Slab Design: Project Settings Page 1 of 1

PROJECT SETTINGS
Project Name : 2-Stories Commercial / Residential Bldg.
Client Name : Emma Pascual Calatan
Engineer Name : DSQ
Design File : F:\IRISAN PROJ_Empr\StaadProConnect Files\Emma Pascual
Calatan - 2 Stories Comml_Resdtl Bldg-R1-Slab-1-7.6m.R1.rcdx
Analysis File : F:\IRISAN PROJ_Empr\StaadProConnect Files\Emma Pascual
Calatan - 2 Stories Comml_Resdtl Bldg-R1.std
Analysis Last Modified : 10/09/2020 10:15:08 PM

Design Settings
Detailing Style : Curtailed Bars
Preferred Span/d
Cantilever : 7
Simply Supported (One-way Slab) : 20
Continuous (One-way Slab) : 26
Simply Supported (Two-way Slab) : 28
Continuous (Two-way Slab) : 32
Curtailment Location
Bottom End Support : L/6
Bottom Cont. Support : L/6
Top End Support : L/4
Top Cont. Support : L/4
Detailing Option : Diameter
Preferred Diameter : 10
Material Property
Analysis materials used : No
Concrete Grade : C20
Steel Grade : Fy275
Cover : 20 mm
Min. Slab Thickness : 100 mm
Rebars
Available Rebars : 8,10,12,16,20,25,32
Bar Spacing
Min. Spacing : 100 mm
Max. Spacing : 300 mm
Roundoff Factor : 5
Crack Width Settings:
Crack Width ACI 224R-01 Check : No

file:///C:/Users/darlq/AppData/Local/Temp/tmp9912.tmp 10/09/2020
Slab Design :Design Summary Page 1 of 3

SLAB DESIGN SUMMARY


Project Name : 2-Stories Commercial / Residential Bldg.
Client Name : Emma Pascual Calatan
Engineer Name : DSQ
Design File : F:\IRISAN PROJ_Empr\StaadProConnect Files\Emma Pascual
Calatan - 2 Stories Comml_Resdtl Bldg-R1-Slab-1-7.6m.R1.rcdx
Analysis File : F:\IRISAN PROJ_Empr\StaadProConnect Files\Emma Pascual
Calatan - 2 Stories Comml_Resdtl Bldg-R1.std
Analysis Last Modified : 10/09/2020 10:15:08 PM

Panel Types:
One Way Slab: 1. Simply Supported
2. End Span
3. Span Next to End Span
4. Interior Span

Two Way Slab: 1. Interior Panel


2. One Short Edge Discontinuous
3. One Long Edge Discontinuous
4. Two Adjacent Edges Discontinuous
5. Two Short Edges Discontinuous
6. Two Long Edges Discontinuous
7. Three Edges Discontinuous (One Long Edge Continuous)
8. Three Edges Discontinuous (One Short Edge Continuous)
9. Four Edges Discontinuous
10.Simply Supported On Four Sides

Level: 7.6m

Slab No. : S1
Ly = 3 m Lx = 3 m
Live Load = 1.9
Imposed Load = 3.76 kN/sqm
kN/sqm
Thickness = 150 mm Span Type = 2-Way Panel Type = 4
Design Code = ACI
Grade of Concrete = C20 Grade of Steel = Fy275
318M - 2011

Bottom SS Bottom LS Top SS Top LS Distribution


#10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250

Slab No. : S2
Ly = 3 m Lx = 3 m
Live Load = 1.9

file:///C:/Users/darlq/AppData/Local/Temp/tmp328.tmp 10/09/2020
Slab Design :Design Summary Page 2 of 3

kN/sqm Imposed Load = 3.76 kN/sqm


Thickness = 150 mm Span Type = 2-Way Panel Type = 2
Design Code = ACI
Grade of Concrete = C20 Grade of Steel = Fy275
318M - 2011

Bottom SS Bottom LS Top SS Top LS Distribution


#10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250

Slab No. : S3
Ly = 3 m Lx = 3 m
Live Load = 1.9
Imposed Load = 3.76 kN/sqm
kN/sqm
Thickness = 150 mm Span Type = 2-Way Panel Type = 4
Design Code = ACI
Grade of Concrete = C20 Grade of Steel = Fy275
318M - 2011

Bottom SS Bottom LS Top SS Top LS Distribution


#10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250

Slab No. : S4
Ly = 3 m Lx = 3 m
Live Load = 1.9
Imposed Load = 3.76 kN/sqm
kN/sqm
Thickness = 150 mm Span Type = 2-Way Panel Type = 4
Design Code = ACI
Grade of Concrete = C20 Grade of Steel = Fy275
318M - 2011

Bottom SS Bottom LS Top SS Top LS Distribution


#10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250

Slab No. : S5
Ly = 3 m Lx = 3 m
Live Load = 1.9
Imposed Load = 3.76 kN/sqm
kN/sqm
Thickness = 150 mm Span Type = 2-Way Panel Type = 2
Design Code = ACI
Grade of Concrete = C20 Grade of Steel = Fy275
318M - 2011

Bottom SS Bottom LS Top SS Top LS Distribution


#10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250

file:///C:/Users/darlq/AppData/Local/Temp/tmp328.tmp 10/09/2020
Slab Design :Design Summary Page 3 of 3

Slab No. : S6
Ly = 3 m Lx = 3 m
Live Load = 1.9
Imposed Load = 3.76 kN/sqm
kN/sqm
Thickness = 150 mm Span Type = 2-Way Panel Type = 4
Design Code = ACI
Grade of Concrete = C20 Grade of Steel = Fy275
318M - 2011

Bottom SS Bottom LS Top SS Top LS Distribution


#10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250 #10 @ 250

file:///C:/Users/darlq/AppData/Local/Temp/tmp328.tmp 10/09/2020
Page 1 of 14

SLAB DESIGN CALCULATIONS


Project Name : 2-Stories Commercial / Residential Bldg.
Client Name : Emma Pascual Calatan
Engineer Name : DSQ
Design File : F:\IRISAN PROJ_Empr\StaadProConnect Files\Emma Pascual
Calatan - 2 Stories Comml_Resdtl Bldg-R1-Slab-1-7.6m.R1.rcdx
Analysis File : F:\IRISAN PROJ_Empr\StaadProConnect Files\Emma Pascual
Calatan - 2 Stories Comml_Resdtl Bldg-R1.std
Analysis Last Modified : 10/09/2020 10:15:08 PM

NOTES:
1. Density of concrete assumed as 25 kN/Cum.

Definitions Of Terms: :
Ratio of flexural stiffness of beam section to flexural
1. αf =
stiffness of slab.
Ratio of torsional stiffness of edge beam section to
2. βt =
flexural stiffness of slab.
3. Φt = Strength reduction factor.
4. As = Area of Tension reinforcement required in sqmm.
5. As,min = Min area of flexural reinforcement in sqmm.
Area of longitudinal reinforcement provided at
6. AstPrv =
given section in sqmm.
Total area of longitudinal reinforcement calculated at
7. Ast =
a given section in sqmm.
8. b = Width of the Slab in mm.
9. B1 to B4 = Width of beams around slab in mm.
10. Cc = Effective Cover to tension reinforcement in mm.
cross-sectional constant to define torsional properties
11. CA and CB =
of slab and beam.
12. deff = Effective depth of slab in mm.
13. D1 to D4 = Depth of beams around slab.
14. Icr = Moment of Inertia of concrete crack section.
Length of clear span in direction that moment are
15. Ln =
being determined in mm.
16. L2 = Length of adjacent span of Ln in mm.
17. lb1 to lb2 = Moment of inertia of beams around slab in mm4.
18. Mcr = Cracking Moment.
19. Mu = Factored Bending Moment at a section in kNm.
20. Ptmin = Minimum percentage steel as per clause 10.
21. PtPrv = Provided percentage steel.
22. Vc = Nominal shear strength provided by concrete in kN.
23. Vu = Factored Shear Force at a section in kN.
24. Vud = Design Shear Force in kN.
25. y = Neutral axis depth.

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 2 of 14

Code References :
ACI 318M - 2011

Item CLAUSE / TABLE


1. Ptmax : 10.3.5
2. Ptmin : 7.12.2.1/10.5.4
3. Vc : 11.11.2.1
4. Av : 11.4.7.2
5. Moment calculations : 13.6
6. spacing between main bars : 10.5.4
7. spacing between distribution bars : 7.12.2.2
8. Minimum reinforcement : 7.12.2.1
9. fs,perm : 10.6.4
10. fc,perm : 10.2.7.1
10. Wcr : Eq 4.2(a)

Slab No. : S1
Level = 7.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C20
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.000 m
Short Span, Lx = 3.000 m
Imposed Load = 3.760 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 12.052 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL

Short Span Long Span


Side1 Side2 Side1 Side2
Beam
        B (mm) 250 250 250 250
        D (mm) 350 350 350 350
        Ib (mm4)    x106 893.23 893.23 893.23 893.23
Adjacent Slab
        Thk (mm) 150 - - 150
        Span (mm) 3000 - - 3000
        Ib (mm4)    x106 843.75 421.88 421.88 843.75
αf lx, αf ly 1.06 2.12 2.12 1.06
αf 1.59

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 3 of 14

Ln (mm) 2750 2750


L2 (mm) 1625 1625
Total BM (kNm) 18.51 18.51
Bottom
        Moment Coefficent 0.57 0.57
        Distributed Moment (kNm) 10.55 10.55
        CS Moment (kNm) 7.91 7.91
        MS Moment (kNm) 2.64 2.64
Moment on Beam (kNm) 6.73 6.73
        Design Moment M1, M3 (kNm) 1.19 1.19
Top
        Moment Coefficent 0.7 0.7
        Distributed Moment (kNm) 12.96 12.96
        CS Moment (kNm) 9.72 9.72
        MS Moment (kNm) 3.24 3.24
        Moment on Beam (kNm) 8.26 8.26
        Design Moment M2, M4 (kNm) 1.461 1.46

Design Moments:
Short Span Positive Moment At Midspan -
M1 = 1.187 kNm
Area Of Reinforcement = 38.469 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.458 kNm
Area Of Reinforcement = 47.270 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 1.187 kNm
Area Of Reinforcement = 41.833 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = 1.458 kNm
Area Of Reinforcement = 51.409 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 225.000 sqmm/m
Required
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 4 of 14

Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 9.039 kN
Nominal Shear, Vc = 95.033 kN
> 9.039 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x (1 = 9.039 kN
- (Lx / (2 x Ly))))
Nominal Shear, Vc = 87.430 kN
> 9.039 Slab Is Safe In Shear

Slab No. : S2
Level = 7.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C20
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.000 m
Short Span, Lx = 3.000 m
Imposed Load = 3.760 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 12.052 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL

Short Span Long Span


Side1 Side2 Side1 Side2
Beam
        B (mm) 250 250 250 250
        D (mm) 350 350 350 350
        Ib (mm4)    x106 893.23 893.23 893.23 893.23
Adjacent Slab
        Thk (mm) 150 150 - 150
        Span (mm) 3000 3000 - 3000
        Ib (mm4)    x106 843.75 843.75 421.88 843.75
αf lx, αf ly 1.06 1.06 2.12 1.06
αf 1.32
Ln (mm) 2750 2750
L2 (mm) 1625 1625
Total BM (kNm) 18.51 18.51

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 5 of 14

Bottom
        Moment Coefficent 0.35 0.57
        Distributed Moment (kNm) 6.48 10.55
        CS Moment (kNm) 4.86 7.91
        MS Moment (kNm) 1.62 2.64
        Moment on Beam (kNm) 4.13 6.73
        Design Moment M1, M3 (kNm) 0.73 1.19
Top
        Moment Coefficent 0.65 0.7
        Distributed Moment (kNm) 12.03 12.96
        CS Moment (kNm) 9.03 9.72
        MS Moment (kNm) 3.01 3.24
        Moment on Beam (kNm) 7.67 8.26
        Design Moment M2, M4 (kNm) 1.351 1.46

Design Moments:
Short Span Positive Moment At Midspan -
M1 = 0.729 kNm
Area Of Reinforcement = 23.599 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.354 kNm
Area Of Reinforcement = 43.884 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 1.187 kNm
Area Of Reinforcement = 41.833 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = 1.458 kNm
Area Of Reinforcement = 51.409 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 225.000 sqmm/m
Required
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 6 of 14

Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 9.039 kN
Nominal Shear, Vc = 95.033 kN
> 9.039 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x (1 = 9.039 kN
- (Lx / (2 x Ly))))
Nominal Shear, Vc = 87.430 kN
> 9.039 Slab Is Safe In Shear

Slab No. : S3
Level = 7.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C20
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.000 m
Short Span, Lx = 3.000 m
Imposed Load = 3.760 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 12.052 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL

Short Span Long Span


Side1 Side2 Side1 Side2
Beam
        B (mm) 250 250 250 250
        D (mm) 350 350 350 350
        Ib (mm4)    x106 893.23 893.23 893.23 893.23
Adjacent Slab
        Thk (mm) - 150 - 150
        Span (mm) - 3000 - 3000
        Ib (mm4)    x106 421.88 843.75 421.88 843.75
αf lx, αf ly 2.12 1.06 2.12 1.06
αf 1.59
Ln (mm) 2750 2750
L2 (mm) 1625 1625
Total BM (kNm) 18.51 18.51

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 7 of 14

Bottom
        Moment Coefficent 0.57 0.57
        Distributed Moment (kNm) 10.55 10.55
        CS Moment (kNm) 7.91 7.91
        MS Moment (kNm) 2.64 2.64
        Moment on Beam (kNm) 6.73 6.73
        Design Moment M1, M3 (kNm) 1.19 1.19
Top
        Moment Coefficent 0.7 0.7
        Distributed Moment (kNm) 12.96 12.96
        CS Moment (kNm) 9.72 9.72
        MS Moment (kNm) 3.24 3.24
        Moment on Beam (kNm) 8.26 8.26
        Design Moment M2, M4 (kNm) 1.461 1.46

Design Moments:
Short Span Positive Moment At Midspan -
M1 = 1.187 kNm
Area Of Reinforcement = 38.469 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.458 kNm
Area Of Reinforcement = 47.270 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 1.187 kNm
Area Of Reinforcement = 41.833 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = 1.458 kNm
Area Of Reinforcement = 51.409 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 225.000 sqmm/m
Required
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 8 of 14

Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 9.039 kN
Nominal Shear, Vc = 95.033 kN
> 9.039 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x (1 = 9.039 kN
- (Lx / (2 x Ly))))
Nominal Shear, Vc = 87.430 kN
> 9.039 Slab Is Safe In Shear

Slab No. : S4
Level = 7.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C20
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.000 m
Short Span, Lx = 3.000 m
Imposed Load = 3.760 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 12.052 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL

Short Span Long Span


Side1 Side2 Side1 Side2
Beam
        B (mm) 250 250 250 250
        D (mm) 350 350 350 350
        Ib (mm4)    x106 893.23 893.23 893.23 893.23
Adjacent Slab
        Thk (mm) 150 - 150 -
        Span (mm) 3000 - 3000 -
        Ib (mm4)    x106 843.75 421.88 843.75 421.88
αf lx, αf ly 1.06 2.12 1.06 2.12
αf 1.59
Ln (mm) 2750 2750
L2 (mm) 1625 1625
Total BM (kNm) 18.51 18.51

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 9 of 14

Bottom
        Moment Coefficent 0.57 0.57
        Distributed Moment (kNm) 10.55 10.55
        CS Moment (kNm) 7.91 7.91
        MS Moment (kNm) 2.64 2.64
        Moment on Beam (kNm) 6.73 6.73
        Design Moment M1, M3 (kNm) 1.19 1.19
Top
        Moment Coefficent 0.7 0.7
        Distributed Moment (kNm) 12.96 12.96
        CS Moment (kNm) 9.72 9.72
        MS Moment (kNm) 3.24 3.24
        Moment on Beam (kNm) 8.26 8.26
        Design Moment M2, M4 (kNm) 1.461 1.46

Design Moments:
Short Span Positive Moment At Midspan -
M1 = 1.187 kNm
Area Of Reinforcement = 38.469 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.458 kNm
Area Of Reinforcement = 47.270 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 1.187 kNm
Area Of Reinforcement = 41.833 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = 1.458 kNm
Area Of Reinforcement = 51.409 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 225.000 sqmm/m
Required
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 10 of 14

Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 9.039 kN
Nominal Shear, Vc = 95.033 kN
> 9.039 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x (1 = 9.039 kN
- (Lx / (2 x Ly))))
Nominal Shear, Vc = 87.430 kN
> 9.039 Slab Is Safe In Shear

Slab No. : S5
Level = 7.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C20
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.000 m
Short Span, Lx = 3.000 m
Imposed Load = 3.760 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 12.052 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL

Short Span Long Span


Side1 Side2 Side1 Side2
Beam
        B (mm) 250 250 250 250
        D (mm) 350 350 350 350
        Ib (mm4)    x106 893.23 893.23 893.23 893.23
Adjacent Slab
        Thk (mm) 150 150 150 -
        Span (mm) 3000 3000 3000 -
        Ib (mm4)    x106 843.75 843.75 843.75 421.88
αf lx, αf ly 1.06 1.06 1.06 2.12
αf 1.32
Ln (mm) 2750 2750
L2 (mm) 1625 1625
Total BM (kNm) 18.51 18.51

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 11 of 14

Bottom
        Moment Coefficent 0.35 0.57
        Distributed Moment (kNm) 6.48 10.55
        CS Moment (kNm) 4.86 7.91
        MS Moment (kNm) 1.62 2.64
        Moment on Beam (kNm) 4.13 6.73
        Design Moment M1, M3 (kNm) 0.73 1.19
Top
        Moment Coefficent 0.65 0.7
        Distributed Moment (kNm) 12.03 12.96
        CS Moment (kNm) 9.03 9.72
        MS Moment (kNm) 3.01 3.24
        Moment on Beam (kNm) 7.67 8.26
        Design Moment M2, M4 (kNm) 1.351 1.46

Design Moments:
Short Span Positive Moment At Midspan -
M1 = 0.729 kNm
Area Of Reinforcement = 23.599 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.354 kNm
Area Of Reinforcement = 43.884 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 1.187 kNm
Area Of Reinforcement = 41.833 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = 1.458 kNm
Area Of Reinforcement = 51.409 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 225.000 sqmm/m
Required
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 12 of 14

Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 9.039 kN
Nominal Shear, Vc = 95.033 kN
> 9.039 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x (1 = 9.039 kN
- (Lx / (2 x Ly))))
Nominal Shear, Vc = 87.430 kN
> 9.039 Slab Is Safe In Shear

Slab No. : S6
Level = 7.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C20
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.000 m
Short Span, Lx = 3.000 m
Imposed Load = 3.760 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 12.052 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL

Short Span Long Span


Side1 Side2 Side1 Side2
Beam
        B (mm) 250 250 250 250
        D (mm) 350 350 350 350
        Ib (mm4)    x106 893.23 893.23 893.23 893.23
Adjacent Slab
        Thk (mm) - 150 150 -
        Span (mm) - 3000 3000 -
        Ib (mm4)    x106 421.88 843.75 843.75 421.88
αf lx, αf ly 2.12 1.06 1.06 2.12
αf 1.59
Ln (mm) 2750 2750
L2 (mm) 1625 1625
Total BM (kNm) 18.51 18.51

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 13 of 14

Bottom
        Moment Coefficent 0.57 0.57
        Distributed Moment (kNm) 10.55 10.55
        CS Moment (kNm) 7.91 7.91
        MS Moment (kNm) 2.64 2.64
        Moment on Beam (kNm) 6.73 6.73
        Design Moment M1, M3 (kNm) 1.19 1.19
Top
        Moment Coefficent 0.7 0.7
        Distributed Moment (kNm) 12.96 12.96
        CS Moment (kNm) 9.72 9.72
        MS Moment (kNm) 3.24 3.24
        Moment on Beam (kNm) 8.26 8.26
        Design Moment M2, M4 (kNm) 1.461 1.46

Design Moments:
Short Span Positive Moment At Midspan -
M1 = 1.187 kNm
Area Of Reinforcement = 38.469 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.458 kNm
Area Of Reinforcement = 47.270 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 1.187 kNm
Area Of Reinforcement = 41.833 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = 1.458 kNm
Area Of Reinforcement = 51.409 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 225.000 sqmm/m
Required
Reinforcement Provided = #10 @ 250 C/C
= 314.000 sqmm/m

file:///C:/Users/darlq/AppData/Local/Temp/tmpB8A1.tmp 10/09/2020
Page 14 of 14

Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 9.039 kN
Nominal Shear, Vc = 95.033 kN
> 9.039 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x (1 = 9.039 kN
- (Lx / (2 x Ly))))
Nominal Shear, Vc = 87.430 kN
> 9.039 Slab Is Safe In Shear