EJX910A and EJX930A
Multivariable Transmitter
HART Communication Type

IM 01C25R02-01E

IM 01C25R02-01E
7th Edition
i

EJX910A and EJX930A


Multivariable Transmitter
HART Communication Type
IM 01C25R02-01E 7th Edition

Contents
1. Introduction................................................................................................ 1-1
 Regarding This Manual..................................................................................... 1-1
1.1 Safe Use of This Product ................................................................................. 1-2
1.2 Warranty.............................................................................................................. 1-2
1.3 ATEX Documentation........................................................................................ 1-3
2. Connection................................................................................................. 2-1
2.1 Integral Indicator Display When Powering On............................................... 2-1
2.2 HART Protocol Revision................................................................................... 2-1
2.3 Device Description (DD) on a Configuration Tool
and Transmitter Device Revision..................................................................... 2-2
2.4 Set the parameters using DTM......................................................................... 2-3
2.5 Interconnection Between DPharp and the HART Configuration Tool......... 2-3
2.6 Power Supply Voltage and Load Resistance.................................................. 2-4
3. Parameter Setting...................................................................................... 3-1
3.1 Menu Tree........................................................................................................... 3-1
3.1.1 For DD (HART 5/HART 7) and DTM (HART 7).................................. 3-1
3.1.2 For DTM (HART 5).............................................................................. 3-9
3.2 Basic Setup....................................................................................................... 3-13
3.2.1 Tag and Device Information.............................................................. 3-13
3.2.2 Process Variable Setup.................................................................... 3-13
3.2.3 Measuring Range ............................................................................ 3-14
3.2.4 Units.................................................................................................. 3-15
3.2.5 Damping Time Constant Setup......................................................... 3-15
3.2.6 Differential Pressure Signal Low Cut Mode Setup........................... 3-16
3.2.7 Impulse Line Connection Orientation Setup..................................... 3-16
3.3 Detailed Setup.................................................................................................. 3-17
3.3.1 Analog Output Signal Adjustable Range.......................................... 3-17
3.3.2 Static Pressure Setup....................................................................... 3-17
3.3.3 External Temperature Fixation Mode................................................ 3-17
3.3.4 Integral Indicator Scale Setup........................................................... 3-17
3.3.5 Total Flow Setup............................................................................... 3-19
3.3.6 Sensor Trim....................................................................................... 3-20

7th Edition: June 2014 (KP) IM 01C25R02-01E


All Rights Reserved, Copyright © 2005, Yokogawa Electric Corporation
ii
3.3.7 Trim Analog Output........................................................................... 3-22
3.3.8 External Switch Mode....................................................................... 3-22
3.3.9 CPU Failure Burnout Direction and Hardware Write Protect........... 3-23
3.3.10 Software Write Protection................................................................. 3-23
3.3.11 Alarm................................................................................................. 3-23
3.3.12 Status Output and Pulse Output....................................................... 3-24
3.3.13 Test Output, Simulation, and Squawk............................................... 3-26
3.3.14 Basic Flow Calculation (Basic mode)............................................... 3-29
3.3.15 Burst Mode........................................................................................ 3-32
3.3.15.1 In the case of using HART 5............................................ 3-32
3.3.15.2 In the case of using HART 7............................................ 3-32
3.3.16 Multidrop Mode................................................................................. 3-37
3.3.16.1 In the case of using HART 5............................................ 3-37
3.3.16.2 In the case of using HART 7............................................ 3-38
3.3.17 Switching HART Protocol Revision.................................................. 3-38
4. Diagnostics................................................................................................ 4-1
4.1 Self-Diagnostics................................................................................................. 4-1
4.1.1 Identify Problems by Using the HART Configuration Tool.................. 4-1
4.1.2 Checking with Integral Indicator.......................................................... 4-2
4.1.3 Status information available for HART 7............................................. 4-2
4.2 Advanced Diagnostics...................................................................................... 4-3
4.2.1 Multi-sensing Process Monitoring....................................................... 4-3
4.2.2 Impulse Line Blockage Detection (ILBD)............................................ 4-3
4.2.2.1 Blockage Detection............................................................ 4-6
4.2.2.2 Combination of Reference Result
and Blockage Detection..................................................... 4-8
4.2.2.3 Operation Parameters....................................................... 4-9
4.2.2.4 Operating Procedure....................................................... 4-11
4.2.2.5 Alarm and Alert Setting.................................................... 4-12
4.2.2.6 Condition Check.............................................................. 4-14
4.2.2.7 Obtain Reference Values................................................. 4-15
4.2.2.8 Capability Test of Blockage Detection Operation............ 4-16
4.2.2.9 Start ILBD Operation....................................................... 4-16
4.2.2.10 Tuning.............................................................................. 4-17
4.2.2.11 Reset of Reference Value................................................ 4-18
4.2.2.12 ILBD Parameter List........................................................ 4-19
4.2.3 Heat Trace Monitoring...................................................................... 4-21
4.2.3.1 Flg Temp Coef Setting..................................................... 4-21
4.2.3.2 Out of Temperature Measurement Range....................... 4-22
4.2.3.3 Parameter Lists for Heat Trace Monitoring...................... 4-22
4.3 Alarms and Countermeasures....................................................................... 4-23
5. Parameter Summary................................................................................. 5-1

IM 01C25R02-01E
iii
Appendix 1. Safety Instrumented Systems Installation.............................A1-1
A1.1 Scope and Purpose........................................................................................ A1-1
A1.2 Using the EJX for an SIS Application........................................................... A1-1
A1.2.1 Safety Accuracy................................................................................A1-1
A1.2.2 Diagnostic Response Time...............................................................A1-1
A1.2.3 Setup.................................................................................................A1-1
A1.2.4 Required Parameter Settings...........................................................A1-1
A1.2.5 Proof Testing.....................................................................................A1-1
A1.2.6 Repair and Replacement..................................................................A1-2
A1.2.7 Startup Time......................................................................................A1-2
A1.2.8 Firmware Update..............................................................................A1-2
A1.2.9 Reliability Data..................................................................................A1-2
A1.2.10 Lifetime Limits...................................................................................A1-2
A1.2.11 Environmental Limits........................................................................A1-2
A1.2.12 Application Limits..............................................................................A1-2
A1.3 Definitions and Abbreviations....................................................................... A1-3
A1.3.1 Definitions.........................................................................................A1-3
A1.3.2 Abbreviations....................................................................................A1-3
Appendix 2. ILBD Check List.........................................................................A2-1
Revision Information

IM 01C25R02-01E
<1. Introduction> 1-1

1. Introduction
Thank you for purchasing the DPharp EJX • If any question arises or errors are found, or if
multivariable transmitter. any information is missing from this manual,
EJX multivariable transmitters are precisely please inform the nearest Yokogawa sales
calibrated at the factory before shipment. office.
To ensure both safety and efficiency, please • The specifications covered by this manual are
read this manual carefully before operating the limited to those for the standard type under the
instrument. specified model number break-down and do not
This manual describes the HART protocol cover custom-made instruments.
communication functions of the EJX multivariable
• Please note that changes in the specifications,
transmitter and explains how to set the parameters
construction, or component parts of the
for EJX multivariable transmitters using the HART
instrument may not immediately be reflected
configuration tool.
in this manual at the time of change, provided
For information on the installation, wiring, and
that postponement of revisions will not cause
maintenance of EJX multivariable transmitters,
difficulty to the user from a functional or
please refer to the user’s manual.
performance standpoint.
For information on the flow setup of EJX
multivariable transmitters, please refer to the user’s • The following safety symbols are used in this
manual and FSA120 FieldMate FlowNavigator on- manual:
line manual.
EJX910A / EJX930A IM 01C25R01-01E WARNING
FSA110 / 111 FieldMate Versatile IM 01R01A01-01E
Device Management Wizard Indicates a potentially hazardous situation which,
FSA120 FieldMate FlowNavigator IM 01C25R51-01E if not avoided, could result in death or serious
injury.

WARNING
When using the EJX in a Safety Instrumented CAUTION
Systems (SIS) application, refer to Appendix 1
in this manual. The instructions and procedures Indicates a potentially hazardous situation which,
in the appendix must be strictly followed in order if not avoided, may result in minor or moderate
to maintain the designed safety integrity of the injury. It may also be used to alert against unsafe
transmitter. practices.

IMPORTANT
 Regarding This Manual
Indicates that operating the hardware or software
• This manual should be provided to the end in this manner may damage it or lead to system
user. failure.
• The contents of this manual are subject to
change without prior notice.
• All rights reserved. No part of this manual may NOTE
be reproduced in any form without Yokogawa’s
Draws attention to information essential for
written permission.
understanding the operation and features.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited
to, implied warranty of merchantability and
fitness for a particular purpose.

IM 01C25R02-01E
<1. Introduction> 1-2
1.1 Safe Use of This Product (e) Modification
• Yokogawa will not be liable for malfunctions or
For the safety of the operator and to protect the
damage resulting from any modification made
instrument and the system, please be sure to follow
to this instrument by the customer.
this manual’s safety instructions when handling this
instrument. If these instructions are not heeded,
the protection provided by this instrument may be 1.2 Warranty
impaired. In this case, Yokogawa cannot guarantee • The warranty shall cover the period noted on
that the instrument can be safely operated. Please the quotation presented to the purchaser at the
pay special attention to the following points: time of purchase. Problems occurring during
the warranty period shall basically be repaired
(a) Installation
free of charge.
• This instrument may only be installed by an
• If any problems are experienced with this
engineer or technician who has an expert
instrument, the customer should contact the
knowledge of this device. Operators are not
Yokogawa representative from which this
allowed to carry out installation unless they
instrument was purchased or the nearest
meet this condition.
Yokogawa office.
• With high process temperatures, care must
• If a problem arises with this instrument,
be taken not to burn yourself by touching the
please inform us of the nature of the problem
instrument or its casing.
and the circumstances under which it
• Never loosen the process connector nuts when the
developed, including the model specification
instrument is installed in a process. This can lead
and serial number. Any diagrams, data and
to a sudden, explosive release of process fluids.
other information you can include in your
• When draining condensate from the pressure communication will also be helpful.
detector section, take appropriate precautions to
• The party responsible for the cost of fixing the
prevent the inhalation of harmful vapors and the
problem shall be determined by Yokogawa
contact of toxic process fluids with the skin or eyes.
following an investigation conducted by Yokogawa.
• When removing the instrument from a
• The purchaser shall bear the responsibility for
hazardous process, avoid contact with the
repair costs, even during the warranty period, if
process fluid and the interior of the meter.
the malfunction is due to:
• All installation shall comply with local installation
requirements and the local electrical code. - Improper and/or inadequate maintenance by
(b) Wiring the purchaser.
- Malfunction or damage due to a failure
• The instrument must be installed by an engineer
to handle, use, or store the instrument in
or technician who has an expert knowledge of
accordance with the design specifications.
this instrument. Operators are not permitted to
- Use of the product in question in a location
carry out wiring unless they meet this condition.
not conforming to the standards specified by
• Before connecting the power cables, please
Yokogawa, or due to improper maintenance
confirm that there is no current flowing through
of the installation location.
the cables and that the power supply to the
- Failure or damage due to modification or
instrument is switched off.
repair by any party except Yokogawa or an
(c) Operation approved representative of Yokogawa.
• Wait 10 min. after the power is turned off before - Malfunction or damage from improper
opening the covers. relocation of the product in question after
(d) Maintenance delivery.
- Reason of force majeure such as fires,
• Please carry out only the maintenance
earthquakes, storms/floods, thunder/
procedures described in this manual. If you
lightening, or other natural disasters, or
require further assistance, please contact the
disturbances, riots, warfare, or radioactive
nearest Yokogawa office.
contamination.
• Care should be taken to prevent the build up of dust
or other materials on the display glass and the name
plate. To clean these surfaces, use a soft, dry cloth.

IM 01C25R02-01E
<1. Introduction> 1-3
1.3 ATEX Documentation
This is only applicable to the countries in European Union.

GB SK

CZ
DK

I LT

E LV

EST
NL

PL

SF

SLO
P

BG

RO

S
M

GR

IM 01C25R02-01E
<2. Connection> 2-1

2. Connection
2.1 Integral Indicator Display
When Powering On NOTE
For models with the integral indicator code “D”, the LCD display can be set to all segments display
display shows all segments in the LCD and then only.
changes to the displays shown below sequentially. • Procedure to call up the display
[Root Menu] (Refer to subsection
DD (HART 5/7)
3.1.1) → Detailed setup → Display
DTM (HART 7)
condition → Chg power on info
Configuration → Local Display
DTM (HART 5)
→ Chg power on info
Show all segments display, Model
On name, Communication Protocol, and
Device Revision when powering on.
All segments display Model name (3 sec.)
Show all segments display when
Off
powering on.

2.2 HART Protocol Revision


For the models with the output signal code “-J”,
Communication Protocol (3 sec.) Device Revision (3 sec.) HART protocol revision 5 or 7 is selectable. The
F0200.ai
protocol revision is set as specified in the order.
Either “5” or “7” is displayed on the communication
The typical function which is available by HART
protocol display as HART protocol revision followed
protocol revision 7 is listed as follows. Refer to
by device revision number on the device revision
HART 7 description in this document or HART 7 mark
display.
for detail.
• Long Tag Supporting Up to 32 Characters
NOTE Long tag secures a better asset management
with abundant digits in its software.
For output signal code “E”, this function is
• Enhanced Burst Mode and Event Notification
available for software revision 3.01 or later.
Advanced burst mode includes the variety
Software revision can be checked by the
of transmission setting by specifying burst
following procedure.
variables, update period, and message trigger
[Root Menu](Refer to subsection
DD(HART 5)
3.1.1) → Review → Software rev
mode, and event notification function gives
you alert signal based on the status change in
Configuration → Device information1
DTM(HART 5) preset values and self-diagnosis.
→ Software rev
• Squawk
Identifying the transmitter by displaying the
particular pattern on LCD
NOTE • Multidrop Communication
In this User’s Manual, HART protocol revision Up to 63 transmitters can be connected. An
5 and 7 are described as HART 5 and HART 7 analog signal output available for one device in
respectively. a loop.
How to confirm protocol revision is shown below.
There are three ways to confirm the protocol
revision set to the transmitter.

IM 01C25R02-01E
<2. Connection> 2-2
(1) Confirmation by the name plate
The HART protocol revision is shown by the last NOTE
number of the serial number.
Refer to Figure 2.1. HART 7 communication is supported by
CAL
FieldMate R2.02 or later.
RNG
MODEL STYLE
SUFFIX

NOTE
SUPPLY V DC
OUTPUT mA DC NO.
MWP
Made in Japan : Refer to USER'S MANUAL.
TOKYO 180-8750 JAPAN

XXX - - - XX  When the output signal code of EJX multivariable


5 : HART 5 transmitter is “-J”, HART protocol revision can be
7 : HART 7 changed. Refer to subsection 3.3.17 about the
F0201.ai procedure of the revision change of HART 5 and
HART 7.
Figure 2.1 Name Plate

(2) Confirmation by using integral indicator (When


the integral indicator code is “D”) 2.3 Device Description (DD) on
Refer to section 2.1. a Configuration Tool and
(3) Confirmation by using HART configuration tool
Follow the procedure below. Transmitter Device Revision
1) Connect the configuration tool to the Before using a HART configuration tool, confirm
transmitter. that the DD for the transmitter is installed in the
2)-1 When using DD(HART 5/HART 7) or configuration tool.
DTM(HART 7) configuration tool.
About the DD, use the device type, device revision
Select the “Root Menu” (Refer to
and DD Revision shown in the Table 2.1.
subsection 3.1.1)
Call up the “Review” display. Table 2.1 HART Protocol Revision, Device
2)-2 When using DTM(HART 5) configuration Revision and DD Revision
tool.
HART EJX Multivariable Transmitter
Call up “HART” display.
Protocol
Configuration → HART Revision (*1) Model Device Device DD
3) HART protocol revision is displayed on the Name Type Revision Revision
“Universal rev” column. EJX910A EJX-MV 2
5 2
EJX930A (0x54) or later
EJX910A EJX-MV 1
IMPORTANT 7
EJX930A (0x3754)
10
or later

Protocol revision supported by HART *1: When the output signal code is “–E”, only “5” is available.
configuration tool must be the same or higher
The device revision of the transmitter and DD can
than that of the EJX multivariable transmitter.
be confirmed as shown below.
Protcol revision
supported by HART If the correct DD is not installed in the configuration
configuration tool tool, download it from the official web site of HART
5 7 Communication Foundation.
Protocol revision of 5  
EJX multivariable
transmitter 7 × 
 : Communication OK

× : Communication NG

IM 01C25R02-01E
<2. Connection> 2-3
(1) Confirming the device revision of the transmitter
● Confirmation by using integral indicator NOTE
(When the integral indicator code is “D”)
The DTM revision can be confirmed by “DTM
Refer to the section 2.1
setup”.
● Confirmation by using HART configuration
Device Files is a Media included in FieldMate.
tool
The user registration site provides Device Files
Follow the procedure below.
with the latest update programs.
1) Connect the configuration tool to the
(URL: https://voc.yokogawa.co.jp/PMK/)
transmitter.
In case update, following operation by “DTM
2) Select the “Root Menu” (Refer to
setup” is required.
subsection 3.1.1)
• Update DTM catalog
Call up the “Review” display.
• Assign corresponding DTM to the device
3) The device revision is displayed on the
(refer to Table 2.2)
“Fld dev rev” column.
Refer to FieldMate Instruction Manual for detail.
(2) Confirming the device revision of the
configuration tool
Confirm the device revision from the installed
DD file name according to the procedure 2.5 Interconnection Between
provided for the configuration tool. DPharp and the HART
The first two digits indicate the device revision
and the next two digits indicate the DD revision.
Configuration Tool
The HART configuration tool can interface with the
0 a 0 1. X X X
transmitter from the control room, the transmitter
DD revision
site, or any other wiring termination point in the
Device revision
loop, provided there is a minimum of 250 Ω
between the connection and the power supply. To
communicate, it must be connected in parallel with
NOTE the transmitter; the connections are non-polarized.
Figure 2.2 illustrates the wiring connections for
Device revision of DD file is given in hexadecimal
direct interface at the transmitter site for the
DPharp. The HART configuration tool can be used
for remote access from any terminal strip as well.
2.4 Set the parameters using
DTM Control room
Relaying Terminal
When configure the parameters using FieldMate, terminals board Distributor
DPharp
use the DTM (Device Type Manager) shown in the
Table 2.2.
Table 2.2 HART Protocol Revision and DTM USB
FieldMate
HART DTM EJX multivariable transmitters Modem
Protocol
Revision Model Device Device
Name Revision USB
Name Type Revision

EJX910 1.4.160.27*1 EJX910A EJX910 PC/FieldMate


5 2
V2.1 or later EJX930A (0x54)
HART configuration tool F0202.ai
EJX910 EJX910_
3.3.0.112*2 EJX910A
7 HART 7 EXP 10 Figure 2.2 Connecting the HART Configuration
or later EJX930A
DTM (0x3754) Tool
*1: The DTM corresponding to this revision is included in
Yokogawa DTM Library HART 2011-3/Device Files R3.03.00
*2: The DTM corresponding to this revision is included in
Yokogawa Device DTM Library 2.0/Device Files R3.03.00

IM 01C25R02-01E
<2. Connection> 2-4
2.6 Power Supply Voltage and
Load Resistance
When configuring the loop, make sure that the
external load resistance is within the range in the
figure below.
(Note) With an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.

600

External E–10.5
R=
load 0.0244 Communication
resistance applicable range
R (Ω)

250

0 10.5 16.6 25.2 42


Power supply voltage E (V DC)
F0203.ai

Figure 2.3 Relationship between Power Supply


Voltage and External Load Resistance

IM 01C25R02-01E
<3. Parameter Setting> 3-1

3. Parameter Setting
3.1 Menu Tree
The menu tree is different in DD(HART 5/HART 7)/DTM(HART 7) and DTM(HART 5).
See the menu tree corresponding to the configuration tool.

3.1.1 For DD (HART 5/HART 7) and DTM (HART 7)

■ DD (HART 5/HART 7)
Root Menu
• Device setup • Process variables A
• PV • Diag/Service B
• PV AO • Basic setup C
• PV LRV • Detailed setup D, E
• PV URV • Review

■ DTM (HART 7)
Root Menu • Basic setup C
• Device Configuration - Configure/Setup • Detailed setup D, E
• Review
• Diagnostic • Diag/Service B
• Process Variable • Process variables A
F0301-01.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-2
A HART 5 : HART 5 only
• Process variables • PV HART 7 : HART 7 only
• PV % (DD)
% Range (DTM) • Flow
• PV AO (DD) • Pres
Loop Current (DTM) • SP
• Engr Disp • ET
• Engr exp • Total Flow
• Engr Unit • Cap temp
• View fld dev vars • Amp temp • Flow
• PV is
• Change PV Assgn • Pres
• PV • SP
• Output vars • PV
• PV Unit • ET
• PV Data Quality HART 7
• PV Limit Status HART 7

• SV is • Flow
• Change SV Assgn • Pres
• SV • SP
• SV
• SV Unit • ET
• SV Data Quality HART 7 • Total Flow
• SV Limit Status HART 7

• TV is • Flow
• Change TV Assgn • Pres
• TV • SP
• TV
• TV Unit • ET
• TV Data Quality HART 7 • Total Flow
• TV Limit Status HART 7

• 4V(QV) is • Flow
• Change 4V(QV) • Pres
Assgn • SP
• 4V HART 5
• ET
• 4V(QV)
• QV HART 7
• Total Flow
• 4V(QV) Unit
• QV Data Quality HART 7
• QV Limit Status HART 7

• Flow
• Device Variables • Flow Data Quality
and Status HART 7 • Flow Limit Status
• Pres
• Pres Data Quality
• Pres Limit Status
• SP
• SP Data Quality
• SP Limit Status
• ET
• ET Data Quality
• ET Limit Status
• Total Flow
• Total Flow Data Quality
• Total Flow Limit Status
• % Range
• % Range Data Quality
• % Range Limit Status
• Loop Current
• Loop Current Data Quality
• Loop Current Limit Status

F0301-02.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-3
B HART 7 : HART 7 only

• Diag/Service • Status • Status group 1


• Status group 2
• Status group 3
• Status group 4
• Status group 5
• Status group 6
• Status group 7
• Status group 8
• Status group 9
• Status group 10
• Status group 11 HART 7
• Device status HART 7
• Ext dev status HART 7
• Cfg chng count HART 7
• Reset Cfg chng flag HART 7
• Time Stamp HART 7 • Loop test
• Self test
• Test • Master test
• Squawk HART 7
• Calibration • Keypad input • PV is • Simulate HART 7
• Change PV Assgn
• PV Unit
• PV LRV
• PV URV
• PV Damp

• Analog output trim • D/A trim


• Scaled D/A trim
• Clear D/A trim

• Pres sensor trim • Pres trim


• Clear P trim

• SP sensor trim • SP trim


• Clear SP trim

• ET sensor trim • ET trim


• Clear ET trim

• Trim info. • Trim Who


• Trim Date
• Trim Loc
• Trim Desc

• Diag Parameters See B1


(next page)

• Error log • Error log view


• Test Auto Release • Error log Clear
Time
F0301-03.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-4
• Ratio fDP Status
• Ratio fDP
• Ratio fSPl Status
• Ratio fSPl
• Ratio fSPh Status
• Ratio fSPh
• BlkF Status
• BlkF
• DP Avg Status
• DP Avg
• CRatio fDP Status
• Diag Mode • CRatio fDP
• Diag Applicable • NRatio fDP Status
• Diag Variables • NRatio fDP

• Diag Reference • Diag Description


• Ref fDP Status
• Ref fDP
• Ref fSPl Status
• Status • Ref fSPl
• Ref fSPh Status
B1 • Ref fSPh
• Ref BlkF Status
• Diag Parameters • Diag Error
• Ref BlkF
• Ref DP Avg Status
• Diag Option
• Ref DP Avg
• ILBD Parameters
• Fluct Variables • fDP Status
• fDP
• fSPl Status
• fSPl
• fSPh Status
• Set Diag Mode • fSPh
• Configuration • Diag Period
• Diag Lim • Lim fDPmax
• Lim fDPmin
• Lim fSPlmax
• Lim fSPlmin
• Lim fSPhmax
• Lim fSPhmin
• Lim BlkFmax
• Lim BlkFmin
• Lim DPAvgmax
• Lim DPAvgmin

• Diag Reference • Diag Description


• Diag Supp Count • Ref fDP
• Ref fSPl
• Ref fSPh
• Ref BlkF
• Ref DP Avg

• Diag Ref Lim • Ref Lim fDPmin


• Diag DPComp • Ref Lim fSPmin
• Ref Lim BlkFmax
• Cap temp
• Status • Amp temp
• Flg temp
• HT Parameters
• Flg temp Coef
• Configuration • Flg temp Hi Alert Val
• Flg temp Lim
• Flg temp Lo Alert Val
• Diag Out Option
• Diag Output
• Diag Fixed Out Val

F0301-04.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-5
C HART 7 : HART 7 only

• Basic setup • Tag

• Long tag HART 7

• Units • Pres Unit


• SP Unit
• ET Unit
• Flow Unit
• Total Flow Unit

• Keypad input • PV is
• Change PV Assgn
• PV Unit
• PV LRV
• PV URV
• PV Damp

• Device infomation • Date


• Descriptor
• Message
• Write Protect
• Model

• Others • Low cut


• Low cut mode
• H/L Swap
F0301-05.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-6

D HART 5 : HART 5 only


• Detailed setup • Sensors • Pres HART 7 : HART 7 only
• SP
• Review • Cap temp • Pres LRV
• Amp temp • Flow LRV • Pres URV
• ET • Flow URV • Pres Unit
• Flow Unit • Pres LSL
• Signal condition • Flow Setup • Flow Damp • Pres USL
• Pres Min span
• DP Setup (DD) • Pres Damp
Pres Setup (DTM) • Low Cut (DTM)
• Low Cut mode(DTM)
• H/L Swap (DTM)

• SP Setup • SP LRV
• SP URV
• SP Unit
• SP LSL
• SP USL
• ET Setup • ET LRV • SP Min span
• ET URV • SP Damp
• ET Unit • A/G Select
• ET LSL • SP H/L Select
• ET USL • Atm. Pres Value
• ET Min span • Auto Atm. Pres
• ET Damp
• Fixed ET • ET Fixed
• Fixed ET Val
• Total Flow • Total Flow
• Total Flow Unit
• Pulse rate
• Freq at 100%
• Total Flow Mode
• Config User Unit • Cvt Val
• Set Base Unit
• Others (DD) • Low cut • Modify Unit
• Low cut mode
• H/L Swap

• Output condition • Process variables • PV


• PV % (DD)
% Range (DTM)
• Analog output • Loop test • PV AO (DD)
• Loop current mode Loop Current (DTM)
HART 7
• Engr Disp
• D/A trim • Engr exp
See D1 • Scaled D/A trim • Engr Unit
(next page) • Clear D/A trim • Digital Output
• AO alm typ
• Display condition • Channel flags HART 7
• Device information • Auto recover
• Test Key • AO lower limit
• Simulation HART 5 See E • AO upper limit
• Flow Simulation
HART 7

• Basic Flow Calc


F0301-06.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-7
D1 HART 5 : HART 5 only
HART 7 : HART 7 only
• Poll addr • Burst Message 1 • Burst Mode
• Loop current mode • Burst Command
HART 7 • Burst Device • Burst Variable Code
• Num req preams Variables
• num resp preams • Set Burst Trigger
HART 7 • Set Burst Period
• HART output
• Burst Condition • Burst Msg Trigger
HART 7 Mode
• Burst mode HART 5 • Burst Trigger Level
• Burst option HART 5 • Update Period
• Burst Xmtr Vals • Max Update Period
HART 5

• Burst Message 2 Same as above • Device Status Mask


• Burst Message 3 Same as above • Status group 1 Mask
to 11 Mask
• Event Notification • Event Notification • Ext dev status Mask
Control • Device Diagnostic
• Flow Update time • Event Mask Status 0 Mask
period • Set Event • Device Diagnostic
• Pres Update time Notification Timing Status 1 Mask
period • Event Notification • AO saturated Mask
• SP Update time Retry Time • AO fixed Mask
period • Max Update Time
• ET Update time • Event Debounce
period Interval • Event Status
• Total Flow Update • Time First Unack
time period • Knowledge (DD) Event Triggered

Knowledge (DTM) • Acknowledge Event


• Process Alerts • Pres Alert • Pres Alert Mode
Notificatoin
• Pres Hi Alert (Val)
• Event Status
• Pres Lo Alert (Val)
• Event Number
• Time First Unack
• SP Alert • SP Alert Mode
Event Triggered
• SP Hi Alert (Val)
• Latched Cfg chng
• SP Lo Alert (Val)
count
• Latched Device
• ET Alert • ET Alert Mode
Status
• ET Hi Alert (Val)
• Latched Status
• ET Lo Alert (Val)
group 1 to 11
• Latched Ext dev
• Flow Alert • Flow Alert Mode
status
• Flow Hi Alert (Val)
• Latched Device
• Flow Lo Alert (Val)
Diagnostic Status 0
• Latched Device
• DO Config • Digital Output
Diagnostic Status 1
• DO Select
• Latched AO
• DO Signal type
saturated
• DO Test
• Latched AO fixed
• DO Frequency
F0301-07.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-8
E HART 5 : HART 5 only
HART 7 : HART 7 only
• Detailed setup • Sensors • Disp1
• Signal condition • Disp2
• Review • Output condition • Disp3
• Display condition • Disp select • Disp4

• Disp % Reso • Flow disp point


• Pres disp point
• Disp condition • SP disp point
• ET disp point
• TF disp point

• Engr disp range • Engr LRV


• Engr URV
• Engr exp
• Engr Unit
• Bar Indicator • Engr point
• Chg power on info • Set Engr Unit
• Modify Engr Unit

• Device information • Field device info • Tag


• Long tag HART 7
• Date
• Test Key • Descriptor
• Message
• MS Code 1
• MS Code 2
• Write protect
• MS Code 3
• Enable wrt 10min
• Write Protect
• New password
• Wrt protect menu
• Software seal

• Ext SW • Universal rev


• Fld dev rev
• Revision #’s • Software rev
• Chg universal rev

• Additional Info • Style No.


• Option Password • Serial No.
• Mftr Date
• Sensor infomation • Isoltr matl • Extra No.
• Self test • Fill fluid • Final asmbly num
• Gasket matl • Dev id
• Simulation HART 5 • (Flow) Simulation • Process Conn matl • Distributor
Mode • Drain vent matl • PT100 Serial No.
• Flow Simulation • (Flow) Sim Pres Unit • Process Conn type • Country HART 7
HART 7 • (Flow) Sim Pres • RS Isoltr matl • Max dev vars
• (Flow) Sim SP Unit • Process Conn size HART 7

• (Flow) Sim SP • Num of RS • Device Profile


• (Flow) Sim Temp Unit • RS fill fluid HART 7

• (Flow) Sim Temp • RS type

• Basic Flow Calc • Flow Calc mode


• Fluid Type
• Flow Calc Fixed
• Ref SP
• Ref Temp
• Temp K1
F0301-08.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-9
3.1.2 For DTM (HART 5)
Root Menu
• Process Variables P
• Device Status Q
• Diag and Service R
• Easy Setup S
• Configuration T
• Calibration U
• Write Protect V

P
• Process Variables • PV %
• PV AO
• PV URV
• PV LRV
• PV Damp
• Pres
• SP
• A/G Select
• ET
• Flow
• Total Flow
• Engr Disp
• Engr exp
• Engr Unit

Q
• Device Status • Process Variable • PV %
• PV is
• Pres
• SP
• ET
• Flow

• Diagnostic List • Device Status


• Hardware Failure
• Transducer Status
• Diag Status
• Configuration
F0301-09.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-10
R
• Diag and Service • Service • Loop test • BlkF
• Master Test • fDP
• DO Test • fSPh
• Error log view • fSPl
• Error log Clear • DPAvg
• Test Key • Diag Description
• Test Auto Release • Ref BlkF
Time • Ref fDP
• Advanced Diag • Ref fSPh
Variables • Ref fSPl
• Ref DPAvg
• CRatio fDP
• NRatio fDP
• Ratio fDP
• Ratio fSPh
• Ratio fSPl
• Cap Temp
• Amp Temp
• Flg Temp

• Advanced Diag • Impulse Line • Diag Mode


Configurations Blockage Detection • Diag Period
• Diag DPComp
• Diag Description
• Ref BlkF
• Ref fDP
• Ref fSPh
• Ref fSPl
• Ref DPAvg
• Alarm Notification
(Diag Option)
• Diag Suppress Count
• Threshold
• Sensitivity
• Heat Trace • Alarm Notification
(Diag Option)
• Threshold
• Flg Temp
Coefficient
• Tuning
• Flg Temp

• Diag Output • Diag Out Option


• Diag Fixed Out Val

• Advanced Diag • Diag Error • Related to high side


Alerts alarm
• Related to both side
alarm
• Related to low side
alarm
• Related to Flg temp
alarm
S
• Easy Setup • Tag
• PV Unit
• PV URV
• PV LRV
• PV Damp
F0301-10.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-11
T
• Configuration • Pressure Sensor • Pres USL
• Pres LSL
• Static Pressure • SP USL • Pres Min span
Sensor • SP LSL • Pres Unit
• SP Min span • Pres URV
• External • ET USL • SP Unit • Pres LRV
Temperature Sensor • ET LSL • SP URV • Pres Damp
• ET Min Span • SP LRV • Low cut
• ET Unit • SP Damp • Low cut mode
• ET URV • SP H/L Select • H/L Swap
• ET LRV • A/G Select
• ET Damp • Atm. Pres Value
• ET Fixed • Auto Atm. Pres
• Fixed ET Val
• Flow Unit
• Flow URV
• Flow
• Flow LRV
• Flow Damp
• Total Flow • Total Flow Unit
• Total Flow Mode
• Physical Information • Process Conn type • Conf User Unit Cvt
• Process Conn matl Val
• Process Conn size • Conf User Unit Set
• Gasket matl Base Unit
• Isoltr matl • Conf User Unit
• Drain vent matl Modify Unit
• Fill fluid • DO Frequency
• RS type • DO Signal type • Pres
• RS isoltr matl • Pulse rate • Pres Unit
• RS fill fluid • Freq at 100% • SP
• Num of RS • SP Unit
• A/G Select
• Process Input • ET
• ET Unit
• Analog Output • PV is • Flow
• PV % • Flow Unit
• Output Variables • PV is • PV AO • Cap temp
• Change PV Assgn • PV Unit • Amp temp
• PV • PV URV
• SV is • PV LRV
• Change SV Assgn • PV Damp
• SV • Low cut
• TV is • Low cut mode
• Change TV Assgn • AO alm typ
• TV • AO upper limit
• 4V is • AO lower limit
• Change 4V Assgn
• 4V

F0301-11.ai

See T1
(next page)

IM 01C25R02-01E
<3. Parameter Setting> 3-12
T1
• Disp Out1
• Configuration • Local Display • Disp Out2
• Disp Out3
• Process Alerts • Pres Alert mode • Disp Out4
• Pres Hi Alert Val • Disp % Reso
• Device Information1 • Model • Pres Lo Alert Val • Pres disp point
• Manufacturer • SP Alert Mode • SP disp point
• Hardware rev • SP Hi Alert Val • ET disp point
• Software rev • SP Lo Alert Val • Flow disp point
• Date • ET Alert Mode • TF disp point
• Descriptor • ET Hi Alert Val • Engr URV
• Message • ET Lo Alert Val • Engr LRV
• Final asmbly num • Flow Alert Mode • Engr Unit
• Auto recover • Flow Hi Alert Val • Engr exp
• Ext SW • Flow Lo Alert Val • Engr point
• Digital Output • Bar Indicator
• DO Select • Chg power on info
• DO Signal type
• Model 1
• Device Information2 • Model 2
• Model 3
• HART • Tag • Style No.
• Poll addr • Serial No.
• Simulation • Simulation Mode • Dev id • Mftr Date
• Sim Pres Unit • Universal rev • Extra No.
• Sim Pres • Fld dev rev • PT100 Serial No.
• Sim SP Unit • Chg universal rev • Option Password
• Sim SP • Num req preams
• Sim Temp Unit • Physical signal code
• Sim Temp • Burst mode • Flow Calc Mode
• Burst option • Fluid Type
• Burst Xmtr Vals • Flow Calc Fixed
• Ref SP
• Basic Flow Calc • Ref Temp
• Temp K1

U
• Calibration • Trim Who
• Trim Date
• Trim Loc
• Trim Desc
• Pressure trim
• Clear Pressure Sensor trim
• Static Pressure trim
• Clear Static Pressure Sensor trim
• External Temp trim
• Clear External Temp Sensor trim
• D/A trim
• Scaled D/A trim
• Clear D/A trim

V
• Write Protect • Write Protect
• Enter new password
F0301-12.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-13
3.2 Basic Setup *1: The characters bounded by the thick line in the following table
can be used.
*2: All characters in the following table can be used.
IMPORTANT SP ! " # $ % & ' ( ) * + , - . /

0 1 2 3 4 5 6 7 8 9 : ; < = > ?
After setting and sending data with the HART @ A B C D E F G H I J K L M N O
configuration tool, wait 30 seconds before P Q R S T U V W X Y Z [ \ ] ^ _
turning off the transmitter. If it is turned off ` a b c d e f g h i j k l m n o
too soon, the settings will not be stored in the p q r s t u v w x y z { | } ~
transmitter.
*: SP shows one-byte space

3.2.2 Process Variable Setup


3.2.1 Tag and Device Information
The multivariable transmitter can handle five kinds
If there are specified when ordering, the desired Tag of Device Variables; differential pressure (DP),
No. and device information are set and shipped. static pressure (SP), external temperature (ET), and
Tag No. and device information can be checked as also flow rate and total flow which are calculated by
follows. using these values.
• Procedure to call up the display using DD Four data selected from these five data can be
(HART 5/HART 7) and DTM (HART 7) assigned to Dynamic Variables; PV (Primary
Item Procedure Variable), SV (Secondary Variable), TV (Tertiary
Tag [Root Menu] → Basic setup → Tag Variable) and 4V* (Fourth Variable) or QV*
Long Tag [Root Menu] → Basic setup → Long
(HART 7 only) Tag
(Quaternary Variable).
Descriptor [Root Menu] → Basic setup → Device Data assigned for PV become the 4 to 20mA
information → Descriptor
current output.
Message [Root Menu] → Basic setup → Device
information → Message Total flow can not be assigned to PV.
Date [Root Menu] → Basic setup → Device These data are set as follows when the instrument
information → Date
is shipped.
• Procedure to call up the display using DTM In case of measurement function code is “A” (Multi
(HART 5) sensing):
Item Procedure PV: Differential pressure
Tag Easy Setup → Tag
SV: Static pressure
or Configuration → HART → Tag
Descriptor Configuration → Device information 1
TV: External temperature
→ Descriptor 4V/QV*: Flow rate
Message Configuration → Device information 1 In case of measurement function code is “B” (Mass
→ Message flow measurement):
Date Configuration → Device information 1 PV: Flow rate
→ Date
SV: Differential pressure
When the Tag No. and device information are TV: Static pressure
changed, input them based on the following 4V/QV*: External temperature
*: 4V is for HART 5, QV is for HART 7
limitations.

Item Limitations
Tag Up to 8 characters or numbers*1
Long tag Up to 32 characters or numbers*2
(HART 7 only)
Descriptor Up to 16 characters or numbers*1
Message Up to 32 characters or numbers*1
Date mm/dd/yyyy
- mm: month (2 digits)
- dd: days (2 digits)
- yyyy: years (4 digits)

IM 01C25R02-01E
<3. Parameter Setting> 3-14
• Procedure to call up the display using DD • Procedure to call up the display
(HART 5/HART 7) and DTM (HART 7) Call up and setting of flow related parameters
PV related [Root Menu] → Process variables → DD (HART 5/7) [Root Menu] → Detailed setup →
parameter Output vars → PV → DTM (HART 7) Signal condition → Flow Setup →
→ PV is Current PV value DTM (HART 5) Configuration → Flow →
→ Change PV Select the variable assigned to PV → Flow LRV Lower range value for flow
Assgn (Flow, Pres, SP, ET) → Flow URV Upper range value for flow
SV related [Root Menu] → Process variables → → Flow Unit Unit for flow
parameter Output vars → SV → → Flow Damp Damping time constant for flow
→ SV is Current SV value
→ Change SV Select the variable assigned to SV
Assgn (Flow, Pres, SP, ET, Total Flow) Call up and setting of differential pressure related
TV related [Root Menu] → Process variables → parameters
parameter Output vars → TV → DD (HART 5/7) [Root Menu] → Detailed setup →
→ TV is Current TV value DTM (HART 7) Signal condition → DP Setup (or Pres
Setup) →
→ Change TV Select the variable assigned to TV
Assgn (Flow, Pres, SP, ET, Total Flow) DTM (HART 5) Configuration → Pressure Sensor →
4V/QV related [Root Menu] → Process variables → → Pres LRV Lower range value for differential
parameter Output vars → 4V/QV → pressure
→ 4V is / QV is Current 4V/QV value → Pres URV Upper range value for differential
pressure
→ Change Select the variable assigned to 4V/QV
4V Assgn (Flow, Pres, SP, ET, Total Flow) → Pres Unit Unit for differential pressure
/Change QV → Pres Damp Damping time constant for differential
Assgn pressure

• Procedure to call up the display using DTM Call up and setting of static pressure related
(HART 5) parameters
PV related item Configuration → Output Variables → DD (HART 5/7) [Root Menu] → Detailed setup →
→ PV is Current PV value DTM (HART 7) Signal condition → SP Setup →
→ Change PV Select the variable assigned to PV DTM (HART 5) Configuration → Static Pressure
Assgn (Flow, Pres, SP, ET) Sensor →
It is similar about SV, TV and 4V. → SP LRV Lower range value for static pressure
The process variables that can be assigned are Flow, → SP URV Upper range value for static pressure
Pres, SP, ET, and Total Flow. → SP Unit Unit for static pressure
→ SP Damp Damping time constant for static
pressure
3.2.3 Measuring Range
This section shows how to confirm and change Call up and setting of external temperature related
the parameters for measuring range of flow rate, parameters
differential pressure, static pressure, external DD (HART 5/7) [Root Menu] → Detailed setup →
temperature, and total flow, and also unit and DTM (HART 7) Signal condition → ET Setup →
damping time constant. DTM (HART 5) Configuration → External
Temperature Sensor →
These parameters are set at the factory before → ET LRV Lower range value for external
shipment if specified at the time of order. temperature
→ ET URV Upper range value for external
Follow the procedure below to change them. temperature
→ ET Unit Unit for external temperature
About the differential pressure, static pressure and
→ ET Damp Damping time constant for external
external temperature, settable range are shown temperature
on the parameters of LSL (Lower settable limit),
USL (Upper settable limit) and Min span (Minimum
Call up and setting of total flow related parameters
span). Set the data within the range.
DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Signal condition → Total Flow →
DTM (HART 5) Configuration → Total Flow →
→ Total Flow Unit for total flow
Unit

IM 01C25R02-01E
<3. Parameter Setting> 3-15
(4) Unit list of flow
NOTE
Mass Flow g/s, g/min, g/h, kg/s, kg/min, kg/h,
The calibration range can be set as PV LRV > kg/d, t/min, t/h, t/d, lb/s, lb/min, lb/h,
lb/d, STon/min, STon/h, STon/d,
PV URV under the following conditions, LTon/h, LTon/d
reversing the 4 to 20 mA output signal. Normal/ Nm3/h, NL/h, SL/h, SL/min, SL/s,
PV LSL -10% of USL ≤ PV LRV ≤ PV USL Standard Nm3/d, SCFD, SCFH, SCFM, SCFS,
+10% of USL Volume Sm3/d, Sm3/h, MSCFD, MMSCFD
Flow
PV LSL -10% of USL ≤ PV URV ≤ PV USL
Volume CFM, GPM, L/min, Impgal/min, m3/h,
+10% of USL Flow gal/s, Mgal/d, L/s, ML/d, CFS, ft3/d,
|PV URV - PV LRV| ≥ PV Min. Span m3/s, m3/d, Impgal/h, Impgal/d, CFH,
m3/min, bbl/s, bbl/min, bbl/h, bbl/d,
If PV is flow, PV LRV and PV URV must be the gal/h, Impgal/s, L/h, gal/d
following conditions.
0 ≤ PV LRV
(5) Unit list of total flow
0 ≤ PV URV
PV LRV < PV URV g, kg, t, lb, Ston, Lton, oz, gal, L, Impgal, m3,
bbl, yd3, ft3, in3, Nm3, NL, SCF, Spcl*
The flow range is set to LRV=0 and URV=100 * The user unit is displayed on LCD.
when the Flow calc mode is changed to Basic To configure the user unit, refer to subsection 3.3.5.
mode or Full Auto mode. 3.2.5 Damping Time Constant Setup
If PV is ET, PV LRV and PV URV must be the Any number from 0.00 to 100.00 can be set for
following conditions. the amplifier damping time constant of process
-210°C ≤ PV LRV ≤ 860°C variables.
(-346°F ≤ PV LRV ≤ 1580°F)
-210°C ≤ PV URV ≤ 860°C Refer to subsection 3.2.3 to call up the display.
(-346°F ≤ PV URV ≤ 1580°F) Damping time constant is set as shown in the
|PV URV - PV LRV| ≥ PV Min. Span following table at the factory when the instrument
is shipped, but in case of the option code /CA is
3.2.4 Units specified, the damping time constant is set as
specified in the order.
Refer to the subsection 3.2.3 to call up the display.
Select the unit from displayed list as shown below. Process variables Factory default value
Differential pressure 2sec
(1) Unit list of differential pressure Static pressure 1sec
mmH2O, mmH2O@68degF, mmHg, Torr, MPa, External temperature 2sec
kPa , Pa, mbar , bar , gf/cm2, kgf/cm2, inH2O, Flow rate 0sec
inH2O@68degF, inHg, ftH2O, ftH2O@68degF, psi,
atm, hPa
NOTE
Note that the Yokogawa default setting for the • When the HART communication is used
standard temperature is 4°C (39.2°F). For the units under the condition of quick output change,
of mmH2O, inH2O, and ftH2O, the pressure varies set the damping time constant more than 0.5
according to the standard temperature definition. sec.
Select the appropriate unit with @68degF when a • The damping time constant for the amplifier
standard temperature of 20°C (68°F) is required. assembly can be set here. The damping time
(2) Unit list of static pressure constant for the entire transmitter is the sum
of the values for the amplifier assembly and
mmH2O, mmH2O@68degF, mmHg, Torr, MPa,
kPa , Pa, mbar , bar , gf/cm2, kgf/cm2, inH2O,
the capsule assembly.
inH2O@68degF, inHg, ftH2O, ftH2O@68degF, psi, About the value for the capsule assembly,
atm, hPa refer to the User’s Manual for EJX910/
EJX930 (IM 01C25R01-01E) or General
(3) Unit list of temperature Specifications (GS 01C25R01-01EN, GS
degC , degF, Kelvin* 01C25R04-01EN).

*: In the case of using DTM(HART 7), it is displayed as “K“.

IM 01C25R02-01E
<3. Parameter Setting> 3-16
3.2.6 Differential Pressure Signal Low Cut 3.2.7 Impulse Line Connection Orientation
Mode Setup Setup
Low cut mode can be used to stabilize the This function reverses the impulse line orientation.
differential pressure output signal near the zero This function is used when the high pressure side
point. The Low cut is applied to the differential impulse line and the low pressure side impulse line
pressure used to flow calculation. The low cut point are connected reverse by mistake.
can be set from 0 to 20% of output. (Hysteresis for
Follow the procedure below to assign the high
the cut point: ±10% of the cut point )
pressure impulse line to the L side of the transmitter.
Follow the procedure below to change the Low cut
• Procedure to call up the display
mode and Low cut point.
DD (HART 5/7) [Root Menu] → Basic setup →
• Procedure to call up the display DTM (HART 7) Others →
DD (HART 5/7) [Root Menu] → Basic setup → DTM (HART 5) Configuration → Pressure Sensor →
DTM (HART 7) Others → → H/L Swap Select “Normal” or “Reverse”
DTM (HART 5) Configuration → Analog Output →
→ Low cut Set from 0 to 20% of output
→ Low cut Select “On” or “Off”
mode

(%) (%)
50 50
DP Output

DP Output

20 20

0 50 0 50
Input (%) Input (%)

For low cut in Off mode For low cut in On mode


F0302.ai

Figure 3.1 Low Cut Mode

The low cut point has hysteresis so that the output


around the point is behaved as below figure.

<Example>
Low cut mode: On
Low cut: 20.00%
Low cut point
DP Output

7.2mA(20%)

4mA
Input 2% 2%

Setting range: 0 to 20% Hysteresis


fixed at 10%
of the cut point
F0303.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-17
3.3 Detailed Setup • Procedure to call up the display
DD (HART 5/7) [Root Menu] → Detailed setup →
3.3.1 Analog Output Signal Adjustable DTM (HART 7) Signal condition → SP Setup →
Range DTM (HART 5) Configuration → Static Pressure
Sensor →
Output signal adjustable range at normal operating → SP H/L Select “High” or “Low”
condition are set as shown below at the factory Select
when the instrument is shipped, and output signal
are limited by these value. 3.3.3 External Temperature Fixation Mode
Lower limit Upper limit The external temperature can be fixed with this
Standard
3.8 mA 21.6 mA mode. The parameter setting to enter the Fixation
Option code /C1 Mode when the RTD sensor is disconnected is also
Option code /C2 and /C3 3.8 mA 20.5 mA
possible.

Output signal range can be changed between • Procedure to call up the display
3.8mA and 21.6mA to match it to the equipment on DD (HART 5/7) [Root Menu] → Detailed setup →
the receiving side. DTM (HART 7) Signal condition → ET Setup → Fixed
ET →
Lower value is set at AO lower limit and upper
DTM (HART 5) Configuration → External
value is set at AO upper limit respectively. Temperature Sensor →
Follow the procedure below to change the upper → ET Fixed Select “No”, “Yes” or “FALL BACK”
and lower values. No: Shows process temperature
value
• Procedure to call up the display Yes: Fix the temperature value
DD (HART 5/7) [Root Menu] → Detailed setup → FALL BACK: Fix the temperature
DTM (HART 7) Output condition → Analog output → value when the RTD
sensor is disconnected.
DTM (HART 5) Configuration → Analog output →
→ Fixed ET Set the fixed temperature value
→ AO lower Set the lower value (mA) Val
limit
→ AO upper Set the upper value (mA)
limit 3.3.4 Integral Indicator Scale Setup
Set the values as below.
Lower value < Upper value The following seven displays are available for
integral indicator. A cycle of up to four displays can
be shown by assigning variables to the parameters
3.3.2 Static Pressure Setup at Disp select.

(1) Selection of Gauge pressure and Absolute • % of PV range


pressure • Flow rate
• Input differential pressure
Either the gauge pressure or absolute pressure can • Input static pressure
be selected to display on the LCD display. • Input external temperature
Absolute pressure is selected when the instrument • User set scaled PV
is shipped. • Total flow
• Procedure to call up the display
DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Signal condition → SP Setup →
DTM (HART 5) Configuration → Static Pressure
Sensor →
→ A / G Select Select “Gauge” or “Absolute”

(2) Selection of pressure side


Either the high or low pressure side of capsule can
be selected to monitor the static pressure.
High pressure side is selected when the instrument
is shipped.

IM 01C25R02-01E
<3. Parameter Setting> 3-18
Available displays Description and related parameters • Procedure to call up the display
% of PV range Indicates input value depending on DD (HART 5/7) [Root Menu] → Detailed setup →
(PV %) the set PV range (PV LRV and PV DTM (HART 7) Display condition → Disp select →
URV). Disp 1
F
DTM (HART 5) Configuration → Local Display →
PV % 92.4 % Disp Out 1
→ Disp 1 / Select desired display from seven
Disp Out 1 kinds of displays shown above.
Flow rate Indicates values of calculated flow
(Flow) with the indication limits –99999 to Set Disp 2, Disp 3 and Disp 4 in the same way if
F
99999. necessary.
Flow 26.0 kg/h In addition to the above item, "Not used" is also
displayed as a selection item.
b. Cyclic Display
Input differential Indicates values of input differential
pressure pressure with the indication limits Up to four displays can be displayed cyclically in the
(Pres) –99999 to 99999. order of the parameter number.
P

PRES 45.6 kPa c. Display Resolution


User can change the position of decimal point
Input static pressure Indicates values of input static
which is shown on the integral indicator.
(SP) pressure with the indication limits
• Procedure to call up the Disp % reso display
–99999 to 99999.
DD (HART 5/7) [Root Menu] → Detailed setup →
SP

SP 6.178 MPa DTM (HART 7) Display condition →


DTM (HART 5) Configuration → Local Display →
→ Disp % Select the decimal point position of
Input ext. temperature Indicates values of input external
Reso PV%
(ET)*1 temperature with the indication limits
Normal: Display one digit below the
–99999 to 99999.
decimal point
T
High Resolution: Display two digits
ET 22.95 degC below the decimal point

• Procedure to call up the Flow Disp point , Pres


User set scaled PV Indicates values depending on the disp point , SP disp point , ET disp point , TF
(Engr Disp)*2 engineering range (Engr LRV and disp point display
Engr URV) with the unit (Engr Unit). DD (HART 5/7) [Root Menu] → Detailed setup →
Engr LRV 0.0
DTM (HART 7) Display condition → Disp Condition
Engr URV 45.0

Engr exp x100 DTM (HART 5) Configuration → Local Display →
Engr Unit m3/min → Flow Disp Select the decimal point position of
Engr point 1 point flow rate (0, 1, 2, 3 or 4)
Total flow Indicates values of calculated total → Pres disp Select the decimal point position of
(Total Flow)*3 flow with the indication limits as point differential pressure (0, 1, 2, 3 or 4)
F
follows. → SP disp Select the decimal point position of
0 to 9.99E29 (Normal mode) point static pressure (0, 1, 2, 3 or 4)
0 to 999999 (Cyclic mode) →ET disp point Select the decimal point position of
external temperature (0, 1, 2, 3 or 4)
Total Flow 123.45 kg
→TF disp point Select the decimal point position of
F0304.ai
total flow (0, 1, 2, 3 or 4)
*1 : “EXT. TEMP” for DD and DTM (HART 5)
*2 : “ENGR. PV” for DD and DTM (HART 5)
*3 : “TOTAL FLOW” for DD and DTM (HART 5)
d. User Setting of Engineering Unit and Scale
See (a) through (d) for the setting procedures. [For DD (HART 5/7) and DTM (HART 7)]
a. Display Selection Engr disp range parameters allow the engineering
At Disp select, select the variable that the unit and scale to be displayed. At Set Engr Unit,
parameter Disp 1 will display on the integral the following engineering units can be selected from
indicator. a list.

IM 01C25R02-01E
<3. Parameter Setting> 3-19
• Procedure to call up the display 3.3.5 Total Flow Setup
DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Display condition → Engr disp range (1) Mode setting
→ Set Engr Select the engineering unit
Unit
Set the parameters to start, stop, and reset the total
→ Engr LRV Lower range value flow.
→ Engr URV Upper range value To start the total flow measurement by normal
→ Engr exp Exponents for user scale display mode, call up the Total Flow Mode display and set
→ Engr point Decimal point position for user scale the mode.
display
• Procedure to call up the display
Select the engineering unit from the list. Available DD (HART 5/7) [Root Menu] → Detailed setup →
units are shown below DTM (HART 7) Signal condition → Total Flow → Total
Flow Mode →
kPa ftH2O Nl/min DTM (HART 5) Configuration → Total Flow → Total
MPa gf/cm2 Nm3/h Flow Mode →
mbar kgf/cm2 Nm3/min
bar kg/cm2G ACFH Reset Reset the total flow value
psi kg/cm2A ACFM Start Start the total flow measurement.
psia atm CFH Total value is limited at 9.99E29.
mmH2O kg/h SCFM Stop Stop the total flow measurement
mmHg t/h GPH Start Cyclic Start the total flow measurement.
mmHgA m3/h GPM When the total flow value reaches
mmAq m3/min m 999999, the count restarts at 0.
mmWG l/h mm
Torr l/min in
inH2O kl/h ft (2) User unit configuration
inHg kl/min kg/m3
inHgA Nl/h g/cm3 You can set your own unit for total flow.
Select the Base Unit as an base unit, then set the
Cvt Val for the conversion coefficient with the user
At Modify Engr Unit parameter, user can set your
unit.
own unit also.
Up to eight alphanumeric characters, spaces or one • Procedure to call up the display for DD
slashe (/) can be input at Modify Engr Unit; only (HART 5/HART 7) and DTM (HART 7)
the first six are displayed on the integral indicator. DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Signal condition → Total Flow →
• Procedure to call up the display Config User Unit →
DD (HART 5/7) [Root Menu] → Detailed setup → → Set Base Select the Base Unit from the list
DTM (HART 7) Display condition → Engr disp range Unit
→ → Modify Unit Set the special total flow unit
→ Modify Engr Set your own unit → Cvt Val Enter the conversion value
Unit
• Procedure to call up the display for DTM
Note that following symbols are not available: (HART 5)
# % & < > . * : + - , ’ ( ) DTM (HART 5) Configuration → Total Flow →
→ Conf User Unit Set Select the Base Unit from
The integral indicator shows “-- -- -- -- -- --” when Base Unit the list
these symbols or more than two slashes are → Conf User Unit Set the special total flow unit
entered. Modify Unit
→ Conf User Unit Cvt Enter the conversion value
[For DTM (HART 5)] Val
User can input the desired unit at Engr Unit.
• Procedure to call up the display Base Unit
DTM (HART 5) Configuration →Local Display → g oz yd3
→ Engr Unit Set the engineering unit kg gal ft3
→ Engr LRV Lower range value t L in3
→ Engr URV Upper range value lb Impgal Nm3
→ Engr exp Exponents for user scale display STon m3 NL
→ Engr point Decimal point position for user scale LTon bbl SCF
display
Available characters and symbols for Engr Unit are
the same as for Modify Engr Unit shown above.
IM 01C25R02-01E
<3. Parameter Setting> 3-20
Typical Unit Conversion Factor 3.3.6 Sensor Trim
Use “kg” in case of mass flow EJX multivariable transmitter is factory
Use “m3” in case of volume flow characterized. Factory characterization is the
Use “Nm3” in case of normal or standard volume flow process of comparing a known pressure input with
the output of each transmitter sensor module over
Set Base Unit User Unit Convert val the entire pressure and temperature operating
kg g 1.0000E+03
range. During the characterization process, this
kg 1.0000E+00
comparison information is stored in the transmitter
t 1.0000E-03
EEPROM. In operation, the transmitter uses this
lb 2.2046E+00
STon 1.1023E-03
factory-stored curve to produce a process variable
LTon 9.8421E-04 output (PV), in engineering units, dependent on the
oz 3.5274E+01 pressure input.
m3 gal 2.6417E+02 The sensor trim procedure allows you to adjust
L 1.0000E+03 for local conditions, changing how the transmitter
Impgal 2.1997E+02
calculates process variables. There are two ways
m3 1.0000E+00
to trim the sensor: a zero trim and a full sensor trim.
bbl 6.2898E+00
A zero trim is a one-point adjustment typically used
bushel 2.8378E+01
to compensate for mounting position effects or
yd3 1.3080E+00
ft3 3.5315E+01 zero shifts caused by static pressure. A full sensor
in3 6.1024E+04 trim is a two-point process, in which two accurate
bbl 6.2898E+00 end-point pressures are applied (equal to or greater
hl 1.0000E+01 than the range values), and all output is linearized
Nm3 Nm3 1.0000E+00 between them.
NL 1.0000E+03
Full Sensor Trim—Auto Trim and Manual Trim 
SCF 3.5315E+01
Full sensor trim is carried out by performing Auto,
<Example> Lower Pt followed by Auto, Upper Pt.
Set the special total flow unit as g (=0.001kg) based
Also, you can manually perform the trimming
kg.
procedure with Manual, Lower Pt and Manual,
(1kg=1.0000E+03g)
Upper Pt.
1) Select “kg” for Set base unit (or Conf User Unit Set
The full sensor trim is a two-point adjustment,
Base Unit).
and the lower point adjustment should always be
2) Set “g” for Modify Unit (or Conf User Unit Modify performed before the upper point adjustment in
Unit). order to maintain the pitch between the zero and
3) Enter 1.0000E+03 for Cvt Val (or Conf User Unit Cvt 100% points within the calibration range.
Val). In the manual method, the reference pressure
should also be applied to the transmitter at both
the lower and upper points. Without the reference
NOTE pressure, Manual, Lower Pt and Manual, Upper
Pt may not represent the correct value for each
Up to eight alphanumeric characters, spaces or
adjustment point.
slash(/) can be input for Modify Unit (or Conf
User Unit Modify Unit).

IM 01C25R02-01E
<3. Parameter Setting> 3-21
(1) Auto Sensor Trim <5> Suppose that a standard pressure of 3000
Applying reference pressure of 0% and 100% of the mmH2O is applied and the value of the Pres for
measurement range to the transmitter, adjust the trim is 3015.0. Firstly, obtain the slope error for
lower and upper points automatically. the span as follows;
Applied Pressure Value−Value of Pres for Trim
• Procedure to call up the display Slope Error = × (URV−LRV)
DD (HART 5/7) [Root Menu] → Diag/Service → Applied Pressure Value
DTM (HART 7) Calibration → Pres sensor trim →
Pres trim → 3000−3015
= × (3000−1000) = −10
DTM (HART 5) Calibration → Pressure trim → 3000
→ Auto, Lower Pt Auto trim for 0% point Then correct for this slope error of −10 by
→ Auto, Upper Pt Auto trim for 100% point adding −10 to Pres UTD (Manual, Upper Pt).
−3.0+(−10.0)=−13.0
(2) Manual Sensor Trim <6> Enter the correction value of “−13” to the Pres
Using the example below, follow the steps to UTD (Manual, Upper Pt).
perform the full sensor trim by manually. The Pres
LTD (Manual, Lower Pt) and Pres UTD (Manual, (3) Sensor Trim for Static Pressure or External
Upper Pt) represent the previously adjusted values. Temperature
Example: For the range of 1000 to 3000 mmH2O For the EJX multivariable transmitter, full sensor
Pres LTD (Manual, Lower Pt) = −4.0 mmH2O trim of the static pressure or external temperature is
Pres UTD (Manual, Upper Pt) = −3.0 mmH2O performed in the same way as with the differential
pressure.
<1> Call up the Manual, Lower Pt.
• Procedure to call up the display for static
• Procedure to call up the display
pressure
DD (HART 5/7) [Root Menu] → Diag/Service →
DTM (HART 7) Calibration → Pres sensor trim → DD (HART 5/7) [Root Menu] → Diag/Service
Pres trim → DTM (HART 7) → Calibration → SP sensor
trim → SP trim →
DTM (HART 5) Calibration → Pressure trim →
DTM (HART 5) Calibration → Static Pressure
→ Manual, Lower Manual trim for 0% point
trim →
Pt
→ Auto, Lower Pt Auto trim for 0% point
→ Manual, Upper Manual trim for 100% point
Pt → Auto, Upper Pt Auto trim for 100% point
→ Manual, Lower Pt Manual trim for 0% point
→ Manual, Upper Pt Manual trim for 100% point
<2> Suppose that a standard pressure of 1000
mmH2O is applied and the value of the “Pres
• Procedure to call up the display for external
for trim” is 994.0. Correct for this output error
temperature
of 6 mmH2O by adding 6 mmH2O to Pres LTD
DD (HART 5/7) [Root Menu] → Diag/Service
(Manual, Lower Pt). DTM (HART 7) → Calibration → ET Sensor
−4.0+6.0=+2.0 trim → ET trim →
DTM (HART 5) Calibration → External Temp
<3> Enter the correction value of “2” to the Pres trim →
LTD (Manual, Lower Pt). → Auto, Lower Pt Auto trim for 0% point
→ Auto, Upper Pt Auto trim for 100% point
<4> Call up the Pres UTD (Manual, Upper Pt). → Manual, Lower Pt Manual trim for 0% point
→ Manual, Upper Pt Manual trim for 100% point

(4) Reset Trim Adjistment to Factory Setting


The Clear P trim, Clear SP trim and Clear ET trim
commands can reset the trim adjustment to the
initial calibrated values that were set. The amount of
the adjustment performed with the external zero-
adjustment screw is returned to the initial setting as
well.

IM 01C25R02-01E
<3. Parameter Setting> 3-22
• Procedure to call up the display for differential <Example>
pressure Adjustment using a volt meter. (4mA → 1V, 20mA
DD (HART 5/7) [Root Menu] → Diag/Service → → 5V)
DTM (HART 7) Calibration → Pres Sensor trim →
Clear P trim → Execute 1) Select “Change”.
DTM (HART 5) Calibration → Clear Pressure Sensor 2) Enter the value read on the voltmeter when the out-
trim → Execute
put signal is 4mA.

• Procedure to call up the display for static In this case, enter the value of the voltage across a
pressure 250Ω resistor (1V).
DD (HART 5/7) [Root Menu] → Diag/Service → 3) Enter the value read on the meter when the output
DTM (HART 7) Calibration → SP Sensor trim →
Clear SP trim → Execute signal is 20mA (5V).
DTM (HART 5) Calibration → Clear Static Pressure 4) Select “Proceed”.
Sensor trim → Execute
5) Connect the voltmeter.
• Procedure to call up the display for external 6) Output the 0% output signal and read the output
temperature value.
DD (HART 5/7) [Root Menu] → Diag/Service → 7) Enter the reading of the voltmeter to the configuration
DTM (HART 7) Calibration → ET Sensor trim →
Clear ET trim → Execute tool. (The output of the transmitter changes).
DTM (HART 5) Calibration → Clear External Temp 8) Confirm the voltmeter reading is 1.000.
Sensor trim → Execute
9) If the reading on the voltmeter is 1.000, select “Yes”.

3.3.7 Trim Analog Output If the reading is not 1.000, select “No” and repeat
steps 6 and 7 until the voltmeter reads 1.000V.
Fine current output adjustment is carried out with
D/A trim or Scaled D/A trim. 10) Output the 100% output signal and read the output
value.
(1) D/A Trim 11) Enter the reading of the voltmeter.
D/A trim is to be carried out if the calibration digital 12) Confirm the voltmeter reading is 5.000.
ammeter does not exactly read 4.000 mA and 13) If the reading of the voltmeter is 5.000, select “Yes”.
20.000 mA with an output signal of 0% and 100%.
If the reading on the voltmeter is not 5.000, select
• Procedure to call up the D/A trim display “No” and repeat steps 10 and 11 until the voltmeter
DD (HART 5/7) [Root Menu] → Diag/Service →
DTM (HART 7) Calibration reads 5.000V.
→ Analog output trim → D/A trim
DTM (HART 5) Calibration → D/A trim
3.3.8 External Switch Mode
Follow the procedure below to enable or inhibit zero
(2) Scaled D/A Trim
point adjustment by means of the zero-adjustment
Scaled D/A trim is to be carried out if the output is screw on the transmitter.
adjusted using a voltmeter or a meter whose scale
This is set to “Disabled” when the instrument is
is 0 to 100%.
shipped.
• Procedure to call up the Scaled D/A trim
To change the mode, follow the procedure below.
display
DD (HART 5/7) [Root Menu] → Diag/Service → • Procedure to call up the display
DTM (HART 7) Calibration DD (HART 5/7) [Root Menu] → Detailed setup →
→ Analog output trim →Scaled D/A DTM (HART 7) Device information → Field device info
trim → Ext SW
DTM (HART 5) Calibration → Scaled D/A trim DTM (HART 5) Configuration → Device information1
→ Ext SW
Enabled Enable the external zero point
adjustment
Disabled Disable the external zero point
adjustment

IM 01C25R02-01E
<3. Parameter Setting> 3-23
3.3.9 CPU Failure Burnout Direction and 3.3.10 Software Write Protection
Hardware Write Protect
EJX multivariable transmitter configured data is
There are two slide switches on the CPU assembly saved by using a write protection function. The
board. One sets the burnout direction at CPU write protection status is set to “Yes” when 8
failure, and the other sets a write protection function alphanumeric characters are entered in the New
which disables parameter changes through password field and transferred to the transmitter.
the use of a handheld terminal or some other
When write protection is set to ”Yes,” the transmitter
communication method.
does not accept parameter changes. When the
CPU assembly same eight alphanumeric string entered in the New
Burnout direction switch password field is also entered in the Enable wrt
10min field and transferred to the transmitter, it
BO H L
will be possible to change transmitter parameters
WR E D
Slide switch
during a 10 minute period.
Write protection switch To change the transmitter from the write protection
”Yes” status back to write protection ”No” status,
Burnout direction switch (BO)
use Enable wrt 10min to first release the write
Burnout Direction H L H L protection function and then enter eight spaces in
Switch Position the New password field.
• Procedure to call up the display using DD
Burnout Direction HIGH LOW (HART 5/HART 7) and DTM (HART 7)
DD (HART 5/7) [Root Menu] → Detailed setup →
Hardware write protection switch (WR) DTM (HART 7) Device information → Field device
info → Wrt protect menu →
Write Protection H L H L → Write Protect Display current protect mode
Switch Position E D E D (Yes: protected, No: not protected)
→ Enable wrt 10 Release the protect function for 10
NO YES min min.
Write Protection
(Write enabled) (Write disabled) → New password Set the new password or change
F0305.ai
the password
The parameter of AO alm typ parameter displays
the status of 4-20 mA DC output if a CPU failure • Procedure to call up the display using DTM
occurs. In case of a failure, communication is (HART 5)
disabled. DTM (HART 5) Write Protect →
→ Write Protect Display current protect mode
Standard specifications or with option code /C3 (Yes: protected, No: not protected)
The burnout direction switch is set to “HIGH”. If a → Enter new Enter the password here to enable
failure occurs, the transmitter outputs a 110% or password the protect function.
Enter eight spaces to disable the
higher signal.
protect function.
With option code /C1 or /C2 → Enable write Enter the password here to release
The burnout direction switch is set to “LOW”. the protect function for 10 min.
If a failure occurs, a –2.5% or lower output is
generated. 3.3.11 Alarm
To confirm the burnout direction at the CPU failure, The function is used to display the alarm codes
follow the procedure below. when the input differential pressure exceeds the
specified value within the calibration range. The
• Procedure to call up the display
same is available for the input static pressure,
DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Output condition → Analog output → external temperature, and flow rate. Refer to table
AO alm typ 4.5 Alarm Message Summary for the specific alarm
DTM (HART 5) Configuration → Analog output → AO code to be generated.
alm typ
High Burnout direction is set to High
Low Burnout direction is set to Low

IM 01C25R02-01E
<3. Parameter Setting> 3-24
(1) Alarm Setting • Procedure to call up the display
DD (HART 5/7) [Root Menu] → Detailed setup →
Select the process variable at Process Alert which DTM (HART 7) Output condition → Process Alerts →
the alarm is set, then set the alert mode for that DO config → DO Signal type
value. DTM (HART 5) Configuration → Process Alerts → DO
Signal type
• Procedure to call up the display Status Output On When Al. Output is “ON” when
DD (HART 5/7) [Root Menu] → Detailed setup → Detect alert is detected
DTM (HART 7) Output condition → Process Alerts → Off When Al. Output is “OFF” when
DTM (HART 5) Configuration → Process Alerts → Detect alert is detected
Selection of → Pres Alert Mode: Differential Pulse Output Scaled Pulse Scaled pulse output
the process pressure Frequency Frequency output
variable for → SP Alert Mode: Static pressure
alarm → ET Alert Mode: External <Example>
temperature
Set the status output to output an off signal when
→ Flow Alert Mode: Flow rate
Selection of Off: Disable the alert function
the input pressure exceeds 75 kPa with the alert
alert mode Hi Al Detect: High side alert detection mode of Hi. Al Detect.
Lo Al Detect: Low side alert detection 1) Select “Off When Al. Detect”
Hi/Lo Al Detect: High and Low side 2) Select “Pres Alert Mode: Differential pressure” (Refer
alert detection
to subsection 3.3.11(1) Alarm Setting)
3) Select “Hi Al Detect: High side alert detection” (Refer
(2) Threshold Level Setting
to subsection 3.3.11(1) Alarm Setting)
Set the threshold of high and low alert value for
4) Enter “75kPa” to Pres Hi Alert Val (Refer to subsec-
alarm generation.
tion 3.3.11(2) Threshold Level Setting)
• Procedure to call up the display
DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Output condition → Process Alerts →
DTM (HART 5) Configuration → Process Alerts →
CAUTION
Parameter Detail
Whenever turning on the transmitter or detecting
→ Pres Hi Alert Set the threshold value of upper side
Val for differential pressure
the short interruption, check if contact output
→ Pres Lo Alert Set the threshold value of lower side correctly reflects the alarm status and test
Val for differential pressure the ON/OFF action of contact output by the
→ SP Hi Alert Set the threshold value of upper side parameter DO test to confirm that the contact
Val for static pressure output operates correctly.
→ SP Lo Alert Set the threshold value of lower side
Val for static pressure
→ ET Hi Alert Set the threshold value of upper side (2) Setting of status output
Val for external temperature
→ ET Lo Alert Set the threshold value of lower side This feature is used for a transistor output (open
Val for external temperature collector) of an on/off signal according to the
→ Flow Hi Alert Set the threshold value of upper side status of high and low alarm limits, which are
Val for flow rate user-configurable values as shown in subsection
→ Flow Lo Alert Set the threshold value of lower side
3.3.11 Alarm. The status output can be assigned
Val for flow rate
as any combination of the high or low limits of
the input pressure, input static pressure, external
3.3.12 Status Output and Pulse Output temperature, or flow.
EJX multivariable transmitter has a contact output.
Select the type of output, status output or pulse
output, and set the unit, value etc.
(1) Selecting of output signal
Status output or pulse output can be selected for
the contact output.

IM 01C25R02-01E
<3. Parameter Setting> 3-25
• Procedure to call up the display Example: Status output operation of ON
DD (HART 5/7) [Root Menu] → Detailed setup → WHEN AL. DETECT
DTM (HART 7) Output condition → Process Alerts
→ DO config → DO Select
 Status output for higher alert value
DTM (HART 5) Configuration → Process Alerts →
DO Select Output
5%* of hysteresis
Display Item Contents (Select a output variable (%)
from the list below) Setting
value
Off –
Pres Differential pressure
SP Static pressure
Temp External temperature
Pres/SP Differential pressure and static On Time (t)
pressure
Pres/Temp Differential pressure and external Status output
temperature On Off
SP/Temp Static pressure and external
temperature
 Status output for lower alert value
Pres/SP/Temp Differential pressure, static pressure Output
and external temperature (%)
Flow Flow rate
Pres/Flow Differential pressure and flow rate Setting
value
SP/Flow Static pressure and flow rate
Temp/Flow External temperature and flow rate 5%* of hysteresis
Pres/SP/Flow Differential pressure, static pressure
and flow rate On Time (t)
Pres/Temp/Flow Differential pressure, external
temperature and flow rate Status output
SP/Temp/Flow Static pressure, external On Off
temperature and flow rate
*: 5% of setting span for differential pressure / pressure
Pres/SP/Temp/ Differential pressure, static pressure,
Flow external temperature and flow rate F0306.ai

Diag Alarm Alarm for advanced diagnostics Figure 3.2 Status Output
(Refer to subsection 4.2.2.5)
All Alarm for differential pressure, static
pressure, external temperature, flow (3) Setting of pulse output
rate, and advanced diagnostics
When the pulse output is used, either scaled pulse
output or frequency output is selected in subsection
NOTE 3.3.12 (1).
Then configure the parameter shown below.
No status output signal has been defined for a a. Scaled pulse
CPU failure or hardware error. Use a 4-20 mA A single pulse is output for a specified flow
signal to indicate a transmitter’s failure. amount.
b. Frequency output
The flow rate is determined from the number of
output pulses per second.

IM 01C25R02-01E
<3. Parameter Setting> 3-26
Example of Pulse Output 3.3.13 Test Output, Simulation, and Squawk
The number of pulses (PPS)
NOTE
T = 1sec
Fixed current output, DO Test, Flow Simulation
Mode, and Device Variable Simulation Function
continue for a given holding time, then is
released automatically. Even if the HART
(*1) Example of scaled pulse configuration tool power supply is turned off or
Pulse Rate =10kg
the communication cable is disconnected, the
(*2) Example of freqency output
Configuration: Freq at 100% =10000Hz
test output will continue for that time.
Flow Rate: URL =100% 10000(PPS) The holding time can be selected from 10 min*,
F0307.ai
30 min, 60 min, 3 hour, 6 hour or 12 hour.
 Scaled pulse *: Default value.

• Procedure to call up the display • Procedure to call up the display


DD (HART 5/7) [Root Menu] → Detailed setup → DD (HART 5/7) [Root Menu] → Diag/Service
DTM (HART 7) Signal condition → Total Flow → DTM (HART 7) → Test Auto Release Time
DTM (HART 5) Configuration → Total Flow → DTM (HART 5) Diag and Service → Service
→ Test Auto Release Time
→ Total Flow Unit Select the unit of total flow
→ Pulse rate Set the volumetric flow rate or
mass flow rate per one pulse.
(1) Fixed current output
<Example> This feature can be used to output a fixed current
Scaled pulse 10 kg Set for loop checks. The available range for test output
1) Enter “kg” to Total Flow Unit depend on the settings for the AO lower limit and
2) Enter “10” to Pulse rate AO upper limit parameters, whose limit is from
3.8mA (-1.25%) to 21.6mA (110%).
 Frequency output
Refer to the subsection 3.3.1 about the setting of
• Procedure to call up the display AO lower limit and AO upper limit.
DD (HART 5/7) [Root Menu] → Detailed setup → While this function works, “TEST” is displayed on
DTM (HART 7) Signal condition → Total Flow →
the integral indicator.
DTM (HART 5) Configuration → Total Flow →
→ Freq at 100% Set the number of output pulse per  In the case of using DD (HART 5/HART 7)
second at 100% flow rate. and DTM (HART 7)
Max. frequency: 10kHz
Duty cycle: Approx 50% Call up the test output parameter (Loop test) and
select the output signal.
<Example>
• Procedure to call up the display
Freq at 100% is 10000 Hz Set
DD (HART 5/7) [Root Menu] → Diag/Service →
1) Enter “10000” to Freq at 100% DTM (HART 7) Test → Loop test →
Display Item Contents
4mA Output a 4mA DC signal
20mA Output a 20mA DC signal
Other Set a desired output signal value
End Exit

 In the case of using DTM (HART 5)


Call up the test output parameter (Loop test) and
select either manual test or auto test, and set the
current value.

IM 01C25R02-01E
<3. Parameter Setting> 3-27
• Procedure to call up the display • Procedure to call up the display
DTM (HART 5) Diag and Service → Service → DD (HART 5/7) [Root Menu] → Detailed setup →
Loop test → DTM (HART 7) Simulation/Flow Simulation* →
Display Item Contents DTM (HART 5) Configuration → Simulation →
Manual Test Set the current value or % value at → Simulation Off: –
Test output value, then click the Mode ON: DP Differential pressure only
Start button. ON: SP Static pressure only
Auto Test Set the interval and rate of change (Select the
combination ON: DP Differential pressure and
of current output at Auto Test SP static pressure
Setting, then click the Start button. of pseudo
variables) ON: ET External temperature only
ON: DP Differential pressure and
(2) DO Test ET external temperature
ON: SP Static pressure and external
This function performs the contact and pulse output ET temperature
test. ON: DP Differential pressure, static
SP pressure and external
• Procedure to call up the display ET temperature
DD (HART 5/7) [Root Menu] → Detailed setup → Check Differential pressure, static
DTM (HART 7) Output condition → Process Alerts → Flow pressure, and external
DO config → DO Test → Calc temperature without
DTM (HART 5) Diag and Service → Service → DO damping
test → → Sim Pres Select the unit for the differential
Display Item Contents Unit pressure
Status High Contact output: OFF → Sim Pres Set the differential pressure value for
Status Low Contact output: ON simulation
Frequency Frequency range 0 to 10,000Hz It is similar about SP and ET.
Exit Output test is canceled
*: “Simulation” is for HART 5, “Flow Simulation” is for HART 7

(3) Flow Simulation Mode


The flow value can be calculated by using pseudo
values instead of using actual measurements of
differential pressure, static pressure, and external
temperature.
This is called “flow simulation mode.”
The output current value becomes the simulation
value and the LCD continuously displays the
simulation value and alarm (AL.90 SIM) in
alternating sequence.

F0308.ai

Select the desired simulation mode from the list


below, and set the unit and value.

IM 01C25R02-01E
<3. Parameter Setting> 3-28
• Procedure of device variable simulation
NOTE Step 1 Call up the [Root Menu] → Diag/
parameter Service → Test → Simulate
The output process value while simulation 2 Selection of Select one parameter from
can be monitored by LCD and through Device Variable the list below
communication as follows. Off
Flow
Process value Output value Pres
DP Simulation value according to SP
simulation mode ET
SP Simulation value according to Total Flow
simulation mode PV
ET Simulation value according to SV
simulation mode TV
QV
Flow Rate Flow calculation value using the
% Range
DP, SP, ET simulation value
Loop Current
Total Flow Flow Rate accumulation value
3 Setting of Value Input the simulate value
Following function is reflected to flow calculation 4 Setting of Data Select one parameter from
quality the list below
while simulation. Bad
Simulation Poor accuracy
Function
value Manual / Fixed
DP/SP/ET Measuring Range (LRV/URV) Good
Alarm 5 Setting of Limit Select one parameter from
Status Output status the list below
Damping Time* Not limited
DP Low Cut Mode Low limited
*: When “Check Flow Calc” is selected, damping is ignored. High limited
Constant
If one of the following alarm occurs while
simulation, all of the output data are held to the
value before alarm occurs. NOTE
AL.01 (CAP. ERR) • The flow rate is calculated from differential
AL.02 (AMP. ERR) pressure, static pressure, and external
AL.03 (ET. ERR) temperature, and the total flow is
accumulated from the flow rate. Therefore,
(4) Device Variable Simulation Function the simulation results for the flow rate and
(Effective only when setting to HART 7) total flow depend on the simulation settings
of differential pressure, static pressure, and
Using the simulation function, the output signal can
external temperature. The total flow depends
be confirmed by setting any value and status to the
on the flow rate as well.
selected device variable.
• The total flow simulation is only applied for
Call up the parameter and follow the message
LCD display and communication output and
shown.
does not affect the total flow value.
After completing the step 5, the simulation starts.
• All the simulations for differential pressure,
Integral indicator shows output and alarm (AL.91)
static pressure, external temperature,
alternately.
flow rate are reflected to the output.
Accordingly, the loop current, LCD display,
and communication output are directly
corresponded to the simulate value.
The alarm output is also available according
to the simulate value.
• Damping is applicable for differential
pressure, static pressure, and external
temperature simulation.

IM 01C25R02-01E
<3. Parameter Setting> 3-29
(5) Squawk (Effective only when setting to 3.3.14 Basic Flow Calculation (Basic mode)
HART 7)
In the case of Basic mode, flow operation and
This feature can be used to identify the density compensation are performed conventionally
communicating transmitter by remotely causing with the flow factors manually input.
LCD to display the particular pattern as shown in
The flow rate is calculated using the constant flow
the Figure 3.3.
factor.
“SQUAWK” continues for approximately 15
seconds, then is released automatically. Density is compensated as follows according to the
Enter the larger number to “Change number of selection of gas or liquid.
squawks to make” in order to prolong the duration Gas: Compensation as ideal gas by
of squawk indication. temperature and pressure.
• Procedure to call up the Squawk display Liquid: Compensation by temperature.
[Root Menu] → Diag/Service → Test → Squawk There are an automatic compensation mode and
basic mode in the flow calculation, and either is
selected in the Flow Calc Mode parameter.
• Procedure to call up the display
P SP T F DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Basic Flow Calc → Flow Calc Mode

DTM (HART 5) Configuration → Basic Flow Calc →
Flow Calc Mode →
Display Item Contents
Basic Mode Basic calculation mode
F0309.ai
Auto Comp. Automatic compensation mode
Mode (Use FSA120 for this mode)
Figure 3.3 LCD display for Squawk
Select “Basic Mode” here, and set the parameters
according to the procedure of Table 3.2.
FSA120 (FieldMate FlowNavigator) can configure
both automatic compensation mode and basic
mode. For detail, refer to the User’s Manual of
FSA120 FieldMate FlowNavigator (IM 01C25R51-
01E).

IM 01C25R02-01E
<3. Parameter Setting> 3-30
Table 3.2 Basic Flow Calc Set-up Steps
Step Parameter Contents Remarks
1 Flow Calc Mode Select Basic Mode
2 Fluid Type Select liquid or gas
3 Flow Calc Fixed Input Kfactor Kfactor calculated by Table 3.3 Flow Equation and Kfactor
Calculation
4 Ref SP Input reference static This factor is used for gas.
pressure When fluid type is liquid, set 0 to Ref SP(Spb).
5 Ref Temp Input reference temperature
6 Temp K1 Input the density rate of This factor is used for mass flow and normal standard volume flow
change per temperature of liquid. When fluid type is gas or volume flow of liquid, set 0 to
1degC. TempK1. Refer to Table 3.4 Symbol

Equation for Basic flow calculation


The flow equation shown in Table 3.3 is applied to the transmitter by combination of fluid type and flow unit
category.
Table 3.3 Flow Equation and Kfactor Calculation
Fluid Type Flow unit category Kfactor *2 Flow Equation
liquid Mass Flow Kfactor = /4 × Nc × C / 1- β × ε × d
4 2 *1
× 2 × ρb
Qm, Qv or Qv_norm
Normal-Standard Kfactor = /4 × Nc × C / 1- β4 × ε × d2
Volume Flow × 2 × ρb / ρ norm = Kfactor × ∆ρ × (1+ Temp K1 × (T-Tb))
Volume Flow Kfactor = /4 × Nc × C / 1- β4 × ε × d2
× 2 / ρb
Gas Mass Flow Kfactor = /4 × Nc × C / 1- β4 × ε × d2 *1
× 2 × ρb × 1/K Qm or Qv_norm
Normal-Standard Kfactor = /4 × Nc × C / 1- β4 × ε × d2 = Kfactor × ∆ρ × Tb/T × SP/SPb
Volume Flow × 2 × ρb × 1/K / ρ norm
Volume Flow Kfactor = /4 × Nc × C / 1- β4 × ε × d2 *1
Qv = Kfactor × ∆ρ × T/Tb × SPb/SP
× 2 / (ρb × 1/K)
T0310.ai
*1 mark indicate user input.
*2 Kfactor must be calculated according to the specified flow unit.

Table 3.4 Symbol


No Symbol Description
1 Qm Mass Flow
2 Qv Volume Flow
3 Qv_norm Normal-Standard Volume Flow
4 Nc Unit convert factor
5 Kfactor Basic flow Calcuration factor
6 C Discharge Coefficient
7 ε Expansion Factor
8 β Diameter Ratio
9 d Diameter of orifice
10 ∆p Differential Pressure (Transmitter setting unit)
11 ρb Base Density on Tb, SPb condition
12 ρ norm Density on Normal, Standard condition
13 Tb Reference temperature (unit: K)
14 T Temperature (unit: K)
15 SPb Reference static pressure (unit: kPa abs)
16 SP Static Pressure (unit: kPa abs)
17 Temp K1 The density rate of change per temperature 1degC of a density base value (value which set 100%
to 1). For volume flow: set 0.
18 K Compressibility factor
Note 1. The flow unit is not automatically converted. Refer to IM 01C25R01-01E for Nc calculation.
Note 2. Kfactor, SPb, and Tb are calculated using the equipment setting unit (differential pressure, static pressure, and temperature).
Note 3. Total flow is calculated using the transmitter setting unit.

IM 01C25R02-01E
<3. Parameter Setting> 3-31
Flow unit category Table 3.7 Volume Flow Unit

Table 3.5 Mass Flow Unit Unit LCD Communication


cubic feet per minute CFM ←
Unit LCD Communication gallons per minute GPM ←
grams per second g/s ← liters per minute L/m L/min
grams per minute g/m g/min imperial gallons per
grams per hour g/h ← IGal/m lmpgal/min
minute
Kilograms per second kg/s ← cubic meter per hour m3/h ←
kilograms per minute kg/m kg/min gallons per second gal/s ←
kilograms per hour kg/h ← million gallons per day Mgal/d ←
kilograms per day kg/d ← liters per second L/s ←
metric tons per minute t/m t/min million liters per day ML/d ←
metric tons per hour t/h ← cubic feet per second CFS ←
metric tons per day t/d ← cubic feet per day ft3/d ←
pounds per second lb/s ← cubic meters per
m3/s ←
pounds per minute lb/m lb/min second
pounds per hour lb/h ← cubic meters per day m3/d ←
pounds per day lb/d ← imperial gallons per
IGal/h lmpgal/h
short tons per minute STon/m STon/min hour
short tons per hour STon/h ← imperial gallons per
IGal/d lmpgal/d
day
short tons per day STon/d ←
cubic feet per hour CFH ←
long tons per hour LTon/h ←
cubic meters per
long tons per day LTon/d ← m3/m m3/min
minute
barrels per second bbl/s ←
Table 3.6 Normal/Standard Volume Flow Unit barrels per minute bbl/m bbl/min
Unit LCD Communication barrels per hour bbl/h ←
normal cubic meter barrels per day bbl/d ←
Nm3/h ←
per hour gallons per hour gal/h ←
normal liter per hour NL/h ← imperial gallons per
IGal/s lmpgal/s
standard cubic feet second
SCFM ←
per minute liters per hour L/h ←
standard liter per hour SL/h ← gallons per day gal/d ←
standard liter per SL/min
SL/m
minute
standard liter per ←
SL/s
second
normal cubic meter ←
Nm3/d
per day
standard cubic feet ←
SCFD
per day
standard cubic feet ←
SCFH
per hour
standard cubic feet ←
SCFS
per second
standard cubic meter ←
Sm3/d
per day
standard cubic meter ←
Sm3/h
per hour
thousand standard ←
MSCFD
cubic feet per day
million standard cubic ←
MMSCFD
feet per day

IM 01C25R02-01E
<3. Parameter Setting> 3-32
3.3.15 Burst Mode • Procedure to call up the display
DD (HART 5) [Root Menu] → Detailed setup →
3.3.15.1 In the case of using HART 5 Output condition → HART output →
Burst mode
When the Burst mode is enabled, the transmitter DTM (HART 5) Configuration → HART → Burst
continuously sends the stored data. The data is mode
sent approximately three times per second as a Display Item Contents
digital signal when the transmitter is set in burst Off Stop the burst mode
mode. When data is being sent in burst mode, On Start the burst mode
other operations can be performed with the HART
configuration tool. 3.3.15.2 In the case of using HART 7

(1) Selection of the transmission data. When the Burst mode is enabled, the transmitter
continuously sends up to three data listed in Table
Call up the Burst option parameter and select the 3.8.
data which is transferred. Refer to the subsection 3.3.15.2.1 Burst Message
• Procedure to call up the display for details.
DD (HART 5) [Root Menu] → Detailed setup →
Output condition When the Burst mode is set to “Wired HART
→ HART output → Burst option → Enabled”, transmitter continuously sends alarm
DTM (HART 5) Configuration → HART → Burst signal also.
option →
Refer to subsection 3.3.15.2.2 Event Notification for
Display Item Contents
detail.
PV Process variable assigned to PV
(Either of differential pressure, static
pressure, external temperature, and When changing the setting of Burst mode, set “Off”
flow rate) to the Burst mode.
%range/current Output in % and mA
Default setting is “Off”.
Process vars/ Output in mA and process variables
crnt assigned to PV, SV, TV, and 4V.
(Output in mA and four variables 3.3.15.2.1 Burst Message and Burst Mode
from differential pressure, static
pressure, external temperature, flow (1) Burst message
rate, and total flow.)
Xmtr Variables Selectable up to four variables from EJX multivariable transmitter can transmit three
differential pressure, static pressure, burst messages at the maximum.
external temperature, flow rate, and
total flow.
The parameters for Burst Message are as follows.
According to the procedure indicated • Burst Command
in Burst Xmtr Vars, set the selected • Update Period and Max Update Period
variables to four Slot. • Burst Msg Trigger Mode
(For the Slot that is not used, set the
same value as others.)

(2) Shift to the Burst mode.


To enable the Burst mode, select “On” at the Burst
mode parameter.
To release the Burst mode, call up the Burst
mode display and set it to “Off”.
This parameter is set to “Off” when the instrument is
shipped.

IM 01C25R02-01E
<3. Parameter Setting> 3-33
Table 3.8 Burst parameters
Burst Msg Trigger Burst Trigger
Command parameter Burst Command Burst Trigger Units
Mode Source
PV Cmd1:PV Continuous --- ---
(Either of differential Window PV Depend on the
pressure, static pressure, Rising assigned variable to
external temperature, flow Falling PV
rate) On-change
% range/current Cmd2:% range/current Continuous --- ---
(Percent of range, Loop Window % range %
current) Rising
Falling
On-change
Process vars/current Cmd3:Dyn vars/current Continuous --- ---
(Loop current, PV, SV, TV, Window PV Depend on the
QV) Rising assigned variable to
Falling PV
On-change
Process vars/% range/ Cmd9:Device vars w/Status Continuous --- ---
current with status*1 Window Top of Burst Depends on mapping
(Select up to eight variables Rising Device Variables
from differential pressure, Falling
static pressure, external On-change
temperature, flow rate, total
flow, percent of range, loop
current, PV, SV, TV and
QV)*2
Process vars/% range/ Cmd33:Device Variables Continuous Top of Burst Depend on the
current Window Device Variables assigned variable to
(Select up to four variables Rising Burst Device Variables
from differential pressure, Falling
static pressure, external On-change
temperature, flow rate, total
flow, percent of range, loop
current, PV, SV, TV, and
QV)*2
Self diagnosis information Cmd48:Read Continuous --- ---
Additional Device Status On-change All status ---
*1 : Output the data with time and status.
*2 : Select at Burst Device Variables

IM 01C25R02-01E
<3. Parameter Setting> 3-34
(2) Burst mode setting procedure
• Procedure to call up the display
DD (HART 7) [Root Menu] → Detailed setup →
DTM (HART 7) Output condition →HART output →
Burst Condition → Burst Message
1,2 or 3 → Burst Command

Burst Command a. Burst Command

Send to EJX

Burst Cmd9, Cmd33


Command?

Cmd1, Cmd2,
Burst Variable Code b. Burst Variable Code
Cmd3, Cmd48

Send to EJX

Update Period c. Update period and


Max Update Period Max Update Period
by “Set Burst Period”

Send to EJX

Burst Msg Trigger Mode d. Burst Msg Trigger Mode


by “Set Burst Trigger”

Window
Rising
Falling
On-change
Burst Msg
Trigger Mode?

Continuous
Burst Trigger Level

Send to EJX

Burst mode e. Burst Mode

Send to EJX
F0311.ai

IM 01C25R02-01E
<3. Parameter Setting> 3-35
a. Burst Command • Procedure to call up the display
DD (HART 7) [Root Menu] → Detailed setup
Select the transmission data at Burst Command DTM (HART 7) →Output condition →HART
parameter. output → Burst condition → Burst
Burst Command Command parameter Message 1,2 or 3 → Set Burst
Cmd1: PV Variable assigned to PV Period
Cmd2: % range/current % range/current (Percent of → Update Period 0.5 s
range, Loop current) / Max Update 1s
Period 2s
Cmd3: Dyn vars/current Process vars/current
(Loop current, PV, SV, TV, 4s
QV) 8s
Cmd9: Device vars Process vars/% range/current 16 s
w/Status Mapping by user
32 s
Cmd33: Device Process vars/% range/current
1 min
Variables Mapping by user
5 min
Cmd48: Read Self diagnosis information
Additional Device 10 min
Status 15 min
30 min
45 min
b. Burst Variable Code
60 min
This parameter need to be set when Burst
Command is Cmd9:Device vars w/Status (up to d. Burst Msg Trigger Mode
eight items) and Cmd33: Device Variables (up to
four items). Set the Burst Msg Trigger Mode from the
parameters shown below.
• Procedure to call up the display When Burst Msg Trigger Mode is Window, Rising
DD (HART 7) [Root Menu] → Detailed setup → or Falling, set the Burst Trigger Level.
DTM (HART 7) Output condition →HART output →
Burst condition → Burst Message • Procedure to call up the display
1,2 or 3 → Burst Device Variables →
Burst Variable Code → DD (HART 7) [Root Menu] → Detailed setup →
DTM (HART 7) Output condition →HART output →
Display Item Contents Burst condition → Burst Message 1,2
Flow Select the flow rate or 3 → Set Burst Trigger →
Pres Select the differential pressure Display Item Contents
SP Select the static pressure Continuous Burst Message is transmitted
ET Select the external temperature continuously.
Total Flow Select the total flow Window In “Window” mode, the Trigger Value
PV Select the PV value must be a positive number and is the
symmetric window around the last
SV Select the SV value
communicated value.
TV Select the TV value
Rising In “Rising” mode, the Burst Message
QV Select the QV value must be published when the source
% rnge Select the % output value exceeds the threshold
Loop current Select the output current established by the trigger value.
Not Used – Falling In “Falling” mode, the Burst Message
must be published when the source
value fall below the threshold
c. Update period and Max Update Period established by the trigger value.
On-change In “On-change” mode, the Burst
Set to Update Period and Max Update Period. Message must be published when the
When the period that is earlier than the operation source value on change established
by the trigger value.
period of each process value was set, it is set
automatically to become bigger than an operation
period of EJX multivariable transmitter.
For Update Period, set the value that is smaller
than Max Update Period.

IM 01C25R02-01E
<3. Parameter Setting> 3-36
e. Burst Mode Event Notification
Retry Time Event Debounce Interval
When the Burst mode is set to “Wired HART /Max Update Time
Enabled”, the transmitter starts to send the data. --- Off
• Procedure to call up the display 0.5 s 0.5 s
DD (HART 7) [Root Menu] → Detailed setup → 1s 1s
DTM (HART 7) Output condition 2s 2s
→HART output → Burst condition
4s 4s
→ Burst Message 1,2 or 3 →
Burst mode → Wired HART 8s 8s
Enabled 16 s 16 s
32 s 32 s
3.3.15.2.2 Event Notification 1 min 1 min
5 min 5 min
When a setting change and a change of the Self- 10 min 10 min
diagnostics occur, device detect it as an event and 15 min 15 min
can transmit an alarm signal continuously. 30 min 30 min
Up to four events that occurred can be stored. 45 min 45 min
When using this function, set to Burst mode as 60 min 60 min
“Wired HART Enabled”.
(1) Set Event Notification c) Event Notification Control
• Procedure to call up the display Select “Enable event notification on token-passing
DD (HART 7) [Root Menu] → Detailed setup data link layer” in the Event Notification Control
DTM (HART 7) →Output condition →HART parameter to shift to the monitor state:
output → Burst condition →
Event Notification → (2) Acknowledge Event Notification
→ Event Mask Set the status to detect
→ Event Set the retry time when the event The transmission of the event message stops when
Notification occur. event is approved.
Retry Time
→ Max Update Set the retry time when the event
• Procedure to call up the display
Time does not occur. DD (HART 7) [Root Menu] → Detailed
→ Event Debounce The setting of the minimum event DTM (HART 7) setup →Output condition →
Interval duration HART output → Burst condition
→ Event Notification →
→ Event Stop the event monitor: Off
Knowledge →
Notification Shift to the monitor state: Enable
Control event notification on token- → Acknowledge Acquisition of the event number
passing data link layer Event Notification and approval.

a) Event Mask a) Get Event Number

Set the status to detect in the Event Mask Confirm the latest event number.
parameter. Execute Acknowledge Event Notification
Device Status Mask method.
Status group 1 Mask to 11 Mask 1) Enter Event Number is set to “0”.
Ext dev status Mask 2) OK.
Device Diagnostic Status 0 Mask 3) Set “Trans 0: Read Event Notificaiton” to
Device Diagnostic Status 1 Mask Select Transaction.
AO saturated Mask 4) OK.
AO fixed Mask 5) Confirm Event Number.

b) Event Notification Retry Time/ Max Update


Time/ Event Debounce Interval
Set to Event Notification Retry Time, Max Update
Time and Event Debounce Interval.
For Event Notification Retry Time, set the value
that is smaller than Max Update Time.

IM 01C25R02-01E
<3. Parameter Setting> 3-37
b) Acknowledge Event Notification 3.3.16 Multidrop Mode
Execute Acknowledge Event Notification
3.3.16.1 In the case of using HART 5
method.
1) Set to Enter Event Number is in confirmed “Multidropping” transmitters refer to the connection
Event Number a)5. of several transmitters to a single communication
2) OK. transmission line. Up to 15 transmitters can be
3) Set “Trans 1: Send Acknowledge” to Select connected when set in the multidrop mode. To
Transaction. activate multidrop communication, the transmitter
4) OK. address must be changed to a number from 1 to
5) Confirm Event Status is 0x00. 15. This change deactivates the 4 to 20 mA analog
output, sending it to 4 mA. The alarm current is also
(3) Event Notification Record
disabled.
• Procedure to call up the display
DD (HART 7) [Root Menu] → Detailed setup → Setting of Multidrop Mode
DTM (HART 7) Output condition →HART output
→ Burst condition → Event (1) Polling address
Notification → Knowledge →
→ Acknowledge Acquisition of the event number • Procedure to call up the display
Event Notification and approval. DD (HART 5) [Root Menu] → Detailed setup →
Output condition → HART output →
DTM (HART 5) Configuration → HART →
a) Get Event Number
→ Poll addr Enter the number from 1 to 15
Confirm the latest event number.
Execute Acknowledge Event Notification
(2) Enabling the Multidrop Mode
method.
1) Enter Event Number is set to “0”. About the procedure to call up the Polling
2) OK. display, please refer to the User’s Manual of each
3) Set “Trans 0: Read Event Notificaiton” to configuration tool.
Select Transaction.
4) OK. NOTE
5) Confirm Event Number.
When the same polling address is set for
b) Confirmation record of Event Notification two or more transmitters in multidrop mode,
Confirm four events checked in a). communication with these transmitters is
Execute Acknowledge Event Notification disabled.
method.
1) Enter the event number to Enter Event (3) Communication when set in multidrop
Number which is confirmed in a)5. mode.
2) OK.
3) Set “Trans 0: Read Event Notificaiton” to • The HART configuration tool searches for a
Select Transaction. transmitter that is set in multidrop mode when
4) OK. it is turned on. When the HART configuration
5) Knowledge menu displays events record. tool is connected to the transmitter, the polling
address and the tag will be displayed.
Ex.) When the confirmed event number is 123. • Select the desired transmitter. After that, normal
Event Number Explanation communication to the selected transmitter is
123 The latest event possible. However, the communication speed
122 An event before the once. will be slow.
121 An event before the twice.
120 An event before three times. To release multidrop mode, call up the Poll addr
display and set the address to “0”.

IM 01C25R02-01E
<3. Parameter Setting> 3-38
3.3.16.2 In the case of using HART 7 • Select the desired transmitter. After that, normal
communication to the selected transmitter is
“Multidropping” transmitters refer to the connection
possible. However, the communication speed
of several transmitters to a single communication
will be slow.
transmission line. Up to 63 transmitters can be
connected when set in the multidrop mode. To To release multidrop mode, call up the Poll addr
activate multidrop communication, the transmitter display and set the address to “0”.
address must be changed to a number from 1 to
3.3.17 Switching HART Protocol Revision
63. This change deactivates the 4 to 20 mA analog
output, sending it to 4 mA. The alarm current is also When the output signal code is “-J”, HART protocol
disabled. revision of EJX multivariable transmitter can be
selectable from 5 or 7.
Setting of Multidrop Mode The HART protocol revision is set and shipped as
specified in the order.
(1) Polling address To change the HART protocol revision after
• Procedure to call up the display shipment, follow the procedure shown below.
DD (HART 7) [Root Menu] → Detailed setup
DTM (HART 7) →Output condition →HART
output →
IMPORTANT
→ Poll addr Enter the number from 1 to 63
When changing the protocol revision, confirm the
items below.
(2) Enabling the Multidrop Mode • Protocol revision supported by HART
configuration tool must be the same or
About the procedure to call up the Polling
higher than new protocol revision of the EJX
display, please refer to the User’s Manual of each
multivariable transmitter. (Refer to Table 2.1)
configuration tool.
• Confirm that the DD or DTM which is suitable
When Loop current mode is set to “Enabled”, an to new protocol revision of EJX multivariable
analog signal output is available for one device in a transmitter is installed in the configuration
loop. tool. (Refer to Section 2.3 or 2.4)
• Procedure to call up the display
DD (HART 7) [Root Menu] → Detailed setup → 1) Call up the parameter for protocol revision
DTM (HART 7) Output condition →Analog output → change
Loop current mode → • Procedure to call up the Chg universal rev
Enabled Loop current mode is enabled. display.
Disabled Loop current mode is disabled. DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Device information → Field device
info → Revision #’s → Chg universal
NOTE rev
DTM (HART 5) Configuration → HART → Chg
When the same polling address is set for universal rev
two or more transmitters in multidrop mode,
communication with these transmitters is 2) Activate the “Chg universal rev” method
disabled.
IMPORTANT
(3) Communication when set in multidrop
The message is displayed to separate the
mode.
transmitter from the automatic control loop.
• The HART configuration tool searches for a Confirm that the transmitter is separated.
transmitter that is set in multidrop mode when
it is turned on. When the HART configuration 3) Input the new revision number
tool is connected to the transmitter, the polling An input column for new protocol revision number is
address and the tag will be displayed. displayed.
Input the new HART protocol revision number of “5”
for HART 5 or “7” for HART 7.

IM 01C25R02-01E
<3. Parameter Setting> 3-39
4) Applying the new protocol revision
a. Close the configuration tool
After completion of Chg universal rev
method, close the HART configuration tool.

NOTE
When using a FieldMate, close the main display
of FieldMate.

b. Restart the transmitter


Turn off the power to the transmitter, and turn
it on.

IMPORTANT
New protocol revision is applied only after having
performed restart of the transmitter.

NOTE
A new HART revision number is displayed on
the integral indicator for three (3) seconds after
restart the transmitter. (Refer to section 2.1)

5) Confirming the new protocol revision


a. Restart the HART configuration tool

NOTE
When execute the other parameter confirmation
or setting change, execute after restart the
configuration tool.

b. Confirm the new HART protocol revision


number
Call up the Universal rev parameter, and confirm
that the new HART revision number is displayed.
• Procedure to call up the Universal rev.
parameter.
DD (HART 5/7) [Root Menu] → Detailed setup
DTM (HART 7) → Device information → Field
device info → Revision #’s →
Universal rev →
DTM (HART 5) Configuration → HART →
Universal rev. →
5 HART protocol revision: 5
7 HART protocol revision: 7

IM 01C25R02-01E
<4. Diagnostics> 4-1

4. Diagnostics
4.1 Self-Diagnostics (2) Using DTM(HART 5)
The Device Status commands are used for self-
4.1.1 Identify Problems by Using the diagnostics. When Device Status is run, the
HART Configuration Tool integral indicator shows an error code and alarm
The HART configuration tool can be used to run message if the transmitter detects any illegal
self-diagnostics on a transmitter and check for parameter settings or functional faults. See Table
incorrect data settings. 4.5 Alarm Message Summary for probable cause
and countermeasures.
(1) Using DD(HART 5/HART 7) and
• Procedure to call up the Device Status display
DTM(HART 7)
Device Status
The Self test and Status commands are available
for self-diagnostics. When Self test is run, the If no error is detected, “Status: Normal” is displayed
integral indicator shows an error code and alarm on the configuration tool.
message if the transmitter detects any illegal If the specific diagnostic item is known for the
parameter settings or functional faults. See Table check, you can directly call up the item by using the
4.5 Alarm Message Summary for probable cause Diagnostic List in the Device Status display.
and countermeasures. The Diagnostic List is categorized to Device Status,
• Procedure to call up the Self test display Hardware Failure, Transducer Status, Diag Status,
[Root Menu] → Diag/Service → Test → Self test and Configuration.
See Table 4.5 Alarm Message Summary.
If no error is detected, “Self test OK” is displayed on If no error is detected, color symbol which shows
the configuration tool. Normal State is displayed on top of the error
If the specific diagnostic item is known for the message.
check, you can directly call up the item by using the If color symbol which shows Error State is
Status command. displayed, there is an error and a countermeasure
The status is categorized from 1 to 10 for HART 5, for that error is necessary.
and from 1 to 11 for HART 7.
See Table 4.5 to determine the status group.
Show an example below to confirm the status of
Status group 1.
• Procedure to call up the Status display
[Root Menu] → Diag/Service → Status → Status group 1

If no error is detected, “Off” is displayed on the


configuration tool.
If there is an error, “On” is displayed on the The HART configuration tool diagnoses at each
configuration tool, and a countermeasure for that communication.
error is necessary. When an improper operation is performed, the error
Example of display: Illegal P LRV On message is displayed.
Illegal P URV Off See Table 4.6 HART Configuration Tool Error
Illegal P SPAN Off Message.
P SPAN trim err Off
P ZERO trim err Off

The HART configuration tool diagnoses at each


communication.
When an improper operation is performed, the error
message is displayed.
See Table 4.6 HART Configuration Tool Error
Message.

IM 01C25R02-01E
<4. Diagnostics> 4-2
4.1.2 Checking with Integral Indicator (3) Data quality and Limit status
EJX multivariable transmitter can handle
NOTE Dynamic Variables (PV, SV, TV, QV) and Device
Variables (DP(Pres), SP, ET, Flow, Total Flow,
If an error is detected by running self-diagnostics, % range, Loop current). Each variable contains
an error number is displayed on the integral data quality and limit status for providing useful
indicator. If there is more than one error, the error status about the data value. The data quality
number changes at three-second intervals. is normally “Good”. However, in the case of a
See table 4.3.1 regarding the alarm codes. sensor failure or out of measurement range,
it turns to “Bad” or “Poor Accuracy”. The limit
status indicates whether the data value is
limited (i.e., not responding to the process).
When the limit status is “Constant”, the value
will not be changed. For detail, refer to Table 4.9
and 4.10.

• Procedure to call up the display using DD


(HART 7) and DTM (HART 7)
F0401.ai
[Dynamic Variables]
DD (HART 7) [Root Menu] → Process variables
Figure 4.1 Integral Indicator
DTM (HART 7) → Output vars → PV →
→ PV Data Good, Poor Accuracy, Manual/
4.1.3 Status information available for Quality Fixed, or Bad is displayed.
HART 7 → PV Limit Constant, Low Limit, High Limit, or
Status Not Limited is displayed.
Status added to HART 7 is explained below. It is the same about the SV, TV, and QV.

(1) Device Status [Device Variables]


Device Status indicates the current operating DD (HART 7) [Root Menu] → Process variables
status of the device. (Refer to Table 4.7) DTM (HART 7) → Device variables and Status →
Table 4.10 indicates the relationship between → Flow Data Good, Poor Accuracy, Manual/
Quality Fixed, or Bad is displayed.
alarm and Device Status. → Flow Limit Constant, Low Limit, High Limit, or
Status Not Limited is displayed.
• Procedure to call up the display using DD It is the same about the Pres, SP, ET, Total Flow, %
(HART 7) and DTM (HART 7) Range, and Loop Current. .
DD (HART 7) [Root Menu] → Diag/Service →
DTM (HART 7) Status → Device Status (4) Time Stamp
Time Stamp displays the date and the time
(2) Extended Device Status information which EJX multivariable transmitter
Ext dev status contains commonly used maintains from the time of the power on.
device information. (Refer to Table 4.8) It is used as the additional information of the
Table 4.10 indicates the relationship between process value and the event.
alarm and Extended Device Status.
• Procedure to call up the display using DD
• Procedure to call up the display using DD (HART 7) and DTM (HART 7)
(HART 7) and DTM (HART 7) DD (HART 7) [Root Menu] → Diag/Service →
DD (HART 7) [Root Menu] → Diag/Service → DTM (HART 7) Status → Time Stamp
DTM (HART 7) Status → Ext dev status → Current Date It shows the number of operating
days.
→ Current Time It shows the running time.

IM 01C25R02-01E
<4. Diagnostics> 4-3
4.2 Advanced Diagnostics
NOTE
4.2.1 Multi-sensing Process Monitoring
Time Stamp is reset when powering on.
Multi-sensing process monitoring function (option
(5) Configuration Change Counter code: /DG6) provides the advanced diagnostics
The Configuration Change Counter is to detect the abnormal conditions in process
incremented once for every user action environment such as an impulse line etc. by using
that changes the device’s configuration or the EJX multisensing technology and its unique
calibration. This value is never reset or written algorithm. There are following two functions.
and maintained even if power is removed from
the device.  Impulse Line Blockage Detection (ILBD)
The fluctuation change of differential pressure and
• Procedure to call up the display using DD static pressure is monitored by a silicone resonant
(HART 7) and DTM (HART 7) sensor and detects a potential blockage condition.
DD (HART 7) [Root Menu] → Diag/Service → The differential pressure transmitter gives also a
DTM (HART 7) Status → result of which pressure-side was plugged.
→ Cfg chng The configuration change times
count are counted. The counted value  Heat Trace Monitoring
cannot be reset. The two temperature sensors built in the EJX
multivariable transmitter calculate the flange
(6) Reset Configuration Changed Flag temperature, the change of which enables to
Configuration Changed Flag can be reset by detect the heat trace breakage or the abnormal
this method. temperature due to the failure.
NOTE 4.2.2 Impulse Line Blockage Detection
(ILBD)
Refer to Configuration Changed (0x40) in the
Table 4.7. ILBD is carried out by using statistical analysis
based on the measured values of process
fluctuations that exist in a fluid. An alarm on the EJX
• Procedure to call up the display using DD multivariable transmitter LCD display or an analog
(HART 7) and DTM (HART 7) alert is generated if blockage reaches a certain
DD (HART 7) [Root Menu] → Diag/Service → level. EJX multivariable transmitter provides the
DTM (HART 7) Status → Reset Cfg Chng flag following results as blockage detection.
(1) A Blocking and B Blocking
These are blockage detections based on
the fluctuation value change of differential
pressure/pressure. With a differential pressure
transmitter, each result indicates that both or
single side is plugged.
(2) L Side Blocking
It is a low-pressure side blockage detection
based on the change of BlkF or low-pressure-
side fluctuation value.
(3) H Side Blocking
It is a high-pressure side blockage detection
based on the change of BlkF or high-pressure-
side fluctuation value.
*: BlkF indicates blockage degree characterized
by a comparison of the high- and low-pressure-
side fluctuation values. For the details, refer to
Figure 4.2.2.

IM 01C25R02-01E
<4. Diagnostics> 4-4

IMPORTANT
• The pressure fluctuation amplitude in fluids
must be sufficiently large for blockages to be
detected.
• If the pressure fluctuation amplitude is too
low for a reference value to be obtained,
blockages detection operation cannot be
performed with an alarm that the reference
value is invalid.
• The pressure fluctuation amplitude may
decrease due to other causes unrelated with
a blockage according to process condition. In
above case, a false alarm of an impulse line
blockage may be generated. Before taking
action in response to a blockage alarm,
consider the plant operating conditions.

 Notes for Pressure or Level


Measurement
With pressure or level measurement, the pressure
fluctuation amplitude may reduce especially for the
following cases.

 Pressure Measurement
• Operational pressure is near outside of
diagnostic range.
• Even though pressure is constant, the flow
decreases than that under normal condition.
• A source of pressure fluctuation (pump,
compressor, blower, etc.) is shut down. As
a result, the pressure fluctuation amplitude
decreases.

 Level Measurement
• A transmitter is used to measure tank level and
the flow of fluid into or out of the tank comes to
a stop.
• The agitator in the tank is shut down.
• A source of pressure variation (a compressor,
etc.) that controls the internal pressure of a
sealed (closed) tank is shut down.
Before taking action in response to a blockage
alarm, consider the plant operating conditions.

IM 01C25R02-01E
<4. Diagnostics> 4-5
 Functional block diagram
The figure below shows the functional block diagram of ILBD.

Pres, SP, ET, Flow,


EJX multivariable transmitter Total Flow,
Engr Disp, PV %,
Cap temp,
Sensor Amp temp
signals Process Value
Sensor 4-20mA DC
calculation
(Analog Output)
-------(6)
Blockage alarm
Diag Output
Option
Blockage alarm Contact Output
DO Config
(Digital Output)
-------(7)

Ratio fDP
Blockage degree Ratio fSPl
Ratio fSPh
Add result of
blockage detection to status
BlkF -------(1)
fDP
fSPl
fSPh
Diag Applicable*1
Execution of Result of blockage detection
Diag Error -------(4)
ILBD
Response Code -------(2)
Alarm Result of blockage detection (Device Status)
Masking Status group 9,10 -------(3)
*1: Only for DD(HART 5/HART 7) and DTM(HART 7)
In the case of DTM(HART 5), color of icon in the Blockage alarm
Diag Error display changes according to the status. Display on LCD -------(5)
F0402.ai

Figure 4.2 Functional Block Diagram of ILBD

The following outputs are given for the ILBD results.


Table 4.1 List of Outputs for ILBD
OUTPUT
# Parameter name Remarks
Parameters based on the fluctuation value and blockage degree.
[ Diag DPComp:: Non-Compensation ]
fDP
Ratio fDP =
Ratio fDP Ref fDP

[ Diag DPComp:
: Compensation ] fDP × Ref DPAvg
Ratio fDP =
Ref fDP DPAvg
fSPl
Ratio fSPl Ratio fSPl =
Ref fSPl
(1) fSPh
Ratio fSPh Ratio fSPh =
Ref fSPh
Blockage degree characterized in comparison of high-pressure side and low-pressure
BlkF
side pressure fluctuation value.
fDP Average value of the sum of squares of differential pressure fluctuations.
fSPI Average value of the sum of squares of low-pressure side static pressure fluctuation.
fSPh Average value of the sum of squares of high-pressure side static pressure fluctuation.
After the reference value is obtained, the applicable blockage defection and the status of
Diag Applicable*1
abnormal fluctuation are displayed on this parameter.
Response Code When an impulse line blockage is detected, “More Status Avairable” is generated in
(2)
Device Status Response Code Device Status.
When an impulse line blockage is detected, the result of the blockage detection
(3) Status group 9,10
(alarm status) is indicated.
When an impulse line blockage is detected, the results of the blockage detection
(4) Diag Error
(alarm status) is indicated.
(5) Display on LCD When impulse line blockage is detected, an alarm status is displayed on LCD.
(6) Analog Output When impulse line blockage is detected, an alarm status is output on 4 to 20mA.
(7) Digital Output When impulse line blockage is detected, an alarm status is output on Status output.
F0403.ai

IM 01C25R02-01E
<4. Diagnostics> 4-6
4.2.2.1 Blockage Detection Table 4.3 Default Values of Limit Parameter
Multivariable Transmitter
 Limit parameter # Parameter
EJX910A, EJX930A
When the parameter based on pressure fluctuation
[1] Lim fDPmax 3
exceeds the preset value, EJX diagnoses an
[2] Lim fDPmin 0.3
impulse line as blockage and gives an alarm. The
threshold values are set to Limit parameter shown [3] Lim fSPlmax 5
in below table. [4] Lim fSPlmin 0.5
[5] Lim fSPhmax 5
• Procedure to call up the display
DD (HART 5/7) [Root Menu] → Diag/Service → Diag [6] Lim fSPhmin 0.5
DTM (HART 7) Parameters → ILBD Parameters → [7] Lim BlkFmax 0.6
Configuration → Diag Lim →
[8] Lim BlkFmin -0.6
DTM (HART 5) Diag and Service → Advanced Diag
Configurations → Impulse Line [9] Lim DPAvgmax 1
Note 1
Blockage Detection → Threshold
→ Sensitivity → [10] Lim DPAvgmin 0.05
Note 1

Note 1: It indicates the threshold value for “ILBD over range”


Table 4.2 Limit Parameter (refer to subsection 4.2.2.5).
# Parameter Threshold value
 A/B Blocking Detection
[1] Lim fDPmax Threshold to detect “A
Blocking” by using Ratio fDP “A Blocking” and “B Blocking” indicates the result
[2] Lim fDPmin Threshold to detect “B estimated from blockage degree based on the
Blocking” by using Ratio fDP difference of the high- and low-pressure-side
[3] Lim fSPlmax Threshold to detect “Large
fluctuation values. Ratio fDP, SQRT (fDP / Ref
Fluct L” by using Ratio fSPl
[4] Lim fSPlmin Threshold to detect “L Side
fDP) is used to detect A/B blocking. Ref fDP is the
Blocking” by using Ratio fSPl average value of the sum of squares of differential
[5] Lim fSPhmax Threshold to detect “Large pressure fluctuations under normal condition.
Fluct H” by using Ratio fSPh
[6] Lim fSPhmin Threshold to detect “H Side As the value of Ratio fDP exceeds the value of
Blocking” by using Ratio fSPh Lim fDPmax, EJX gives basically an alarm of “A
[7] Lim BlkFmax Threshold to detect “H Side Blocking”. On the other hand, if this value is below
Blocking” by using BlkF the value of Lim fDPmin, EJX gives an alarm of “B
[8] Lim BlkFmin Threshold to detect “L Side Blocking.
Blocking” by using BlkF
[9] Lim DPAvgmax Threshold to detect “ILDB over As a high- or low-pressure-side blockage
range” by using DPAvg and to progresses, fDP increases. Therefore, “A Blocking”
detect “Invalid Ref xx” by using
Ref DPAvg with a differential pressure transmitter indicates
[10] Lim DPAvgmin Threshold to detect “ILDB over that a single-side impulse line is plugged for a
range” by using DPAvg and to differential pressure transmitter. As the both-side
detect “Invalid Ref xx” by using blockages progress simultaneously, fDP decreases.
Ref DPAvg
Therefore, “B Blocking” with a differential pressure
transmitter indicates that both-side impulse lines
Table 4.3 shows the default values at the factory are plugged.
setting.
NOTE
NOTE
A single-side impulse line blockage may
• When ILBD is performed for the first time, generate “B blocking” under the condition where
use the default value. If the pressure the fluctuation amplitude is much different
fluctuation amplitude is low or a false alarm between high- and low-pressure sides.
is often generated after ILBD is performed,
change the values of Limit parameters
according to the procedure described in
subsection 4.2.2.10. Tuning

IM 01C25R02-01E
<4. Diagnostics> 4-7
 H/L Blocking Detection On the other hand, if this value exceeds the value of
EJX differential pressure transmitter enables Lim fSPhmax, EJX gives an alarm of “Large Fluct
to detect both-, a high-, or low-pressure-side H”.
blockage. The blockage degree characterized
 Large Fluctuation Detection
by a comparison of high-pressure side and low-
pressure-side fluctuation values, BlkF, is used to When a pump or compressor starts, the large
detect it. The value changes within a range of –1 fluctuation is generated as process condition
to +1. As BlkF approaches +1, the high-pressure- changes rapidly. This phenomenon affects process
side blockage progresses. On the other hand, if it fluctuation measurement; so correct blockage
approaches –1, the low-pressure-side blockage detection is not performed.
progresses. If “Large Fluct L” or “Large Fluct H” is detected,
1 1 consider whether a blockage result is correct.
The threshold values to detect large fluctuation are
Threshold set to Lim fSPlmax and Lim fSPhmax.
Blockage Progress
0 0 Since these values are enough to detect large
BlkF
BlkF

Blockage Progress fluctuation, it is not almost necessary to change


them.
Threshold
-1 -1
Blockage detection for Blockage detection for
high-pressure side low-pressure side
F0404.ai

Figure 4.3 Relation between Blockage Progress


and BlkF

The each threshold value to detect the high- or low-


pressure-side blockage is set to Lim BlkFmax or
Lim BlkFmin.

 L Side Blocking Detection


BlkF is preferentially used to "L Side Blocking"
detection. If BlkF cannot be used, Ratio fSPl,
SQRT (fSPl / Ref fSPl) is used to "L Side Blocking"
detection. Ref fSPl is the average value of the sum
of squares of low-pressure-side static pressure
fluctuations under normal condition.
As the value of Ratio fSPl is below the value of Lim
fSPlmin, EJX gives an alarm of "L Side Blocking".
On the other hand, if this value exceeds the value of
Lim fSPlmax, EJX gives an alarm of “Large Fluct
L”.

 H Side Blocking Detection


BlkF is preferentially used to "H Side Blocking"
detection. If BlkF cannot be used, Ratio fSPh,
SQRT (fSPh / Ref fSPh) is used to "H Side
Blocking" detection. Ref fSPh is the average value
of the sum of squares of high-pressure-side static
pressure fluctuations under normal condition.
As the value of Ratio fSPh is below the value
of Lim fSPhmin, EJX gives an alarm of "H Side
Blocking".

IM 01C25R02-01E
<4. Diagnostics> 4-8
4.2.2.2 Combination of Reference Result
and Blockage Detection NOTE
• Ref fDP must be larger than the specified
 Diag Applicable
level shown in Table 4.4 (refer to subsection
An EJX multivariable transmitter can detect four 4.2.2.6). No blockage can be detected when
modes of impulse line blockage: both-sides, high- Ref fDP is not large enough.
pressure side, low-pressure side, and/or single-side • The plausibility of blockage detection needs
and abnormal fluctuation when all the reference to be confirmed by blockage simulation test.
values are properly measured. However, the The simulation test can be performed by
detectable alarm mode combination is limited when the appropriate manifold operation (refer to
some of the reference values are invalid. Available subsection 4.2.2.8).
Blockage Detection are shown in the below figure.

[Differential pressure measurement]


Fluctuation Parameters Simulation Test Available Blockage Detection
Ref fDP: OK • B Blocking detection
• Test for low-pressure side (by using Ratio fDP)
Ref fSPI: OK • L Side Blocking detection
• Test for high-pressure side (by using Ratio fSPI)
Ref fSPh: OK • H Side Blocking detection
• Test for both-pressure sides (by using Ratio fSPh)
Ref BlkF: OK • H/L Side Blocking detection
(by using BlkF)
Ref fDP: OK • A/B Blocking detection
• Test for low-pressure side (by using Ratio fDP)
Ref fSPI: OK • L Side Blocking detection
• Test for high-pressure side (by using Ratio fSPl)
Ref fSPh: OK • Test for both-pressure sides • H Side Blocking detection
(by using Ratio fSPh)
Ref BlkF: NG

Ref fDP: OK • A Blocking detection


(by using Ratio fDP)
Ref fSPI: NG • H Side Blocking detection
(by using Ratio fSPh)
• Test for high-pressure side
Ref fSPh: OK

Ref BlkF: NG

Ref fDP: OK • B Blocking detection


(by using Ratio fDP)
Ref fSPI: NG
• Test for both-pressure sides
Ref fSPh: NG

Ref BlkF: NG

[Gauge/absolute pressure and level measurement]


Fluctuation Parameters Simulation Test Available Blockage Detection
Ref fDP: OK • B Blocking detection
• Test for high-pressure side
(by using Ratio fDP)
F0405.ai

IM 01C25R02-01E
<4. Diagnostics> 4-9
4.2.2.3 Operation Parameters  Diag Period
The values such as Ratio fDP and BlkF are
 Diag Mode averaged based on several hundreds of pressure
Diag Mode gives the directive for the ILBD fluctuation values in constant time. Diag Period
operation. There are following three modes. defines the sampling time is. The default value at
• Procedure to call up the display the shipment is set to 180 sec.
DD (HART 5/7) [Root Menu] → Diag/Service → Diag • Procedure to call up the display
DTM (HART 7) Parameters → ILBD Parameters →
DD (HART 5/7) [Root Menu] → Diag/Service → Diag
Configuration → Set Diag Mode →
DTM (HART 7) Parameters → ILBD Parameters →
DTM (HART 5) Diag and Service → Advanced Diag Configuration → Diag Period →
Configurations → Impulse Line
DTM (HART 5) Diag and Service → Advanced Diag
Blockage Detection → Diag Mode →
Configurations → Impulse Line
Blockage Detection → Diag Period →
Diag Mode
Mode Function For the information on how to change the sampling
Stop The blockage detection operation is period, refer to subsection 4.2.2.10.
stopped.
Calculation The blockage detection operation is  Diag Supp Count
performed.
Alarms are generated along with the When the value as Ratio fDP or BlkF exceeds
result. the threshold value for several times in a row,
Reference Reference values for the blockage it is estimated that the impulse line is plugged.
detection are obtained and updated to the Diag Supp Count defines the number of times to
latest. After sampling reference values,
this mode changes to "Calculation". estimate blockage detection.
• Procedure to call up the display
When the blockage detection operation is DD (HART 5/7) [Root Menu] → Diag/Service → Diag
performed, set “Calculation” to Diag Mode. “Stop” DTM (HART 7) Parameters → ILBD Parameters →
must be set when you change a threshold value or Configuration → Diag Supp Count →
set an alarm. “Reference” is set in order to obtain DTM (HART 5) Diag and Service → Advanced Diag
Configurations → Impulse Line
the reference fluctuation values under the normal Blockage Detection → Threshold →
configuration. Diag Suppress Count →

NOTE If Diag Supp Count is set to three times, an


alarm is not generated at part ‘A’ in Figure 4.4.
When setting ILBD parameters in the transmitter Because the first and second values only exceeded
via “Online Parameter” of the DTM (HART 5) consecutively the threshold.
menu, Diag Mode automatically changes to 0
When the value exceeds consecutively the
(Stop). After the setting, Diag Mode automatically
threshold value three times, an alarm is generated
returns to the original value.
(see part ‘B’ in Figure 4.4).

NOTE
When setting ILBD parameters in the transmitter
via “Download to device” of the DTM (HART 5)
menu, Diag Mode automatically changes to 0
(Stop).

IM 01C25R02-01E
<4. Diagnostics> 4-10

Diag Supp Count (Number of times: 3)


An alarm is generated.

A B B B

Upper Threshold
(Ex.Lim fDPmax)
Diag Period

Time

Diag Period
Lower Threshold
(Ex.Lim fDPmin)

A A A B

An alarm is generated.

Diag Supp Count (Number of times: 3)

Time
F0406.ai

Figure 4.4 Relationship of Diag Supp Count and


Alarm

The number of detection to give an alarm is set for


each blockage detection function. The default value
at the shipment is set to three times.
If fluctuating around the threshold value, an alarm
may be often generated. In this case, change the
threshold value (Limit parameter) or the sampling
time (Diag Period) to enhance the accuracy of the
blockage detection. Refer to subsection 4.2.2.10.

IM 01C25R02-01E
<4. Diagnostics> 4-11
4.2.2.4 Operating Procedure If an alarm is often generated or the process
condition changed in the ILBD operation, do
The basic flow of the ILBD operation is as follows.
tuning to change the alarm setting, or to reset the
1) Initial setting reference values.
2) Condition check
Fill out the information to the checklist, at the
3) Start up
process shown in below figure.
4) Perform the ILBD algorithm.
(Refer to the Appendix 1. ILBD Check List)

Items on
Check sheet
1-1) Alert Setting
1, 2 • Enable an alert to be generated by
Diag Out Option parameter.
Refer to subsection 4.2.2.5
1) Initial Setting
1-2) Alarm Masking
• Select the alarm status to display on
7
LCD or to give an alert by Diag
Option parameter.
Refer to subsection 4.2.2.5

2-1) Check Stability of pressure


3
• Check the stability of Pres value.
2) Condition Refer to subsection 4.2.2.6
Check
2-2) Check Fluctuation Values
4 • Check whether the fluctuation values
are available for ILBD.
Refer to subsection 4.2.2.6

3-1) Obtain Reference Values


• Obtain a reference fluctuation value of
5, 6
differential pressure/pressure and
static pressure under normal condition.
Refer to subsection 4.2.2.7

3) Start up 3-2)
Check Detection Tuning
Capability • Change the threshold value by
• Simulate the blockage detection NG
10 Limit parameter.
operation with a three-valve • Change the sampling time by
manifold or stop valve. Diag Period parameter.
Refer to
Refer to subsection 4.2.2.8 subsection 4.2.2.10
OK
4) Perform ILBD algorithm
Spurious alarm detection.
Refer to
subsection 4.2.2.9 Reset Reference Values
• Reset a reference fluctuation
Process condition is value of differential
changed by a pressure/pressure according to
comparison of the process condition.
condition when the Refer to subsection 4.2.2.11
reference values were
obtained.

Blockage Detection
Alarm is generated.
F0407.ai

Figure 4.5 Flow Chart of ILBD Operation

IM 01C25R02-01E
<4. Diagnostics> 4-12
4.2.2.5 Alarm and Alert Setting DD
Bit (HART 5/HART 7) DTM (HART 5) Category
The abnormal results as the blockage detection and DTM (HART 7)
high/low flange temperature (heat trace monitoring) 0 Not used Not used
are given through an analog alert or the LCD 1 Not used Not used
display of alarm status. Before performing the ILBD 2 A Blocking A Blocking
operation, it is necessary to set the alarm and alert Large Fluctuation
according to the following procedure. 3 Large Fluct L of Low Side
Large Fluctuation
Storage of Abnormal results 4 Large Fluct H of High Side
(Diag Error)
5 L Side Blocking Low Side Blocking
Alarm Masking
High Side
(Diag Option) 6 H Side Blocking
Blocking ILBD
7 B Blocking B Blocking
Outside Diagnosis Range/
Invalid Ref xx 8 Invalid Ref F Invalid Ref BlkF
Masking 9 Invalid Ref SPH Invalid Ref fSPh
10 Invalid Ref SPL Invalid Ref fSPl
Alarm on Alarm on Alarm Display 11 Invalid Ref DP Invalid Ref fDP
Analog Output Status Output on LCD
Outside Diagnosis
12 ILBD over range
Device Status Range
Field Device More Status Available Flg Temp Low
13 FT low alarm
Additional Device Status Alarm Heat trace
(Status group 9 and 10)
Flg Temp High monitoring
F0408.ai 14 FT high alarm
Alarm
Figure 4.6 Alarm and Alert Setting 15 Not used Not used

 Alarm Status Note: FT indicates the flange temperature.

When the algorithm of ILBD and Heat trace


 ILBD over range (Outside Diagnosis
monitoring detect the abnormality, the result is
Range)
stored in Diag Error. The alarm status based on the
detected abnormality is displayed to Diag Error. • Procedure to call up the display
DD (HART 5/7) [Root Menu] → Diag/Service → Diag
(Displayed to Impulse Line Blockage Detection DTM (HART 7) Parameters → ILBD Parameters →
and Heat Trace for DTM(HART 5)) Configuration → Diag Lim →
DTM (HART 5) Diag and Service → Advanced Diag
• Procedure to call up the display Configurations → Impulse Line
DD (HART 5/7) [Root Menu] → Diag/Service → Diag Blockage Detection → Threshold →
DTM (HART 7) Parameters → Diag Error →
DTM (HART 5) Diag and Service → Advanced Diag 1) Lim DPAvgmax
Alerts → Diag Error
Lim DPAvgmax is the upper limit of the
diagnostic capability range. The limit value can
be changed when Diag Mode is “Stop”.
DPAvg indicates the ratio of the average of
differential pressure to the EJX maximum span
regarded as 1. When DPAvg exceeds this
limit, “ILBD over range” is generated so that the
blockage detection becomes impossible.
2) Lim DPAvgmin
Lim DPAvgmin is the lower limit of the
diagnostic capability range. The limit value can
be changed when Diag Mode is “Stop”.
When DPAvg is below this limit, “ILBD over
range” is generated so that the blockage
detection becomes impossible.

IM 01C25R02-01E
<4. Diagnostics> 4-13
<Example> DD
When the level range that can be measured by the (HART 5/HART 7) DTM (HART 5)
transmitter with 100 kPa span is –80 to 80 kPa, the DTM (HART 7)
limits are set as follows. A Blocking A Blocking
Large Fluct L Large Fluctuation of Low Side
• Lim DPAvgmax: 0.80
Large Fluct H Large Fluctuation of High Side
• Lim DPAvgmax: –0.80
L Side Blocking Low Side Blocking
1.000
ILBD over range H Side Blocking High Side Blocking
0.80 B Blocking B Blocking
Invalid Ref DP Invalid Ref fDP

Detectable
range
To Link the alarm to an analog alert and LCD
0.000
display, follow the procedure below.
1) Set “Stop” to Diag Mode.
DPAvg 2) Check each checkbox of the alarm, which is
selectable from bit 2 to 14.
-0.80 Note: Set to “Calculation” after setting the parameter.
ILBD over range
-1.000
F0409.ai  Alert Setting

 Invalid Ref F, SPH, SPL, or DP  Diag Out Option


This alarm indicates that the reference value under When an alert regarding the impulse line blockage
normal condition is invalid. If Ref F is invalid, the or high/low flange temperature is generated, the
blockage detection excluding BlkF is carried out. output value of 4-20 mA analog signal can be
If blockage detection function based on BlkF is changed.
required, obtain the reference value again.
Mode Function
Also when Ref DPAvg is below Lim DPAvgmin Keeping PV measurement. The alert is not
Off
or exceeds Lim DPAvgmax, all reference value reflected to 4-20 mA analog signal.
becomes invalid so that “Invalid Ref DP”, “Invalid The analog signal is shifted to the value of
Ref SPL”, “Invalid Ref SPH”, and “Invalid Ref F” are AO upper limit or AO lower limit when an
Burnout alert is generated.
generated. The shifted direction follows Burnout switch
setting.
 Alarm Masking The analog signal is hold to the specific
Fall back value, Diag Fixed Out Val, when an alert is
generated.
 Diag Option
The alarms linked to an analog alert and LCD • Procedure to call up the display
display are selected by Diag Option. DD (HART 5/7) [Root Menu] → Diag/Service → Diag
DTM (HART 7) Parameters → Diag Output → Diag
• Procedure to call up the display Out Option →
DD (HART 5/7) [Root Menu] → Diag/Service → Diag DTM (HART 5) Diag and Service → Advanced Diag
DTM (HART 7) Parameters → Diag Option → Configurations → Diag Output → Diag
DTM (HART 5) Diag and Service → Advanced Diag Out Option →
Configurations → Impulse Line
Blockage Detection → Diag Option →
 Diag Fixed Out Val
The bit of Diag Option is corresponding to that This parameter is used when “Fall back” is selected
of Diag Error. The following alarms are set at to Diag Output Option.
the factory setting, which is corresponding to
When an alert is generated, the 4-20 mA analog
hexadecimal 0x08FC.
signal is held on the value specified by this
parameter.
The value can be entered within 3.8 to 21.6 mA.

IM 01C25R02-01E
<4. Diagnostics> 4-14
• Procedure to call up the display 4.2.2.6 Condition Check
DD (HART 5/7) [Root Menu] → Diag/Service → Diag
DTM (HART 7) Parameters → Diag Output → Diag After the EJX multivariable transmitter was
Fixed Out Val → installed, it is necessary to confirm if Pres is
DTM (HART 5) Diag and Service → Advanced Diag stable under the normal operating condition or if
Configurations → Diag Output → Diag fluctuation amplitude under the normal operating
Out Option →
condition is large enough to detect the blockage.

 Stability of Pressure Value


 Status Output for Advanced diagnostic
1) Observe the value change of Pres under the
The output of the abnormal results are applicable normal operating condition for 10 minutes.
for a transistor output (open collector) of an on/off 2) Confirm the value change is less than 10%.
signal according to the status of high and low alarm
limits, which are values set to Limit parameters as • Procedure to call up the display
shown in subsection 4.2.2.1. About the Flg temp Hi DD (HART 5/7) [Root Menu] → Detailed setup →
DTM (HART 7) Sensors → Pres
Alert Val, or Flg temp Lo Alert Val for Heat trace
DTM (HART 5) Configuration → Process Input → Pres
monitoring, refer to subsection 4.2.3.2.

 DO Select If the value change is more than 10%, the error


influences pressure fluctuation value so that the
If the advanced diagnostic function is installed, the
blockage detection becomes impossible. Consider
following modes can be also assigned to the status
the plant operating conditions.
output in addition to Pres, SP, Temp and Flow.
Mode Function  Fluctuation Value
The status regarding advanced diagnostic
Diag Alarm
masked by Diag Option is output. NOTE
All All status of Press, SP, Temp, Flow and
advanced diagnostic are output. The blockage detection may not be carried
out correctly when pressure fluctuation
amplitude especially with the pressure and level
 Alarm Display on LCD
measurement, is small.
If the ILBD algorithm detects the abnormality, the
content of the detected result is displayed with Confirm that each value of fDP, fSPl, fSPh, and
“AL.88” or “AL.89” on the LCD. “AL.88” indicates BlkF is more than the value specified in the below
that condition is not applicable for the abnormality table.
detection and “AL.89” indicates the abnormality is
detected. • Procedure to call up the fDP, fSPl, fSPh display
DD (HART 5/7) [Root Menu] → Diag/Service → Diag
DTM (HART 7) Parameters → ILBD parameters →
Status → Fluct Variables → fDP/fSPl/
fSPh
DTM (HART 5) Diag and Service → Advanced Diag
Variables → fDP/fSPl/fSPh

F0410.ai
• Procedure to call up the BlkF display
DD (HART 5/7) [Root Menu] → Diag/Service → Diag
Figure 4.7 Display Example of H Side Blocking
DTM (HART 7) Parameters → ILBD parameters →
Status → Diag Variables → BlkF
The alarm display on LCD regarding the advanced DTM (HART 5) Diag and Service → Advanced Diag
diagnostic is described in Table 4.5. Variables → BlkF

Table 4.4 Requirements to apply ILBD


NOTE Condition
fDP 7×10-10 or more
The alarms of “Invalid Ref xx” and “ILBD over
fSPI 1×10-10 or more
range” do not link to the 4-20 mA analog signal
fSPh 1×10-10 or more
and Status output.
BlkF -0.5 to 0.5

IM 01C25R02-01E
<4. Diagnostics> 4-15
 fDP is not enough.  Start of Sampling
No blockage can be detected if fDP is not larger The sampling of reference value is carried out for
than the specified value. 180 sec, which is the default value set to Diag
Period.
 Only fDP is enough. 1) Confirm that the sampling period (Diag Period)
“A Blocking” or “B Blocking” can be detected is set to 180 sec.
if fSPl and fSPh are not larger than specified 2) Set “Reference” to Diag Mode.
values. The sampling starts soon after the setting.

 fDP and fSPl are enough. IMPORTANT


“H Side Blocking” and “Large Fluct H” can not • For the each parameter, the one value is
be detected if fSPh is not larger than specified given. If Reference is set to Diag Mode
value. again, the value is updated and overwritten.
• If the power supply is shut down during the
 fDP and fSPh are enough. sampling, Diag Mode becomes “Stop”. Set
“L Side Blocking” and “Large Fluct L” can not “Reference” to Diag Mode in order to carry
be detected if fSPl is not larger than specified out the sampling again.
value.
 End of Sampling
 fDP, fSPl and fSPh are enough.
After about 180 sec, the sampling automatically
All alarm modes can be detected even if BlkF is finishes. The “Reference” setting of Diag Mode
not within the specified values. moves automatically to “Calculation”.
Confirm that the setting of Diag Mode moves to
4.2.2.7 Obtain Reference Values
“Calculation”.
The pressure fluctuation values are reduced
when the impulse line is plugged. Therefore, the  Reference Values
reference value is required to determine the degree Confirm the latest values are obtained into the
of reduction. following parameters.
• Ref fDP
IMPORTANT • Ref fSPl
• Ref fSPh
• If the impulse line is about to be plugged at
• Ref BlkF
the time when a reference value is obtained,
• Ref DPAvg
blockages cannot be detected accurately.
The impulse lines on both the high-pressure • Procedure to call up the display
and low-pressure sides need to be cleaned DD (HART 5/7) [Root Menu] → Diag/Service → Diag
before a reference value is obtained. DTM (HART 7) Parameters → ILBD parameters →
Status → Diag Reference → Ref fDP/
• All air bubbles need to be adequately purged Ref fSPl/Ref fSPh/Ref BlkF/Ref DPAvg
before a reference value is obtained. DTM (HART 5) Diag and Service → Advanced
• Reference values must be obtained under Diag Configuration → Impulse Line
operating condition. Blockage Detection → Ref fDP/Ref
fSPl/Ref fSPh/Ref BlkF/Ref DPAvg

IM 01C25R02-01E
<4. Diagnostics> 4-16
 Invalid Ref F, SPH, SPL, or DP  Simulation of Low-pressure Side
When the enough reference fluctuation value is Blockage
not obtained, an alarm of invalid reference value 1) Close the low-pressure-side valve.
for each parameter is generated and also the ILBD 2) Confirm the value of Pres is stable. If not,
operation is not carried out. open the valve a little.
3) Set “Calculation” to Diag Mode so as to start
Confirm the alarm of Invalid Ref F, SPH, SPL, or
blockage detection operation.
DP is not displayed in Diag Error.
4) Check that an alarm of “L Side Blocking” is
If an alarm of Invalid Ref F, SPH, SPL, or DP is generated after the time that consists of Diag
generated, consider the process condition or obtain Period and Diag Supp Count passed.
the reference fluctuation values again. 5) Check also the operation of the analog alert if
an analog alert is set.
NOTE 6) Open the valve completely and check that
there are no alarms.
Even if an alarm of Invalid Ref F, SPH, SPL, or
DP is generated, “Calculation” in Diag Mode is  Simulation of Both-pressure Side
kept. Blockage
1) Close the both-pressure-side valves.
2) Confirm the value of Pres is stable. If not,
4.2.2.8 Capability Test of Blockage
open the valve a little.
Detection Operation
3) Set “Calculation” to Diag Mode so as to start
Before performing the ILBD operation, check the blockage detection operation.
capability of the blockage detection operation. 4) Check that an alarm of “B Blocking” is
The simulation test is performed by closing motion generated in the Diag Error after the time
of a three-valve manifold or stop valve. When that consists of Diag Period and Diag Supp
simulated blockage occurs, confirm that an alarm is Count passed.
generated. 5) Check also the operation of the analog alert if
an analog alert is set.
NOTE 6) Open the valve completely and check that
there are no alarms.
The fluctuation amplitude of atmospheric
pressure is nearly zero with pressure or level 4.2.2.9 Start ILBD Operation
measurement. In such case, simulate the
blockage detection by closing the valve where If process condition and capability to detect a
the fluctuation existed. blockage are confirmed, you can start the ILBD
operation according to the following procedure.

 Simulation of High-pressure Side 1) Check the value of sampling period (Diag


Blockage Period).
2) Check the number of times that detect the
1) Close the high-pressure-side valve.
blockage consecutively in order to give an
2) Confirm the value of Pres is stable. If not,
alarm (Diag Supp Count). The default value
open the valve a little.
at the shipment is set to 3 times.
3) Set “Calculation” to Diag Mode so as to start
3) Set “Calculation” to Diag Mode.
blockage detection operation.
If the reference value has not yet been
4) Check that an alarm of “H Side Blocking” is
obtained, set “Reference” to Diag Mode.
generated after the time that consists of Diag
After obtained the reference values, the
Period and Diag Supp Count passed.
ILBD starts automatically. At the same time,
5) Check also the operation of the analog alert if
Diag Mode changes automatically from
an analog alert is set.
“Reference” to “Calculation”.
6) Open the valve completely and check that
there are no alarms.

IM 01C25R02-01E
<4. Diagnostics> 4-17
4.2.2.10 Tuning (1) For DD (HART 5/HART 7) and DTM (HART 7)
When the pressure fluctuation amplitude in fluids is • Procedure to call up the threshold related
not sufficiently large or an alarm is often generated display
according to the process condition, tune up by DD (HART 5/7) [Root Menu] → Diag/Service → Diag
changing the threshold for the blockage detection DTM (HART 7) Parameters → ILBD parameters →
Configuration → Diag Lim →
(Limit parameters) or the sampling period (Diag
Period) to enhance the accuracy of the blockage
The default values at the factory setting are the
detection The ILBD operation must be stopped to
values of Lim fDPmax to Lim BlkFmin shown in
tune up. Set “Stop” to Diag Mode.
Table 4.3.
 Threshold Value Change the threshold value to solve your problem
The figure below shows the image of tuning effect according to the above image.
with a monochrome bar. 1) Set “Stop” to Set Diag Mode.
(a) The tuning image of the threshold values for 2) Change the unsuitable value of Diag Lim
(1) Ratio fDP: Sqrt (fDP/Ref fDP), parameters corresponding to the each
(2) Ratio fSPl: Sqrt (fSPl/Ref fSPl), blockage detection.
(3) Ratio fSPh: Sqrt (fSPh/Ref fSPh)
Note: Set to “Calculation” after setting the parameter.
0 1 3
Limit parameter
# Parameter Threshold value
Threshold (lower side) Threshold (upper side) [1] Lim fDPmax Threshold to detect “A
Blocking” by using Ratio fDP
(1) Lim fDPmin (1) Lim fDPmax [2] Lim fDPmin Threshold to detect “B
(2) Lim fSPlmin (2) Lim fSPlmax Blocking” by using Ratio fDP
(3) Lim fSPhmin (3) Lim fSPhmax [3] Lim fSPlmax Threshold to detect “Large
F0411-1.ai Fluct L” by using Ratio fSPl
[4] Lim fSPlmin Threshold to detect “L Side
(b) The tuning image of the threshold values for Blocking” by using Ratio fSPl
(4) Sqrt (BlkF/Ref BlkF) [5] Lim fSPhmax Threshold to detect “Large
Fluct H” by using Ratio fSPh
-1 0 1
[6] Lim fSPhmin Threshold to detect “H Side
Blocking” by using Ratio fSPh
Threshold (lower side) Threshold (upper side)
[7] Lim BlkFmax Threshold to detect “H Side
Blocking” by using BlkF
[8] Lim BlkFmin Threshold to detect “L Side
(4) Lim BlkFmin (4) Lim BlkFmax Blocking” by using BlkF
F0411-2.ai

Figure 4.8 Tuning Image of Threshold Value


(2) For DTM (HART 5)

 Move the threshold toward the white. Combination of threshold depend on the sensitivity
of blockage detection can be selected from High,
• It becomes increasingly likely to give a false Medium, or Low in the Sensitivity parameter.
alarm due to the disturbance from environment • Procedure to call up the display
change. DTM (HART 5) Diag and Service → Advanced
• If flow/differential pressure is below Lim Diag Configuration → Impulse Line
DPAvgmin or exceeds Lim DPAvgmax, Blockage Detection → Threshold →
sensitivity
pressure fluctuation is likely too small or too
large to detect the blockage.
When select “Custom” in the Sensitivity parameter,
you can set each threshold individually.
 Move the threshold toward the black.
Set the Diag Mode to “Stop” before changing the
• It enables to be insusceptible to disturbance threshold.
such as environment change and to detect the
blockage easier.
• It becomes giving an alarm of the blockage after
the blockage has been progressed.

IM 01C25R02-01E
<4. Diagnostics> 4-18
Combination of threshold for sensitivity parameter  Ratio fDP Compensation
High Medium Low
When the flow change is too large or small, an
Lim fDPmax 1.50 3.00 3.00
alarm maybe often generated. When the above
Lim fDPmin 0.40 0.30 0.20 case happens, the Ratio fDP can be compensated
Lim fSPlmax 5.00 5.00 5.00 so as to enhance the accuracy of the blockage
Lim fSPlmin 0.50 0.50 0.30 detection.
Lim fSPhmax 5.00 5.00 5.00
Lim fSPhmin 0.50 0.50 0.30
 Diag DPComp
Lim BlkFmax 0.60 0.60 0.80
Lim BlkFmin -0.60 -0.60 -0.80 When “Compensation” is selected in Diag
DPComp, Ratio fDP is compensated by following
formula and used as treatable monitoring value,
 Sampling Period CRatio fDP.
If fluctuating around the threshold value, an
alarm maybe often generated. When the above fDP Ref DPAvg
phenomenon happens, the sampling time (Diag
CRatio fDP = DPAvg
Ref fDP
Period) can be changed so as to enhance the
accuracy of the blockage detection. On the other hand, if the compensation is not
necessary, “Non-compensation” is selected in Diag
The longer the sampling time, better the expected
DPComp and Ratio fDP is used as NRatio fDP.
accuracy.
(1) Set “Stop” to Diag Mode. fDP
NRatio fDP =
Ref fDP
(2) Enter the value to Diag Period within the
range of 20 to 65535 (sec).
Note: Set to “Calculation” after setting the parameter. • Procedure to call up the display
DD (HART 5/7) [Root Menu] → Diag/Service → Diag
Also, the accuracy can be improved by increasing DTM (HART 7) Parameters → ILBD parameters →
the number of Diag Supp Count. Status → Diag Vriables → CRatio
fDP/NRatio fDP
 ILBD Range Setting DTM (HART 5) Diag and Service → Advanced
Diag Configuration → Impulse Line
If flow/differential pressure is less than the default Blockage Detection → Threshold →
threshold value of Lim DPAvgmin, pressure
fluctuation is not large enough to detect the
4.2.2.11 Reset of Reference Value
blockage. To prevent the fault blockage detection,
the threshold should be changed to larger value. When there are large flow change or the change of
fluid conditions, obtain the reference value again. If
(1) Set “Stop” to Diag Mode.
flow change by a comparison of the reference value
(2) Enter the value to Lim DPAvgmin or Lim is ±25% or more, obtain the reference value again.
DPAvgmax.
Note Set to “Calculation” after setting the parameter.

• Procedure to call up the threshold display


DD (HART 5/7) [Root Menu] → Diag/Service → Diag
DTM (HART 7) Parameters → ILBD parameters →
Configuration → Diag Lim →
DTM (HART 5) Diag and Service → Advanced
Diag Configuration → Impulse Line
Blockage Detection → Threshold →

IM 01C25R02-01E
<4. Diagnostics> 4-19
4.2.2.12 ILBD Parameter List
# Parameter name Default value Explanation
1 Diag Error 0x0000 The results detected by ILBD or Heat trace monitoring are stored into this
parameter.
Also the condition abnormality in the diagnostic process is stored as an error.
2 Diag Option 0x08FC The masking in this parameter enable to display each error message and the
status to the output signal or LCD.
The error assigned to each bit is corresponding to that of Diag Error.
Writable only when Diag Mode is "Stop".
3 Diag Out Option Off Output mode of 4-20mA when an advanced diagnostic alarm is generated.
There are following three output modes; Off, Burnout, or Fall back.
4 Diag Fixed Out 21.6 mA Parameter for "Fall back" function in the Diag Out option. The output value of
Val 4-20 mA analog signal is specified when an alarm is generated. The value can be
entered within 3.8 to 21.6 mA.
5 DO Select Off The variables for status output are specified to this parameter. When the
advanced diagnostic function (option code /DG6) is installed, the parameters
monitoring in diagnostic process can be also assigned to the status output.
6 Diag Mode Stop The operation mode of ILBD is set.
Stop: The blockage detection is stopped.
Calculate: The blockage detection is carried out.
The alarms are generated along with the detected result.
Reference: The reference values are obtained and the update values are
overwritten.
After setting, this mode moves automatically to "Calculation".
7 Diag Period 180 (sec) The data acquisition period for ILBD is set within 20 to 65535 (sec). If the process
fluctuation values are unsteady, this value is changed to the longer to enhance
the accuracy of the blockage detection.
Writable only when Diag Mode is "Stop".
8 Diag Supp Count 3 Detection count to generate an alarm. When the statistical value as Ratio fDP
and BlkF exceeds consecutively the threshold by number of times preset to this
parameter, it is estimated that the impulse line is plugged.
9 Diag Description Memo field. 32 alphanumerics
10 fDP Average value of the sum of squares of differential pressure fluctuation.
11 fDP Status Status of fDP
12 fSPl Average value of the sum of squares of low-pressure-side static pressure
fluctuation. For gauge/absolute pressure transmitter, 0 is set.
13 fSPl Status Status of fSPl
14 fSPh Average value of the sum of squares of high-pressure-side static pressure
fluctuation. For gauge/absolute pressure transmitter, 0 is set.
15 fSPh Status Status of fSPh
16 BlkF Blockage degree characterized in comparison of high- and low-pressure side
pressure fluctuation value.
17 BlkF Status Status of BlkF
18 DPAvg Ratio of the average of differential pressure/pressure to the maximum span of an
EJX transmitter.
19 DPAvg Status Status of DPAvg
20 Ratio fDP CRatio fDP or NRatio fDP is used by Diag Comp setting.
fDP decreases and this parameter is used to determine whether one or both
sides are plugged.
21 Ratio fDP Status Status of Ratio fDP
22 Ratio fSPl SQRT (fSPl/Ref fSPl).
fSPl decreases and this parameter is used to determine whether low-pressure-
side is plugged.
23 Ratio fSPl Status Status of Ratio fSPl
24 Ratio fSPh SQRT (fSPh/Ref fSPh).
fSPh decreases and this parameter is used to determine whether high-pressure-
side is plugged.
25 Ratio fSPh Status of Ratio fSPh
Status
26 Ref fDP Value of fDP obtained under normal condition.
27 Ref fDP Status Status of fDP obtained under normal condition.

IM 01C25R02-01E
<4. Diagnostics> 4-20
# Parameter name Default value Explanation
28 Ref fSPl Value of fSPl obtained under normal condition.
29 Ref fSPl Status Status of fSPl obtained under normal condition.
30 Ref fSPh Value of fSPh obtained under normal condition.
31 Ref fSPh Status Status of fSPh obtained under normal condition.
32 Ref BlkF Value of BlkF obtained under normal condition.
33 Ref BlkF Status Status of BlkF obtained under normal condition.
34 Ref DPAvg Value of DPAvg obtained under normal condition.
35 Ref DPAvg Status of DPAvg obtained under normal condition.
Status
36 Lim fDPmax Refer to Upper limit for Ratio fDP to detect the blockage.
Table 4.3 Writable only when Diag Mode is "Stop".
37 Lim fDPmin Lower limit for Ratio fDP to detect the blockage.
Writable only when Diag Mode is "Stop".
38 Lim fSPlmax Upper limit for Ratio fSPl to detect the blockage.
Writable only when Diag Mode is "Stop".
39 Lim fSPlmin Lower limit for Ratio fSPl to detect the blockage.
Writable only when Diag Mode is "Stop".
40 Lim fSPhmax Upper limit for Ratio fSPh to detect the blockage.
Writable only when Diag Mode is "Stop".
41 Lim fSPhmin Lower limit for Ratio fSPh to detect the blockage.
Writable only when Diag Mode is "Stop".
42 Lim BlkFmax Upper limit for BlkF to detect the blockage.
Writable only when Diag Mode is "Stop".
43 Lim BlkFmin Lower limit for BlkF to detect the blockage.
Writable only when Diag Mode is "Stop".
44 Lim DPAvgmax Upper limit for DPAvg. Writable only when Diag Mode is "Stop".
45 Lim DPAvgmin Lower limit for DPAvg. Writable only when Diag Mode is "Stop".
46 Ref Lim fDPmin 7.0E-10 Lower limit to judge whether Ref fDP is available for ILBD operation.
Writable only when Diag Mode is "Stop".
47 Ref Lim fSPmin 1.0E-10 Lower limit to judge whether Ref fSPl and Ref fSPh are available for ILBD
operation.
Writable only when Diag Mode is "Stop".
48 Ref Lim BlkFmax 0.5 Upper limit to judge whether Ref BlkF is available for ILBD operation.
Writable only when Diag Mode is "Stop".
49 Status group 9 Refer to Table 4.5.
50 Status group 10 Refer to Table 4.5.
51 CRatio fDP Ratio fDP is compensated by following formula and used as treatable monitoring
value when the flow change is too large or small.
Sqrt (fDP / Ref fDP) X | Ref DPAvg / DPAvg |
When compensation is selected in Diag DP Comp, CRatio fDP is used as
monitoring value.
52 CRatio fDP Status of CRatio fDP
Status
53 NRatio fDP When Non-compensation is selected in Diag DP Comp, NRatio fDP is used as
monitoring value. NRatio fDP = Sqrt (fDP / Ref fDP)
54 NRatio fDP Status of NRatio fDP
Status
55 Diag DPComp 0: Whether fDP is referred by CRatio fDP or NRatio fDP is selected.
Compensation
56 Diag Applicable After the reference value is obtained, the applicable blockage detection is
displayed on this parameter.

IM 01C25R02-01E
<4. Diagnostics> 4-21
4.2.3 Heat Trace Monitoring 4.2.3.1 Flg Temp Coef Setting
The EJX multivariable transmitter with Heat The value calculated according to the following
trace monitoring function calculates the flange procedure is set to Flg temp Coef.
temperature by using the two temperature sensors
• To enhance the calculation accuracy of the
built in the EJX multivariable transmitter.
flange temperature, measure the actual flange
An analog alert is generated if the temperature temperature by using the temperature sensor
reached to the preset level. etc.
The flange temperature is based on the following • Calculate the ratio of the capsule temperature
parameters and calculation formula. to the capsule temperature minus the amplifier
temperature from the two temperature values
[Parameters] measured by EJX multivariable transmitter.
• Derive the Flg temp Coef from the measured
Parameter name Explanation
Cap temp (CT) Measured capsule temperature
flange temperature and the ratio of the capsule
value temperature to the amplifier temperature in
Amp temp (AT) Measured amplifier temperature accordance with the following calculation
value formula.
Flg temp (FT) Flange temperature value
(Calculated value) Flg temp Coef (Cf) =
Flg temp Coef (Cf) Coefficient to calculate flange (Actual measured value of Flange temperature) - CT
temperature CT - AT
Flg temp Hi Alert Val Threshold to generate FT high
alarm
For DTM (HART 5), Flg Temp Coef parameter can
Flg temp Lo Alert Val Threshold to generate FT low
alarm be set by using Tuning function.
By setting the measured value of flange
temperature, Flg Temp Coef is calculated by using
[Calculation formula] capsule temperature and amplifier temperature.

Flg temp (FT) = CT + Cf X (CT-AT) • Procedure to call up the Tuning display.


Diag and Service → Advanced Diag Configuration →
If the flange temperature exceeds the value preset Heat Trace → Tuning
to Flg temp Hi Alert Val or Flg temp Lo Alert Val,
an alert is generated.

NOTE
The flange temperature is calculated by the
calculation formula assumed that the capsule
part of EJX multivariable transmitter is heated up
or kept warm by an electrical heater or steam. In
the case of an atmosphere temperature or less,
the difference of temperature of approximately
3 to 4 °C, may occur because the amplifier
temperature becomes higher than the capsule
temperature.

IM 01C25R02-01E
<4. Diagnostics> 4-22
Sensor Sensor signals Process Value 4-20mA DC
calculation (Analog Output)
Amplifier Amp temp Amp temp
Temperature

Capsule Cap temp Cap temp


Temperature
HTM alarm

Calculation of Diag Output HTM alarm Contact Output


DO Config (Digital Output)
Flg temp Option
Flg temp Coef

CT+(CT-AT) x Cf

Flg temp Flg temp

Result of HTM detection


Execution HTM Diag Error
Result of HTM detection Response Code
Alarm Masking (Device Status)
Status group 9
HTM alarm
Display on LCD F0412.ai

Figure 4.9 Functional Block Diagram of Heat Trace Monitoring (HTM)

4.2.3.2 Out of Temperature Measurement


Range An alarm is generated.

When the flange temperature is out of Flg temp Hi Alert


measurement range, the alarm or alert is
generated. For the detail of alarm and alert setting,
refer to subsection 4.2.2.5. Flg temp Lo Alert

The measurement range is set to Flg temp Hi Alert Flg temp An alarm is generated.
Flgtemp
Val and Flg temp Lo Alert Val, which values can
be specified within -50 to 130 deg C. Time
F0413.ai

4.2.3.3 Parameter Lists for Heat Trace Monitoring


# Parameter name Default value Explanation
1 Diag Error 0x0000 The results detected by ILBD or Heat trace monitoring are stored into this
parameter. Also the condition abnormality in the diagnostic process is
stored as an error.
2 Diag Option 0x08FC The masking in this parameter enable to display each error message and
the status to the output signal or LCD.
The error assigned to each bit is corresponding to that of Diag Error.
Writable only when Diag Mode is "Stop".
3 Diag Out Option Off The error status can be output by 4-20 mA analog signal.
There are following three output modes; Off, Burnout, or Fall back.
4 Diag Fixed Out Val 21.6mA Parameter for "Fall back" function in the Diag Out option.
The output value in 4-20 mA analog signal is specified when an alarm is
generated.
The value must be entered within 3.8 to 21.6 mA.
5 Cap temp Measured capsule temperature value
6 Amp temp Measured Amplifier temperature value
7 Flg temp (Note) Calculated flange temperature value
8 Flg temp Coef 0 Coefficient to calculate flange temperature (Cf: Rt1/Rt2)
Rt1: Thermal resistance between the flange and capsule.
Rt2 : Thermal resistance between the cupsule and amplifier.
9 Flg temp Hi Alarm Val 120 deg C Upper limit of Flg temp
10 Flg temp Lo Alarm Val -40 deg C Lower limit of Flg temp
11 DO Select Off See subsection 3.3.12 Status Output
12 DO Signal type ON WHEN See subsection 3.3.12 Status Output
AL DETECT
13 Digital Output Off See subsection 3.3.12 Status Output

Note: The Flg temp Coef is 0 at the shipment so that the Flg temp outputs the same value as that of Cap temp.

IM 01C25R02-01E
<4. Diagnostics> 4-23
4.3 Alarms and Countermeasures
Table 4.5 Alarm Message Summary
Status Diagnostic
Integral HART configuration 4-20mA Output
Cause Countermeasure group List
indicator tool display operation during error
*1 group *2
AL. 01 P sensor error *1 Sensor problem. Outputs the signal (High Replace capsule if
CAP.ERR Pressure Sensor or Low) set with burnout the error recurs after
Error *2 direction switch. the transmitter is
[status output: undefined] restarted.
CT sensor error *1 Capsule temperature (About the output signal, Replace capsule.
Capsule Temperature sensor problem. refer to subsection 3.3.9)
Sensor Error *2
Cap EEPROM error *1 Capsule EEPROM
1
Capsule EEPROM problem.
Error *2

Hardware Failure
AL. 02 AT sensor error *1 Amplifier temperature Replace amplifier.
AMP.ERR Amp Temp Sensor sensor problem.
Error *2
Amp EEPROM error *1 Amplifier EEPROM
Amp EEPROM Error problem.
*2
CPU board error *1 Amplifier problem.
2
CPU Board Error *2
AD Converter Error *1 A/D Converter problem.
A/D Converter Error *2
AL. 03 ET sensor error *1 External temperature Check external 4
ET.ERR External Temp Sensor sensor disconnection. temperature sensor.
Error *2
No device ID *1 No device ID is found. Continues to operate and Replace amplifier.
— 2
No Device ID *2 output.
AL. 10 P outside limit *1 Differential pressure is When PV is Pres Check input or
PRESS Pressure Outside outside measurement Output AO upper limit or replace capsule
Limit *2 range limit of capsule. AO Lower limit. (Refer to when necessary.
subsection 3.3.1)
AL. 11 SP outside limit *1 Static pressure exceeds When PV is SP
ST. PRSS Static Pressure limit. Output AO upper limit or
Outside Limit *2 AO Lower limit. (Refer to
subsection 3.3.1)
AL. 12 CT outside limit *1 Capsule temperature is Continues to operate and Use heat insulation

Transducer Status
CAP.TMP Cap Temp Outside outside range (–50 to output. or make lagging to
Limit *2 130°C). keep temperature
AL. 13 AT outside limit *1 Amplifier temperature within range. 3
AMP.TMP Amp Temp Outside is outside range (–50 to
Limit *2 95°C).
AL. 14 ET outside limit *1 External temperature is When PV is ET
EXT. TMP External Temp outside range. Output AO upper limit or
Outside limit *2 AO Lower limit. (Refer to
AL. 15 OHM outside limit *1 External temperature subsection 3.3.1)
EXT. TMP OHM Outside limit *2 sensor resistance is out
specification.
AL. 16 PLS PLS outside limit *1 Pulse output is out Continues to operate and Check settings and
PLS RNG Outside specification. output. change them.
Limit *2
*1: DD (HART 5/HART 7), DTM (HART 7)
*2: DTM (HART 5)
*3: Available only for HART 7

IM 01C25R02-01E
<4. Diagnostics> 4-24
Status Diagnostic
Integral HART configuration 4-20mA Output
Cause Countermeasure group List
indicator tool display operation during error
*1 group *2
AL. 30 P over range *1 Differential pressure When PV is Pres. Check input and
PRS.RNG Pressure Over Range exceeds specified range. Output AO upper limit or range setting, and
*2 lower limit. change them as
(Refer to subsection 3.3.1) needed.
AL. 31 SP over range *1 Static pressure exceeds When PV is SP
SP. RNG Static Pressure Over specified range. Output AO upper limit or
Range *2 lower limit.
(Refer to subsection 3.3.1)
4
AL. 32 F over range *1 Flow exceeds specified When PV is Flow
F. RNG Flow Over Range *2 range. Output AO upper limit or
lower limit.
(Refer to subsection 3.3.1)
AL. 33 ET over range *1 External temperature When PV is ET
ET. RNG External Temp Over exceeds specified range. Output AO upper limit or
Range *2 lower limit.
(Refer to subsection 3.3.1)

Transducer Status
AL. 35 P.HI P high alarm *1 Input pressure exceeds Continues to operate and Check input.
Pressure High Alarm *2 specified threshold. output.
AL. 36 P.LO P low alarm *1
Pressure Low Alarm *2
AL. 37 SP high alarm *1 Input static pressure 5
SP.HI Static Pressure High exceeds specified
Alarm *2 threshold.
AL. 38 SP low alarm *1
SP.LO Static Pressure Low
Alarm *2
AL. 41 F.HI F high alarm *1 Input flow exceeds
Flow High Alarm *2 specified threshold.
AL. 42 F.LO F low alarm *1
Flow Low Alarm *2
AL. 43 ET high alarm *1 Input external 8
ET.HI External Temp High temperature exceeds
Alarm *2 specified threshold.
AL. 44 ET low alarm *1
ET.LO External Temp Low
Alarm *2
AL. 50 Illegal P LRV *1 Specified value is outside Holds at the output value Check settings and
P. LRV Illegal Pressure LRV of setting range. that existed immediately change them as
*2 before the error occurred. needed.
AL. 51 Illegal P URV *1
P. URV Illegal Pressure URV
*2
AL. 52 Illegal P SPAN *1
P. SPN Illegal Pressure SPAN
*2
AL. 53 P SPAN trim err *1 Continues to operate and Adjust settings and
Configuration

P. ADJ Pressure SPAN Trim output. change them as


Error *2 needed.
6
P ZERO trim err *1
Pressure ZERO Trim
Error *2
AL. 54 Illegal SP LRV *1 Holds at the output value Check settings and
SP. RNG Illegal Static Pressure that existed immediately change them as
LRV *2 before the error occurred. needed.
Illegal SP URV *1
Illegal Static Pressure
URV *2
Illegal SP SPAN *1
Illegal Static Pressure
SPAN *2
*1: DD (HART 5/HART 7), DTM (HART 7)
*2: DTM (HART 5)
*3: Available only for HART 7

IM 01C25R02-01E
<4. Diagnostics> 4-25
Status Diagnostic
Integral HART configuration 4-20mA Output
Cause Countermeasure group List
indicator tool display operation during error
*1 group *2
AL. 55 SP SPAN trim err *1 Specified value is outside Continues to operate and Adjust settings and
SP. ADJ Static Pressure SPAN of setting range. output. change them as
Trim Error *2 needed.
7
SP ZERO trim err *1
Static Pressure ZERO
Trim Error *2
AL. 56 Illegal ET LRV *1 Holds at the output value Check settings and
ET. RNG Illegal External Temp that existed immediately change them as
LRV *2 before the error occurred. needed.
Illegal ET URV *1
Illegal External Temp 8
URV *2
Illegal ET SPAN *1

Configuration
Illegal External Temp
SPAN *2
AL. 57 ET SPAN trim err *1 Continues to operate and Adjust settings and
ET. ADJ External Temp SPAN output. change them as
Trim Error *2 needed.
7
ET ZERO trim err *1
External Temp ZERO
Trim Error *2
AL. 58 F set outside Range *1 Specified value is outside Holds at the output value Check settings and
FL. ADJ Flow set Outside of setting range. that existed immediately change them as 8
Range *2 before the error occurred. needed.

AL. 59 PLS set err *1, *2 Specified value is outside Normal calculation.
PLS.ADJ of setting pulse output. 7

ET Fixed Mode *1, *2 Under Temperature Fix Temp. Output Fix at 4mA. Leave from
— Mode. PV is ET Temperature Fix 7
Mode.
AL. 79 — Displayed value exceeds Continues to operate and Check settings and
OV. DISP limit. output. change them as —
needed.
AL.87 FT high alarm *1 Flange temperature It depends on the Diag Out Check the heater
FLG. HI Flg Temp High Alarm exceeds a preset upper Option setting. failure.
*2 limit.
AL.87 FT low alarm *1 Flange temperature is Off: Continue to operate and Check the capsule
FLG. LO Flg Temp Low Alarm below a preset lower output. temp. and Amplifier
*2 limit. Burnout:Outputs AO upper temp.
limit or AO lower limit.
Fall back:Outputs Diag Out Adjust Flg Temp
Fixed Val. Coef.
AL.88 Invalid Ref DP *1 Differential pressure/ Continue to operate and Check process
INVR.DP Invalid Ref fDP *2 pressure fluctuation does output. condition.
not reach the reference
level required to blockage
Diag Status
detection so that no
blockage detection is
carried out.
AL.88 Invalid Ref SPL *1 Low-pressure-side 9
INVR.SL Invalid Ref fSPl *2 fluctuation does not
reach the reference
fluctuation level required
to blockage detection.
AL.88 Invalid Ref SPH *1 High-pressure-side
INVR.SH Invalid Ref fSPh *2 fluctuation does not reach
the reference fluctuation
level required to blockage
detection.
AL.88 Invalid Ref F *1 BlkF can not be used for
INVR.F Invalid Ref BlkF *2 blockage detection for
some reasons.
AL.89 ILBD over range *1 Appointed the diagnosis
ILBD.OV Outside Diagnosis range outside.
Range *2
*1: DD (HART 5/HART 7), DTM (HART 7)
*2: DTM (HART 5)
*3: Available only for HART 7

IM 01C25R02-01E
<4. Diagnostics> 4-26
Status Diagnostic
Integral HART configuration 4-20mA Output
Cause Countermeasure group List
indicator tool display operation during error
*1 group *2
AL.89 B Blocking *1, *2 B Blocking (both-side It depends on the Diag Out Check process
B BLK blockage) is detected. Option setting. condition.
AL.89 H Side Blocking *1 High-pressure-side
Off: Continue to operate and
H BLK High Side Blocking *2 blockage is detected.
output.
AL.89 L Side Blocking *1 Low-pressure-side Burnout: Outputs AO upper
limit or AO lower limit.

Diag Status
L BLK Low Side Blocking *2 blockage is detected.
Fall back: Outputs Diag Out
AL.89 Large Fluct H *1 Pressure fluctuation Fixed Val. 10
H LRG Large Fluctuation of amplitude of high-
High Side *2 pressure side is large.
AL.89 Large Fluct L *1 Pressure fluctuation
L LRG Large Fluctuation of amplitude of low-
Low Side *2 pressure side is large.
AL.89 A Blocking *1, *2 A Blocking (single-side
A BLK blockage) is detected.
AL. 90 Flow Simulation Under Simulation Mode Simulate input output. Check Simulation

Transducer
SIM mode *3 for flow. Mode.

Status
Simulation mode *4 5

AL. 91 *3 F Simulate Mode Under Simulation Mode Output the setting value of Check Simulation
F. SIM for device variables. Simulate-Value Mode

AL. 91 *3 P Simulate Mode


P. SIM

AL.91 *3 SP Simulate Mode


SP. SIM

AL. 91 *3 ET Simulate Mode —


11
ET. SIM

AL. 91 *3 TF Simulate Mode


TF. SIM

AL. 91 *3 % Simulate Mode


PCT. SIM

AL. 91 *3 AO Simulate Mode


AO. SIM

*1: DD (HART 5/HART 7), DTM (HART 7)


*2: DTM (HART 5)
*3: Available only for HART 7
*4: HART 5

IM 01C25R02-01E
<4. Diagnostics> 4-27
Table 4.6 HART Configuration Tool Error Messages
Error message Probable cause Countermeasure
Invalid selection —
Passed Parameter Too Large Set value is too high. Change the setting.
Passed Parameter Too Small Set value is too low.
Too Few Data Bytes Received — —
In Write Protect Mode Operation is set in the Write Protect mode. —
Lower Range Value too High LRV set point is too high.
Lower Range Value too Low LRV set point is too low.
Upper Range Value too High URV set point is too high. Change the range.
Upper Range Value too Low URV set point is too low.
Span too Small Set span is too small.
Applied Process too High Applied pressure is too high.
Adjust the applied pressure.
Applied Process too Low Applied pressure is too low.
New Lower Range Value Pushed The shift of URV according to the new LRV Change the URV setting within the
Upper Range Value Over Sensor Limit setting exceeds USL. range of USL.
Excess Correction Attempted Amount of correction is too much. Adjust the amount.
Small Char. did not convert successfully Characters are not convertible. e.g. % Correct the setting.
Not in fixed current mode The fixed current mode is desired but not
Set in the fixed current mode.
set in that mode.
In Multidrop Mode Operation is set in the multi-drop mode. —
Not write Protect Operation is set without a password. —

Table 4.7 Device Status Table 4.8 Extended Device Status


Item Description Item Description
Field Device Malfunction Field device has Maintenance Required Device requires
(0x80) malfunctioned due to a (0x01) maintenance.
hardware error or failure.
Device Variable Alert Configuration is invalid or
Configuration Changed A modification has been (0x02) device is under simulation
(0x40)* made to the configuration mode.
of the field device.
Cold Start A reset of the field device Table 4.9 Data Quality and Limit Status
(0x20) has occurred, or power
has been removed and Data Quality Description
reapplied.
Good The value may be used in
More Status Available Field device has more control.
(0x10) status available.
Poor Accuracy The quality of the value is
PV Analog Output Fixed Analog output 1 and its less than normal, but the
(0x08) digital representation value may still be useful.
are in fixed mode, and
Manual / Fixed The value is manually
not responsive to input
fixed.
changes.
Bad The value is not useful.
PV Analog Output Analog output 1 and its
saturated digital representation are
(0x04) outside the operating
range limits, and not Limit Status Description
responding to input. Constant The value cannot be
Non-PV out of Limits Process applied to the changed, no matter what
(0x02) non-primary variable is the process does.
outside the operating Low Limited The value is out of the
limits of the field device. high or low limit.
High Limited
PV out of Limits Process applied to the
(0x01) primary variable is outside Not Limited The value is free to
the operating limits of the change.
field device.

*: This flag can be reset. Refer to subsection 4.1.3 (6) Reset


Configuration Changed Flag

IM 01C25R02-01E
<4. Diagnostics> 4-28
Table 4.10 Relationship between Alarm and Status available for HART 7

Value and Status (Data Quality and Limit Status)


HART
Integral Device Extended Differential Static External
configuration Loop
Indicator Status Device Status Flow Pressure Pressure Temperature Total Flow % range
tool display current
(DP) (SP) (ET)
AL.01 P sensor Device Maintenance Value: Hold value Value:Hold value
CAP.ERR error Malfunction Required Status: Bad and Constant Status:Bad and Low
CT sensor (0x80) (0x01) Value: Hold value Limited/High Limited*1
error Status: Bad and Constant
Cap Value: Hold value
EEPROM Status: Bad and Constant
error
AL.02 AT sensor Value: Hold value Value: Hold value
AMP.ERR error Status: Bad and Constant Status: Bad and Low
Amp Value: Hold value Limited/High Limited*1
EEPROM Status: Bad and Constant
error
CPU board Value: Hold value
error Status: Bad and Constant
AD Value: Hold value
Converter Status: Bad and Constant
error
AL.03 ET sensor Value: Hold value Value: Hold value
ET. ERR error Status: Bad and Constant Status: Bad and Low
Limited/High Limited*1
--- No device --- --- Value: Measured value
ID Status: Good and Not Limited
AL.10 P outside In the case Device Value: Value: Value: Value: Same as Value and
PRESS limit of PV: Variable Alert Measured Measured value Measured Measured Status of PV
Primary (0x02) value Status: value value
Variable Status: Poor Accuracy and Not Status: Status:
Out of Poor Limited Good and Poor
Limits Accuracy Not Limited Accuracy
(0x01) and and
Not Limited Not Limited
In the case
AL.11 SP outside except PV:
ST.PRSS limit Non-
Primary
Variable
Out of
Limits
(0x02)

AL.12 CT outside Non-


CAP.TMP limit Primary
Variable
AL.13 AT outside Out of Value: Measured value
AMP.TMP limit Limits Status: Good and Not Limited
(0x02)
AL.14 ET outside In the case Value: Value: Measured value Value: Value: Same as Value and
EXT.TMP limit of PV: Measured Status: Good and Not Measured Measured Status of PV
Primary value Limited value value
Variable Status: Status: Poor Status:
Out of Poor Accuracy Poor
Limits Accuracy and Not Accuracy
(0x01) and Limited and
Not Limited Not Limited
In the case
AL.15 OHM except PV:
EXT.TMP outside limit Non-
Primary
Variable
Out of
Limits
(0x02)
AL.16 PLS outside --- Value: Measured value
PLS limit Status: Good and Not Limited
*1: Depend on the setting of hardware switch
*2: Depend on the direction of range over (high or low)

IM 01C25R02-01E
<4. Diagnostics> 4-29
Value and Status (Data Quality and Limit Status)
HART
Integral Device Extended Differential Static External
configuration Loop
Indicator Status Device Status Flow Pressure Pressure Temperature Total Flow % range
tool display current
(DP) (SP) (ET)
AL.30 P over In the case Device Value: Measured value In the case of PV
PRS.RNG range of PV: Variable Alert Status: Good and Not Limited Value: Hold value
Loop (0x02) Status: Bad and
AL.31 SP over Current Low Limited/High
SP. RNG range Saturated Limited*2
AL.32 F over (0x04) In the case except PV
F. RNG range Value: Measured
value
AL.33 ET over Status: Good and
ET. RNG range Not Limited
AL.35 P high --- Value: Measured value
P. HI alarm Status: Good and Not Limited
AL.36 P low alarm
P. LO
AL.37 SP high
SP. HI alarm
AL.38 SP low
SP. LO alarm
AL.41 F high
F. HI alarm
AL.42 F low alarm
F. LO
AL.43 ET high
ET. HI alarm
AL.44 ET low
ET. LO alarm
AL.50 Illegal P Value: Measured value In the case PV is DP
P. LRV LRV Status: Good and Not Limited Value: Hold value
Status: Bad and
Constant
AL.51 Illegal P
In the case except
P. URV URV
shown above
Value: Measured
AL.52 Illegal P value
P. SPN SPAN Status: Good and
Not Limited
AL.53 P SPAN Value: Value: Value: Value: In the case PV is DP
P. ADJ trim err Measured Measured Measured value Measured or Flow
value value Status: value Value: Measured
Status: Status: Good and Not Limited Status: value
Poor Poor Poor Status: Poor
Accuracy Accuracy Accuracy Accuracy and Not
and and and Limited
P ZERO Not Limited Not Limited Not Limited In the case except
trim err shown above
Value: Measured
value
Status: Good and
Not Limited
AL.54 Illegal SP Value: Measured value In the case PV is SP
SP. RNG LRV Status: Good and Not Limited Value: Hold value
Status: Bad and
Constant
Illegal SP
In the case except
URV
shown above
Value: Measured
Illegal SP value
SPAN Status: Good and
Not Limited
*1: Depend on the setting of hardware switch
*2: Depend on the direction of range over (high or low)

IM 01C25R02-01E
<4. Diagnostics> 4-30
Value and Status (Data Quality and Limit Status)
HART
Integral Device Extended Differential Static External
configuration Loop
Indicator Status Device Status Flow Pressure Pressure Temperature Total Flow % range
tool display current
(DP) (SP) (ET)
AL.55 SP SPAN --- Device Value: Value: Value: Value: Value: In the case PV is SP
SP. ADJ trim err Variable Alert Measured Measured Measured Measured Measured or Flow
(0x02) value value value value value Value: Measured
Status: Status: Status: Status: Status: value
Poor Good and Poor Good and Poor Status: Poor
Accuracy Not Accuracy Not Accuracy Accuracy and Not
and Limited and Limited and Limited
SP ZERO Not Limited Not Limited Not Limited In the case except
trim err shown above
Value: Measured
value
Status: Good and
Not Limited
AL.56 Illegal ET Value: Measured value In the case PV is ET
ET. RNG LRV Status: Good and Not Limited Value: Hold value
Status: Bad and
Constant
Illegal ET
In the case except
URV
shown above
Value: Measured
Illegal ET value
SPAN Status: Good and
Not Limited
AL.57 ET SPAN Value: Value: Measured value Value: Value: In the case PV is ET
ET. ADJ trim err Measured Status: Good and Not Measured Measured or Flow
value Limited value value Value: Measured
Status: Status: Status: value
Poor Poor Poor Status: Poor
Accuracy Accuracy Accuracy Accuracy and Not
and Not and Not and Not Limited
ET ZERO Limited Limited Limited In the case except
trim err shown above
Value: Measured
value
Status: Good and
Not Limited
AL.58 F set Value: Measured value In the case PV is Flow
FL. ADJ outside Status: Good and Not Limited Value: Hold value
Range Status: Bad and
Constant
In the case except
shown above
Value: Measured
value
Status: Good and
Not Limited
AL.59 PLS set err Value: Measured value
PLS.ADJ Status: Good and Not Limited
--- ET Fixed --- --- Value: Measured value Value: Value: In the case PV is ET
Mode Status: Good and Not Limited Hold value Measured Value: Hold value
Status: value Status: Good and
Good and Status: Constant
Constant Good and In the case except
Not shown above
Limited Value: Measured
value
Status: Good and
Not Limited
AL.79 (None) --- --- Value: Measured value
OV.DISP Status: Good and Not Limited
*1: Depend on the setting of hardware switch
*2: Depend on the direction of range over (high or low)

IM 01C25R02-01E
<4. Diagnostics> 4-31
Value and Status (Data Quality and Limit Status)
HART
Integral Device Extended Differential Static External
configuration Loop
Indicator Status Device Status Flow Pressure Pressure Temperature Total Flow % range
tool display current
(DP) (SP) (ET)
AL.87 FT high --- Maintenance Value: Measured value In the case “Off” is set
FLG. HI alarm Required Status: Good and Not Limited to Diag Out Option
(0x01) Value: Measured
value
Status: Good and
Not Limited
In the case “Burnout”
is set to Diag Out
Option
Value: Low Limited/
AL.87 FT low High Limited
FLG. LO alarm Status: Bad and
Low Limited/High
Limited*1
In the case “Fall back”
is set to Diag Out
Option
Value: Fixed value
Status: Bad and
Constant

AL.88 Invalid Ref Value: Measured value


INVR.DP DP Status: Good and Not Limited
AL.88 Invalid Ref
INVR.SL SPL
AL.88 Invalid Ref
INVR.SH SPH
AL.88 Invalid
INVR.F Ref F
AL.89 ILBD over Value: Measured value
ILBD.OV range Status: Good and Not Limited
AL.89 B Blocking Value: Measured value In the case “Off” is set
B BLK Status: Good and Not Limited to Diag Out Option
Value: Measured
value
AL.89 H Side
Status: Good and
H BLK Blocking
Not Limited
In the case “Burnout”
AL.89 L Side is set to Diag Out
L BLK Blocking Option
Value: Low Limited/
AL.89 Large Fluct High Limited
H LRG H Status: Bad and
Low Limited/High
Limited*1
AL.89 Large Fluct In the case “Fall back”
L LRG L is set to Diag Out
Option
AL.89 A Blocking Value: Fixed value
A BLK Status: Bad and
Constant

AL.90 Flow --- Device Value: Value: Measured value Value: Same as Value and
SIM Simulation Variable Alert Measured Status: Good and Not Limited Measured Status of PV
mode (0x02) value or value
Status: Value: Simulation value Status:
Good and Status: Manual/Fixed and Constant Good and
Not Limited Not Limited
*1: Depend on the setting of hardware switch
*2: Depend on the direction of range over (high or low)

IM 01C25R02-01E
<4. Diagnostics> 4-32
Value and Status (Data Quality and Limit Status)
HART
Integral Device Extended Differential Static External
configuration Loop
Indicator Status Device Status Flow Pressure Pressure Temperature Total Flow % range
tool display current
(DP) (SP) (ET)
AL.91 F Simulate In the case Device Value and Same as Value and
F. SIM Mode of PV: Variable Alert Status: Status of PV
Loop (0x02) Flow
Current simulation
Fixed value
AL.91 P Simulate (0x08) Value and Value: Measured value
P. SIM Mode Status: Status: Good and Not Limited
Pressure
simulation
value
AL.91 SP Simulate Value and
SP.SIM Mode Status:
Static
Pressure
simulation
value
AL.91 ET Simulate Value: Measured value Value and
ET.SIM Mode Status: Good and Not Limited Status:
Temperature
simulation
value
AL.91 TF Simulate --- Value and Value: Measured
TF.SIM Mode Status: value
Total Flow Status: Good and Not
simulation Limited
value
AL.91 % Simulate Loop Device Value: Measured value Value and Status:
PCT. SIM Mode Current Variable Alert Status: Good and Not Limited Simulation value (%)
AL.91 AO Fixed (0x02) Value and Status:
AO.SIM Simulate (0x08) Simulation value (mA)
Mode
*1: Depend on the setting of hardware switch
*2: Depend on the direction of range over (high or low)

IM 01C25R02-01E
<5. Parameter Summary> 5-1

5. Parameter Summary
Function Label Item Contents Default value Handling *1
Analog output AO alm typ Analog output alarm type High or Low R
AO lower limit Lower limit of analog output 3.8000 to 21.6000 mA 3.8000 mA W
AO upper limit Upper limit of analog output 3.8000 to 21.6000 mA 21.6000 mA W
Auto recover Auto-recover from hardware error Off or On On W
Analog output Clear D/A trim Reset analog output trim M
trim D/A trim Analog output trim with ammeter M
Scaled D/A trim Analog output trim with voltmeter M
Channel flags Analog channel flags 0x00 R
Burst mode Burst mode Burst mode *2 Off or On HART 5 Off W
Off or Wired HART Enabled
HART 7

Burst option Burst option Xmtr Variables, PV, % range/ W


current, Process vars/crnt
HART 5

Burst Xmtr Vals Burst transmitter values M


HART 5

Burst Command Burst Command *2 Cmd 1: PV Cmd 1: PV W


HART 7
Cmd 2: % range/current
Cmd 3: Dyn vars/current
Cmd 9: Device vars w/status
Cmd33: Device Variables
Cmd 48: Read Additional
Device Status.
Burst Variable Device Variable for the Burst Max 8 slots. Flow W
Code Message *2
HART 7

Burst Msg Trigger Burst Trigger Mode Selection Code (Continuous, Window, Rising, Continuous R
Mode *2 Falling, On-change)
HART 7

Set Burst Trigger Configure burst trigger Configure Burst Msg Trigger M
HART 7
Mode and Burst Trigger Level

Set Burst Period Configure burst period Configure Update Period and M
HART 7
Max Update Period

Burst Trigger Level Burst Trigger Level *2 0.0 R


HART 7

Update Period Update Period for Burst mode *2 Update period for burst Burst Message R
HART 7
message 1: 0.5sec
2: 60sec
3: 60sec
Max Update Period Max Update Period for Burst mode Maximum update period for 60 min R
HART 7
*2 burst message

Date Date Date **/**/** W


Descriptor Descriptor Descriptor 16 alphanumerics W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-2
Function Label Item Contents Default value Handling *1
Device Country Country code US, JP, DE, FR, ES, RU, CN JP W
information
HART 7

Dev id Device ID R
Distributor Yokogawa R
Drain vent matl Drain and vent plug material W
Extra No. Customizaion number R
Ext SW External zeroing permission Disabled or Enabled Disabled W
Fill fluid Fill fluid W
Final asmbly num Final assembly number W
Fld dev rev Field device revision R
Gasket matl Gasket material W
Isoltr matl Capsule material W
Mftr Date Manufactured date R
Model 1/MS Code 1 Memo field for MS code 1 32 alphanumerics W
Model 2/MS Code 2 Memo field for MS code 2 32 alphanumerics W
Model 3/MS Code 3 Memo field for MS code 3 32 alphanumerics W
Num of RS Number of remote seal W
Process Conn matl Process connection material W
Process Conn size Process connection size W
Process Conn type Process connection type W
PT100 Serial No. Serial number of PT100 W
RS fill fluid Fill fluid of remote seal W
RS Isoltr matl Remote seal material W
RS type Remote seal type W
Serial No. Serial number R
Sofftware rev Software revision R
Style No. Style number Style number of product R
Universal rev Universal revision 16 alphanumerics R
Cfg chng count Configuration change counter 0 R
HART 7

Reset Cfg chng flag Reset Configuration change flag M


HART 7

Device Profile Device Profile Process R


HART 7
automation
device
Max dev vars Max device variables 3 R
HART 7

Model Model Model name + Measurement R


span in the Suffix Codes
Ex) “EJX910 M”
Device Simulate Execution of device variable Execute the simulation M
Variable HART 7
simulation
Simulation
Diag Diag Applicable Appicable blockage detection Disabled or Enabled RG
Applicable
Diag DPComp Diag DPComp fDP compensation selection Compensation or Compensation WG
Non-compensation
Diag Error Diag Error Results detected by ILBD or Heat RG
trace monitoring
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-3
Function Label Item Contents Default value Handling *1
Diag Lim Lim fDPmax Upper limit for Ratio fDP Refer to Table 4.2.3 WG
Lim fDPmin Lower limit for Ratio fDP Refer to Table 4.2.3 WG
Lim fSPlmax Upper limit for Ratio fSPl Refer to Table 4.2.3 WG
Lim fSPlmin Lower limit for Ratio fSPl Refer to Table 4.2.3 WG
Lim fSPhmax Upper limit for Ratio fSPh Refer to Table 4.2.3 WG
Lim fSPhmin Lower limit for Ratio fSPh Refer to Table 4.2.3 WG
Lim BlkFmax Upper limit for BlkF Refer to Table 4.2.3 WG
Lim BlkFmin Lower limit for BlkF Refer to Table 4.2.3 WG
Lim DPAvgmax Upper limit for DPAvg Refer to Table 4.2.3 WG
Lim DPAvgmin Lower limit for DPAvg Refer to Table 4.2.3 WG
Diag Mode Diag Mode ILBD operation mode Stop, Calculation, or WG
Reference
Diag Option Diag Option Alarm masking WG
Diag Output Diag Out Option Output mode of 4-20mA when Off, Burnout, or Fall back Off WG
an advanced diagnostic alarm is
generated
Diag Fixed Out Val 4-20 mA output when an advanced 3.8000 to 21.6000 mA 21.6 mA WG
diagnostic alarm is generated
Diag Period Diag Period Sampling period per one Diag count 180 sec WG
Diag Diag Description Memo field 32 alphanumerics WG
Reference Ref fDP Reference value of fDP WG
Ref fDP Status Status of Reference fDP RG
Ref fSPl Reference value of fSPl WG
Ref fSPl Status Status of Reference fSPl RG
Diag Ref fSPh Reference value of fSPh WG
Reference Ref fSPh Status Status of Reference fSPh RG
Ref BlkF Reference value of BlkF WG
Ref BlkF Status Status of Reference BlkF RG
Ref DPAvg Reference value of DPAvg WG
Ref DPAvg Status Status of Reference DPAvg RG
Diag Ref Lim Ref Lim fDPmin Lower limit of fDP 7.0E-10 WG
Ref Lim fSPmin Lower limit of fSPl and fSPh 1.0E-10 WG
Ref Lim BlkFmax Upper limit of BlkF 0.5 WG
Diag Supp Diag Supp Count Detection count to generate an WG
Count alarm
Diag Variables Ratio fDP SQRT (fDP/Ref fDP). RG
Ratio fDP Status Status of Ratio fDP RG
Ratio fSPl SQRT (fSPl/Ref fSPl). RG
Ratio fSPl Status Status of Ratio fSPl RG
Ratio fSPh SQRT (fSPh/Ref fSPh). RG
Ratio fSPh Status Status of Ratio fSPh RG
BlkF Blockage degree characterized in RG
comparison of high-pressure side
and low-pressure side pressure
fluctuation values
BlkF Status Status of BlkF RG
DPAvg Ratio of the average of differential RG
pressure/pressure to the maximum
span of an EJX transmitter.
DPAvg Status Status of DPAvg RG
CRatio fDP Compensated fDP RG
CRatio fDP Status Status of CRatio fDP RG
NRatio fDP Non-compensated fDP RG
NRatio fDP Status Status of NRatio fDP RG
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-4
Function Label Item Contents Default value Handling *1
Display setup Bar Indicator Bar indicator Off or On On W
Disp Out 1/Disp1 LCD output 1 PV %, Flow, Pres, SP, EXT. PV % W
TEMP, ENGR.PV, or TOTAL
FLOW
Disp Out 2/Disp2 LCD output 2 PV %, Flow, Pres, SP, EXT. Not used W
TEMP, ENGR.PV, TOTAL
FLOW, or Not used
Disp Out 3/Disp3 LCD output 3 (Ditto) Not used W
Disp Out 4/Disp4 LCD output 4 (Ditto) Not used W
Disp % Reso % display resolution Normal or High resolution Normal W
Engr exp User set exponent ---, x10, x100, x1000 --- or as W
specified
Engr LRV User set lower range value Unit specified in Set Engr Unit As specified W
Engr point Decimal place for user set 0 to 4 2 W
Engr URV User set upper range value Unit specified in Set Engr Unit As specified W
ET disp point Decimal place for external 0 to 4 2 W
temperature
Flow disp point Decimal place for flow 0 to 4 2 W
Modify Engr Unit User set engineering unit M
Pres disp point Decimal place for differential 0 to 4 2 W
pressure
Set Engr Unit Engineering unit select M
SP disp point Decimal place for static pressure 0 to 4 2 W
TF disp point Decimal place for total flow 0 to 4 2 W
Squawk Squawk Specify the device under the M
HART 7
communication (turn the LCD
on).
DP setup Pres Damp Damping time constant for DP 0.00 to 100.00 sec W
Pres Min Span Minimum span for differential R
pressure
Pres LRV Lower range value for differential W
pressure
Pres LSL Lower sensor limit for differential R
pressure
Pres URV Upper range value for differential W
pressure
Pres USL Upper sensor limit for differential 0 to 4 R
pressure
Error log Error log Clear Clear error records M
Error log view Error records Log1 (latest) to log4 M
ET setup ET Damp Damping time constant for ET 0.00 to 100.00 sec W
ET Fixed External temperature fix mode No,Yes, or FALL BACK No W
ET Min Span Minimum span for external R
temperature
ET LRV Lower range value for ET W
ET LSL Lower sensor limit for ET R
ET URV Upper range value for ET W
ET USL Upper sensor limit for ET R
Fixed ET Val Temperature value at ET fix mode 20 °C (deg C) W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-5
Function Label Item Contents Default value Handling *1
Event Event Notification Event Notification (Enable event notification on Off W
Notification Control token-passing data link layer,
HART 7
Off)

Device Status Event Masking W


Mask
HART 7

Status group 1 to
11 Mask
HART 7

Ext dev status


Mask
HART 7

Device Diagnostic
Status 0 Mask
HART 7

Device Diagnostic
Status 1 Mask
HART 7

AO saturated Mask
HART 7

AO fixed Mask
HART 7

Set Event Configure Event Notification Timing Configure Event Notification M


Notification Timing Retry Time, Event Max
Update Time and Event
HART 7 Debounce Interval
Event Notification Event Notification Retry Time R
Retry Time
HART 7

Max Update Time Max Update Time for Event R


HART 7
Notification

Event Debounce Event Debounce Interval Debounce Interval to detect R


Interval an event.
HART 7

Acknowledge Event Acknowledge Event Notification W


Notification
HART 7

Event Status Event Status 0x00 Approved event or no R


HART 7
event
0x10 Configuration changed
event pending
0x20 Device status event
pending
0x40 More status available
event pending
Event Number Event Number W
HART 7

Time First Unack Time First Unack Event Triggered W


Event Triggered
HART 7

Latched Cfg chng Latched Cfg chng count W


count
HART 7

*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-6
Function Label Item Contents Default value Handling *1
Event Latched Device Device status when event occurred W
Notification Status
HART 7

Latched Status Field device status when event W


group 1 to 11 occured
HART 7

Latched Ext dev


status
HART 7

Latched Device
Diagnostic Status 0
HART 7

Latched Device
Diagnostic Status 1
HART 7

Latched AO
saturated
HART 7

Latched AO fixed
HART 7

Flow setup Flow Damp Damping time constant for flow 0.00 to 100.00 sec W
Flow LRV Lower range value for flow W
Flow URV Upper range value for flow W
Vol Flow Base Dens Volume Flow Base Density Value W
Flg temp Flg temp Calculated flange temperature RG
value
Flg temp Coef Flg temp Coef 0 WG
Flg temp Lim Flg temp Hi Alarm Upper limit of Flange temperature 120 °C (deg C) WG
Val
Flg temp Lo Alarm Lower limit of Flange temperature -40 °C (deg C) WG
Val
Fluct Variables fDP Average value of the sum of RG
squares of differential pressure/
pressure fluctuations
fDP Status Status of fDP RG
fSPl Average value of the sum of RG
squares of low-pressure-sidestatic
pressure fluctuations
fSPl Status Status of fSPl RG
fSPh Average value of the sum of RG
squares of high-pressure-side
static pressure fluctuations
fSPh Status Status of fSPh RG
Flg temp Flg temp Calculated flange temperature RG
value
Keypad Input Change PV Assgn Change the allocation to PV M
PV Damp Damping time constant for PV W
PV is Current PV R
PV LRV Lower range value for PV W
PV URV Upper range value for PV W
Loop test Loop test Test output setting Within AO lower and upper M
limits
Test Auto Release “Flow simulation”, “DO Test” 10min, 30min, 60min, 3h, 10min W
Time and “Test output” duration time 6h, 12h
selection.
Low cut Low cut Low cut 0.00 to 20.00% 10.00% W
Low cut mode Low cut mode Off or On Off W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-7
Function Label Item Contents Default value Handling *1
Master test Master test Software reset and self test M
Message Message Message 32 alphanumerics As specified W
Model Model Model W
Number of Num req preams Number of requested preambles R
requested
preambles Num resp preams Number of response preambles 5 W
HART 7

Optional Optional function activation


Option Password W
function password
Piping H/L Swap Impulse piping accessing direction Normal or Reverse Normal R
orientation
Poll address Poll addr Poll address for multidrop use 0 to 15(HART 5), 0 to 0 W
63(HART 7)
Loop current mode Loop current mode in Multi Drop (Disabled, Enabled) Disabled W
HART 7
mode

Process Alerts Digital Output Display of contact output Off or On Off W


DO Frequency Frequency of Digtal Output W
DO Select Contact output select Combination of Pres, SP, W
Temp, and Flow
DO Signal type Signal type select On When Al. Detect, Off W
When Al. Detect, Scaled
Pulse, or Frequency
DO Test Test output contact Status High, Status Low, M
Freguency, Exit
Test Auto Release “Flow simulation”, “DO Test”, 10min, 30min, 60min, 3h, 10min W
Time “Device Variable Simulation” 6h, 12h
and “Test output” duration time
selection.
Pres Alert Mode Alert Mode for differential pressure Off, Hi Al Detect,Lo Al Detect, Off W
Hi/Lo Al Detect
Pres Hi Alert Val High alert value for differential Set the threshold value for W
pressure high side alarm
Pres Lo Alert Val Low alert value for differential Set the threshold value for W
pressure low side alarm
SP Alert Mode Alert Mode for static pressure Off, Hi Al Detect,Lo Al Detect, Off W
Hi/Lo Al Detect
SP Hi Alert Val High alert value for static pressure Set the threshold value for W
high side alarm
SP Lo Alert Val Low alert value for static pressure Set the threshold value for W
low side alarm
ET Alert Mode Alert Mode for external temperature Off, Hi Al Detect,Lo Al Detect, Off W
Hi/Lo Al Detect
ET Hi Alert Val High alert value for external Set the threshold value for W
temperature high side alarm
ET Lo Alert Val Low alert value for external Set the threshold value for W
temperature low side alarm
Flow Alert Mode Alert Mode for flow Off, Hi Al Detect,Lo Al Detect, Off W
Hi/Lo Al Detect
Flow Hi Alert Val High alert value for flow Set the threshold value for W
high side alarm
Flow Lo Alert Val Low alert value for flow Set the threshold value for W
low side alarm
Process Change 4V Assgn Change the allocation to 4V M
variables HART 5

4V 4V value Unit specified in 4V Unit R


HART 5

4V is Current 4V R
HART 5

Amp temp Amplifier temperature R


Cap temp Capsule temperature R
Engr Disp User scaled value Unit specified in Set Engr Unit R
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-8
Function Label Item Contents Default value Handling *1
Process Engr exp Exponents x1, x10, x100, or x1000 As specified W
variables or -
Engr Unit User set engineering unit Unit specified in Set Engr Unit R
ET External temperature value R
ET Data Quality*3 Device variable process data Device variable process R
HART 7
quality data quality of external
temperature
ET Limit Status Device variable limit status Device variable limit status of R
HART 7
external temperature

ET Update time ET Update time period 400ms R


period
HART 7

Flow Flow value R


Flow Data Quality*3 Device variable process data Device variable process data R
HART 7
quality quality of flow rate

Flow Limit Status Device variable limit status Device variable limit status of R
HART 7
flow rate

Flow Update time Flow Update time period 100ms R


period
HART 7

Loop Current Loop current value 3.8 to 21.6 mA R


HART 7
(Analog Output Current)

Loop Current Data Device variable process data Device variable process data R
Quality*3 quality quality of Loop Current (mA)
HART 7

Loop Current Limit Device variable limit status Device variable limit status of R
Status Loop Current (mA)
HART 7

Pres Differential pressure value R


Pres Data Quality*3 Device variable process data Device variable process data R
HART 7
quality quality of differential pressure

Pres Limit Status Device variable limit status Device variable limit status of R
HART 7
differential pressure

Pres Update time Pres Update time period 100ms R


period
HART 7

Change PV Assign Change the allocation to PV M


PV PV value Unit specified in PV Unit R
PV is Current PV R
PV % PV value in % -2.50 to 110.00% R
HART 5

PV AO Analog output current 3.8000 to 21.6000 mA R


HART 5

PV Data Quality*3 Device variable process data Device variable process data R
HART 7
quality quality of PV

PV Limit Status Device variable limit status Device variable limit status R
HART 7
of PV

Change QV Assgn Change the allocation to QV M


HART 7

QV QV value Unit specified in QV Unit R


HART 7

*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-9
Function Label Item Contents Default value Handling *1
Process QV is Current QV R
variables HART 7

QV Data Quality*3 Device variable process data Device variable process data R
HART 7
quality quality of QV

QV Limit Status Device variable limit status Device variable limit status R
HART 7
of QV

% Range % of range value (PV value in %) -2.50 to 110.00% R


HART 7

% Range Data Device variable process data Device variable process data R
Quality*3 quality quality of % Range
HART 7

% Range Limit Device variable limit status Device variable limit status of R
Status % Range
HART 7

SP Static pressure value R


SP Data Quality*3 Device variable process data Device variable process data R
HART 7
quality quality of static pressure

SP Limit Status Device variable limit status Device variable limit status of R
HART 7
static pressure

SP Update time SP Update time period 100ms R


period
HART 7

Change SV Assgn Change the allocation to SV M


SV SV value Unit specified in SV Unit R
SV is Current SV R
SV Data Quality*3 Device variable process data Device variable process data R
HART 7
quality quality of SV

SV Limit Status Device variable limit status Device variable limit status R
HART 7
of SV

Total Flow Total flow value R


Total Flow Data Device variable process data Device variable process data R
Quality*3 quality quality of total flow
HART 7

Total Flow Limit Device variable limit status Device variable limit status of R
Status total flow
HART 7

Total Flow Update Total Flow Update time period 1s R


time period
HART 7

Change TV Assgn Change the allocation to TV M


TV TV value R
TV is Current TV R
TV Data Quality*3 Device variable process data Device variable process data R
HART 7
quality quality of TV

TV Limit Status Device variable limit status Device variable limit status R
HART 7
of TV

*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-10
Function Label Item Contents Default value Handling *1
Self test Self test Self-diagnostics M
Sensor trim Clear ET trim Reset ET trim to factory setting M
Clear P snsr trim Reset pressure trim to factory M
setting
Clear SP snsr trim Reset SP trim to factory setting M
ET trim External temperature trim M
Pres trim Pressure trim M
SP trim Static pressure trim M
Trim Date Trim date **/**/** W
Trim Desc Trim description 16 alphanumerics W
Trim Loc Trim location 8 alphanumerics W
Trim Who Trim person 8 alphanumerics W
Simulation/ (Flow) Simulation Simulate Flow Mode W
Flow Mode
Simulation (Flow) Sim Pres Differential pressure value for W
simulation
(Flow) Sim Pres Differential pressure unit for W
Unit simulation
(Flow) Sim SP Static pressure value for simulation W
(Flow) Sim SP Unit Static pressure unit for simulation W
(Flow) Sim Temp Temperature value for simulation W
(Flow) Sim Temp Temperature unit for simulation W
Unit
Basic Flow Flow Calc Fixed Calculation fixation value of flow W
Calc Flow Calc mode Flow cauculation mode Auto Comp. Mode or Basic W
Mode
Fluid Type Fluid type W
Ref SP Referrence static pressure W
Ref Temp Referrence temperature W
Temp K1 The first in temperature correction W
coefficient for liquid
SP setup A/G Select W
Atm. Pres Value W
SP Damp Damping time constant for SP As specified or - W
SP H/L Select W
SP Min Span Minimum span for static pressure R
SP LRV Lower range value for static W
pressure
SP LSL Lower sensor limit for static R
pressure
SP URV Upper range value for static W
pressure
SP USL Upper sensor limit for static R
pressure
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<5. Parameter Summary> 5-11
Function Label Item Contents Default value Handling *1
Status Status group 1 Device status information for Display the hardware error R
hardware
Status group 2 Device status information for Display the hardware error R
hardware
Status group 3 Device status information for Display the process error R
process (Out of specification)
Status group 4 Device status information for Display the process error R
process (Out of setting range)
Status group 5 Device status information for Display the process error R
process (Alarm)
Status group 6 Device status information for data Display the setting error R
Status group 7 Device status information for data Display the setting error R
Status group 8 Device status information for data Display the setting error and R
process error (Alarm)
Status group 9 Device status information for data Display the diagnostic alarm R
Status group 10 Device status information for data Display the diagnostic alarm R
Status group 11 Device status information for data Display the simulation mode R
HART 7

Ext dev status Extended Device Status R


HART 7

Tag Tag Tag number 16 alphanumerics As specified W


Long tag Long tag Max 32 alphanumerics As specified W
HART 7

Test key Test key Special maintenance parameter M


Total Flow Cvt Val Convert value for total flow base W
unit
Freq at 100% Digtal otput fequency at 100% W
Pulse rate Pulse rate W
Modify Unit Modify flow base unit M
Set Base Unit Set total flow base unit M
Total Flow Mode Total flow mode Reset, Start, Start Cyclic or W
Stop
Total Flow Unit Current total flow unit W
Units Density Unit Density unit W
ET Unit External temperature unit W
Flow Unit Flow unit W
Pres Unit Differential pressure unit W
PV Unit PV unit W
SP Unit Static pressure unit W
SV Unit SV unit W
Total Flow Unit Total flow unit W
TV Unit TV unit W
4V Unit 4V unit W
HART 5

QV Unit QV unit W
HART 7

Write Enable wrt 10min Write protection release 8 alphanumerics M


protection New password User set password for write 8 alphanumerics M
menu protection
Write protect Write protection indicator Yes or No No R
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

IM 01C25R02-01E
<Appendix1. Safety Instrumented Systems Installation> A1-1

Appendix 1. Safety Instrumented Systems


Installation
The calibration of the transmitter must be performed
WARNING after parameters are set.

The contents of this appendix are cited from A1.2.4 Required Parameter Settings
exida.com safety manual on the EJX series
The following parameters need to be set in order to
pressure transmitters specifically observed for
maintain the designed safety integrity.
the safety transmitter purpose. When using the
EJX for Safety Instrumented Systems (SIS) Table A1.1 Required Parameter Settings
application, the instructions and procedures in Item Description
this section must be strictly followed in order to Burnout direction To specify if the output should go
preserve the transmitter for that safety level. switch 21.6 mA or higher or 3.6 mA or lower
upon detection of an internal failure.
Write protection The write function should be
switch disabled.
A1.1 Scope and Purpose
This section provides an overview of the user A1.2.5 Proof Testing
responsibilities for installation and operation of the
EJX in order to maintain the designed safety level The objective of proof testing is to detect failures
for Safety Instrumented Systems (SIS) applications. within the transmitter that are not detected by the
Items that will be addressed are proof testing, repair diagnostics of the transmitter. Of main concern
and replacement of the transmitter, reliability data, are undetected failures that prevent the safety
lifetime, environmental and application limits, and instrumented function from performing its intended
parameter settings. function. See table A1.2 for proof testing method.
The frequency of the proof tests (or the proof
test interval) is to be determined in the reliability
A1.2 Using the EJX for an SIS
calculations for the safety instrumented functions
Application for which the EJX is applied. The actual proof tests
must be performed more frequently or as frequently
A1.2.1 Safety Accuracy as specified in the calculation in order to maintain
The EJX has a specified safety accuracy of 2%. required safety integrity of the safety instrumented
This means that the internal component failures are function.
listed in the device failure rate if they will cause an The following tests need to be specifically executed
error of 2% or greater. when a proof test is performed. The results of
the proof test need to be documented and this
A1.2.2 Diagnostic Response Time documentation should be part of a plant safety
The EJX will report an internal failure within 5 management system. Failures that are detected
seconds of the fault occurrence. should be reported to Yokogawa.
The personnel performing the proof test of the
A1.2.3 Setup
transmitter should be trained in SIS operations
During installation the transmitter must be setup including bypass procedures, EJX transmitter
with engineering units parameters. This is typically maintenance, and company management of
done with a handheld terminal. These parameters change procedures.
must be verified during the installation to insure
that the correct parameters are in the transmitter.
Engineering range parameters can be verified by
reading these parameters from the optional local
display or by checking actual calibration of the
transmitter.

IM 01C25R02-01E
<Appendix1. Safety Instrumented Systems Installation> A1-2
Table A1.2 Proof Testing
Testing method Tools required Expected outcome Remarks
Functional test: • Handheld terminal Proof Test Coverage The output needs to be
1. Follow all Management of Change =52% monitored to assure that the
procedures to bypass logic solvers if transmitter communicates
necessary. the correct signal.
2. Execute HART/BRAIN command to
send value to high alarm (21.5 mA) and
verify that current has reached this level.
3. Execute HART/BRAIN command to
send value to low alarm (3.6 mA) and
verify that current has reached this level.
4. Restore logic solvers operation and
verify.
Perform three point calibration along with • Handheld terminal Proof Test Coverage
the functional test listed above. • Calibrated pressure =99%
source

A1.2.6 Repair and Replacement The development process of the EJX is certified up
to SIL3, allowing redundant use of the transmitter
If repair is to be performed with the process online
up to this Safety Integrity Level, depending
the EJX will need to be bypassed during the
the PFDavg calculation of the entire Safety
repair. The user should setup appropriate bypass
Instrumented Function.
procedures.
When using the transmitter in a redundant
In the unlikely event that the EJX has a failure, the
configuration, the use of a common cause factor
failures that are detected should be reported to
(β-factor) of 2% is suggested. (However, if the
Yokogawa.
redundant transmitters share an impulse line or if
When replacing the EJX, the procedure in the clogging of the separate impulse lines is likely, a
installation manual should be followed. common cause factor of 10% is suggested.)
The personnel performing the repair or replacement Note that the failure rates of the impulse lines need
of the EJX should have a sufficient skill level. to be accounted for in the PFDavg calculation.

A1.2.7 Startup Time A1.2.10 Lifetime Limits


The EJX generates a valid signal within 1 second of The expected lifetime of the EJX is 50 years. The
power-on startup. reliability data listed the FMEDA report is only valid
for this period. The failure rates of the EJX may
A1.2.8 Firmware Update increase sometime after this period. Reliability
In case firmware updates are required, they calculations based on the data listed in the FMEDA
will be performed at factory. The replacement report for EJX lifetimes beyond 50 years may yield
responsibilities are then in place. The user will not results that are too optimistic, i.e. the calculated
be required to perform any firmware updates. Safety Integrity Level will not be achieved.

A1.2.9 Reliability Data A1.2.11 Environmental Limits


A detailed Failure Mode, Effects, and Diagnostics The environmental limits of the EJX are specified in
Analysis (FMEDA) report is available from the user’s manual IM 01C25.
Yokogawa with all failure rates and failure modes.
A1.2.12 Application Limits
The EJX is certified up to SIL2 for use in a simplex
(1oo1) configuration, depending on the PFDavg The application limits of the EJX are specified in the
calculation of the entire Safety Instrumented user’s manual IM 01C25. If the transmitter is used
Function. outside of the application limits, the reliability data
listed in A1.2.9 becomes invalid.

IM 01C25R02-01E
<Appendix1. Safety Instrumented Systems Installation> A1-3
A1.3 Definitions and A1.3.2 Abbreviations
Abbreviations FMEDA Failure Mode, Effects and Diagnostic
Analysis
A1.3.1 Definitions
SIF Safety Instrumented Function
Safety Freedom from unacceptable
SIL Safety Integrity Level
risk of harm
SIS Safety Instrumented System
Functional Safety The ability of a system to carry
out the actions necessary SLC Safety Lifecycle
to achieve or to maintain a
defined safe state for the
equipment/machinery/plant/
apparatus under control of the
system
Basic Safety The equipment must be
designed and manufactured
such that it protects against
risk of damage to persons
by electrical shock and other
hazards and against resulting
fire and explosion. The
protection must be effective
under all conditions of the
nominal operation and under
single fault condition
Verification The demonstration for each
phase of the life-cycle that the
(output) deliverables of the
phase meet the objectives
and requirements specified by
the inputs to the phase. The
verification is usually executed
by analysis and/or testing
Validation The demonstration that the
safety-related system(s) or
the combination of safety-
related system(s) and external
risk reduction facilities meet,
in all respects, the Safety
Requirements Specification.
The validation is usually
executed by testing
Safety Assessment The investigation to arrive at a
judgment -based on evidence-
of the safety achieved by
safety-related systems
Further definitions of terms used for safety
techniques and measures and the description of
safety related systems are given in IEC 61508-4.

IM 01C25R02-01E
<Appendix2. ILBD Check List> A2-1

Appendix 2. ILBD Check List


Fill out the below checklist according to the operation flow of the ILBD in order to keep the important
information for the blockage detection.

Checklist (1/5)
No. Items Parameters Result Example
1 4-20 mA Analog Signal Setting Off:  
Diag Out Option Burnout:  
• Select the output mode when an alarm is
generaed. Fall back:  
Diag Fixed Out Val mA 21.6 mA
2 Status Output Pres:  
SP:  
Temp:  
DO Select
Flow:  
Diag:  
All:  
3 Stability of Pres
(differential pressure/pressure) Status Good
under normal condition

• Check that the status of Pres is “GOOD”. Max.: Max.: 12.3 kPa
• Check the maximum and minimum values of Pres
Pres. Min.: Min.: 12.1 kPa
4 fDP under normal condition
fDP  
• Check that the value of fDP is more than
7x10-10.
5 Start to obtain Reference values
Diag Mode  
• Set "Reference" to Diag Mode.
6 End of Reference Value Sampling
Diag Mode  
• Check that Diag Mode is “Calculation” after
the time set to "Diag Period" passed.
7 Alarm setting Diag Option
A Blocking  
• Record the status of Checkbox in Diag
Large Fluct L  
Option.
Large Fluct H  
L Side Blocking  
H Side Blocking  
B Blocking  
Invalid Ref F  
Invalid Ref SPH  
Invalid Ref SPL  
Invalid Ref DP  
ILBD over range  

IM 01C25R02-01E
<Appendix2. ILBD Check List> A2-2
Checklist (2/5)
No. Items Parameters Result Example
8 Alarm status Diag Error
A Blocking  
• Check the alarm status shown in Diag Error.
• Check that the alarm status of “ILBD over Large Fluct L  
range” is not shown in Diag Error. Large Fluct H  
L Side Blocking  
H Side Blocking  
B Blocking  
Invalid Ref F  
Invalid Ref SPH  
Invalid Ref SPL  
Invalid Ref DP  
ILBD over range  
9 ILBD parameters Diag Period 180
Lim fDPmax 3.000000
• Record the values of parameters for ILBD
operation. Lim fDPmin 0.300000
• Check the status of parameters for ILBD Lim fSPlmax 5.000000
operation. Lim fSPlmin 0.500000
Lim fSPhmax 5.000000
Lim fSPhmin 0.500000
Lim BlkFmax 0.600000
Lim BlkFmin -0.600000
Lim DPAvgmax 1.000000
Lim DPAvgmin 0.050000
Diag Supp Count 3
Ref fDP* 7.43245E-09
*: Record the value after checked that the
Ref fSPl* 7.25765E-09
status of each parameter is “GOOD”.
Ref fSPh* 7.18374E-09
Ref DPAvg* 5.36425E+00
fDP* 7.48562E-09
fSPl* 7.23277E-09
fSPh* 7.14085E-09
BlkF* -0.287259
DPAvg* 0.055957

IM 01C25R02-01E
<Appendix2. ILBD Check List> A2-3
Checklist (3/5)

Go to the following step according to the result of "Invalid Ref xx" shown in the Diag Error of 8th check item.
Diag Error Check
Invalid Ref SPH Invalid Ref SPL Invalid Ref DP item
   → 10-a
   → 10-b

: The alarm is generated.


: The alarm is not generated.

No. Items Parameters Result Example


10-a Simulation of Blockage detection operation
• H Side Blocking: 10-a-1
• L Side Blocking: 10-a-2
• Both Side Blocking: 10-a-3
10-a-1 H Side Blocking
• Close the high-pressure side valve
completely.
• Record the values of fDP, fSPl, fSPh, BlkF, fDP* 7.48562E-09
and DPAvg after the certain time,
(Diag Period X Diag Supp Count), passed. fSPI* 7.23277E-09
fSPh* 7.14085E-09
*: Record the value after checked that the
status is “GOOD”. BlkF -0.287259
• Record the status of Checkbox in Diag Diag Option
Option. A Blocking  
• Check that the alarms status of “A Blocking”
and “H Side Blocking” are set. Large Fluct L  
Large Fluct H  
Note: If the alarm of “ILBD over range” is generated, L Side Blocking  
the valve may be closed too much tightly. Open H Side Blocking  
valve a little and record the updated status of the
parameters. B Blocking  
Invalid Ref F  
Invalid Ref SPH  
Invalid Ref SPL  
Invalid Ref DP  
ILBD over range  
• Check that the alarm of “H Side Blocking” is Diag Error
generated.
• Check that the alarm of “L Side Blocking” is L Side Blocking  
not generated. H Side Blocking  

IM 01C25R02-01E
<Appendix2. ILBD Check List> A2-4
Checklist (4/5)
No. Items Parameters Result Example
10-a-2 L Side Blocking
• Close the low-pressure side valve completely.
• Record the values of fDP, fSPl, fSPh, BlkF, fDP* 7.48562E-09
and DPAvg after the certain time,
(Diag Period X Diag Supp Count), passed. fSPI* 7.23277E-09
fSPh* 7.14085E-09
*: Record the value after checked that the
status is “GOOD”. BIkF -0.287259
• Record the status of Checkbox in Diag Diag Option
Option. A Blocking  
• Check that the alarms status of “A Blocking”
and “L Side Blocking” are set. Large Fluct L  
Large Fluct H  
Note: If the alarm of “ILBD over range” is generated, L Side Blocking  
the valve may be closed too much tightly. Open H Side Blocking  
valve a little and record the updated status of the
parameters. B Blocking  
Invalid Ref F  
Invalid Ref SPH  
Invalid Ref SPL  
Invalid Ref DP  
ILBD over range  
• Check that the alarm of “L Side Blocking” is Diag Error
generated.
• Check that the alarm of “H Side Blocking” is L Side Blocking  
not generated. H Side Blocking  
10-a-3 Both Side Blocking
• Close the both-pressure side valves
completely.
• Record the values of fDP, fSPl, fSPh, BlkF, fDP* 7.48562E-09
and DPAvg after the certain time,
(Diag Period X Diag Supp Count), passed. fSPI* 7.23277E-09
fSPh* 7.14085E-09
*: Record the value after checked that the
status is “GOOD”. BIkF -0.287259
• Record the status of Checkbox in Diag Diag Option
Option. A Blocking  
• Check that the alarms status of “H Side
Blocking”, “L Side Blocking”, and “B Blocking” Large Fluct L  
are set. Large Fluct H  
L Side Blocking  
Note: If the alarm of “ILBD over range” is generated, H Side Blocking  
the valve may be closed too much tightly. Open
valve a little and record the updated status of the B Blocking  
parameters. Invalid Ref F  
Invalid Ref SPH  
Invalid Ref SPL  
Invalid Ref DP  
ILBD over range  
• Check that the alarm of “B Blocking” is Diag Error
generated. B Blocking  

IM 01C25R02-01E
<Appendix2. ILBD Check List> A2-5
Checklist (5/5)
No. Items Parameters Result Example
10-b Simulation of Blockage detection operation
• Close completely the valve for the side where
the alarm of Invalid Reference Value is not
generated.
For the case that the high-pressure side value is
closed;
fDP* 7.48562E-09
• Record the values of fDP, fSPl, fSPh, BlkF,
and DPAvg after the certain time,
(Diag Period X Diag Supp Count), passed.
fSPh* 7.14085E-09
*: Record the value after checked that the
status is “GOOD”.
For the case that the low-pressure side value is
closed;
fDP* 7.48562E-09
• Record the values of fDP, fSPl, fSPh, BlkF,
and DPAvg after the certain time,
(Diag Period X Diag Supp Count), passed.
fSPI* 7.23277E-09
*: Record the value after checked that the
status is “GOOD”.
• Record the status of Checkbox in Diag Diag Option
Option. A Blocking  
• Check that the alarms status of “B Blocking” is
set. Large Fluct L  
Large Fluct H  
Note: If the alarm of “ILBD over range” is generated, L Side Blocking  
the valve may be closed too much tightly. Open H Side Blocking  
valve a little and record the updated status of the
parameters. B Blocking  
Invalid Ref F  
Invalid Ref SPH  
Invalid Ref SPL  
Invalid Ref DP  
ILBD over range  
• Check that the alarm of “B Blocking” is not Diag Error
generated. B Blocking  

IM 01C25R02-01E
i

Revision Information
 Title : EJX910A and EJX930A
Multivariable Transmitter HART Communication Type
 Manual No. : IM 01C25R02-01E

Edition Date Page Revised Item


1st Mar. 2005 — New publication
2nd Mar. 2009 — Add model EJX930A.
3rd Aug. 2009 3-25 and 3-26 3.5.10 Revise the description.
3-30 3.5.13 Add the detail of the status output hysteresis.
4th Apr. 2010 Revise the description for device revision 2.
1-4 1.4 Revise explanation of device revision.
1-4 1.5 Add explanation of DTM.
3-6 3.3 Add Advanced diagnostic and device revision 2 upgrade function
menu.
3-12 to 3-40 3.4, 3.5, 3.6
Add device revision 2 upgrade function operation.
4-2 to 4-18 4.2 Add Advanced diagnostic operation (for option code /DG6).
4-19 4.3 Add alarms regarding Advanced diagnostic.
5-1 5 Add Advanced diagnostic and device revision 2 upgrade function
parameters.
A-1 Appendix 1 Add check list for ILBD.
5th July 2011 Add HART 7
6th Mar. 2012 2-3 2.4 Revise revision in formation in Table 2.2.
3-6 3.1.1 Add parameters in the Pres Setup (DTM) menu.
3-13 3.2.1 Change the limitation of 'Date' in the table.
7th June 2014 3-22, 5-2 Revise default value of External Switch Mode.

IM 01C25R02-01E