15
OPERATING MANUAL
SEGBA DOCK SUD
GENERATOR
YOLVYINID
Fig. 3.5.1. Connection diagram for Generator Control EquipmentOPERATING MANUAL
SEGBA DOCK SUD
GENERATOR 3-16
3.6
EXCITATION SYSTEM
As shown in Fig. 3.6.1, the excitation system for the turbogenerator consists of:
exciter machine
rectifier unit
permanent-magnet generator, and
control equipment.
‘The arrangement permits the necessary excitation current to be fed to the field winding
of the main machine without any brush contact.
‘The shaft of the main revolving field machine carries the rotor of the ROTADUCT*
revolving-armature exciter machine. The stator of the exciter machine contains the
stationary exciter poles, and its rotating armature contains a three-phase winding with
totating silicon diodes which rectify the armature current. Connecting leads run
through a corresponding bore in the shaft to feed the DC current to the field winding of
‘the main machine.
‘The control equipment compares at its inputs the reference value against the actual
values from the main machine (for the parameters: voltage, reactive power or power
factor etc.) and alters the necessary exciter current to the exciter machine as a func-
tion of the differance between actual and reference values. The necessary excitation
energy is supplied from a permanent-magnet generator (PMG) flanged onto the exciter
machine.
To increase the magnetic flux of the PMG under load, a supplementary exciter winding
around the permanent magnets is fed via an auxiliary rectifier from the armature win-
ding of the exciter machine, This supplementary winding can also be used for magneti-
zation of the permanent pole is weakened, e.g. after a long period of shut-down or of
dismantiing.
* ROTADUCT: AEG proprietary name, from Rotating semiconductor“17
OPERATING MANUAL
SEGBA DOCK SUD
GENERATOR
Joye10U08 snouciyouAS : suojesoueBucsyoukg
ssejysruq e jo weiGeip jediouug uesojua}sing seule piimeyosdizuud
BYEMIIOS / SAN|EA e0Ualejoy
| ‘eyamys] / SenjeA jenOY
n
siayqoe: Areyrx
TSOUNOOIeSHN
Supum-“Ud& = Gujpuimy piel Bupa & Burpy piel
GunpIM-SG Bunppmpied Bunppim-Sa_——Bunpjompie
Jax JEYOXA Id
eujyoseundney UNDND-OU euyoseuueieu3
euIyseW UW ys rouney me JojeravaBjodjuaueuued
Tu NOES
Fig. 3.6.1 Principle diagram of a brushless turbogeneratorOPERATING MANUAL
SEGBA DOCK SUD
GENERATOR 3-18
3.6.1
EXCITER MACHINE
‘The exciter machine used is an eight-pole synchronous revolving-armature generator.
‘The laminated poles of the stator are bolted on inside the stator yoke. The pole cores
have insulated round-wire coils of electrolytic copper, and the pole shoes a closed
short-circuit damper winding formed of copper rods and connecting strips. Protective
caps bolted onto the stator yoke protect against electrically live or rotating parts, and
feed the cooling air. They can be removed for maintenance work.
The rotor body, welded from rolied steel, carries outside the laminated magnetic core,
in whose slots the armature winding lies. The armature winding consists of electrolytic
copper insulated with varnished glass silk. The end-windings are held by poly glass-
fibre bandages. The rotor body, including the lamination stack and the winding, is fully
impregnated in a vacuum impregnating plant.
The exciter machine, the rectifier unit and the permanent-magnet generator form a
single structural unit. The stationary portion is anchored onto the common base frame
‘by means of welded-on feet, and the rotating portion is flanged onto the main machine
shaft.
‘The three rectifier inserts within the rotor body are held by electrically insulating
mounts. The star-point connector ring of the armature winding and of the rectifier insert
are each bolted to a supply rail of the field winding of the main machine.
‘A tan bolted onto the drive side dissipates the haat generated in the windings and the
rectifier unit.
Fig. 3.6.1.1 Laminated poles of the StatorOPERATING MANUAL
‘SEGBA DOCK SUD
GENERATOR 3-19
3.6.2
RECTIFIER UNIT
‘The rectifier unit consists of three segment-shaped inserts, each comprising the heat
sink, the power diode and the RC module.
The diodes operate at highly derated voltage and current levels, to give highest
possible reliability,
Type AEG-D 1800 N 3600
Permissible reverse voitage 3600 V
Continuous limit current 1400 A at 120 °C
Peak surge current limit 25500 A max. 10 ms
‘The actual electrical operating conditions can be calculated from the technical data
(Section 1)
0, = 141 UE=209U,, (8. Fig. 3.6.1)
\ 0.33 |,
\ 0.577 ly
Vaat
In order to attenuate the peak voltage spikes occurring as the diodes commutate (TSE
effect), each rectifier has an RC module connected in parallel.
For redundancy reasons, each RC module consists of several individual resistorcapa-
citor links connected in parallel. If one component fails, the turbogenerator can still be
run at full continuous-duty rating without restrictions.
‘The capacitors are potted in a closed housing with insulating resin of high thermal
conductivity. The resistors are mounted on the cover of the housing, to achieve the
necessary coming
Fig. 3.6.2 Rectifier UnitOPERATING MANUAL
SEGBA DOCK SUD
GENERATOR 3-20
3.6.3
PERMANENT-MAGNET GENERATOR
‘The permanent-magnet generator serves to supply the necessary excitation energy for
the exciter machine and to supply the electronics of the control equipment. The ma-
Qnetically active part of the stator consists of low-loss dynamo steel in sheets 0.5 mm
thick, insulated one side. The laminations are compressed into a steel housing ring
and are held by compression rings at the face end. The haltclosed stator slots contain
the corded stator winding of varnish-insulated round wire. The entire stator package,
including the winding, is impregnated in a vacuum impregnating plant.
The rotor is designed as an eight-pole salient-pole rotor with solid pole core, perma-
nent-magnet plates and solid pole-shoes. The magnetic plates are made of magneti-
cally hard, anisotropic ALNICO material. Exciter coils of round wire are laid around the
eight pole-cores: these windings are likewise vacuumimpregnated. A short-circuit
damper winding of sheet copper encloses the
pole cores from all directions and bridges over the pole gaps.
‘The basic voltage induced by air-gap induction of the permanent magnets represents
about 60% of the rated voltage. The coils underneath the magnetic poles produce an
additional excitation varying with load, which prevents the PMG voltage from reducing
as the load increases.
Fig. 3.6.3 Rotor body of the Excitation System
In front: Salient poles of the PMGOPERATING MANUAL
SEGBA DOCK SUD
GENERATOR 3-21
oe
3.6.4
3.6.44
3.6.4.2
CONTROL EQUIPMENT
GENERAL
The control equipment is supplied as a self-contained unit in an Intermas cabinet.
Modular construction in a swing-out frame offers great flexiblity and unusually easy
access for maintenance, Adding additional systems at a later date to meet changed
operating conditions, for instance, can be achieved at minimum trouble and cost:
Either by inserting additional modules in existing, ready wired plug-in
positions,
or fitting supplementary systems into empty locations in the cabinet.
MODE OF OPERATION, CHARACTERISTIC DATA
The control equipment is designed as a
2-channel system (code letter: AM)
‘A: automatic channel
B: manual channel
‘The automatic channel is used for normal operation while the manual remains always
continuously available on standby, ready to take over manual control if necessary
without stopping the generator (s. Fig. 3.6.4.1). The manual channel is also especially
suitable for adjusting the protective circuitry and for use when commissioning the
turbogenerator (exciter current control)
The control equipment ensures
- high ceiling voltages for rapid and safe
‘excitation, when considerable over-excitation
is required for optimum system function.
By using
~ fully-controlled thyristor bridges, the system offers the
advantage of
= counter voltage excitation (inverter operation of SCR's)
of the brushless exciter G2 for rapid reductionof the exciter field current
‘evenduring de-excitation processes in case of sudden dropsin the applied
load.OPERATING MANUAL
‘SEGBA DOCK SUD
GENERATOR 3-22
= high service quality due to 2-channe! design and limiting regulation circuits.
‘The regulating channels (A- and M-channel) operate on independently fused, fuily-
controlled rectitier bridges, which are disconnected via overdimensioned block diodes
on the DC-voltage side for increases safety. The thyristors of the bridge, not being in
operation, are blocked by biocking circuits.
For emergency operation if the AC-powering circuit via pilot exciter fails and for testing
purposes the exciter can be supplied from the 3-phase AC-voltage network using.
‘And even in this operating condition all channels are fully operational.
Al regulator parameters which can be changed during operation are designed for
remote actuation and at the same time the regulator generates signals indicating the
mode of operation eto.
The whole excitation system is connected to other parts of the plant exclusively via
potential-isolating coupling elements (intermediate transformers, isolating converters,
relay contacts etc.)OPERATING MANUAL
SEGBA DOCK SUD
GENERATOR 3-23
Q1 main breaker
Gt main machine
G21 rectifier (rotating
aoe eee G2__ brushless exciter
m4 . G3_permament magnetic
generator
actual
values $21 AC-power selector switch
VP aver voltage protector
Q11_ excitation switch
V.. decoupling diodes
SCR silicon controlled rectifier
(Type: fully controtted
bridge)
firing pulse unit
remote.
(external)
Fig. 3.6.4 Rotaduct-Excitation and Control Equipment Standard version with pilot exciterOPERATING MANUAL
SEGBA DOCK SUD
6.2.4.3 AUTOMATIC-CHANNEL (AVR)
GENERATOR
The automatic channel offers not only the
U = const. voltage regulation code: A/C 02.30
but also the possibilty of regulatingfimiting other modes.
In addition the following limiting functions are installed:
react.
Ut =const. =
lexc. max.
pole-angle
Igen. max.
reactive droop compensation code: A 02.42
voltage proportional to
frequency at underspeed code: A 02.26
exciter current limiting
with time delay code: A 02.54
version: V20
rotor load angle limiting
max.(load dependent limiting of
the exciter current)
version: V40 code: A 02.70
stator current (main machine)
limiting with time delay
version: A7 code: A 02.58
Remark: The setting limit value is influenced
by temperatures of the cooling air.
For this a special plug-in is used.
Limit code: A 02.74OPERATING MANUAL
‘SEGBA DOCK SUD
GENERATOR 3-25
3.6.4.4 MANUAL-CHANNEL
‘The manual channel is designed as an exciter current controller.
lexe. Exciter current regulation
(subsidiary control loop) code: B 02.18
To prevent excessively high voltages (e.g. on isolating the machine from the grid), the
‘manual channel is always fitted with a voltage limitation circuit.
Umax. Overvoltage (main machine) limiter code: BO2.22
During the manual mode, the
reference setter B 02.10
must be continuously adjusted (via remote control) to match any load variations.
‘The electronic modules of the manual contro! device are largely identical with those of
the AVR, resulting in a low cost spare parts inventory.OPERATING MANUAL
SEGBA DOCK SUD
GENERATOR 3-26
3.6.4.5 TECHNICAL DATA
1. Type TSG2-PL3-AMO2-V10+V20+V404V71
TSG2- Thytistor controlled equipment
PL3- Power supply via - Pilot exciter or stabilized 380 V, 3 Ph. System
AMO2- Automatic / Manual / Version 02
(AM - Two channel regulator)
V- Additional System
V10- Electronic reference setter
20 Maximum excitation limiter
V40- Rotor angle limiter
71 - Stator current limiter, setting limit value of stator currant is
influenced by the cooling air temperature.
2. Power supply 3 KVA, 3 Phase: 150 V to 320 V 200 C/S Pilot
exciter or 380 V, 50 C/S-mains via potential transformer
3. Exciter Field Voltage
Field forcing 250 V DC max. at 220 V AC input
Rated exciter
field voltage max. 100 VDC
4. — Exciter Field Current
Field forcing 30 A max. for 20S
Rated exciter
field currant 4-12A
5. Generator Voltage Transformers
100 V + 10% (line to line)
50 c/s, 10 VA, class 0.5OPERATING MANUAL
SEGBA DOCK SUD
GENERATOR 3-27
6. Generator Current Transformers
1A+0%50 c/s, 10 VA
20%
Class and overcurrent factor: 1 M5
7. Setting Range:
Generator Voltage (A): 0.9 U, SU $1.1 U, (atno load)
Exciter Field Current (M): 0 < les 1-1 hey
U= Generator Voltage
U, = Nominal Generator Voltage
le = Exciter Field Current
he
| Exciter Field Current (nominal)
hen
8, Reactive Droop Setting Range 0 - 10 %
9. Accuracy of Control
Over entire control range + 0.5 %
10. Failsafe DC Power supply 125 VDC
11. Environmental Conditions
‘Storage temperature = 20 °C to 80°C
Operating temperature - 10 °C to 85 °C
Permissible relative humidity to DIN 40 040, Class G
More detailed information on the control is given in a separate service instruction.