Manual 37615B SPM-D2-10 - Synchronizing Unit

Chapter 5.
Description of Functions

Function Tables
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Table for Terminal 6 if Configured "Enable/Release Control"
The unit may be used as an SPM-A by energizing terminal 6.

The status of the discrete inputs "Reply: CB is open" (terminal 4) and "Enable CB" (terminal 3) are displayed on
the face of the controller via the LEDs "Gen CB - ON" and "Gen CB free" respectively. In addition to the state of
the discrete input signals, the conditions in Table 5-3: Operating conditions - terms will affect the controller as
follows:

Input signal Operating condition Cond. Relay "Command: Operating mode


close CB" SPM-A
(terminals 14/15)
LED

LED

Discr. inp term. 5: "Enable


"Gen-CB ON"

Discr. inp. term. 6

Refer to Table 5-3


"Gen CB free"

"Enable controller"
Isolated operation/dead bus start"

Off or - OFF OFF


0 0 x 0
automatic no-load control C1 OFF
No-load operation or C OFF CHECK
0 0 x 1
synchronization A OFF
0 1 0 0 OFF A Slip or phase match PERMISSIVE
No-load operation or C OFF
0 1 0 1 RUN
synchronization A Slip or phase match
0 1 1 0 OFF A Synchro-Check -
No-load operation or C - RUN
0 1 1 1 synchronization or A Slip or phase match or (extended)
dead bus start B dead bus start
1 x 0 x OFF - OFF -
1 x 1 0 OFF - OFF -
1 x 1 1 Isolated operation D OFF -
0: "OFF" / 1: "ON" / x: Signal of no significance (0 or 1)
Table 5-1: Operating conditions - terminal 6 = "Enable/Release control"

© Woodward Page 21/68