Professional Documents
Culture Documents
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
OPERATING INSTRUCTIONS
LIST OF CONTENTS
1. INTRODUCTION 5 3.5 ACCEPT EVENTS 18
1.1 KEY FUNCTIONS AND FEATURES 5 3.6 VIEW STATUS 18
3.7 ISOLATE/DE-ISOLATE 20
3.8 TIME/DATE 21
2. OPERATING INSTRUCTIONS 6 3.8.1 SET TIME/DATE 21
2.1 OPERATOR’S INDICATORS 3.8.2 SUMMER/WINTER 21
AND CONTROLS 6
3.9 EVENT LOG 21
2.1.1 GENERAL 6
3.9.1 VIEW EVENT LOG 22
2.1.2 OPERATOR DISPLAY
MODULE 6 3.9.2 PRINT EVENT LOG 22
2.1.3 OPERATOR CONTROL 3.9.3 FILTER 22
MODULE 9 3.10 VIEW/PRINT STATUS 23
2.1.4 DCM800 DISPLAY CONTROL 3.10.1 VIEW/PRINT POINTS
MODULE 9 ISOLATED 23
2.2 LCD DISPLAY 11 3.10.2 VIEW/PRINT POINTS
2.2.1 FIRE WINDOW 11 UNTESTED/FAILED 23
2.2.2 STATUS WINDOW 11 3.10.3 VIEW/PRINT POINT VALUES 23
2.2.3 MAIN WINDOW 11 3.10.4 VIEW FAULTS 24
2.2.4 SOFTKEY WINDOW 11 3.10.5 VIEW LOOP POINT COUNTERS 24
2.3 NORMAL OPERATION 12 3.11 SERVICE 25
2.3.1 EVENT MONITORING 12 3.11.1 WALK TEST 26
2.3.2 EVENT DISPLAY 12 3.11.2 MAINTENANCE 28
2.4 OPERATION IN ALARM 12 3.11.3 CONFIGURATION 29
2.4.1 SYSTEM RESPONSE 12
2.4.2 SOUNDER SILENCING 13 4. ROUTINE CHECKS 34
2.4.3 RESETTING THE CONTROLLER 14
4.1 GENERAL 34
2.4.4 MULTIPLE EVENTS 14
4.2 DAILY CHECKS 34
2.4.5 PRE-ALARM WARNINGS 14
4.3 WEEKLY CHECKS 34
2.5 OPERATION IN FAULT CONDITION 14
2.5.1 SYSTEM RESPONSE 14
2.5.2 OPERATOR ACTION 14
2.6 FIRE CONTROL KEYS 15
2.6.1 EVACUATE or FIRE ALARM 15
2.6.2 DAY/NIGHT MODE 15
2.6.3 TEST 15
2.7 AUXILIARY DISPLAY DEVICES 15
2.7.1 GENERAL 15
2.7.2 REPEATERS 16
2.7.3 PRINTERS 16
3. CONTROLLER FUNCTIONS 16
3.1 ACCESS LEVELS 16
3.1.1 GENERAL 16
3.2 ENTERING PASSCODES 17
3.3 VALID VALUES 17
3.4 MAIN MENU 18
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
PAGE 2 of 35
First Fire 1 2
ABC
3
DEF
Zone 002 B002
1st Floor Corridoor
Room 117
4 5 6
Last Fire 002 GHI JKL MNO
Registered Office:
Washroom / Window 7 8 9
PQRS TUV WXYZ
General Information
Fig. 1
First Floor
LED Tst More
F1 F2 F3 F4 F5
North Building
Walden Court
GENERAL MISCELLANEOUS CONTROLLER
Parsonage Lane
POWER FAULT
DISABLED
SOUNDERS SIGNALLING
FAULT
EQUIPMENT:
FAULT
DISABLED DISABLED
ISSUE No. & DATE:
I
SILENCE SILENCE/ DAY INVESTIGATE
BUZZER RESET EVACUATE
RESOUND NIGHT DELAY
CM23 5DB
17A-05-O
11/04
PAGE 3 of 35
MX
17A-05-O
5 11/04
Main menu
SYSTEM 1 2 3
1 - Accept Events
Wed, 01-Mar-00 2 - Actual Status * ABC DEF
14:15 3 - (De-) Isolate
4 - Time / Date
Company Name 5 - Event Log 4 5 6
6 - View/Prn Status GHI JKL MNO
General 7 - Service
9 - Test Buzzer,
LED's Display 7 8 9
Alarm Count: 0021 PQRS TUV WXYZ
0000
Back SounSIL
0
F1 F2 F3 F4 F5
GENERAL
GENERAL SYSTEM SOUNDERS
SOUNDERS SIGNALLING CONTROLLER
TEST STATUS 2
ZONE DISPLAY
1 11 21 31 41 51 61 71
2 12 22 32 42 52 62 72
3 13 23 33 43 53 63 73
4 14 24 34 44 54 64 74
5 15 25 35 45 55 65 75
6 16 26 36 46 56 66 76
7 17 27 37 47 57 67 77
8 18 28 38 48 58 68 78
9 19 29 39 49 59 69 79
10 20 30 40 50 60 70 80
PAGE 4 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
PAGE 6 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
ALPHANUMERIC KEYPAD
WXYZ
MNO
DEF
9
3
6
ABC
JKL
TUV
8
0
5
2
PQRS
7
GHI
1
SCROLL DOWN
SCROLL UP
More
F5
Information
F4
SOFTKEYS
F3
002
1st Floor Corridoor
Washroom / Window
B055
B002
F2
General
First Fire
Last Fire
4th Floor
Room 117
Zone 030
Zone 002
LED Tst
F1
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
ALPHANUMERIC
KEYPAD
Main menu 2 3
SYSTEM 1
1 - Accept Events SCROLL * ABC DEF
Wed, 01-Mar-00 2 - Actual Status
14:15 3 - (De-) Isolate UP
4 - Time / Date 4 5 6
Company Name 5 - Event Log
6 - View/Prn Status GHI JKL MNO
General 7 - Service
9 - Test Buzzer, 7 8 9
LED's Display PQRS TUV WXYZ
Alarm Count: 0021 SCROLL
DOWN
Back 0
F1 F2 F3 F4 F5
SOFTKEYS
GENERAL
GENERAL SYSTEM SOUNDERS
SOUNDERS SIGNALLING CONTROLLER
TEST STATUS 2
ZONE DISPLAY
1 11 21 31 41 51 61 71
2 12 22 32 42 52 62 72
3 13 23 33 43 53 63 73
4 14 24 34 44 54 64 74
5 15 25 35 45 55 65 75
6 16 26 36 46 56 66 76
7 17 27 37 47 57 67 77
8 18 28 38 48 58 68 78
9 19 29 39 49 59 69 79
10 20 30 40 50 60 70 80
CONTROLLER
• A green Power ON LED.
• A yellow Charger Fault LED.
• A yellow Processor Fault LED.
• A yellow Power Fault LED indicates loss of
mains and back up power (T2000 only).
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
5
MX
17A-05-O
PAGE 10 of 35
11/04
Fig. 5
FIRE DAY MODE MAINS FAULT
DISABLED
SOUNDERS SIGNALLING
FAULT FAULT
DISABLED DISABLED
1
1234567890123456789 1
1234567890123456789
2 2
3 Fire 3 Main
4 Window 4 Window
5 5
6 6
7 7
8 8
9
1 0
2 Status 1
3 Window 2
4 3
5 4
S'key 1 S'key 2 S'key 3 S'key 4 S'key 5
Fig. 6
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
When the controller is initially powered up, with no faults or The display automatically shows the last event of the
alarms in the system and the ‘Enable’ key in the ‘off’ category with the highest priority. With Scroll keys, it is
position, the following screen is displayed: possible to get all events in this category in chronological
order. With Softkey F5 the user can change to another
category (if available).
MX Panel Important: Category ‘Full Alarm/Alert’ shows only the first
Fri, 17-Mar-00 point of a zone in alarm. If two points of one zone are in
11:57 alarm, only the first one which was in alarm will be
displayed. The second alarm can only be accessed via the
Company Name menu option ‘View Event Log’.
General
2.4 OPERATION IN ALARM
2.4.1 SYSTEM RESPONSE
When a fire condition is detected, the system responds as
LED Tst Light
follows:
1) The internal buzzer will sound in a
2.3.1 EVENT MONITORING continuous tone.
The term ‘event’ is used to describe a change in system 2) Both red ‘FIRE’ LEDs will light.
status that must be acknowledged and/or generates an 3) The SOUNDERS and NOTIFICATION
output. STATUS ‘ACTIVATED’ red LEDs will
Examples of events include: light.
• Mains failure
Note: If the alarm is initiated by a detector, there may
• Detection of a fire condition be a delay of from 1 to 10 minutes before the
• Operation of ‘EVACUATE/FIRE ALARM’ NOTIFICATION STATUS ‘ACTIVATED’ led
lights. This is to allow time for the alarm to be
key
investigated and any relevant action taken
before signalling is initiated. A Callpoint set to
All events trigger a response, the category of which depends evacuate will initiate signalling
on the event type and will be one of the following (in immediately. Refer to Section 2.6.3.
priority order):
• Full Alarm or Alert 4) For the MX controllers, the sounders and
• Pre-Alarm
any other configured outputs will be
activated.
• Fault
5) The LCD will display a message in the
• Isolation format:
• Test Mode
• Warning FirstFirst
Fire Fire
Zone 002 B002
• Information 1st Floor Corridoor
Room 117
001
When an event occurs, it is stored in the event log. The
contents of this log may be displayed in two formats:
General Information
• Unaccepted and locally accepted events
• All events in chronological order of
occurrence
The events are stored in chronological order with Menu Passcode More
unaccepted events marked as outstanding. The event log
may hold up to 3000 events; in the unlikely occurrence of
the log filling up, the oldest record will be overwritten.
PAGE 12 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
WARNING:
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
2.4.3 RESETTING THE CONTROLLER If the detector subsequently shows an alarm condition, an
alarm will be generated, regardless of whether the pre-
Note: alarm warning was accepted.
1) When the system is in a Fire Alarm state,
Silence must be operated before Reset is
possible. This interlock is always present 2.5 OPERATION IN FAULT CONDITION
under Fire Alarm condition, even if all sounders
2.5.1 SYSTEM RESPONSE
are isolated.
2) The controller should also NOT be reset until When a Fault condition is detected, the system will respond
the source of the alarm has been determined as follows:
by the Fire Brigade or the cause otherwise a) The internal buzzer will pulse.
found (and the condition removed).
b) The yellow ‘GENERAL FAULT’ LED will
light.
Once the notes above have been observed, press the
‘RESET’ key. The display will show the following message: c) The LCD backlight will come on and will
display the following type of screen:
Reset
in
Progress... MX Panel FAULT
PAGE 14 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
b) Investigate the source of the fault and where 2.6.2 DAY/NIGHT MODE
possible remove.
In night mode the system activates immediately when an
alarm is received, the internal buzzer, all sounders and
Note: If the fault cannot be cured, contact your local alarm signalling outputs operate.
supplier and arrange for a service visit.
In day mode, on receipt of an alarm, only the internal
buzzer and sounders are activated immediately. A delay
The fault information will be displayed until the fault is time is started (default 60 seconds) in which the alarm
cleared. message must be acknowledged (‘Investigate delay’
switch) to start the investigation time. If there is no
2.6 FIRE CONTROL KEYS acknowledgement within this time, the alarm signalling
outputs will be activated.
There are six fire control keys on the Operator Control Module
(or Display Control Module for MX2), namely: The investigation time (default 10 minutes) is the time
remaining for staff to carry out investigation of the alarm
• SILENCE BUZZER source, before the alarm signalling outputs will be
• SILENCE/RESOUND
activated.
• RESET
An evacuate callpoint will initiate an immediate alarm.
• DAY MODE
Signalling is always immediate if sounder faults exist in
the system.
• INVESTIGATE DELAY
• EVACUATE (FIRE ALARM for Marine)
2.6.3 INVESTIGATE DELAY
The ‘INVESTIGATE DELAY’ switch is only active when
Only the ‘SILENCE BUZZER’ key is active without the the controller is in the ‘DAY MODE’ of operation. If a
‘Enable’ key being inserted and turned to the ‘Enabled’ Fire Alert is received at the controller, the signalling output
position. is delayed for 1 minute, if the ‘Investigate Delay’ switch is
pressed during this period a further delay (configurable
The functions of ‘SILENCE BUZZER’, SILENCE/
between 1 and 10 minutes) is initiated. This delay allows
RESOUND’ and ‘RESET have already been described. The
for the alarm to be investigated, if it is a false alarm, the
functions of ‘EVACUATE or FIRE ALARM’,
cause of the alarm can be removed and the controller to be
‘INVESTIGATE DELAY’ and ‘DAY MODE’ are described in
silenced and reset. If the alarm is real, then pressing the
the following paragraphs.
‘EVACUATE/FIRE ALARM, switch will cause the
signalling output to activate.
2.6.1 EVACUATE or FIRE ALARM
Once enabled by the keyswitch, pressing ‘EVACUATE or
2.6.4 TEST
FIRE ALARM’ will cause the following:
a) The internal buzzer will sound continuously. Pressing ‘LED TEST’ causes all the LEDs and internal
buzzer to operate for a few seconds. If the system includes
b) The red ‘FIRE’ LEDs will light. a repeater panel, only the panel that is operated is activated.
c) The sounders and any other configured outputs
are activated.
2.7 AUXILIARY DISPLAY DEVICES
d) The LCD will display the following type of
screen: 2.7.1 GENERAL
Depending on the configuration of the system, there may
FirstFirst
Fire Fire be one or more auxiliary display devices fitted. These
Zone 000 RB002R12 F I R E
devices may be of the following types:
System Zone
Evacuate Button
001
• Repeaters
• Printers
General Information
The functions of and operating instructions for these
devices are given in the following paragraphs.
Not Available
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
3. CONTROLLER FUNCTIONS
As stated, the MX controller has built-in functions. These
functions allow the operator to perform such actions as
viewing the event log, setting the date and time, etc. The
functions are arranged according to sophistication and
access to certain of them necessarily needs to be restricted
to trained staff.
The control of access has been achieved by assigning
functions to Access Levels, each Access Level having an
associated numeric passcode. The passcode for a
particular Access Level is defined at system configuration.
PAGE 16 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
PAGE 18 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
MX Panel
View Status • Normal
Wed, 01-Mar-00
Point • Fault
14:15 Panel
02
• Active
Company Name Loop • PreAlarm
General A 001
Actual Status OP can be in one of the following conditions:
• On
• Off
Back >> - + Enter • Pulse 1
• Loop Point (Addressable Loop) • Pulse 2
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required Loop and Point, then press Enter Selecting Zone will display the following type of screen:
key.
• RBus Point (Remote Bus)
View Status
Use the ‘+’, ‘-’ and ‘>>’ keys to select the MX Panel
required RBus, Category and Point, then Zone 002
press Enter key. Wed, 01-Mar-00 South Building
14:15 1st Floor Corridoor
• Local I/O Point (Field Interface Module)
Company Name Alarm : NO
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required Category and Point, then press Enter Fault : NO
General Isolate : NO
key. Walk Test : NO
The following type of screen will be displayed:
MX Panel
View Status
Back _ +
Point
Wed, 01-Mar-02 Zone 006 A007 Function Keys F3/F4 will decrement/increment the zone
14:15 number.
Zone 06
Company Name Call alarm in room
CP 820
General
Description
Input Output
Normal Alarm Yes One or more devices of a
zone in Alarm Mode
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
3.7 ISOLATE/DE-ISOLATE
CAUTION:
The Isolate/De-isolate option allows the following to be
isolated/de-isolated: Isolating I/O points may break compliance with
• Point Complete 1 EN54. Caution should be exercised when
dealing with mandatory switches and
• Point Input 2 indicators. Such operations are reserved for
• Point Output 3 authorised trained personnel only.
• Zone Detectors 4
• Zone Callpoints
(also interrupt devices) 5 The following screen shows an example of Point isolation:
• Zone Alarm I/Ps 6
Isolate/De-Isolate
• Zone Sounders 7 MX Panel
Point Complete
• Zone Controls 8 Wed, 01-Mar-00 Zone 002 B002
14:15 South Building
• Zone Extinguish 9 1st Floor Corridoor
Company Name Room 117
• Extinguish Controls F2 801 H
• Fault Signalling F3
General
Status IP: Normal
• Alarm Signalling F4
ISOLATED INPUT
• All Sounders F5
Isola 001 1 - Isolate
2 - De-Isolate
Press 3 from the Main menu. The following screen will be
displayed: Back
Isolation Status
Isolate/De-Isolate In the ‘Customer Operator’ access levels, only points on the
MX Panel addressable loop can be isolated or de-isolated.
1 - Point
Wed, 01-Mar-00 2 - Point I/P only Isolations are counted and displayed (eg, Isol 001). If only
14:15 3 - Point O/P only the input or output of a point is isolated, this is counted as a
4 - Zone Detectors complete isolation of the point.
Company Name 5 - Zone Callpoints
6 - Zone Alarm I/Ps The following screen shows an example of Zone isolation:
General 7 - Zone Sounders
8 - Zone Controls
9 - Zone Extinguish Isolate/De-Isolate
MX Panel Zone Detectors
Wed, 01-Mar-00 Zone 001
14:15 Zone 01
Back Ext.Ctl Flt Sig Alm Sig All SND
Company Name
Select the required number from the Isolate/De-Isolate menu, General Isolate
then select the type of point (as described in Section 3.5): All
• Loop Point (Addressable Loop)
Isola 003 Successes : 003
Use the ‘+’, ‘-’ and ‘>>’ keys to select the Matches : 003
required Loop and Point, then press Enter
key. Back
• RBus Point (Remote Bus) Successes: Number of points that were
Use the ‘+’, ‘-’ and ‘>>’ keys to select the De-Isolated
required RBus, Category and Point, then Matches: Number of points in Zone (detectors)
press Enter key.
• Local I/O Point (Field Interface Module)
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required Category and Point, then press Enter
key.
PAGE 20 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
The following screen shows an example of All Sounders Use the ‘>>’ key to move the cursor between options, enter
isolation: date and time values via the keypad or Softkey F3 (‘-’) and
F4 (‘+’).
Isolate/De-Isolate
MX Panel Note:
All Sounders
Wed, 01-Mar-00 1) When a value has been changed, F5 shows
14:15 ‘Save’, use this key when all editing has been
completed.
Company Name
2) Months January to September can also be
General entered with the keypad:
1 = January
Isola 006 Successes : 006
Matches : 006 ...................
9 = September
Back
Back
Back >> - + Save
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
3.9.1 VIEW EVENT LOG The destination printer can be selected if more than one
printer is configured.
This option allows all events in the event log to be viewed The priorities available are shown in the following table:
or printed.
Select option 1 from the Event Log menu, the following type Lowest Priority Information Only
of screen will be displayed: . Level 2
. Expected Events
Event Log . Isolates
MX Panel . Warnings
Event ID 00010
Wed, 01-Jan-00 Zone 000 . Visible Isolate
14:15 System Zone . Other Faults
Company Name TEST FINISHED . Critical Faults
. Gas Alert
General 04-Feb-02 19:30:00
- Empty - . Alarm Threshold
Information only . Non-Life Risk
. Level 12
0001/0010 . Life Risk Alarms
Highest Priority General Alarm
Back << << >> >>
The latest event is displayed, use the ‘<<’ and ‘>>’ keys to It is always printed from the selected priority (eg, Non Life
scroll through the log and the ‘|<<’ to move to the back of Risk) to the Highest Priority (eg, Non Life Risk, Level 12,
the log or the ‘>>|’ key to move to the front of the log. Life Risk Alarm and General Alarm).
• EventID - Displays the absolute number of
an event (1 to 65,535). After 65,535 it starts
with 1 again. 3.9.3 FILTER
• 0001/0010 - The first number is the actual Select option 3 from the Event Log menu, the following
position in the event log (1 means it displays type of screen will be displayed:
the newest event log entry. The second Event Log
number displays the number of entries in the MX Panel
event log (max. 3,000). 1 - Fire -
Wed, 01-Mar-00 2 - Gas Alert -
14:15 3 - Pre Alarm -
4 - Supervisory -
The newest/last event will be displayed when the Event Log Company Name 5 - Fault -
is entered. 6 - Isolate -
General 7 - Test Mode -
8 - Warning -
9 - Information -
3.9.2 PRINT EVENT LOG
Select option 2 from the Event Log menu, the following type
of screen will be displayed: Back View Print
PAGE 22 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
Pressing F5 displays the following screen: Note: Only the Loop will be shown if the panel is not
networked.
Point Values
MX Panel Select the required panel (only if the panel is networked)
Zone 002 B002
Wed, 01-Jan-00 South Building and loop, then press the Enter key. The following message
14:15 1st Floor Corridoor is displayed:
Room 117
Company Name 801H Please Wait...
General Real: 801 H (020)
Mode: 1 Sens.: 0 for approximately 2 minutes until the count is complete, if
no faults are found, the following type of screen will be
20 oC (032) displayed:
View Faults
MX Panel
Total : 002 Back Details Scan
Wed, 01-Jan-00
14:15 Zone 000
Zone 000
R10
R12
• Configured - the number of points
configured in CONSYS.
Company Name
General
• There are no multiple reserved point
addresses.
PAGE 24 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
• Conf & Ident - shows how many points are 3.10.5.2 SCAN
connected, identified and configured on the
loop. Press the ‘Scan’ key (F3), the following type of screen will
be displayed:
• Not Conf. - shows how many points were
identified on the loop but not configured in
CONSYS. Loop Point Counters
MX Panel
• Both Sides/Left Side/Right Side - Shows
Wed, 01-Jan-00
Left / Right Scan
Loop : A
how many points on the loop are recognised
14:15 Point 0123456789
by the panel. ‘Left Side’ and ‘Right Side’ is 0 : ....l.....
the count from both sides. ‘Both Sides’ Company Name 10 : ..........
means the detection of a closed loop. 20 : .l........
General 30 : ...*......
40 : ..........
Note: If the value of ‘Conf & Ident’ is different to the 50 : ..........
number of installed devices, multiple reserved 60 : rrrrr.....
70 : ..........
address may be the cause. 80 : ..*.......
Back >>
3.10.5.1 DETAILS
The points are shown which were detected from both sides
Press the ‘Details’ key (F2), the following type of screen (Left/Right).
will be displayed:
They are displayed as follows:
All 250 addresses may be displayed using the ‘>>’ key. 3.11 SERVICE
The connection detail of each point is shown by the Press 7 from the Main menu, the following screen will be
following symbols: displayed:
o OK: point connected, configured and Service
identified (eg, point 33 and points 60 to 64) MX Panel
Point was configured (in MX CONSYS) but 1 - Walk Test
c Wed, 09-Aug-00 2 - Maintenance
not connected or identified (eg, point 21) 00:01 3 - Diagnostics
Point was not configured but connected (eg, Company Name
u
point 6)
General
Function key F2 scrolls through the loop.
Back
Note: The Maintenance and Diagnostics options are
only available at Customer Manager level and
will not be displayed for lower levels.
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
General Loop
Automatic : NO Only with Area as ‘All’ or ‘Zone’.
Multisensor : Part Walk Test of all loops or of a specific loop (A, B, C or D).
Use the ‘>>’, ‘-’ and ‘+’ keys to select the required Only with Area selected as ‘Point’.
options. The Panel number is only displayed when it is part
of a networked system.
• Loop A point on the loop.
Walk test
• Loop Selection of a specific zone is possible.
MX Panel
Panel : 01 Point
Wed, 09-Mar-02 Area : Point
00:01 Type : Input Only with Area selected as ‘Point’.
Location : Loop
Company Name Zone : 01 Selection of a specific zone is possible.
Point : 01
General
Automatic : NO Automatic
Multisensor : Part Only if type selected is ‘detectors’.
• YES Self test will be carried out by
Back >> + - Start detectors. The following detectors support
the self test function:
To start the Walk Test press F5. 801PH
801CH
Possible Settings 801I
Panel •NO No self test will be done by the detectors.
PAGE 26 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
• TestZ 001 Number of zones which are in Walk 3.11.2.2 VIEW/PRINT MAINTENANCE
REQUEST
Test. (The pointer is only counted if all
points of a zone are in Walk Test. If one When selected, this option displays a list of detectors which
detector on the zone is switched off, the are near the limit of their threshold compensation limit.
pointer is not decreased. In the case of
Press 3 from the Maintenance menu. The following type of
Walk Test for one point, the pointer is
screen will be displayed:
only decreased if that point is the only
point on the zone). Maintenance Request
Press F3 for a display of selected settings. MX Panel
Press F5 to end Walk Test. Wed, 01-Mar-00 Total : 003
14:15
Zone 002 B002
Company Name Zone 004 A126
CAUTION: Zone 008 B006
General
THE FINISHING OF A WALK TEST IS ONLY
POSSIBLE IF ALL POINTS IN THE WALK
TEST ARE INACTIVE.
Back Print
3.11.2 MAINTENANCE
Press 2 from the Service menu. The following type of Press F5 to print the Maintenance Request.
screen will be displayed:
Back
PAGE 28 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
‘Menu option 9- Restart’ will only be displayed if text has 3.11.3.2 POINT TEXT MODIFY
been changed and the changes saved.
Press 1 from the Change Text menu. The following screen
will be displayed:
RESTRICTIONS ON THE USE OF THE
FOLLOWING OPTION Point Text Modify
MX Panel
When using Configuration menu option 1, ALWAYS Loop : A
commit configuration changes by using ‘Menu option 9 - Wed, 01-Mar-00 Point : 001
Restart’ before leaving the panel. 14:15
NEVER use the ‘Back’ option from the configuration menu General
if ‘Menu option 9 - Restart’ is showing.
If you do not want to commit changes, by using ‘Menu
option 9 - Restart’, option, turn the keyswitch to ‘OFF’
position to avoid a timeout situation, do NOT USE the
‘Back’ option. Back >> - + Enter
Configuration changes across a network are possible, but Select the required loop and point then press Enter. The
changes to more than one panel at a time MUST NOT be following type of screen will be displayed:
attempted within one session. When a panels configuration
has been changed, it must be restarted using menu option 9 Point Text Modify
‘Restart’. MX Panel Zone 255 -007 A
Failure to comply with these restrictions may lead to Wed, 01-Mar-00
unpredictable effects or system instability. 14:15 Old text
Callp. alarm room
Company Name New text
3.11.3.1 CHANGE TEXT General
Press 1 from the Configuration menu. The following screen
will be displayed:
Change Text
MX Panel 1 - Point Text Back >> - + Enter
Wed, 01-Mar-00 2 - Zone Text
14:15 3 - Sector Text ‘>>’ - copies the ‘old text’ to the ‘New text’ position.
4 - Panel Text
Company Name 5 - Info Text ‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position.
General
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter.
Pressing the scroll up key allows text to be entered in
upper case.
Back Pressing the scroll down key changes to lower case
text.
The message ‘Save Data?’ appears and the functions
change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the
text modifications to be changed.
Selecting F4 ‘Yes’ displays the message:
Please wait.....
PAGE 30 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
Configuration Modify the old text or insert new text using the
MX Panel 1 - Change Text alphanumeric keypad, when finished press Enter.
Wed, 01-Mar-00 The message ‘Save Data?’ appears and the function change
14:15
F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text
Company Name modifications to be changed.
General Selecting F4 ‘Yes’ displays the message:
9 - Restart Please wait.....
Back - + Enter
Select the required and press Enter. The following type of
screen will be displayed:
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
PAGE 32 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
3.11.3.5 PANEL TEXT MODIFY Selecting F1 ‘Back’ will display the following screen:
Press 4 from the Configuration menu. The following screen Configuration
will be displayed: MX Panel 1 - Change Text
Wed, 01-Mar-00
Panel Text Modify 14:15
MX Panel Panel 00 Company Name
Wed, 01-Mar-00 Old Text
14:15 ADT General
Company Name 9 - Restart
New Text
General
Back
Select the required Panel. This option allows Info Text created in Consys to be
modified. Press 5 from the Change Text menu. The
‘>>’ - copies the ‘old text’ to the ‘New text’ position. following screen will be displayed:
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position. Info text modify
MX Panel
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter. Wed, 01-Mar-03
14:15
The message ‘Save Data?’ appears and the function change
F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text Company Name Infotext No. : 001
modifications to be changed. General
Selecting F4 ‘Yes’ displays the message:
Please wait.....
Using the ‘+’ and ‘-’ keys select the Info Text message to
Change Text modify, then press ‘Enter’.
MX Panel
The following type of screen will appear:
Wed, 01-Mar-00
14:15 4 - Panel Text
Company Name Info text modify
MX Panel Infotext No. : 001
General This zone is in a
Wed, 01-Mar-03 Hazardous Area
14:15 Special
Company Name precautions
are required
General
Back
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-05-O
5 11/04
Use the alphanumeric keys to modify the text, when 4. ROUTINE CHECKS
finished, press ‘Enter’.
4.1 GENERAL
The following screen will be displayed:
In order to comply with the requirements of British
Standard BS 5839 Part 1 (1988), the installation must be
Info text modify checked on a regular basis by a responsible member of staff
MX Panel Infotext No. : 001 to confirm that the controller and all ancillary devices are
Wed, 01-Mar-03 This zone is in a operating correctly. The required routine checks are
14:15 Hazardous Area described in the following paragraphs.
Special
Company Name precautions For Marine Systems, carry out routine checks in accordance
are required
with the customer’s own procedures.
General
WARNING:
Proceed as follows:
a) If necessary, clean the front panel of the
controller with a suitable cleansing agent.
b) Set one device (either a callpoint or
detector) from one zone into alarm and
check that the system responds as follows:
• The controller’s internal buzzer sounds in
a continuous tone.
• The two red ‘FIRE’ LEDs on the
controller front panel light.
• The appropriate red ‘FIRE ZONAL’ LED
flashes (if configured).
• The general and zonal sounders operate.
PAGE 34 of 35
EQUIPMENT: MX
PUBLICATION: 17A-05-O
ISSUE No. & DATE: 5 11/04
JM/jm
28th November 2004
Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB