37615B SPM-D2-10 TechManual 15
37615B SPM-D2-10 TechManual 15
Measuring Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
The SPM-D2-10 can only operate one circuit breaker. This limits the controller to operating one syn-
chronization point. The voltage measured by terminals 23/24 is the synchronization reference voltage
for the generator (variable system) voltage measured by terminals 20/21. The synchronization refer-
ence voltage can be the mains or busbar voltage.
The mains voltage (measured via terminals 50/51/52) is used for monitoring over-/undervoltage and
over-/underfrequency as well as phase/vector shift.
NOTE
There are three variations for connection to the generator (variable system) voltage:
Direct connection to the low voltage system
Connection to medium voltage via two-pole isolated transformer (e.g. Connection to a 3Ph3W sys-
tem)
Connection to medium voltage via single-pole isolated transformer (e.g. Connection to a 3Ph4W
system).
Generator
MCB GCB
L1
L2
L3
G
N
0 20 21
L2 Generator
L1 voltage
3 2 1
NOTE
Connection corresponding to the mains configuration (see wiring diagram).