Manual 37615B SPM-D2-10 - Synchronizing Unit

Synchronization
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Configure Synchronization

CAUTION
Please consider that the unit does not have an internal rotating field monitoring.
The unit assumes always a clockwise phase rotation direction of all voltage systems, which are meas-
ured.
A rotating field monitoring must be provided by the customer in order to avoid a CB closure with a
counter-clockwise rotating field.

Parameter 6665 Synchronization functions ON/OFF


Synchronizing
functions ON ON................ The generator frequency and voltage is adjusted to the permissible dif-
ferential ranges for the busbar/mains prior to issuing a connect com-
mand. The subsequent screens of this function are displayed.
OFF.............. Synchronization does not occur, but no-load control is performed if
necessary. A connect command is not output. The subsequent screens
of this function are not displayed.

Parameter 5701 Max. perm. frequency differential (pos. slip) 0.02 to 0.49 Hz
Synchronization
df max = 0.00Hz
This value specifies the upper generator frequency limit for breaker closure. A close
command will not be issued until the generator and busbar/mains frequency differen-
tial falls below the value configured in this screen. A positive value corresponds to
positive slip  generator frequency is greater than the busbar frequency.

Parameter 5702 Max. perm. differential frequency (neg. slip) 0.00 to -0.49 Hz
Synchronization
df min =-0.00Hz
This value specifies the lower generator frequency limit for breaker closure. A close
command will not be issued until the generator and busbar/mains frequency differen-
tial exceeds the value configured in this screen. A negative value corresponds to neg-
ative slip  generator frequency is less than the busbar frequency.

Parameter 5700 Max. perm. differential voltage 1 to 60 V


Synchronization
dV max = 00V
This value specifies the maximum permissible voltage differential for breaker clo-
sure. A close command will not be issued until the generator and busbar/mains volt-
age differential falls below the value configured in this screen.

Parameter 3416 Min. pulse duration of connect relay 0.04 to 0.50 s


Synchronization
Brk.hold T>0.00s
The duration of the connect pulse can be adjusted to meet the requirements of the
switchgear.

© Woodward Page 51/68