Manual 37615B SPM-D2-10 - Synchronizing Unit

Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
Please note that the maximum voltages which may be applied at the discrete inputs are defined as fol-
lows. Voltages higher than those specified will damage the hardware!
 Maximum input range: +/-18 to 250 Vac.

18 to 250 Vac/dc

Signal device

B A
Discrete input
Reply CB 3

D C
Discrete input

Figure 4-10: Discrete inputs

Input terminal Common ter- Description Amax


minal (acc. DIN 40 719 part 3, 5.8.3)
Normally open contact
A B
3 Enable CB 2.5 mm²
5 7 Enable isolated operation / dead bus start 2.5 mm²
6 Enable control or OFF * 2.5 mm²
Normally closed contact
C D
4 7 Reply: CB is open 2.5 mm²
* refer to Parameter "Terminal 6" on page 42