A. GENERAL CHARACTERISTICS
Design standars : IEC 76
Transformer type : Totally Oil Filled
Service Condition : Indoor
Type of oil : Mineral Oil
Number of phase : 3 Phase
Frequency : 50 Hz
B. TECHNICAL SPECIFICATION
Capacity : 315 kVA
High voltage : 20 kV (Delta)
Low Voltage : 0.4 kV (Wye - Netral)
Vector Group : Dyn5
Cooling : ONAN
Temperature Rise : - Oil : 50 K
- Winding : 55 K
No load losses at nominal voltage : 700 Watts
Full load losses at nominal tapping : 4600 Watts
Impedance voltage at nominal tapping : 4 %
Off load current at nominal voltage : 2 %
Insulation Class : A
Sound Pressure Level at 0,3 m : 56 dB
Off Circuit tapping value : 7 Tap (+2x2.5% ; -4x2.5%)
Winding Material LV /HV : Copper / Copper
D. LIST OF TEST
Routine Test : Yes No
- Measurement of winding resistance : √
- Measurement of voltage ratio and check of phase displacement : √
- Measurement of short circuit impedance and load loss : √
- Measurement of no load loss and current : √
- Applied potensial test : √
- Induced Voltage test
* Test other than the above mentioned list needs further confirmation
Revision Original Client / project
Date No : TR-CIA7A41-OAAA
Dsg.
Chk Page : 1/2
App.
TECHNICAL SPECIFICATIONS
Surabaya - Indonesia
E. ACCESSORIES
- Name plate and rating plate - Corrugated fins
- HV Plug-in and LV porcelain bushings - Pressure relief device
- Oil filling valve - Dial type, oil temperature indicator
- Oil draining valve w/ sampling valve - Oil level indicator w/ sight glass
- Lifting lugs
- Ground base
- Grounding terminal, 2 unit
F. VISUAL ARRANGEMENT
* Dimension, weight & oil volume will be fixed after job order issued
H. DEVIATIONS / EXCEPTIONS
- None
I. NOTES
- None