Manual 37615B SPM-D2-10 - Synchronizing Unit

Relay Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
max. 250 Vac

B A
Relay output
external device

Figure 4-11: Relay outputs - control output #1 (CB control)

Root Switched Description Amax


A B
NO (make contact)
14 15 Synchronizing pulse, Command: close CB 2.5 mm²

max. 250 Vac

B A
Relay output
external device

Figure 4-12: Relay outputs - control output #2 (messages)

Root Switched Description Amax


A B Note: The relays change state when the described func-
tion is met.
NO (make contact)
18 19 Ready for operation 2.5 mm²
NC (break contact)

Controller Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The SPM-D2-10 is equipped with two three-position controllers (made of a form C and form A relay) for raising
and lowering voltage and frequency. The SPM-D2-10/X & SPM-D2-10/XN controllers can be configured for dif-
ferent output signals. The terminal connects differ dependent upon the signal selected.

SPM-D2-10 / SPM-D2-10/N / SPM-D2-10/

max. 250 Vac


9 10

Speed Lower

controller Raise
Speed / frequency
controller
8

Common
11 12 13

Voltage Lower

controller Raise Voltage controller


Common

Figure 4-13: Controller - SPM-D2-10 - three-position controller

Terminal Description Amax


8 common 2.5 mm²
9 raise Speed/frequency controller 2.5 mm²
10 lower 2.5 mm²
11 common 2.5 mm²
12 raise Voltage controller 2.5 mm²
13 lower 2.5 mm²

Page 18/68 © Woodward