Wrong Method of Storing of the Busducts.
DO NOT REMOVE THE PLASTIC
WRAPPPING UNTIL TAKEN FOR ASSEMBLY
Correct Method of Storing of the Busducts.
Fig. 4 5. OPERATION 5.1. Provide sufficient horizontal and vertical clearance from walls and ceilings to provide easy access to joints, both for the original installation and possible removal of a section when required. Copper Size & Weight Aluminum Size & weight Weig Width Weight Width Busduct ht Busduct (W) mm Kg/m (W) mm Rating in Kg/m Rating in Amps Amps Height Conductor size 3PH Height Conductor size - Type 3PH 4W Type 3PH 4W 3PH 4W mm – mm 4W mm mm
400 115 One – 5 x 50 21 400 125 One – 5x60 15
630 125 One – 5 x 60 27 630 125 One – 6 x 60 15
800 125 One – 6 x 60 27 800 140 One – 6 x 75 17
1000 140 One – 6 x 75 31 1000 165 Fig. 1 One 6 x 100 20
Fig. 1 1250 165 One – 6 x 100 39 125 1250 205 One – 6 x 140 26 125
1600 205 One – 6 x 140 52 1600 240 One – 6 x 175 30
2000 240 One – 6 x 175 63 2000 305 One – 6 x 240 38
2500 305 One – 6 x 240 83 2500 405 Two – 6 x 140 45
Fig. 2 3200 405 Fig. 2 Two – 6 x 140 98 3200 475 Two – 6 x 175 54