Abstract

The intention of the release notes is to supply both internal and external
customers with information about the contents of the delivery. This information
should be used as a reference for software and hardware revisions, changes,
contents, and references to other documents where greater detail is required. The
purpose is not to duplicate information but to flag important information and
where possible reference other documents that need to be studied to ensure
successful implementation of the package.

© Ericsson AB 2019-2020
All rights reserved. The information in this document is the property of Ericsson.
Except as specifically authorized in writing by Ericsson, the receiver of this
document shall keep the information contained herein confidential and shall
protect the same in whole or in part from disclosure and dissemination to third
parties. Disclosure and disseminations to the receiver's employees shall only be
made on a strict need to know basis. The information in this document is
subject to change without notice and Ericsson assumes no responsibility for
factual inaccuracies or typographical errors.

2020-04-24
Contents

1 Executive Summary .............................................................................................. 3


2 Revision History..................................................................................................... 3
3 Release Information ............................................................................................. 3
3.1 SW Identity ...................................................................................................... 3
3.2 SW Content ...................................................................................................... 3
3.2.1 Corrected Trouble Reports .......................................................................... 3
3.2.2 General Public Licensed Code .................................................................... 3
3.2.3 Handling of Security Vulnerabilities in FOSS components ............... 4
3.3 New Functionality .......................................................................................... 4
3.4 Security fixes .................................................................................................... 4
3.5 System Level .................................................................................................... 4
3.6 Applicable Hardware Configurations ...................................................... 5
3.7 Dependencies and Requirements ............................................................. 5
3.8 Parameters and Counters ............................................................................ 5
3.9 CPI Library ........................................................................................................ 5
3.10 Supported Upgrade Paths ........................................................................... 5
3.11 Alarms ................................................................................................................ 5
3.12 OAM .................................................................................................................... 5
3.13 License ............................................................................................................... 5
3.14 Common Restrictions and Limitations .................................................... 6
3.14.1 Restrictions ....................................................................................................... 6
3.14.2 Known Limitations ......................................................................................... 6

2020-04-24 2 (6)
1 Executive Summary
This release is intended for general cabinet controller use.

2 Revision History
Revision Prepared by Date Comments
A UABENGT 2020-04-07 First revision

3 Release Information

3.1 SW Identity

The software is available in SW Gateway.

The table below defines the SW for this release.

Prod. No R-state Description


CXP 901 7878/2 R20A SCU

3.2 SW Content

3.2.1 Corrected Trouble Reports

The following customer TR’s have been corrected in revision R20A.

TR-ID TR Heading Description


HY17453 ESC Ethernet port Leds become ESC ethernet ports were turned on by default,
illuminated on ports which are failing to check that the port was configured.
not defined

HY17460 ESC EthernetInterface 'link When an ethernet cable is disconnected, a link


down' alarm is not working down alarm is expected. This alarm was not
raised.

HY21934 Unable to change threshold via Some requirements on relations between


ESC different thresholds were not in place with the
result that the power controller did not accept
some changes.

HY35269 After ESC restart, If specificProblem texts were configured they


LoadDisconnect / AlarmEntry were lost at SCU/ESC restart causing the
MOs specificProblem text values to revert back to default values.
reverts back to default values

3.2.2 General Public Licensed Code

This release includes Free and Open Source SW (FOSS) under the terms of GNU
General Public License (GPL) and GNU Lesser General Public License (LGPL).

2020-04-24 3 (6)
These programs are free software, which can be re-distributed and/or modified
under the terms of GPL respectively LGPL as published by the Free Software
Foundation.

To fulfill the GPL terms, the corresponding source code can be delivered upon
customer request through SW Gateway.

Product in SW Gateway R-State Description


3/CXP 901 7878/2 R4A 3PP Package

A list of all included FOSS can be found in document Free and Open Source
Software, included in the CPI library.

3.2.3 Handling of Security Vulnerabilities in FOSS components

Monitoring of security vulnerabilities in Free and Open Source Software


components is an ongoing process. Vulnerabilities are typically not addressed by
stepping the version of a component, but by patching the current version of the
component. Therefore, it is not possible to rely on version banners to assess
vulnerability to certain security threats. Please contact PLM Helpdesk for any
specific security related questions.

3.3 New Functionality

This SCU introduces support for the following new batteries:

Product Function designation Intended use


BKB 902 71/13 Battery 6613 Li 50Ah 2U 2C RBS 6101, 6102, 6120
BKB 902 71/131 Battery 6613 Li 50Ah 2U 2C RBS 6101, 6102, 6120
UL
BKB 902 71/22 Battery 6612 Li 100Ah 4U 1C RBS 6101, 6102, 6120,
SSC02, BBS 6101
BKB 902 71/221 Battery 6612 Li 100Ah 4U 1C RBS 6101, 6102, 6120
UL
BKB 902 71/21 Battery 6611 Li 100Ah 2U 1C Enclosure B174

3.4 Security fixes

Security vulnerabilities are continuously monitored, and relevant fixes have been
applied.

3.5 System Level

This SCU release is supported by ENM 19.04 and later releases.

It also supports the following ESCM versions:

- CXP 902 0902/1 R13A, R13B

2020-04-24 4 (6)
SCU supports new releases of ESCM based on these SW’s for 18 months after its
own release. This means that ESCM versions released until 21.Q3 will work with
this revision unless they are configured with new functionality not known to this
SCU version.

3.6 Applicable Hardware Configurations

This product does not add any HW requirements.

3.7 Dependencies and Requirements

See 3.5.

3.8 Parameters and Counters

Nothing new.

3.9 CPI Library

Enclosure library (SCU R20), EN/LZN 760 4008 R3A

3.10 Supported Upgrade Paths

Solution From state To state


HGM 6150 SB Incell Gen4 R7E R20A
HGM 6150 SB Incell Gen 5 R7F R20A
HGM 6130 SB Shoto
HGM 6150 LA R13B R20A
HPM 6160 SB Incell Gen 5 R15F R20A
R17D R20A
R19B R20A

3.11 Alarms

Alarm MO Severity Comment


OverVoltage DC PowerSystem systemDefined Name changed from “OverVoltage”
UnderVoltage DC PowerSystem systemDefined Name changed from “UnderVoltage”
OverVoltage AC Rectifier cleared Name changed from “OverVoltage”
UnderVoltage AC Rectifier cleared Name changed from “UnderVoltage”

3.12 OAM

3.13 License

No licenses are needed.

2020-04-24 5 (6)
3.14 Common Restrictions and Limitations

3.14.1 Restrictions

Upgrading from R13B needs to be performed in two steps. First from R13B to
R15F, then from R15F to R20A.

3.14.2 Known Limitations

TR-ID TR Heading Description


HX47016 ESC Battery test not working on For several power systems the battery test is not reliable.
multiple PowerSystems

HX96408 ESC Full maintenance mode on IPv6 Even when using IPv6 addressing, full maintenance mode
node available only through IPv4 still needs to use IPv4 addresses.