ARTECHE latching relays range is designed to guarantee the best features and complete
security even in the hardest working environment.
The design, durability and quality of the different alternatives that ARTECHE latching relays
can offer (FF range and standard range), make them suitable for high responsibility controls in
different areas, highlighting:
ELECTRICAL UTILITIES:
Power plants, electrical substations.
RAILWAY SECTOR:
Electrification, signalling, interlocking and rolling stock.
INDUSTRIAL SECTOR:
Continuous process industries (Petrochemical, concrete, iron
industries), water treatment, ...
GENERAL STANDARDS
E322124
All the relays include a diode in parallel with the coil (see
bistable relays with overvoltage protection characteristic).
››World-class range of
auxiliary relays for
energy sector, specially
designed for the most
demanding applications
Applications Relays with two stable positions. Required when the position memory
(open-close, automatic-manual, local-remote...) is needed.
Construction characteristics
80 80 80
8 8 81 8 81
81
Options Options are not available
Weight (g) 300 600 1400
Dimensions (mm) 45 x 45 x 96,5 (F large Type) 90 x 50 x 100,5 120 x 110 x 105
(J large Type)
Coil characteristics
Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac (50-60 Hz) 24, 48, 72, 110, 125, 220
Vcc/Vca (50/60 Hz)
Voltage range +25% -30% UN +10% -20% Un
Pick-up voltage See pick-up voltage / temperature curves for Latching relays
Average consumptions only in the 6W 12 W 24 W
change-over
Operating time
Pick-up time <20 ms
Contacts
Contact material AgNi
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms 80 A during 200 ms /
150 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact configuration)
Max. breaking capacity See value for 50.000 operations
Umax opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations 106 operations
Operating temperature -40ºC +70ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m
(1)
Other voltage upon request
(2)
Ask for higher altitudes
Applications Intended for trip and lockout applications where high demanding requirements in operating
time and breaking capacity are needed.
Construction characteristics
10
A Terminals B Terminals
1 11 10 10
20 1 11 1 11
2 21 20 20
b 2 21 2 21
+ 11 30
Trip
+ b
Trip
14 3
=
+
=
11 3 31 30 30
Connections
Trip
7 +
=
3 B1 3 3
Trip
7 40 31 31
=
12
- 12 a 4 40 40
4 8 41 a
10 - 4 4
4 8 2 41 - 41
50
- 13 d 50 50
Reset
+ 13 5 51
d
5 +
Reset
Reset
-
9 5 + 5
-
2 5 51 51
-
9
Reset
60
14 60 60
-
+ 6
6 c 61 6 c 6
- 1 10 61 61
- 70 -
1 70 70
7 71 7 7
71 71
80 80 80
8 81 8 8
81 81
Options Options are not available
Weight (g) 300 600 1250
Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac (50-60 Hz)
Voltage range +10% -20% UN
Pick-up voltage See pick-up voltage / temperature curves for Latching relays
Average consumptions only in 17 W 17 W 30 W 90 W
the change-over
Operating time
Pick-up time <10 ms (Vdc) <20 ms (Vac)
Contacts
Contact material AgNi
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact configuration)
Max. breaking capacity See value for 50.000 operations
Umax opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations 106 operations
Operating temperature -40ºC +70ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m
(1)
Other voltage upon request
(2)
Ask for higher altitudes
Applications Intended for tripping and locking applications where high quality requirements in operating time and breaking capacity are
needed, with manual reset.
Construction characteristics
10 A Terminals B Terminals
1 11 10 10
1 11 1 11
20
2 21 20 20
11 2 2
21 21
+ 3 b 30 b
Connections 7 30 30
B1 3
Trip
Trip
Trip
31 +
=
=
12 3 31 3 31
4 40
8 40 40
2 a 4 41 a
4 4
- 13 - 41 - 41
5 50
-
50 50
Reset
9 d
5
Reset
d 51 5 + 5
-
51 51
Reset
14 +
+
-
6 60 60 60
1 10
6 61 6 61 c 6 61
c -
70 70 70
- 7 7
7 71 71 71
80 80
80
8 81 8 81
8 81
Options Options are not available
Weight (g) 300 600 1400
Dimensions (mm) 45 x 45 x 96,5 90 x 50 x 100,5 (A) 120 x (B) 110 x (C) 105
(F large Type) (J large Type)
Coil characteristics
Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc 110, 125, 220 Vcc(3)
63,5, 110, 127, 230 Vac (50-60 Hz)
Voltage range +10% -20% UN
Pick-up voltage (20ºC) See pick-up voltage / temperature curves for Latching relays
(1)
Other voltage upon request
(2)
Ask for higher altitudes
(3)
Vac voltage upon request
Intended to protect the contact of the equipment that feeds the coil in our relay.
Applications
Construction characteristics
+
=
11 + 3 30 30
Trip
3 + 31
=
Connections 3 B1
7 3 31
b 3 31
Trip
Trip
+
=
=
12 40
10 12 40 40
- 4 a 4 41
4 8 4 41 4 41
2 8 2 - a
13 50
Reset
+ - 50 - 50
13
-
5 d 5 5 5
-
Reset
9 51 51 d 51
Reset
5 +
Reset
9 +
-
14 60 60 60
1 + 6 6
- 6 6 61 61 61
1 10 c
70 c 70
- 70 -
7 7
7 71
71 71
80 80
80 8 8
8 81 81
81
Options Options are not available
Weight (g) 300 600 1400
Dimensions (mm) 45 x 45 x 96,5 (F large Type) 90 x 50 x 100,5 120 x 110 x 105
(J large Type)
Coil characteristics
Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc(3) 24, 48, 72, 110, 125, 220
Vcc/Vca (50/60 Hz)
Voltage range +25% -30% UN +10% -20% Un
Pick-up voltage See pick-up voltage / temperature curves for Latching relays
Average consumptions only in the 6W 12 W 24 W
change-over
Operating time
Pick-up time <20 ms
Contacts
Contact material AgNi
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms 80 A during 200 ms /
150 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact configuration)
Max. breaking capacity See value for 50.000 operations
Umax opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations 106 operations
Operating temperature -40ºC +70ºC
Storage temperature -40ºC +85ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m
(1)
Other voltage upon request
(2)
Ask for higher altitudes
(3)
Vac voltages upon request
Likewise, the values showed in the following charts have been obtained
in standard conditions in the laboratory, and they could be different
in real conditions. In any case, the possibility of connecting serial
contacts or a bigger distance between contacts makes these values to
be considerably increased.
24 Vdc voltage
Different loads configurations.
106
1000000 106
1000000
No. operations
No. operations
100000
105 100000
105
104
10000 10000
104
0
0,00 5
5,00 10
10,00 15
15,00 20
20,00 25
25,00 0
0,00 2
2,00 4
4,00 6
6,00 8
8,00 10
10,00 12
12,00
Current Current
1 contact
0 ms 20 ms 40 ms
106
1000000
No. operations
No. operations
106
1000000
100000
105 105
100000
104
10000 104
10000
0
0,00 1
1,00 2
2,00 3
3,00 4
4,00 5
5,00 6
6,00 7
7,00 8
8,00 9
9,00 10
10,00 0
0,00 1
1,00 2
2,00 3
3,00 4
4,00 5
5,00 6
6,00 7
7,00
Current Current
1 contact
2 contacts
0 ms 20 ms 40 ms
106
1000000 106
1000000
No. operations
No. operations
105
100000 105
100000
104
10000 104
10000
0,00
0,00 0,20
0,20 0,40
0,40 0,60
0,60 0,80
0,80 1,00
1,00 1,20
1,20 1,40
1,40 1,60
1,60 0,00
0,00 0,10
0,10 0,20
0,20 0,30
0,30 0,40
0,40 0,50
0,50 0,60
0,60 0,70
0,70 0,80
0,80
Current Current
1 contact
2 contacts
0 ms 20 ms 40 ms
General purpose latching relays and relays with coil overvoltage protection.
200
150
Pick-up voltage limit
50
0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130
Temperature (ºC)
200
50
0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130
Temperature (ºC)
Model Selection
Options
Diode in parallel with the coil
BB
(only Vdc)
Fast acting trip and lock out
R
relay (electrical reset only)
Fast acting trip and lock out
relay (electrical and manual RP
reset)**
Range FF
Rolling stock applications or No -
low duty loads*** Yes FF
Aux. Supply
Vdc or Vac
Indicate voltage level and if it
is VDC or VAC
(ex: 24 VDC)
DIMENSIONS OF THE
RELAYS
F large J large
120 115
96 105 10
45 90
Relay
Dimensions
45
50
110
96,5 100,5
10,5
10,5
I-DE IP10
155
44 84
43 83
64
64
105
105
154
29 29
48 32,3 88 32,3
Sockets
for DIN
rail
(1) (2)
42,7 31 82,7 31
39,8 29 79,8 29
112
112
Fix Drilling
45 12 117
5
eø
4d
145
20 60
= = 3,5 = = 3,5
2 of 2 of
FN-TR OP IP10 FN-TR2C OP IP10 JN-TR OP IP10 JN-TR2C OP IP10 I-TR, I-TR2C IP10
41
120 6
44 43 84
40 6 43
80 6
110
51,2
41,8
51,2
41,8
Sockets
for rear
connection
108
40,5 +- 0,2 80,5 +- 0,2 84
Cut-out
= 52,6 =
104
90
42
42
112 min.
5
fø 122 min.
8o
75 120
Sockets
for flush
mounting
124
124
15
8 12,5
15
8 12,5
106
96 4,5
61
Cut out
50
66
90 min
57
4,5
Cut out
125
66
57
90 min
Cut-out 66
57
R2
80 min
Cut out
106
96
125
90 min
4,5
(1)
DIN rail according to EN50022 (2)
Minimum distance between sockets will depend on type of relay and
DIN46277/3 sockets. Please request sockets user manual for more detailed information.
www.arteche.com ©Arteche