3 3 N.C. 23 N.C.
4 N.C. 24 N.C.
7 N.C. 27 N.C.
8 N.C. 28 N.C.
11 N.C. 31 N.C.
12 N.C. 32 N.C.
15 N.C. 33 N.C.
16 N.C. 34 N.C.
19 N.C. 35 N.C.
20 N.C. 36 N.C.

Interface Module Installation and Application Considerations


Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306486 (Version 00)

120 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIV1 to 1756-IF6I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1756-IF6I
RTP4
1492-CONACAB020N7
SH B1 N/A
5 W2 B2 N/A
Cable”B”
W3 B3 N/A
R8 B4 15 White/Red
2 12 RTN-3 4
I8 B5 16 Red
8 IN-3V
S8 A4
O8 A5
- R7 B8 19 Yellow
VOLTAGE 7 RTN-2
I7 B9 18 Green
LOAD 13 IN-2V
S7 A6
+ O7 A7
R6 B12 22 Brown
2 RTN-1
I6 B13 21 White/Black
S6 6 IN-1V
A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0V
O5 A10
S5 A11

W1 A1 N/A
CR A2 N/A
1492-CONACAB020N7 1756-IF6I
CL A3 N/A
Cable”A”
R4 B12 15 White/Red 4
12 RTN-3
I4 B13 16 Red
8 IN-3V
S4 A12
O4 A13
R3 B14 19 Yellow
7 RTN-2
I3 B15 18 Green
S3 13 IN-2V
A14
O3 A15
R2 B16 22 Brown
2 RTN-1
I2 B17 21 White/Black
S2 6 IN-1V
A16
O2 A17
- R1 B18 24 Black
VOLTAGE 5 RTN-0
I1 B19 25 Violet
LOAD 1 IN-0V
O1 A19
+ S1 A18

CONVERSION MODULE INSTALLATION


3
AND APPLICATION CONSIDERATIONS
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of
terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for proper
shield grounding instructions.
4 RTN terminals are internally connected on the
1756-IF6I.
5 Terminals w1, w2, w3, are spares used f or field
wire convenience. NOTE: this is only true
for modules RTP3 and RTP4. The Bul. 1492 41171-078 (00)
cable does not connect to these terminals.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 121


Wiring Diagrams - High Resolution Isolated Analog

1771-NT2 to 1756-IRT8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Interface Module
1
1771-RT41 1492-CONACAB020N68 1756-IRT8I
4 SH B1 Cable “B”
W1 A1
2 White/Red
R4 B2 15 32 IN_7(-)/B
I4 B3 16 Red
31 IN_7(+)/A
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
28 IN_6(-)/B
I3 B5 19
27 IN_6(+)/A
S3 A4
+ O3 A5

14 White/Violet
35 CJC1
Thermocouple 1 White/Grey
36 CJC1

R2 B6 21 White/Black
24 IN_5(-)/B
I2 B7 22 Brown
23 IN_5(+)/A
S2 A6
O2 A7
R1 B8 24 Black
20 IN_4(-)/B
I1 B9 25 Violet
19 IN_4(+)/A
O1 A9
S1 A8

Interface Module
1771-RT41
4 SH B1 Cable “A”
W1 A1
2 White/Red
R4 B2 15 16 IN_3(-)/B
I4 B3 16 Red
15 IN_3(+)/A
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
12 IN_2(-)/B
I3 B5 19
11 IN_2(+)/A
S3 A4
+ O3 A5

14 White/Violet
1 CJC0
Thermocouple 1 White/Grey
2 CJC0

R2 B6 21 White/Black
8 IN_1(-)/B
I2 B7 22 Brown
7 IN_1(+)/A
S2 A6
O2 A7
R1 B8 24 Black
4 IN_0(-)/B
I1 B9 25 Violet
3 IN_0(+)/A
O1 A9
S1 A8

5 N.C. 18 N.C.
3 6 N.C. 21 N.C.
9 N.C. 22 N.C.
10 N.C. 25 N.C.
13 N.C. 26 N.C.
14 N.C. 29 N.C.
17 N.C. 30 N.C.
33 N.C.
34 N.C.
Interface Module Installation and Application Considerations
Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.
This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules.
Each 1771-RTP1 and RT41 module has there own cold junction compensation thermocouple attached to the interface module.

DIR 10002306849 (Version 00)

122 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NT2 to 1756-IT6I2

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

1771-RT41 1
1492-CONACAB020N6 1756-IT6I2
4 SH B1 Cable “B”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
11 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
10 RTN-2
I3 B5 19
9 IN-2
S3 A4
+ O3 A5
White/Violet
3 CJC+
Thermocouple White/Grey
4 CJC-

R2 B6 21 White/Black
8 RTN-1
I2 B7 22 Brown
7 IN-1
S2 A6
O2 A7
R1 B8 24 Black
6 RTN-0
I1 B9 25 Violet
5 IN-0
O1 A9
S1 A8

1771-RT41 1
1492-CONACAB020N6 1756-IT6I2
4 SH B1 Cable “A”
W1 A1
2 White/Red
R4 B2 15 12 RTN-3
I4 B3 16 Red
11 IN-3
S4 A2
O4 A3
THERMOCOUPLE
- R3 B4 18 Green
Yellow
10 RTN-2
I3 B5 19
9 IN-2
S3 A4
+ O3 A5
White/Violet
3 CJC+
Thermocouple White/Grey
4 CJC-

R2 B6 21 White/Black
8 RTN-1
I2 B7 22 Brown
7 IN-1
S2 A6
O2 A7
R1 B8 24 Black
6 RTN-0
I1 B9 25 Violet
5 IN-0
O1 A9
S1 A8

CONVERSION MODULE INSTALLATION


AND APPLICATION CONSIDERATIONS
c Cables are available in 2.0M or 5.0M.
dTerminals starting with A are the lower row of
terminals, B terminals are the upper row.
eFollow your PLC Analog User Manual for proper
shield grounding instructions. 41171-077 (01)
fTerminals W1, W2 and W3 are spares used for field wire
convenience. NOTE. This is only true for modules RT41 .
The Bul. 1492 cable does not connect to these terminals.

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 123


Wiring Diagrams - High Resolution Isolated Analog

Combination High Resolution I/O

1771-NIVR to1756-IRT8I and -IF8I

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
1492-CONACAB020N44
B1
SH N/A 1756-IRT8I
W2 B2 N/A CABLE “B”
W3 B3 N/A
R8 B4 15
       


18 IN_3/RTD C
I8 B5 16
 

16 IN_3(-)/B
S8 A4
O8 A5 4
   

15 IN_3(+)/A
R7 B8 18

 

14 IN_2/RTD C
I7 B9 19      

RTD 12 IN_2(-)/B
ANSMITTER S7 A6
O7 A7 7
         

11 IN_2(+)/A
R6 B12 21          

10 IN_1/RTD C
I6 B13 22
  

S6 8 IN_1(-)/B
A8
O6 A9 10
 

7 IN_1(+)/A
R5 B16 24    

6 IN_0/RTD C
I5 B17 25     

4 IN_0(-)/B
O5 A10 13     

3 IN_0(+)/A
S5 A11

W1 A1 N/A
CR A2 N/A
1492-CONACAB020N74 1756-IF8I
CL A3 N/A CABLE “A”
R4 B12 15
       

13 RTN_3
I4 B13 16
 

9 IN_3/V
S4 A12
O4 A13
R3 B14 18
 

14 RTN_2
I3 B15 19
     

S3 10 IN_2/V
A14
O3 A15
R2 B16 21          

5 RTN_1
I2 B17 22
  

S2 1 IN_1/V
A16
O2 A17
- R1 B18 24
   

VOLTAGE 6 RTN_0
I1 B19 25
    

LOAD 2 IN_0/V
O1 A19
+ S1 A18

Interface Module Installation and Application Considerations


Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306496(Version 00)

124 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIVR to 1756-IR6Iand -IF6I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
Cable “B”
SH B1 N/A 1756-IR6I
g 1492-CONACAB020N4c
W2 B2 N/A
W3 B3 N/A
R8 B4 15 12 RTN-3 f
d I8 B5 16 10 IN-3/B
S8 A4
O8 A5 4 8 IN-3/A
R7 B8 18 11 RTN-2
I7 B9 19
RTD 9 IN-2/B
TRANSMITTER S7 A6
O7 A7 7 7 IN-2/A
R6 B12 21
6 RTN-1
I6 B13 22
S6 4 IN-1/B
A8
O6 A9 10
2 IN-1/A
R5 B16 24
5 RTN-0
I5 B17 25 3 IN-0/B
O5 A10 13
1 IN-0/A
S5 A11

W1 A1 N/A
CR A2 N/A
Cable “A” 1756-IF6I
CL A3 N/A
1492-CONACAB020N7c
R4 B12 15 White/Red
12 RTN-3
f
I4 B13 16 Red
8 IN-3V
S4 A12
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Brown
2 IN-1V
S2 A16
O2 A17
- R1 B18 24 Black
VOLTAGE 5 RTN-0
I1 B19 25 Violet
LOAD 1 IN-0V
O1 A19
+ S1 A18

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-IF6I.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-082 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 125


Wiring Diagrams - High Resolution Isolated Analog

1771-NIVR to 1756-IRT8I and -IF8I

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
1492-CONACAB020N44
B1
SH N/A
CABLE “B”
1756-IRT8I
W2 B2 N/A
W3 B3 N/A
R8 B4 15
      


18 IN_3/RTD C
I8 B5 16
 

16 IN_3(-)/B
S8 A4
O8 A5 4
 

15 IN_3(+)/A
R7 B8 18

14 IN_2/RTD C
I7 B9 19     

RTD 12 IN_2(-)/B
TRANSMITTER S7 A6
O7 A7 7
      

11 IN_2(+)/A
R6 B12 21         

10 IN_1/RTD C
I6 B13 22
 

S6 8 IN_1(-)/B
A8
O6 A9 10
 

7 IN_1(+)/A
R5 B16 24    

6 IN_0/RTD C
I5 B17 25     

4 IN_0(-)/B
O5 A10 13    

3 IN_0(+)/A
S5 A11

W1 A1 N/A
CR A2 N/A
1492-CONACAB020N34 1756-IF8I
CL A3 N/A CABLE “A”
R4 B12 15
      

13 RTN_3
I4 B13 16
 

11 IN_3/I/SRC
S4 A12
O4 A13
R3 B14 18

14 RTN_2
I3 B15 19
      

S3 12 IN_2/I/SRC
A14
O3 A15
R2 B16 21         

5 RTN_1
I2 B17 22

 

S2 3 IN_1/I/SRC
A16
O2 A17
- R1 B18 24
   

CURRENT 6 RTN_0
I1 B19 25
   

LOAD 4 IN_0/I/SRC
O1 A19
+ S1 A18

Interface Module Installation and Application Considerations


Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306490 (Version 00)

126 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIVR to 1756-IR6I and -IF6I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP4
Cable “B”
SH B1 N/A 1756-IR6I
g 1492-CONACAB020N4c
W2 B2 N/A
W3 B3 N/A
R8 B4 15 12 RTN-3 f
d I8 B5 16 10 IN-3/B
S8 A4
O8 A5 4 8 IN-3/A
R7 B8 18 11 RTN-2
I7 B9 19
RTD 9 IN-2/B
TRANSMITTER S7 A6
O7 A7 7 7 IN-2/A
R6 B12 21
6 RTN-1
I6 B13 22
S6 4 IN-1/B
A8
O6 A9 10
2 IN-1/A
R5 B16 24
5 RTN-0
I5 B17 25 3 IN-0/B
O5 A10 13
1 IN-0/A
S5 A11

W1 A1 N/A
Cable “A”
CR A2 N/A 1756-IF6I
1492-CONACAB010N3c
CL A3 N/A
R4 B12 15 White/Red
12 RTN-3
f
I4 B13 16 Orange
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 White/Orange
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Gray
4 IN-1/I
S2 A16
O2 2 IN-1/V
A17
- R1 B18 24 White
VOLTAGE 5 RTN-0
I1 B19 25 Black
LOAD 3 IN-0/I
O1 A19
+ S1 A18
1 IN-0/V

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-IF6I.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-083 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 127


Wiring Diagrams - High Resolution Isolated Analog

1771-NIVT to 1756-IRT8I and -IF8I

IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP1
CABLE “B”
4 SH B1 1492-CONACAB020N54 1756-IRT8I
W2 B2
2 W3 B3
White/Red
R8 B4 15 16 IN_3(-)/B
I8 B5 16 Red
15 IN_3(+)/A
THERMOCOUPLE S8 A4
O8 A5
- B8 18 Green
R7 12 IN_2(-)/B
I7 B9 19 Yellow
11 IN_2(+)/A
S7 A6
+ O7 A7
R6 B12 21 White/Black
8 IN_1(-)/B
I6 B13 22 Brown
7 IN_1(+)/A
S6 A8
O6 A9
R5 B16 24 Black
4 IN_0(-)/B
I5 B17 25 Violet
3 IN_0(+)/A
O5 A10
S5 A11
10 CJC+
14 CJC-
14
Thermocouple 1

CABLE “A”
W1 A1 1756-IF8I
CR A2 1492-CONACAB020N74
CL A3
R4 B12 15
       

13 RTN_3
I4 B13 16
 

9 IN_3/V
S4 A12
O4 A13
R3 B14 18
 

14 RTN_2
I3 B15 19
     

S3 10 IN_2/V
A14
O3 A15
R2 B16 21          

5 RTN_1
I2 B17 22
  

1 IN_1/V
S2 A16
O2 A17
- R1 B18 24
   

6 RTN_0
VOLTAGE I1 B19 25
    

LOAD 2 IN_0/V
O1 A19
+ S1 A18

Interface Module Installation and Application Considerations


Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306594 (Version 00)

128 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIVT to 1756-IT6I and -IF6I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP1

4 SH B1 1492-CONACAB010N5 1756-IT6I
W2 B2 CABLE “B”
2 W3 B3
White/Red
R8 B4 15 12 RTN-3
I8 B5 16 Red
11 IN-3
THERMOCOUPLE S8 A4
O8 A5
- R7 B8 18 Green
Yellow
10 RTN-2
I7 B9 19
9 IN-2
S7 A6
+ O7 A7
R6 B12 21 White/Black
8 RTN-1
I6 B13 22 Brown
7 IN-1
S6 A8
O6 A9
R5 B16 24 Black
6 RTN-0
I5 B17 25 Violet
5 IN-0
O5 A10
S5 A11
10 CJC+
CABLE “B” CJC-
14 14
Thermocouple 1

W1 A1
CR A2 Cable “A” 1756-IF6I
CL A3 1492-CONACAB020N7c
R4 B12 15 White/Red
12 RTN-3
f
I4 B13 16 Red
8 IN-3V
S4 A12
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 Yellow
S3 7 IN-2V
A14
O3 A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Brown
2 IN-1V
S2 A16
O2 A17
- R1 B18 24 Black
VOLTAGE 5 RTN-0
I1 B19 25 Violet
LOAD 1 IN-0V
O1 A19
+ S1 A18

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-IF6I.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
[Reference Doc: 41171-084 (Version 00)]

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 129


Wiring Diagrams - High Resolution Isolated Analog

1771-NIVT to 1756-IRT8I and -IF8I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP1
CABLE “B”
4 SH B1 1492-CONACAB020N54 1756-IRT8I
W2 B2
2 W3 B3
White/Red
R8 B4 15 16 IN_3(-)/B
I8 B5 16 Red
15 IN_3(+)/A
THERMOCOUPLE S8 A4
O8 A5
- R7 B8 18 Green
Yellow
12 IN_2(-)/B
I7 B9 19
11 IN_2(+)/A
S7 A6
+ O7 A7
R6 B12 21 White/Black
8 IN_1(-)/B
I6 B13 22 Brown
7 IN_1(+)/A
S6 A8
O6 A9
R5 B16 24 Black
4 IN_0(-)/B
I5 B17 25 Violet
3 IN_0(+)/A
O5 A10
S5 A11
10 CJC+
14 CJC-
14
Thermocouple 1

CABLE “A”
W1 A1 1756-IF8I
CR A2 1492-CONACAB020N34
CL A3
R4 B12 15
      

13 RTN_3
I4 B13 16
 

S4 A12 11 IN_3/I/SRC
O4 A13
R3 B14 18

B15 14 RTN_2
I3 19
      

S3 12 IN_2/I/SRC
A14
O3 A15
R2 B16 21         

5 RTN_1
I2 B17 22

 

S2 3 IN_1/I/SRC
A16
O2 A17
- R1 B18 24
   

CURRENT 6 RTN_0
I1 B19 25
   

LOAD 4 IN_0/I/SRC
O1 A19
+ S1 A18

Interface Module Installation and Application Considerations


This Bul. 1492 cable consists of a cable wired to one 1756-IF8I (or 1756-IRT8I). Recommended cable lengths of 2.0M or 5.0M
(020=2.0M, 050=5.0M). See table 2 for other lengths.

Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
for module RTP4. The Bul. 1492
cable does not connect to these terminals.

DIR 10002306504 (Version 00)

130 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016


Wiring Diagrams - High Resolution Isolated Analog

1771-NIVT to 1756-IT6I and -IF6I

There are several key application considerations and system specifications (bottom of drawing) when
IMPORTANT using these components (conversion module, cable and input module). Read and understand these
considerations before installation.

Interface Module
1771-RTP1

4 SH B1 1492-CONACAB010N5 1756-IT6I
W2 B2 CABLE “B”
2 W3 B3
White/Red
R8 B4 15 12 RTN-3
I8 B5 16 Red
8 IN-3
THERMOCOUPLE S8 A4
O8 A5
- R7 B8 18 Green
Yellow
11 RTN-2
I7 B9 19
7 IN-2
S7 A6
+ O7 A7
R6 B12 21 White/Black
6 RTN-1
I6 B13 22 Brown
2 IN-1
S6 A8
O6 A9
R5 B16 24 Black
5 RTN-0
I5 B17 25 Violet
1 IN-0
O5 A10
S5 A11
10 CJC+
CABLE “B” CJC-
14 14
Thermocouple 1

W1 A1 N/A
CR A2 N/A 1492-CONACAB010N3 c 1756-IF6I
CL A3 N/A CABLE “A”
R4 B12 15 White/Red
12 RTN-3
f
I4 B13 16 Orange
10 IN-3/I
S4 A12
8 IN-3/V
O4 A13
R3 B14 18 Green
11 RTN-2
I3 B15 19 White/Orange
S3 9 IN-2/I
A14
O3 7 IN-2/V
A15
R2 B16 21 White/Black
6 RTN-1
I2 B17 22 Gray
4 IN-1/I
S2 A16
2 IN-1/V
O2 A17
- R1 B18 24 White
RTN-0
CURRENT 5
I1 B19 25 Black
LOAD 3 IN-0/I
O1 A19
+ S1 A18
1 IN-0/V

Conversion Module Installation and Application Considerations


c Cables are available in 2.0m, or 5.0m
d Terminals starting with A are the lower row of terminals, B terminals are the upper row.
e Follow your PLC Analog User Manual for proper shield grounding instructions.
f RTN terminals are internally connected on the 1756-IF6I.
g Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The
Bul. 1492 cable does not connect to these terminals.
41171-085 Ver (00)

Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 131


Rockwell Automation Support
Use the following resources to access support information.

Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User www.rockwellautomation.com/knowledgebase
Forums, and Product Notification Updates.
Local Technical Support Phone Numbers Locate the phone number for your country. www.rockwellautomation.com/global/support/get-support-
now.page
Direct Dial Codes Find the Direct Dial Code for your product. Use the code to www.rockwellautomation.com/global/support/direct-dial.page
route your call directly to a technical support engineer.
Literature Library Installation Instructions, Manuals, Brochures, and www.rockwellautomation.com/literature
Technical Data.
Product Compatibility and Download Center Get help determining how products interact, check www.rockwellautomation.com/global/support/pcdc.page
(PCDC) features and capabilities, and find associated firmware.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/
documents/du/ra-du002_-en-e.pdf.

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-
ethics/product-environmental-compliance.page.

Allen-Bradley, ControlLogix, LISTEN. THINK. SOLVE, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1492-SG121E-EN-P - July 2016


Supersedes Publication 1492-SG121D-EN-P - October 2014 Copyright © 2016 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like