Wrong Method of Storing of the Busducts.

DO NOT REMOVE THE PLASTIC


WRAPPPING UNTIL TAKEN FOR
ASSEMBLY

Correct Method of Storing of the Busducts.


Fig. 4
5. OPERATION
5.1. Provide sufficient horizontal and vertical clearance from walls and ceilings to provide easy access to
joints, both for the original installation and possible removal of a section when required.
Copper Size & Weight Aluminum Size & weight
Weig
Width Weight Width
Busduct ht Busduct
(W) mm Kg/m (W) mm
Rating in Kg/m Rating in
Amps Amps
Height Conductor size 3PH Height Conductor size -
Type 3PH 4W Type 3PH 4W 3PH 4W
mm – mm 4W mm mm

400 115 One – 5 x 50 21 400 125 One – 5x60 15

630 125 One – 5 x 60 27 630 125 One – 6 x 60 15

800 125 One – 6 x 60 27 800 140 One – 6 x 75 17

1000 140 One – 6 x 75 31 1000 165 Fig. 1 One 6 x 100 20


Fig. 1
1250 165 One – 6 x 100 39 125 1250 205 One – 6 x 140 26 125

1600 205 One – 6 x 140 52 1600 240 One – 6 x 175 30

2000 240 One – 6 x 175 63 2000 305 One – 6 x 240 38

2500 305 One – 6 x 240 83 2500 405 Two – 6 x 140 45


Fig. 2
3200 405 Fig. 2 Two – 6 x 140 98 3200 475 Two – 6 x 175 54