You are on page 1of 34

EQUIPMENT: MX

PUBLICATION: 17A-04-S
ISSUE No. & DATE: 5 11/04

DOCUMENT CONTROL NUMBER /


‘MX’ ADDRESSABLE FIRE CONTROLLERS
SERVICE AND MAINTENANCE INSTRUCTIONS FOR VERSION 6.0
LIST OF CONTENTS
1. GENERAL INFORMATION 3 4. DEFAULT SYSTEM POINTS 32
4.1 LOCAL I/0 (Field Interface Module/
CPU) 32
2. ROUTINE CHECKS 4 4.2 RBUS 32
2.1 GENERAL 4 4.3 ADDRESSABLE LOOP 33
2.2 WEEKLY CHECKS 4
2.3 THREE-MONTHLY CHECKS 4
2.4 ANNUAL CHECKS 5 5. DEVICE IDENTIFICATION AND
2.5 THREE-YEARLY CHECKS 5 UNIVERSAL ADDRESSES 34
2.6 FOUR-YEARLY CHECKS 5

3. CONTROLLER FUNCTIONS 5
3.1 GENERAL 5
3.2 MOVING THE CURSOR 5
3.3 ENTERING INFORMATION 5
3.3.1 ENTERING PASSCODES 8
3.4 POINT DEFINITIONS 8
3.5 VALID VALUES 8
3.6 MAIN MENU 9
3.7 VIEW STATUS 9
3.8 ISOLATE/DE-ISOLATE 10
3.9 TIME/DATE 11
3.9.1 SET TIME/DATE 11
3.9.2 SUMMER/WINTER 12
3.10 EVENT LOG 12
3.10.1 VIEW EVENT LOG 12
3.10.2 PRINT EVENT LOG 12
3.10.3 FILTER 13
3.11 VIEW/PRINT STATUS 13
3.11.1 VIEW/PRINT POINTS
ISOLATED 13
3.11.2 VIEW/PRINT POINTS
UNTESTED/FAILED 14
3.11.3 VIEW/PRINT POINT VALUES 14
3.11.4 VIEW FAULTS 14
3.11.5 VIEW LOOP POINT
COUNTERS 14
3.12 SERVICE 16
3.12.1 WALK TEST 16
3.12.2 MAINTENANCE 19
3.12.3 DIAGNOSTICS 21
3.12.4 TEST BUZZER/LEDs/
DISPLAY 23
3.13 CONFIGURATION 23
3.13.1 CHANGE TEXT 24
3.13.2 INSERT POINT 28
3.13.3 DELETE POINT 28
3.13.4 MODIFY POINT 29
3.13.5 AUTOCONFIGURATION 29

© 2004 Tyco Safety Products PAGE 1 of 34

Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

This page has intentionally been left blank

PAGE 2 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

1. GENERAL INFORMATION
WARNING:
This manual is written for firmware Version 6.0.
ENSURE THAT ANY EXTINGUISHING
As the ‘MX’ equipment forms a fire control system, the SYSTEMS ARE “MADE SAFE”
following periodical checks must be carried out in order to (SEE 05A-03-S1) BEFORE CARRYING OUT
comply with the requirements of BS 5839 : Part 1 (2002) THE DESCRIBED PROCEDURES.
and marine customer requirements to ensure the continued
correct operation of the system. ANY AUXILIARY DEVICES CONNECTED TO
The following checks and servicing must be carried out: THE SYSTEM MAY OPERATE DURING THE
FOLLOWING PROCEDURES UNLESS
• Weekly checks of the controller, one DISABLED. NOTIFY THE CUSTOMER
detector per zone and the fire detection PRIOR TO ANY DISABLEMENT.
sounders.
• Three-monthly checks.
• Annual visual, fixture security and zone
checks on all units. Note: The EVACUATE or FIRE ALARM, SILENCE
• Three-yearly check of all detectors. and RESET keys on the front panel are
inoperative until the keyswitch has been turned
• Four-yearly replacement of batteries. to the ‘enable’ position.

The following are also described:


• Use of built-in controller functions.
• Recommended spares list. WARNING:

Wherever possible, faults must be rectified by exchange of In order to prevent TERMINAL DAMAGE to the
the faulty PCB or other part for a working spare. MINERVA MX Controller the following rules
MUST be strictly followed:

1) ENSURE THAT THERE IS NO FAULT IN THE


ADDRESSABLE LOOP
BEFORE IT IS CONNECTED TO THE
MINERVA MX CONTROLLER.

2) NEVER CONNECT THE


ADDRESSABLE LOOP WIRING TO THE
MINERVA MX CONTROLLER WHILST THIS
UNIT IS POWERED-UP.

3) NEVER MAKE ANY CHANGES TO THE


ADDRESSABLE LOOP WIRING WITHOUT
EITHER DISABLING THE ADDRESSABLE LOOP
OR POWERING DOWN THE MINERVA
MX CONTROLLER.

4) DO NOT LEAVE ANY DOCUMENTATION IN


CONTROLLER OR ANCILLARY HOUSINGS

© 2004 Tyco Safety Products PAGE 3 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

2. ROUTINE CHECKS • The two red ‘FIRE’ LEDs on the


controller front panel light.
2.1 GENERAL • The appropriate red ‘FIRE ZONAL’ LED
The checks described in the following paragraphs would (if configured) flashes.
normally be carried out at the intervals stated. The Detector • The general and zonal sounders operate.
Condition Monitoring facility checks the condition of 800 • The alphanumeric display gives the
series smoke detectors and will signal a fault when a smoke location of the alarm.
detector reaches the limit of its compensation.
Therefore, if a controller has detector condition monitoring, f) Record the device used to initiate the test in
the following procedure should be carried out: the site log book and reset the controller.
a) At regular intervals, or when a detector g) Check the condition of the printout on any
condition monitoring fault is generated, printers attached to the system and replace
obtain a printout of all points out of the ribbon if it is becoming faint.
compensation (see section 3.12.2.2).
h) Ensure that each printer has an adequate
b) From the data obtained, replace only those supply of paper.
detectors which are out of compensation.

Any defect should be recorded in the log book and


For Marine Systems carry out routine checks in accordance appropriate action taken. On completion of the work,
with the customer’s own procedures. obtain the signature of the customer or his representative for
the Routine Maintenance Visit Record. Leave a copy of
this record with the customer for his files.
2.2 WEEKLY CHECKS
These checks would normally be carried out by a
2.3 THREE-MONTHLY CHECKS
responsible member of the customer’s staff. They should
also be carried out by the service engineer after all routine Proceed as follows:
maintenance checks:
a) Perform the weekly checks as detailed in
section 2.2.
WARNING: b) Check the entries in the log book and carry
out any necessary action.
WARN ALL PERSONNEL THAT THE c) Check the batteries and their connections in
SOUNDERS ARE ABOUT TO BE TESTED. accordance with publication 05A-10-S1.
d) Check all the ancillary functions of the
controller.
e) Check all fault indicators by simulating a
Proceed as follows: FAULT condition in each zone by either:
a) If necessary, clean the front panel of the i) removing a detector from its base, or;
controller with a suitable cleansing agent.
ii) disconnecting the local circuit from an
b) Check all batteries in accordance with ancillary unit, or;
publication 05A-10-S1.
iii) removing the end-of-line resistor from an
c) Service Engineer only - Check the ancillary unit’s circuit.
tightness of all terminal block screws inside
the controller.
d) Using the walk test function (see sections f) Visually check the condition of the
3.12.1), check the operation of at least one controller and other ancillary equipment for
zone. If a printer is available, print out the signs of moisture ingress and other
results of the walk test (see section 3.11.2). deterioration.

e) Set one device (either a callpoint or detector) g) Visually check the installation to ascertain
from one zone into alarm and check that the whether structural or occupancy changes
system responds as follows: have affected the requirements for the siting
of manual callpoints, detectors, line isolator
• The controller’s internal buzzer sounds in base, sounders or sounder bases.
a continuous tone.

PAGE 4 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

Note: Any changes must be made the subject of a 2.5 THREE-YEARLY CHECKS
report to the Service Department.
In addition to the normal yearly checks, filters of VESDA™
Aspirating detectors must be changed.
h) Ensure that a clear space of at least 750 mm
is preserved in all directions below heat and
smoke detectors, that they are correctly sited 2.6 FOUR-YEARLY CHECKS
and that all manual callpoints remain In addition to the normal yearly checks, internal standby
unobstructed and conspicuous. batteries must be renewed.
i) Ensure that no physical obstruction has been
placed in the line-of-sight between flame
detectors and the protected area. CAUTION:

TAKE CARE WHEN HANDLING THE


Any defect should be recorded in the log book and BATTERY. DO NOT CONNECT THE
appropriate action taken. On completion of the work, BATTERY THE WRONG WAY
obtain the signature of the customer or his representative for ROUND. WHEN THE BATTERY IS NOT
the Routine Maintenance Visit Record. Leave a copy of this CONNECTED, COVER TERMINALS WITH
record with the customer for his files. INSULATING TAPE TO PREVENT
ACCIDENTAL SHORT CIRCUIT.

2.4 ANNUAL CHECKS


Proceed as follows:
a) Perform the three-monthly checks as 3. CONTROLLER FUNCTIONS
detailed in section 2.3.
3.1 GENERAL
b) Visually check the inside and outside of the
controller and ancillary devices for damage. The ‘MINERVA MX’ fire controller has a large number of
built-in functions. These functions allow system
c) Check for damage to, and paint on, heat parameters to be viewed and/or changed and a number of
detectors; check for dirt, grease, etc. on the operations to be performed.
lenses of flame detectors.
As the available functions allow access to system
d) Clean or exchange units as necessary. parameters, it is necessary to restrict the use of these
e) Check for damage and accumulations of dirt functions to trained staff. This is achieved by the use of
on ion-chamber smoke detectors. DO NOT passcodes. In order to gain access to the controller
CLEAN; these units MUST be exchanged functions, the user enters a passcode via the front panel
and returned to the factory for disposal. keypad. The function is then either selected from the menu.
Access to the keypad is gained via the five ‘Softkeys’ on the
Note: The return of ion-chamber smoke detectors is Operator Display Module (see Fig. 1) or MX2 Display
to be carried out in accordance with the latest Control Module (see Fig. 2).
company standing instructions for storage and
transportation of radioactive materials.
3.2 MOVING THE CURSOR
f) Check the fixings for the controller and all The cursor is moved through the options using the softkey
detectors, sounders and ancillary equipment associated with the double arrow sign ‘>>’.
which form part of the fire detection system.
g) Check the cable fixings at the controller and
each ancillary device for correct connection. 3.3 ENTERING INFORMATION
h) Test ALL detectors and callpoints for When the cursor is over information that can be changed,
correct operation. either use the ‘+’ or ‘-’and softkeys or enter the number/
letter via the keypad.
Record any defect in the log book and rectify as
required. On completion of the work, obtain the signature Note: For speed, Point Numbers should be entered
of the customer or his representative for the Routine via the keypad.
Maintenance Visit Record. Leave a copy of this record with
the customer for his files.

© 2004 Tyco Safety Products PAGE 5 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
5
MX
17A-04-S

PAGE 6 of 34
11/04

ALPHANUMERIC KEYPAD

1 2
ABC
3
DEF
First Fire
Zone 002 B002 SCROLL UP
1st Floor Corridoor
Room 117 4 5 6
GHI JKL MNO

Fig. 1
Last Fire 002
Zone 030 B055
4th Floor
Washroom / Window 7 8 9
PQRS TUV WXYZ
General Information
SCROLL DOWN

Operator Display Module


LED Tst More

F1 F2 F3 F4 F5

SOFTKEYS
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

ALPHANUMERIC
KEYPAD
Main menu 2 3
SYSTEM 1
1 - Accept Events SCROLL * ABC DEF
Wed, 01-Mar-00 2 - Actual Status
14:15 3 - (De-) Isolate UP
4 - Time / Date 4 5 6
Company Name 5 - Event Log
6 - View/Prn Status GHI JKL MNO
General 7 - Service
9 - Test Buzzer, 7 8 9
LED's Display PQRS TUV WXYZ
Alarm Count: 0021 SCROLL
DOWN
Back 0

F1 F2 F3 F4 F5

SOFTKEYS

GENERAL
GENERAL SYSTEM SOUNDERS
SOUNDERS SIGNALLING CONTROLLER

FIRE PRE ALARM ACTIVATED ACTIVATED POWER ON

FAULT DAY MODE FAULT FAULT MAINS FAULT

DISABLED STATUS 1 DISABLED DISABLED SYSTEM FAULT

TEST STATUS 2

SILENCE SILENCE DAY INVESTIGATE


RESET FUNCTION EVACUATE
BUZZER RESOUND NIGHT DELAY

ZONE DISPLAY

1 11 21 31 41 51 61 71

2 12 22 32 42 52 62 72

3 13 23 33 43 53 63 73

4 14 24 34 44 54 64 74

5 15 25 35 45 55 65 75

6 16 26 36 46 56 66 76

7 17 27 37 47 57 67 77

8 18 28 38 48 58 68 78

9 19 29 39 49 59 69 79

10 20 30 40 50 60 70 80

Fig. 2 Display Control Module

© 2004 Tyco Safety Products PAGE 7 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.3.1 ENTERING PASSCODES

Supervisor
Engineer

Engineer
In order to avoid repetition, however, the general procedure Enable
for entering a PASSCODE is described as follows: Key

i) Press F3 (Passcode), enter your ID (press


F5 ‘Enter’ if the ID has only one digit), Lamp/Buzzer/LCD Test ✔ ✔ OFF
Unrestored Events ✔ ✔ OFF
then enter your Passcode (press F5 ‘Enter’ Information Text ✔ ✔ OFF
if the ID has less than 6 digits) . View Events (Scrolling) ✔ ✔ OFF

MAIN MENU ✔ ✔ ON
3.4 POINT DEFINITIONS View Status ✔ ✔ ON
Real point - A physical input/output point
Isolate/De-Isolate ✔ ✔ ON
Pseudo point - A software derived fault number
eg, Communications Fault or Time/Date ✔ ✔ ON
Set time/Date ✔ ✔ ON
RAM Fault Summer/Winter ✔ ✔ ON
Timer - Point activated by user
(MX CONSYS) configured timer Event Log ✔ ✔ ON
View Event Log ✔ ✔ ON
Menu - Up to 10 points configured for Print Event Log ✔ ✔ ON
specific site functions
View/Print Data ✔ ✔ ON
Points Isolated ✔ ✔ ON
3.5 VALID VALUES Points Untested/Failed ✔ ✔ ON
Point Values ✔ ✔ ON
The following are values which may be entered for each View Faults ✔ ✔ ON
option: Loop Point Count (not ver. 1.3) ✔ ✔ ON

Service ✔ ✔ ON
Panel Number 1 - 99 Walk Test ✔ ✔ ON
Maintenance engineer ✔ ✔ ON
Zone Number 1 - 240* Fire Alarm Cycle Count ✔ ✔ ON
Sector Number 1 - 240 Maintenance Request ✔ ✔ ON
Battery Test ✔ ✔ ON
RBus Number 0 - 15 Software Initialisation Count ✔ ✔ ON
Real Point 1 - 24 Project Numbers ✔ ✔ ON
Pseudo Point 1-8 Software Versions ✔ ✔ ON
Menu points ✔ ✔ ON
XBus Point 1 - 96 Diagnostics ✔ ✔ ON
Local I/O Force Device Output ✔ ✔ ON
Force Device Input ✔ ✔ ON
Real Point 1 - 18 Shutdown/Restart ✔ ✔ ON
Pseudo Point 1 - 42 Fast Fault Mode ✔ ✔ ON
IOBus point 1 - 24 Rate of Rise Processing ✔ ✔ ON
Single device poll mode ✔ ✔ ON
Timer Point 1 - 10 Change Address ✔ ✔ ON
Menu Point 1 - 10 Fast Logic ✔ ✔ ON
‘*’ depending on the configuration 40/80/120/160/200 or Configuration ✔ ✔ ON
240 zones. Change Text ✔ ✔ ON
Insert Point ✔ ON
Delete Point ✔ ON
Modify Point ✔ ON
Auto Configure ✔ ON
Table. 1 Menu Options and Access Levels

PAGE 8 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

3.6 MAIN MENU


View Status
When the system is in quiescent mode (ie, displaying the MX Panel
date and time), entering a high level passcode affords the Point
user access to the main menu. The structure of this menu is Wed, 01-Mar-00
14:15 1 - Loop Point
shown below. 2 - RBus Point
Company Name 3 - Local I/O Point
Main menu General
MX Panel
1 - Accept Events
Wed, 01-Aug-00 2 - View Status
00:01 3 - Isolate/De-Isol
4 - Time / Date
Company Name 5 - Event Log
6 - View/Print Data Back
General 7 - Service
8 - Configuration Select the type of Point or Zone:
9 - Test Buzzer,
LEDs & Display 1) Loop Point (Addressable Loop).
Alarm Count: 0021 2) RBus Point.

Back 3) Local I/O Point.

Each of the options available leads to further menus or The following type of screen will be displayed:
functions, which are described in the following paragraphs. Note: If the panel is in a networked system, the panel
number will be shown as in the following
example.
3.7 VIEW STATUS
Allows the status of all points and zones on the system to be View Status
viewed. Press 2 from the Main menu, the following type of MX Panel
screen will be displayed: Point
Wed, 01-Mar-00
14:15 Panel
02
View Status Company Name Loop
MX Panel
1 - Point General A 001
Wed, 01-Mar-00 2 - Point I/P only
14:15 3 - Point O/P only
4 - Zone
Company Name
General
Back >> - + Enter

• Loop Point (Addressable Loop)


Use the ‘+’, ‘-’ and ‘>>’ keys to select the
Back
required Loop and Point, then press Enter
key.
Point Complete - allows the status of all points on the • RBus Point (Remote Bus)
system (both inputs and outputs) to be checked. Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required RBus, Category and Point, then
Point Input - allows the status of only input devices to be press Enter key.
checked (eg, detectors).
Point Output - allows the status of only output devices to
• Local I/O Point (Field Interface Module)
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
be checked (eg, functional bases, sounder etc.). required Category and Point, then press
Zone - allows the total status of all points in a specified zone Enter key.
to be checked.
Select the required number from the Actual Status menu, the
following type of screen will be displayed:

© 2004 Tyco Safety Products PAGE 9 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

The following type of screen will be displayed: Function Keys F3/F4 will decrement/increment the zone
number.
View Status
MX Panel
Point
Wed, 01-Mar-02 Zone 006 A007 Description
14:15
Zone 06 Alarm Yes One or more devices of a
Company Name Call alarm in room zone in Alarm Mode
CP 820
General
Fault Yes One or more devices of the
Input Output zone in Fault Mode
Normal
Isolate Yes All alarm input devices of the
zone are Isolated
Back
Walk Test Yes All alarm input devices of a
Point Input and Point Output are displayed in the same
zone in Walk Test
format.
The top line shows the selected option.
The second line shows the Zone and Point number of the 3.8 ISOLATE/DE-ISOLATE
device.
The Isolate/De-isolate option allows the following to be
The third line shows the Sector description (defined at isolated/de-isolated:
configuration).
The fourth line shows the Zone description (defined at • Point Complete 1*
configuration). • Point Input 2*
The fifth line shows the Point description (defined at
configuration).
• Point Output 3*

The sixth line shows the device type.


• Zone Detectors 4**
• Zone Callpoints 5**
Actual Status IP can be in one of the following states: • Zone Alarm I/Ps 6**
• Normal • Zone Sounders 7***
• Fault
• Zone Controls 8***
• Active
• Zone Extinguishing Equipment 9***
• PreAlarm
Actual Status OP can be in one of the following conditions:
• Extinguish Controls (all) F2*

• On
• Fault Signalling (all) F3*

• Off
• Alarm Signalling (all) F4*

• Pulse 1 • All Sounders F5*


• Pulse 2
Note: Other options are available for some of the
Selecting 4 Zone will display the following type of screen: above:
1) * No extra options.
View Status
MX Panel 2) ** The following options are available:
Zone 002
Wed, 01-Mar-00 South Building 1 - All
14:15 1st Floor Corridoor 2- In Fault
Company Name Alarm : NO 3 - Active
Fault : NO 4 - Not Normal (either In Fault or Active)
General Isolate : NO
Walk Test : NO 3) *** The following options are available:
1 - All
2 - In Fault

Back _ +

PAGE 10 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

Press 3 from the Main menu. The following screen will be The following screen shows an example Zone isolation:
displayed:
Isolate/De-Isolate
Isolate/De-Isolate MX Panel
MX Panel Zone Detectors
1 - Point Wed, 01-Mar-00 Zone 001
Wed, 01-Mar-00 2 - Point I/P only 14:15
14:15 3 - Point O/P only Zone 01
4 - Zone Detectors Company Name
Company Name 5 - Zone Callpoints
6 - Zone Alarm I/Ps General
General 7 - Zone Sounders Isolate
8 - Zone Controls All
9 - Zone Extinguish
Isola 003 Successes : 003
Matches : 003

Back Ext.Ctl Flt Sig Alm Sig All SND Back

Select the required number from the Isolate/De-Isolate Successes: Number of points that were
menu or from the soft keys, then select the type of point (as (De-)Isolated
described in Section 3.7): Matches: Number of points in Zone (detectors)
• Loop Point (Addressable Loop)
The following screen shows an example of All Sounders
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required Loop and Point, then press Enter isolation:
key.
• RBus Point (Remote Bus) MX Panel
Isolate/De-Isolate
All Sounders
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required RBus, Category and Point, then Wed, 01-Mar-00
press Enter key. 14:15

• Local I/O Point (Field Interface Module) Company Name


Use the ‘+’, ‘-’ and ‘>>’ keys to select the General
required Category and Point, then press
Enter key.
Isola 006 Successes : 006
Matches : 006
The following screen shows an example Point isolation:
Back
Isolate/De-Isolate
MX Panel Successes: Number of sounders (De-)Isolated
Point Complete Matches: Number of sounders in all Zones
Wed, 01-Mar-00 Zone 002 B002
14:15 South Building
1st Floor Corridoor 3.9 TIME/DATE
Company Name Room 117
801 H
General Press 4 from the Main menu. The following type of screen
Status IP: Normal will be displayed:
ISOLATED INPUT
Isola 001 1 - Isolate Time / Date
2 - De-Isolate MX Panel
1 - Set Time/Date
Back Wed, 01-Mar-00 2 - Summer/Winter
14:15
Isolation Status
Company Name
In the ‘Customer Operator’ access levels, only points on the
addressable loop can be isolated or de-isolated. General
Isolations are counted and displayed (eg, Isol 001). If only
the input or output of a point is isolated, this is counted as a
complete isolation of the point.

Back

© 2004 Tyco Safety Products PAGE 11 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.9.1 SET TIME/DATE 3.10 EVENT LOG


Press 1 from the Time/Date menu. The following type of Press 5 from the Main menu. The following type of screen
screen will be displayed: will be displayed:

Time / Date
MX Panel Event Log
Date : 01-Mar-00 MX Panel
Wed, 01-Mar-00 Time : 14:15:17 1 - View Event Log
14:15 Wed, 09-Aug-00 2 - Print Event Log
00:01 3 - Filter
Company Name
Company Name
General
General

Back >> - + Save


Back

Use the ‘>>’ key to move the cursor between options, enter
date and time values via the keypad. 3.10.1 VIEW EVENT LOG
Note: This option allows all events in the event log to be viewed
or printed.
1) When a value has been changed, F5 shows
‘Save’, use this key when all editing has been Select option 1 from the Event Log menu, the following
completed. type of screen will be displayed:
2) Months January to September can also be
entered with the keypad: Event Log
MX Panel
1 = January Event ID 00010
................... Wed, 01-Jan-00 Zone 000
14:15 System Zone
9 = September
Company Name TEST FINISHED
3.9.2 SUMMER/WINTER General 04-Feb-02 19:30:00
- Empty -
Press 2 from the Time/Date menu. The following type of Information only
screen will be displayed:
0001/0010
Summer/Winter Back << << >> >>
MX Panel Summertime
Wed, 01-Jan-00 The latest event is displayed, use the ‘<<’ and ‘>>’ keys to
14:15 scroll through the log and the ‘|<<’ to move to the back of
Company Name the log or the ‘>>|’ key to move to the front of the log.

General • EventID - Displays the absolute number of


an event (1 to 65,535). After 65,535 it
starts with 1 again.
• 0001/0010 - The first number is the actual
position in the event log (1 means it
displays the newest event log entry. The
Back Winter
second number displays the number of
These screens show the date of change between Summer entries in the event log (max. 3,000).
and Winter time and cannot be changed, the information is
configured in MX CONSYS, use F5 to toggle between
Winter and Summer. The newest/last event will be displayed when the Event Log
is entered.
Dates are not shown on a T2000 Marine panel.

PAGE 12 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

3.10.2 PRINT EVENT LOG It is possible to view and to print the events of single
categories. The category is selected by pressing the
Select option 2 from the Event Log menu, the following type appropriate option number. It is also possible to select
of screen will be displayed: several categories, the selected categories are denoted by a
‘+’ sign.
Event Log
MX Panel Press F4 to view the selected categorie(s) as described in
Destination : Section 3.8.1 or F5 to print the selected category(s) as
Wed, 01-Jan-00 Default Printer described in Section 3.8.2.
14:15
How far back:
Company Name to start: 0010
3.11 VIEW/PRINT STATUS
General How many entries Allows the following options to be viewed/printed:
required: 0010
Lowest priority • Points Isolated
of interest : 00
Print initiated
• Points Untested/Failed (during Walk Test)
• Point Values
Back >> - + Print
• View Faults (no print option)
This menu option is only available if at least one printer is • Loop Point Counters (no print option)
configured.
Select option 6 from the Main menu, the following type of
The destination printer can be selected if more than one screen will be displayed:
printer is configured.
The priorities available are shown in the following table: View/Print Data
MX Panel
1 - Points Isolated
Lowest Priority Information Only Wed, 01-Jan-00 2 - Pts Unt./Failed
. Level 2 14:15 3 - Point Values
. Expected Events 4 - View Faults
. Isolates Company Name 5 - Loop Point Ctrs
. Warnings General
. Visible Isolate
. Other Faults
. Critical Faults
. Gas Alert
. Alarm Threshold
. Non-Life Risk Back
. Level 12
. Life Risk Alarms 3.11.1 VIEW/PRINT POINTS ISOLATED
Highest Priority General Alarm Select option 1 from the View/Print Status menu, the
It is always printed from the selected priority (eg, Non Life following type of screen will be displayed:
Risk) to the Highest Priority (eg, Non Life Risk, Level 12,
Life Risk Alarm and General Alarm).
Points Isolated
MX Panel
3.10.3 FILTER Input
Wed, 01-Mar-00 Total : 004
Select option 3 from the Event Log menu, the following type 14:15
of screen will be displayed: Zone 001 -001 B
Company Name Point Text
--------------------
Event Log General 001 -002 B
MX Panel Point Text
1 - Fire -
Wed, 01-Mar-00 2 - Gas Alert -
14:15 3 - Pre Alarm -
4 - Supervisory -
Company Name 5 - Fault -
6 - Isolate - Back Output Print
General 7 - Test Mode -
8 - Warning - Note: If the panel is part of a networked system,
9 - Information -
another screen is displayed before the above
screen where the panel number may be
selected.
Back View Print

© 2004 Tyco Safety Products PAGE 13 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

Press F5 ‘Print’ to print a list of all isolated points. Select the panel number (if the panel is part of a networked
system), loop and point number required.
The F2 Key selects either isolated inputs or isolated outputs.
After pressing Enter, the following type of screen will be
Points which are completely isolated (input and output) will displayed:
be shown in both lists.
Point Values
MX Panel
Zone 002 B002
3.11.2 VIEW/PRINT POINTS UNTESTED/ Wed, 01-Jan-00 South Building
FAILED 14:15 1st Floor Corridoor
Room 117
Note: Note this option only works whilst still in Company Name 801H
Walktest.
General Real: 801 H (020)
Mode: 1 Sens.: 0
Select option 2 from the View/Print Status menu, the 20 oC (032)
following type of screen will be displayed:

Pts Untested/Failed Back Print


MX Panel Press F5 to print Point Values, values for all devices on the
Wed, 01-Jan-00 Total : 004 loop will be printed.
14:15
Zone 001 -001 B
Company Name Point Text 3.11.4 VIEW FAULTS
--------------------
General Zone 001 -002 B Select option 4 from the View/Print Status menu, the
Point Text following type of screen will be displayed:

View Faults
MX Panel
Total : 002
Back Print Wed, 01-Jan-00
14:15 Zone 000 R10
Note: If the panel is part of a networked system, Zone 000 R12
Company Name
another screen is displayed before the above
screen where the panel number may be General
selected.
Flt P 002
Press F5 to print the Untested/Failed points.
Points which are not tested or points which return the wrong Back
condition are then listed.
This option is view only.

3.11.3 VIEW/PRINT POINT VALUES 3.11.5 VIEW LOOP POINT COUNTERS


Select option 3 from the View/Print Status menu, the This option is view only. Select option 5 from the View/
following type of screen will be displayed: Print Status menu, the following screen will be displayed:

Point Values Loop Point Counters


MX Panel MX Panel
Panel 02 Panel
Wed, 01-Mar-00 Wed, 01-Jan-00 02
14:15 Loop Point 14:15
A 002 Loop
Company Name Company Name A
General General

Back >> - + Enter Back >> - + Enter

PAGE 14 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

Note: Only the Loop will be shown if the panel is not • Configured - the number of points
networked. configured in CONSYS.
Select the required panel (only if the panel is networked) • Conf & Ident - shows how many points are
and loop, then press the Enter key. The following message connected, identified and configured on the
is displayed: loop.
Please Wait... • Not Conf. - shows how many points were
identified on the loop but not configured in
CONSYS.
for approximately 2 minutes until the count is complete, if
no faults are found, the following type of screen will be
• Both Sides/Left Side/Right Side - Shows
how many points on the loop are recognised
displayed: by the panel. ‘Left Side’ and ‘Right Side’ is
the count from both sides. ‘Both Sides’
Loop Point Counters means the detection of a closed loop
MX Panel
Counter Note: If the value of ‘Conf & Ident’ is different to the
Wed, 01-Jan-00 Loop : A
14:15 PASSED number of installed devices, multiple reserved
address may be the cause.
Company Name Configured : 010
General
3.11.5.1 DETAILS
Press the ‘Details’ key (F2), the following type of screen
will be displayed:

Back Details Scan Loop Point Counters


MX Panel
• Configured - the number of points Details
configured in CONSYS. Wed, 01-Jan-00 Loop : A
14:15 Point 0123456789
• There are no multiple reserved point
Company Name
0 :
10 :
......u...
..........
addresses.
20 : .c........
General 30 : ...o......
40 : ..........
Conditions for ‘PASSED’ 50 : ..........
60 : ooooo.....
• The number of configured points is equal 70 :
80 :
..........
..........
the detected count of points on the loop.
• There are no unconfigured points. Back >>
• Detected points from left, right and both All 250 addresses may be displayed using the ‘>>) key.
sides are equal.
The connection detail of each point is shown by the
If all conditions are not satisfied, the ‘ATTENTION’ screen following symbols:
will be displayed showing the relevant counters.
o OK: point connected, configured and
identified (eg, point 33 and points 60 to 64)
Loop Point Counters Point was configured (in MX CONSYS) but
MX Panel c
Counter not connected or identified (eg, point 21)
Wed, 01-Jan-00 Loop : A
14:15 A T T E N T I O N Point was not configured but connected (eg,
u
point 6)
Company Name Configured : 010
General Function key F2 scrolls through the loop.
Conf. & Ident: 009

Back Details Scan

© 2004 Tyco Safety Products PAGE 15 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.11.5.2 SCAN 3.12.1 WALK TEST


Press the ‘Scan’ key (F3), the following type of screen will When selected, this option allows single or multiple points
be displayed: to be tested without an alarm being raised.
Press 1 from the Service menu.
Loop Point Counters Only one Walk Test session can be active at one time.
MX Panel
Left / Right Scan
Wed, 01-Jan-00 Loop : A Walk test
14:15 Point 0123456789 MX Panel
0 : ....l..... Panel : 01
Company Name 10 : .......... Wed, 09-Mar-02 Area : All
20 : .l........ 00:01 Type : Input
General 30 : ...*...... Loop : All
40 : .......... Company Name
50 : ..........
60 : rrrrr..... General
70 : ..........
80 : ..*....... Automatic : NO
Back >> Multisensor : Part

The points are shown which were detected from both sides
(Left/Right). Back >> + - Start

They are displayed as follows: Select the required option:


Use the ‘>>’, ‘-’ and ‘+’ keys to select the required
options. The Panel number is only displayed when it is part
. of a networked system.
Empty (not used)
OK: detected from both sides (eg, points 33 and Depending on the selected settings, the display will
* change. The following screen is an example of ‘Area’
82)
selected as ‘Point’.
Only detected from left side (eg, points 4 and 21)
l
Walk test
r Only detected from right side (eg, 60 to 64) MX Panel
Panel : 01
Wed, 09-Mar-02 Area : Point
00:01 Type : Input
Function key F2 scrolls through the loop. Location : Loop
Company Name Zone : 01
Point : 01
General
3.12 SERVICE Automatic : NO
Press 7 from the Main menu. The following type of screen Multisensor : Part
will be displayed:

Service Back >> + - Start


MX Panel
1 - Walk Test
Wed, 09-Aug-00 2 - Maintenance To start the Walk Test press F5.
00:01 3 - Diagnostics
Company Name Possible Settings
General Panel
The selection of panel is only available for panels that are
in a networked system.

Back

PAGE 16 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

Area Automatic
Only if type selected is ‘detectors’.
• All Walk Test of all elements of a special type.
• YES Self test will be carried out by
(Selection in the field ‘Type’ eg, callpoints).
detectors. The following detectors support
• Zone Walk Test of all elements of a specific type
the self test function:
801PH
in a specific zone.
801CH
801I
• Point Walk Test of the input of a single point.
• NO No self test will be done by the detectors.

Type
Multisensor
• Input Walk Test of all inputs.
• Full
• Detectors Walk Test of detectors. • Part
• Alarm I/Ps Walk Test of default inputs covered by
It is only possible to select either ‘Automatic’ or
supergroup ‘Fire Alarm Inputs SG’.
‘Multisensor. The panel itself prevents selection of more
• Call Points Walk Test of call points. than one option.

• Sounders Walk Test of sounders by loop or all


loops plus FIM sounders. Note: If ‘Full’ Walk Test is selected, both modes of
the detector must be activated (eg, both heat
and optical mode for 801PH).
Loop
If ‘Part’ Walk Test is selected, the detector has
Only with Area as ‘All’ or ‘Zone’. to be activated in the mode in which it is
Walk Test of all loops or of a specific loop (A, B, C or D). operating (eg, for 801PH optical and heat, both
modes active, then activation of either the
optical or heat will activate processing. If only
Location the heat mode is active, then only activation of
the heat mode will create an alarm.
Only with Area ‘Point’.
•Loop Point is on the loop.

Zone
Only with Area selected as ‘Point’.
• Loop Selection of a specific zone is possible.

Point
Only with Area ‘Point’.
Selection of a special point is possible.

© 2004 Tyco Safety Products PAGE 17 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.12.1.1 ALL INPUTS 3.12.1.2 SOUNDERS


Select the following settings: Select ‘Sounders’ in the Type field.
• Area: All No results will be shown on the display. The selected
• Type: Input
sounders will be activated in a configuration specified
mode.
• Loop: All
Press F5 to start the Walk Test. 3.12.1.3 POINT
The following screen shows an example for the Walk Test Select the following settings:
‘All Inputs’ option:

Walk test
• Area: Point.
MX Panel
Panel : 01 • Type: Input (appears automatically).
Wed, 09-Mar-02 Area : Point
00:01 Type : Input
Location : Loop • Location: Loop (appears automatically).
Company Name Zone : 01
Point : 01
General • Zone Required number.
Automatic : NO
Multisensor : Part • Point: Required number.

Back >> + - Start Press F5 to stare the Walk Test.


The following screen shows an example for the Walk Test of
‘Point Input’:
Selected: Number of points selected by the test. Walk test
Excluded: Number of Points not in Walk Test (ie, MX Panel
points isolated). Point I/P only
Wed, 09-Mar-02 Zone 006 A007
Been Active: Number of points which have been 00:01
activated during Walk Test Zone 06
Company Name Call alarm in room
Been Clear Number of points which were not CP820
active when starting Walk Test General
Successful: Number of tested points TestZ 001 Selected : 1
Excluded : 0
Curr.Active: Points which are currently active. Activations : 0
TestZ001 Number of zones which are in Walk Curr.Active : NO
Test. The zone is only counted if all
Back Settings End
points in a zone are in Walk Test.

• Selected 1, if point is in Walk test.


Press F3 to display selected settings. • Excluded 1, if point is not in Walk Test (ie, if
Press F5 to end Walk Test. point is isolated).
• Activations: 1, if point was activated during Walk
Test.
CAUTION:
• Curr.Active: Yes, if point is currently active.
• TestZ 001 Number of zones which are in Walk
THE FINISHING OF A WALK TEST IS ONLY Test. (The pointer is only counted if all
POSSIBLE IF ALL POINTS IN THE WALK points of a zone are in Walk Test. If one
TEST ARE INACTIVE. detector on the zone is switched off, the
counter is not decreased. In the case of
Walk Test for one point, the counter is
only decreased if that point is the only
point on the zone).

PAGE 18 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

Press F3 for a display of selected settings.


CAUTION:
Press F5 to end Walk Test.
THIS WILL ALSO CLEAR THE EVENT LOG
AND RESET THE SOFTWARE
INITIALISATION COUNT.
CAUTION:

THE FINISHING OF A WALK TEST IS ONLY a) Open the front panel of the controller.
POSSIBLE IF ALL POINTS IN THE WALK b) On the CPU, fit a link to header H2, then
TEST ARE INACTIVE. press and hold switch SW1 until the
Watchdog LED flashes.
c) Release SW1, remove the link from H2 then
press and hold switch SW1 until the
3.12.2 MAINTENANCE Watchdog LED flashes.

Press 2 from the Service menu. The following type of d) Press switch S8 on the Operator Control
screen will be displayed: Module to clear the processor fault.
The Fire Alarm Cycle Count will have been reset to zero.
Maintenance
MX Panel
Total: 000 3.12.2.2 VIEW/PRINT MAINTENANCE
Wed, 01-Mar-00 REQUEST
14:15
Company Name When selected, this option displays a list of detectors which
are near the limit of their threshold compensation limit.
General
Press 3 from the Maintenance menu. The following type of
screen will be displayed:

Maintenance
MX Panel
Back Print Total: 000
Wed, 01-Mar-00
14:15
3.12.2.1 VIEW FIRE ALARM CYCLE COUNT Company Name
When selected, the number of Alarm sequences may be General
viewed.
Press 1 from the Maintenance menu. The following type of
screen will be displayed:

Fire AL.Cycle Count Back Print


MX Panel
Press F5 to print the Maintenance Request.
Wed, 01-Mar-00 Count :
14:15
0025
Company Name
General

Back

To reset the Fire Alarm Cycle Count, proceed as follows:

© 2004 Tyco Safety Products PAGE 19 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.12.2.3 BATTERY TEST


When selected, this option allows the state of the battery Project Numbers
MX Panel
and the charger current to be displayed. Project:
Wed, 01-Mar-00 Queen El. Hospital
Press 4 from the Maintenance menu. The following type 00:01
of screen will be displayed:
Company Name Consys: V1.0
Battery Test General Created:
MX Panel 21-Jul-00 10:18
Battery State : Downloaded:
Wed, 01-Mar-00 Battery Low 27-Jul-00 08:20
14:15 Last User Update:
Battery Voltage : 26-Jul-00 09:10
Company Name 20.764 V
Back
General Charger Current :
00.500 A
3.12.2.6 SOFTWARE VERSIONS
When selected, The software versions of the following are
displayed:
Back
• Firmware
• Boot ROM
3.12.2.4 VIEW/RESET SOFTWARE
INITIALISATION COUNT
• Local I/O

When selected, the number of software initialisations (ie,


• Each Loop
operating program restarts) may be viewed/reset. • Each MPM
Press 5 from the Maintenance menu. The following type • Network board
of screen will be displayed:

Softw. Init. Count Press 7 from the Maintenance menu. The following type
MX Panel of screen will be displayed:
-Firmware 25
Wed, 01-Mar-00 Software Versions
14:15
MX Panel
Company Name -Firmware V 2.0
Wed, 01-Mar-00 -Bootrom V 1.1
General 14:15 -Local I/O V 1.0
-Loop A V 1.0
Company Name -MPM 00 V 1.1
-Net V 1.5
General

Back Reset

Press F5 to reset the Software Initialisation Count.


Back +
3.12.2.5 PROJECT NUMBERS
Press F5 key (+) for additional details of software versions.
When selected, this option allows the project and
CONSYS information to be displayed.
Press 6 from the Maintenance menu. The following type
of screen will be displayed:

PAGE 20 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

3.12.2.7 MENU POINTS


Force Device Input
When selected, this option allows any configured point MX Panel
displayed to be operated by pressing the appropriate Zone 002 B002
Wed, 01-Mar-00 1st Floor Corridoor
number button, this will toggle from OFF to ON and ON to 14:15 Sounder in 1st Flo.
OFF. SNM 800
Company Name
Press 9 from the Maintenance menu. The following type Status: Unforced
of screen will be displayed: General
1 - Force ON
2 - Force Pulse 1
Menu Points 3 - Force Pulse 2
MX Panel 4 - Force OFF
Menu Point 1: OFF
Wed, 01-Mar-00 Isolate Zone
14:15 Back
Menu Point 2: ON
Company Name Sensit.Change Select the options as required.
General Menu Point 3:
-Unconfigured-
Menu Point 4: 3.12.3.2 FORCE DEVICE INPUTS
-Unconfigured-
Press 2 from the Diagnostics menu.
Select the type of point as described in Section 3.7:
Back >>
3.12.3 DIAGNOSTICS
• Loop Point (Addressable Loop)
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required Loop and Point, then press Enter
Press 3 from the Service menu. The following type of key.
screen will be displayed:
• RBus Point (Remote Bus)
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
Diagnostics required RBus, Category and Point, then
MX Panel press Enter key.
1 - Force Dev.Outp.
Wed, 01-Mar-00
14:15
2
3
-
-
Force Dev. Inp.
Shutdown/Rstart • Local I/O Point (Field Interface Module)
4 - Fast Fault Mode Use the ‘+’, ‘-’ and ‘>>’ keys to select the
Company Name 5 - Rate of Rise required Category and Point, then press
6 - Sgl. dev. poll Enter key.
General 7 - Change Address
8 - Fast Logic Mode Force Device Input
MX Panel
Zone 002 B007
Wed, 01-Mar-00 1st Floor Corridoor
14:15 Room 117
801 H
Back Company Name
Status: Unforced
Pressing F4 (>>) will show further menu points. General
1 - Force ON
3.12.3.1 FORCE DEVICE OUTPUTS
Press 1 from the Diagnostics menu.
Select the type of point as described in Section 3.7: Back
• Loop Point (Addressable Loop) Press 1 to force the point ON.
Use the ‘+’, ‘-’ and ‘>>’ keys to select the Press 9 to unforce the point.
required Loop and Point, then press Enter
key.
• RBus Point (Remote Bus)
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required RBus, Category and Point, then
press Enter key.
• Local I/O Point (Field Interface Module)
Use the ‘+’, ‘-’ and ‘>>’ keys to select the
required Category and Point, then press
Enter key.

© 2004 Tyco Safety Products PAGE 21 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.12.3.3 SHUTDOWN/RESTART 3.12.3.5 RATE OF RISE PROCESSING


When selected, this option allows the rate of rise processing
Press 3 from the Diagnostic menu. The following screen
to be either standard processing (OFF) or extended
will be displayed:
processing before alarm is reported to the panel (ON).
Shutdown / Restart Press 5 from the Diagnostics menu. The following screen
MX Panel will be displayed:
Loop A
Wed, 01-Mar-00 Rate of Rise Proc.
14:15
MX Panel
Company Name 1 - Shutdown Status: OFF
2 - Restart Wed, 01-Mar-00
General 14:15 1 - ON
Company Name
General

Back - +
Select the loop using the ‘-’ or ‘+’ keys.
Selecting ‘1 - Shutdown’, removes the loop voltage and all Back
devices are switched off.
Selecting ‘2 - Restart’, reconnects the loop voltage. 3.12.3.6 SINGLE DEVICE POLL MODE
When selected, this option allows a single device to be
3.12.3.4 FAST FAULT MODE polled continuously.
When selected, this option allows faults to be detected in 5
seconds. Press 6 from the Diagnostics menu, select the Loop and
Point to be polled then press Enter. The following type of
Press 4 from the Diagnostics menu. The following screen screen will be displayed:
will be displayed:
Single Device Poll
Fast Fault Mode MX Panel
MX Panel Zone 002 B002
Status: Stand.Fault Wed, 01-Mar-00 South Building
Wed, 01-Mar-00 14:15 1st Floor Corridoor
14:15 Room 117
1 - Fast Fault Company Name 801 H
Company Name
General
General

Back Start
Back
Devices that are not configured in Fast Logic mode cannot Press F4 to start the device poll, F5 will change to End.
be set to the Fast Logic mode from this menu. Press F5 to end the device poll.

PAGE 22 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

3.12.3.7 CHANGE ADDRESS 3.12.4 TEST BUZZER/LEDs/DISPLAY


When selected, this option allows the address of a device to Selecting option 9 from the Main menu causes the following
be changed. to happen for approximately 2 seconds:
Press 7 from the Diagnostics menu. The following type of • The LCD Backlight to extinguish
screen will be displayed: • All LEDs to illuminate

Change Address
• Internal buzzer to pulse
MX Panel
Loop : B WARNING:
Wed, 01-Mar-00
14:15 Old Address : 017
Type : 801H BEFORE LEAVING SITE, ANY FORCED
Company Name INPUT/OUTPUT MUST BE UNFORCED.
New Address : 025 FAST FAULT, RATE OF RISE PROCESSING
General OR SINGLE DEVICE POLL MODE MUST BE
SET TO THEIR DEFAULT SETTINGS.

Any non-standard settings will display


Back New - + Enter ‘COMMISSIONING’ on the bottom line of the LCD.
Use the ‘>>’, ‘-’ and ‘+’ keys to select the options. Press
Enter when all options have been selected. 3.13 CONFIGURATION

CAUTION: Press 8 from the Main menu. The following screen will be
displayed:
DO NOT SELECT A NEW ADDRESS THAT IS
ALREADY BEING USED ON THE LOOP. Configuration
MX Panel 1 - Change Text
Wed, 01-Mar-00 2 - Insert Point
14:15 3 - Delete Point
4 - Modify Point
3.12.3.8 FAST LOGIC MODE Company Name
Press 8 from the Diagnostic menu. The following screen General 7 - Autoconfig.
will be displayed: 9 - Restart

Fast Logic Mode


MX Panel Status:
Wed, 01-Mar-00 AS CONFIGURED Back
14:15
Menu option 9 will only be displayed if an action has been
Company Name 2 - OFF carried out and saved. The relevant action will only be
carried out after the panel has been restarted.
General
After an action has been carried out, not all menu options
from the configuration menu are displayed.

Back
‘As Configured’ - means that the devices will operate as
they have been programmed in ‘MX Consys’.
‘OFF’ - regardless of how the devices have been configured
in ‘MX Consys’ the Fast Logic algorithm is not used.

© 2004 Tyco Safety Products PAGE 23 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

RESTRICTIONS ON THE USE OF THE Select the required loop and point then press Enter. The
FOLLOWING OPTIONS following type of screen will be displayed:
When using Configuration menu options 2 to 4, ALWAYS
commit configuration changes by using option 9 ‘Restart’ Point Text Modify
MX Panel Zone 255 -007 A
before leaving the panel.
Avoid ‘inactivity’ timeouts.
Wed, 01-Mar-00 Old text
14:15 Callp. alarm room
NEVER use the ‘Back’ option from the configuration menu Company Name
if option 9 ‘Restart’ is showing. New text
General
If you do not want to commit changes, by using 9 ‘Restart’,
option, turn the keyswitch to ‘OFF’ position to avoid a
timeout situation, do NOT USE the ‘Back’ option.
Configuration changes across a network are possible, but
changes to more than one panel at a time MUST NOT be
attempted within one session. When a panels configuration Back >> - + Enter
has been changed, it must be restarted using menu option 9
‘>>’ - copies the ‘old text’ to the ‘New text’ position.
‘Restart’.
‘-’ moves the cursor back one position.
Failure to comply with these restrictions may lead to
unpredictable effects or system instability ‘+’ moves the cursor forward one position.
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter.
3.13.1 CHANGE TEXT
Pressing the scroll up key allows text to be entered in
Press 1 from the Configuration menu. The following screen upper case.
will be displayed:
Pressing the scroll down key changes to lower case
Change Text text.
MX Panel 1 - Point Text The message ‘Save Data?’ appears and the functions
Wed, 01-Mar-00 2 - Zone Text change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the
14:15 3 - Sector Text text modifications to be changed.
4 - Panel Text
Company Name 5 - Info Text Selecting F4 ‘Yes’ displays the message:
General Please wait.....

then the following screen is displayed:

Back Change Text


MX Panel 1 - Point Text
3.13.1.1 POINT TEXT MODIFY
Wed, 01-Mar-00
14:15
Press 1 from the Change Text menu. The following screen Company Name
will be displayed:
General
Point Text Modify
MX Panel
Wed, 01-Mar-00 Loop : A
14:15 Point : 001
Back
Company Name
It is now possible to change the text for another Point.
General

Back >> - + Enter


PAGE 24 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

Selecting F1 ‘Back’ will display the following screen: Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter.
Configuration The message ‘Save Data?’ appears and the function change
MX Panel 1 - Change Text F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text
Wed, 01-Mar-00 modifications to be changed.
14:15
Selecting F4 ‘Yes’ displays the message:
Company Name
Please wait.....
General
9 - Restart
then the following screen is displayed:

Change Text
Back MX Panel
Wed, 01-Mar-00 2 - Zone Text
Only ‘Change Text’ and ‘Restart’ are available allowing 14:15
more points to be changed or using ‘Restart’ to allow the
changes to take effect. Company Name
General
3.13.1.2 ZONE TEXT MODIFY
Press 2 from the Configuration menu. The following screen
will be displayed:
Back
Zone Text Modify
MX Panel It is now possible to change the text for another Zone.
Wed, 01-Mar-00 Zone : 001 Selecting F1 ‘Back’ will display the following screen:
14:15
Company Name Configuration
General MX Panel 1 - Change Text
Wed, 01-Mar-00
14:15
Company Name

Back - + Enter
General
9 - Restart
Select the required and press Enter. The following type of
screen will be displayed:

Zone Text Modify Back


MX Panel Zone : 001 Only ‘Change Text’ and ‘Restart’ are available allowing
Wed, 01-Mar-00 more points to be changed or using ‘Restart’ to allow the
14:15 Old text
Zone 01 changes to take effect.
Company Name New text
General

Back >> - + Enter


‘>>’ - copies the ‘old text’ to the ‘New text’ position.
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position.

© 2004 Tyco Safety Products PAGE 25 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.13.1.3 SECTOR TEXT MODIFY


Change Text
Press 3 from the Configuration menu. The following screen MX Panel
will be displayed:
Wed, 01-Mar-00 3 - Sector Text
14:15
Sector Text Modify Company Name
MX Panel
Wed, 01-Mar-00
General
14:15 Sector : 001
Company Name
General
Back
It is now possible to change the text for another Sector.
Selecting F1 ‘Back’ will display the following screen:
Back - + Enter
Select the required sector, then press Enter. The following Configuration
type of screen will be displayed: MX Panel 1 - Change Text
Wed, 01-Mar-00
14:15
Sector Text Modify
MX Panel Sector 001 Company Name
Wed, 01-Mar-00 Old text General
14:15 Sector 01 9 - Restart
Company Name New text
General
Back

3.13.1.4 PANEL TEXT MODIFY


Back >> - + Enter
Press 4 from the Configuration menu. The following screen
‘>>’ - copies the ‘old text’ to the ‘New text’ position. will be displayed:
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position. Panel Text Modify
MX Panel Panel 00
Modify the old text or insert new text using the
alphanumeric keypad, when finished press Enter. Wed, 01-Mar-00 Old Text
14:15 ADT
The message ‘Save Data?’ appears and the function change
F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text Company Name New Text
modifications to be changed. General
Selecting F4 ‘Yes’ displays the message:
Please wait.....

then the following screen is displayed: Back >> - + Enter


Select the required Panel.
‘>>’ - copies the ‘old text’ to the ‘New text’ position.
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position.

PAGE 26 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

Modify the old text or insert new text using the


alphanumeric keypad, when finished press Enter. Info text modify
The message ‘Save Data?’ appears and the function change MX Panel
F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text Wed, 01-Mar-03
modifications to be changed. 14:15
Selecting F4 ‘Yes’ displays the message: Company Name Infotext No. : 001
Please wait..... General

then the following screen is displayed:

Change Text Back - + Enter


MX Panel
Wed, 01-Mar-00 Using the ‘+’ and ‘-’ keys select the Info Text meaasage to
14:15 modify, then pres’Enter’.
4 - Panel Text
Company Name The following type of screen will appear:
General
Info text modify
MX Panel Infotext No. : 001
Wed, 01-Mar-03 This zone is in a
14:15 Hazardous Area
Special
Back Company Name precautions
are required
General
It is now possible to change the text for another Panel.
Selecting F1 ‘Back’ will display the following screen:

Configuration
MX Panel >> +
1 - Change Text Back - Enter
Wed, 01-Mar-00
14:15 The ‘>>’ key deletes all text.
Company Name The ‘+’ key advances the cursor one space, the ‘-’ key goes
one space back.
General
9 - Restart Use the the alphanumeric keys to modify the text, when
finished, press ‘Enter’.
The following screen will be displayed:

Back
Info text modify
MX Panel Infotext No. : 001
Wed, 01-Mar-03 This zone is in a
3.13.1.5 INFO TEXT MODIFY Hazardous Area
14:15 Special
This option allows Info Text created in Consys to be Company Name precautions
modified. Press 5 from the Change Text menu. The are required
following screen will be displayed General

Save data?
Back Yes No

© 2004 Tyco Safety Products PAGE 27 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

3.13.2 INSERT POINT


Configuration
MX Panel
WARNING:
Wed, 01-Mar-00 2 - Insert Point
14:15 3 - Delete Point
ONLY SUITABLY QUALIFIED PERSONNEL 4 - Modify Point
IN INTRINSICALLY SAFE SYSTEMS MUST Company Name
BE ALLOWED TO INSERT INTRINSICALLY
SAFE EQUIPMENT. General 7 - Autoconfig.
9 - Restart

Connect the new device(s) to the addressable loop, when a


fault has been generated, ‘Accept’ the fault(s).
Press 2 from the Configuration menu. The following screen Back
will be displayed:
Press ‘9’ to complete the configuration or ‘2’ to insert
another point.
Point insert
MX Panel 3.13.3 DELETE POINT
Wed, 01-Mar-00 Remove the device(s) to be deleted from the addressable
14:15
Loop A loop,when a fault has been generated, ‘Accept’ the fault(s).
Company Name Point 001 Press 3 from the Configuration menu. The following screen
General will be displayed:

Point delete
MX Panel
Wed, 01-Mar-00
Back >> - + Enter 14:15
Loop A
Company Name Point 001
Select the Loop and Point to be inserted, then press
‘F5’. The following type of screen will be displayed: General

Point insert
MX Panel Zone 000 -001 A
Wed, 01-Mar-00
14:15 Device Type / Use:
Back >> - + Enter
Company Name 801 H Select the Loop and Point to be deleted, then press
801H - Heat
‘F5’. The following screen will be displayed:
General
Zone : 80 Point delete
MX Panel Zone 001 -001 B
Photo Sensor Device
Wed, 01-Mar-00
14:15 Device Type / Use:
Back >> <- -> Enter
Company Name
811 PH
--
Use the ‘>>’ key to move between the options, use the ‘+’ General
and ‘-’ keys to select the type of point and zone number. Loop : B
When finished, press ‘Enter’, the message ‘Please wait...’ Phys. Address: 001
Zone : 01
will be displayed then:
Delete from Config?
Back Yes No
Select ‘No’ to return to the previous screen. Press ‘Yes’ to
delete the configuration, the message ‘Please wait...’ will be
displayed then:

PAGE 28 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

When finished, press ‘Enter’, the message ‘Please wait...’


Configuration will be displayed then:
MX Panel
Wed, 01-Mar-00 2 - Insert Point
14:15 3 - Delete Point Configuration
4 - Modify Point MX Panel
Company Name 2 - Insert Point
Wed, 01-Mar-00 3 - Delete Point
General 7 - Autoconfig. 14:15 4 - Modify Point
9 - Restart Company Name
General 7 - Autoconfig.
9 - Restart
Back
Press ‘9’ to complete the configuration or ‘3’ to delete
another point. Back
Press ‘9’ to complete the configuration or ‘4’ to modify
3.13.4 MODIFY POINT another point.
Remove the device(s) to be modified and replace with the
new device(s). When faults have been generated, ‘Accept’ 3.13.5 AUTOCONFIGURATION
the fault(s)
Note: This option should only be used on a new
Press 4 from the Configuration menu. The following
system with an empty configuration and
screen will be displayed:
should not be for additions to the system.
Point modify
MX Panel
Press 7 from the Configuration menu. The following
Wed, 01-Mar-00 screen will be displayed:
14:15
Loop A
Company Name Point 001 Autoconfiguration
General MX Panel
Wed, 01-Mar-00 Panel : 01
14:15 Loop : A
Topology : Loop
Company Name Zone : 001

Back >> - + Enter General

Select the Loop and Point to be inserted, then press


‘F5’. The following type of screen will be displayed:

Point modify Back >> - + Enter


MX Panel Zone 001 -001 B Panel will only be displayed if it is part of a networked
Wed, 01-Mar-00 system.
14:15 Device Type / Use:
811 H Select the panel, Loop, Topology (Loop or Spur) and Zone
Company Name 811H - Heat (the Zone number is selected will be allocated to all
General devices), then press F5 ‘Enter’, the following screen will be
Loop : B displayed.
Phys. Address: 001
Zone : 01
Note: Autoconfiguration will not configure
Intrinsically Safe equipment or callpoints.
Back >> <- -> Enter
Use the ‘>>’ key to move between the options, when the
cursor is moved to the next option, key 3 changes to ‘-’ and
key 4 changes to ‘+’. Use the ‘+’ and ‘-’ keys to select the
type of point, loop, physical address and zone number.

© 2004 Tyco Safety Products PAGE 29 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

a) d)
LoopTest Autoconfiguration
MX Panel MX Panel Details
Loop : A
Wed, 01-Mar-00 Wed, 01-Jan-00 Point 0123456789
14:15 14:15 0 : ......u...
Please wait... 10 : ..........
Company Name Company Name 20 : .u........
30 : ...u......
General General 40 : ..........
Flt P 015 50 : ..........
60 : ..........
70 : ..........
80 : ..........
90 : .u....u...
Abort Back >>
When the ‘Loop Test’ has been completed, the following The ‘Us’ denote unconfigured devices.
type of screen will be displayed:
Pressing F2 (>>) will display further point screens.

b) Pressing F3 (Scan from step c) will display the following


type of screen:
Autoconfiguration
MX Panel
Panel : 01 e)
Wed, 01-Mar-00
14:15 Loop : A Loop Point Counters
Topology : Loop MX Panel Left / Right Scan
Company Name Zone : 001 Loop : A
Wed, 01-Jan-00 Point 0123456789
General 015 from left 14:15 0 : ......*...
015 from right 10 : ..........
015 from both Company Name 20 : .*........
30 : ...*......
General 40 : ..........
50 : ..........
60 : ..........
70 : ..........
Abort Details Enter 80 : ..*.......
90 : .*....*...
Pressing F2 (Details) will display the following type of
screen (see also Section 3.11.5, View Loop Point Counters): Back >>

c) The ‘stars’ denote devices that will be configured.


Pressing F2 (>>) will display further point screens.
Autoconfiguration
MX Panel Pressing F5 (Enter from step b) will display the following
Counter type of screen:
Wed, 01-Mar-00 Loop : A
14:15 A T T E N T I O N f)
LoopScan
Company Name Configured : 000
MX Panel
General Unconfigured: 015 Wed, 01-Jan-00
14:15
Please wait...
Company Name
General
Back Details Scan
Pressing F2 (Details) will display the following type of
screen:
Abort

PAGE 30 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

When the ‘Loop Scan’ has been completed, the following Pressing F5 (Save) from step f) will display the following
type of screen will be displayed: type of screen:
i)
Result
MX Panel Result
Wed, 01-Mar-00 MX Panel
14:15
Wed, 01-Mar-00
Company Name no errors 14:15
015 points added no errors
General 000 points unchanged Company Name
000 pnt. with error 015 points added
General 000 points unchanged
000 pnt. with error

Save data?
Abort Details Save
Yes No

Pressing F2 (Details) will display the following screen: Pressing F4 (Yes) will save the configuration. When the
save is complete, the controller will re-initialise.
g)
Result
MX Panel
View details of
Wed, 01-Mar-00
14:15 1 - Added point
Company Name
General
Flt P 015

Back
Pressing ‘1’ from the alpha numeric keypad will display the
following type of screen:
h)
Result
MX Panel
Added Points
Wed, 01-Mar-00
14:15 Panel : 01
Loop : A
Company Name Zone : 001
Point : 006
General Mode : 2
Device Type
RIM800
001/015

Back << >> >>|


‘<<‘, ‘>>’ and ‘>>|’ navigate through the points.

© 2004 Tyco Safety Products PAGE 31 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

4. DEFAULT SYSTEM POINTS P24 BAD PACKET CHAN H


4.1 LOCAL I/0 (Field Interface Module/ P25 FIM BAD PACKET
CPU) P26 FIM FAULT
P27 MP ROM FAIL
REAL
P28 MP SYSTEM RAM
R01 SOUNDER 1
P29 MP CLOCK
R02 SOUNDER 2
P30 MONITOR POINT
R03 ALARM RELAY
P31 BATTERY LOW
R04 FAULT RELAY
P32 RBUS CIRCUIT FAULT
R04 FIM PSU MONITOR
P33 STACK OVERFLOW
R06 SUPERVISED INPUT
P34 SYSTEM HEAP ERROR
R07 UNSUPERVISED INPUT
P35 UNSUPERVISED PANEL
R08 EMERGENCY ALARM I/P
P36 RUI CONNECTION
R09 MP EARTH FAULT IP
P39 RBUS FIRMWARE
R10 BATTERY FAULT I/P
P40 LOCAL I/O F/W
R11 MAINS SUPPLY I/P
P42 DELAY POOL FULL
R12 CHARGER FAULT I/P
P43 WALKTEST SOUNDERS
R14 I/O 2
P44 INHIBIT SOUND LED
R15 I/O 1
P45 COMMISSIONING
R16 24V RESET
P46 DOWNLOAD REQUIRED
P47 TEST EQUIPMENT
PSEUDO
P01 DATA PACKET ERROR
4.2 RBUS
P02 FIFO FULL
REAL
P03 EA FIFO FULL
P04 LNET DATA PATH FLT RBxxR01 KEY SWITCH
P05 LNET MODULE FLT RBxxR06 SILENCE BUZZ BUTTON
P06 CONFIGURATION STORE RBxxR07 SILENCE/RESOUND BUTTON
P07 SLAVE BUSY LOCAL I/O RBxxR08 RESET BUTTON
P08 SLAVE BUSY CHAN A RBxxR09 DAY MODE BUTTON
P09 SLAVE BUSY CHAN B RBxxR10 INVESTIGATE BUTTON
P10 SLAVE BUSY CHAN C RBxxR12 EVACUATE BUTTON
P11 SLAVE BUSY CHAN D RBxxR14 BUZZER
P12 SLAVE BUSY CHAN E RBxxR15 FAULT LED
P13 SLAVE BUSY CHAN F RBxxR16 BACKLIGHT INHIBIT
P14 SLAVE BUSY CHAN G
P15 SLAVE BUSY CHAN H PSEUDO
P16 BAD PACKET LOCAL I/O RBxxR01 MPIM DISPLAY FAIL
P17 BAD PACKET CHAN A RBxxR02 MPIM ROM FAIL
P18 BAD PACKET CHAN B RBxxR03 MPIM RAM FAIL
P19 BAD PACKET CHAN C RBxxR06 BAD PACKET
P20 BAD PACKET CHAN D RBxxR07 MULTICAST SEQ ERR
P21 BAD PACKET CHAN E RBxxR08 CHAR CHIP CSUM ERR
P22 BAD PACKET CHAN F
P23 BAD PACKET CHAN G

PAGE 32 of 34
EQUIPMENT: MX
PUBLICATION:
17A-04-S
ISSUE No. & DATE:
5 11/04

XBUS
RBxxX1 - 40 ZONAL x ALARM
RBxxX41 - 80 ZONAL x FAULT
RBxxX81 SIGNALLING ACTIVE
RBxxX82 SIGNALLING FAULT
RBxxX83 SIGNALLING DISABLED
RBxxX84 DAY MODE ACTIVE
RBxxX85 SOUNDERS ACTIVE
RBxxX86 SOUNDERS FAULT
RBxxX87 SOUNDERS DISABLED
RBxxX88 SPARE
RBxxX89 PRE-ALARM O/P
RBxxX90 SPARE
RBxxX91 MAINS FAULT O/P
RBxxX92 LAMP TEST SPECIAL
RBxxX93 FIRE O/P
RBxxX94 FAULT O/P
RBxxX95 DISABLED O/P
RBxxX96 TEST O/P

xx = MPM800 address

4.3 ADDRESSABLE LOOP


PSEUDO
P01 LOOP FAULT

© 2004 Tyco Safety Products PAGE 33 of 34


Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB
MX
17A-04-S
5 11/04

5. DEVICE IDENTIFICATION AND


UNIVERSAL ADDRESSES

1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9
Z o n e z z z Stand Alone
Z o n e p p . z z z Network
S e c t s s s Stand Alone
S e c t p p . s s s Network

1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9
l n n n Loop Point Standard
l n n n . e e Loop Point Extended
R B r r c n n RBus Points
c n n Main Processor Points
N E T n n n Network Mode
R B u s n n RBus Mode
C O M 1 Device on COM1
C O M 2 Device on COM2
T L I c n n TLI Event

Where: pp = Panel Number


zzz = Zone Number
sss = Sector Number
rr = RBus Node as Source
l = Loop Letter (‘A’, ‘B’, ‘C’, ‘D’, ‘E’, ‘F’, ‘G’ or ‘H’)
c = Category (‘Xbus’, ‘Real’, ‘Pseudo’, ‘Timer’ or ‘Menu’)
nn = Digital Point Number or RBus Node Number (null if don’t care)
nnn = Analogue Point Number or Net Node Number (null if don’t care)
ee = Extended Point Number (null if don’t care)

Examples of Device Identification and Universal Addresses


Z o n e 0 0 1 A 0 0 2
Z o n e 0 7 . 0 0 3 B 0 1 8
S e c t 0 1 5 A 1 0 1 . 0 5
S e c t 1 3 . 1 1 2 C 1 2 3 . 1 2
Z o n e 0 1 . 0 0 1 R B 0 1 X 0 1
Z o n e 0 4 . 1 2 3 R 9 9
Z o n e 0 3 . 1 4 5 A 1 2 3
S e c t 1 7 . 2 3 3 C O M 1
S e c t 2 3 . 0 0 1 T L I P 1 5
S e c t 0 1 . 1 0 0 R B u s 0 2
Z o n e 0 0 2 C 0 2 2
Z o n e 0 1 3 B 0 1 2 . 1 5

JM/jm
30th November 2004

PAGE 34 of 34

You might also like