Manual 37615B SPM-D2-10 - Synchronizing Unit

Parameter 5608 Initial voltage controller state 0 to 100%


V control output
Init.state 000%
This parameter is the set point for the voltage when the voltage controller is not ena-
bled. The value will be entered as a percentage that relates to the minimum and max-
X & XN Packages: imum values for the signal output (refer to Parameter and Parameter ).
only with 'ANALOG' setting

Parameter 5607 Voltage controller ON/OFF


Volt. controller
ON ON................ Generator voltage control is performed by the SPM-D2. The generator
voltage is controlled in various manners depending on the task (no
X & XN Packages: load / isolated operation / synchronization). The subsequent screens of
only with 'ANALOG' setting
this function are displayed.
OFF.............. Voltage control is not performed by the SPM-D2, and the subsequent
screens of this function are not displayed.

Parameter 6657 Voltage controller isolated mode ON/OFF


Volt. controller
Isol. oper. ON ON................ In isolated operation the voltage controller is enabled.
OFF.............. In isolated operation the voltage controller is disabled.
X & XN Packages:
only with 'ANALOG' setting

Parameter 5603 Voltage controller set point ramp 1 to 99 V/s


Volt. Controller
Ramp = 00V/s
The controller increases the voltage from the initial set point to the configured volt-
age via a ramp. The slope of the ramp is used to determine how quickly the controller
X & XN Packages: changes the voltage. The larger the value configured here, the more rapid the change
only with 'ANALOG' setting
in voltage.

Parameter 5220 Maximal value voltage controller 0 to 100 %


V control output
(max.) 000%
This parameter permits the user to tailor the controller to their specific needs. This
value specifies the upper limit of the analog voltage controller output.
X & XN Packages: Example: The voltage controller requires a +/-4 volt input. The user would configure
only with 'ANALOG' setting
a +/-5 volt signal in Parameter and configure 90% here to limit the output to +4
volts.

Parameter 5218 Minimal value voltage controller 0 to 100 %


V control output
(min.) 000%
This parameter permits the user to tailor the controller to their specific needs. This
value specifies the lower limit of the analog voltage controller output.
X & XN Packages: Example: The voltage controller requires a +/-4 volt input. The user would configure
only with 'ANALOG' setting
a +/-5 volt signal in Parameter and configure 10% here to limit the output to -4
volts.

© Woodward Page 49/68