1、Specifications for Lubricating oil System
Oil ejector
Oil ejector is the key equipment in
lubricating oil system of turbo generator
unit, and oil ejector is divided into oil
supply ejector and lubricating oil supply
ejector according to its application in
lubricating oil system of turbo generator
unit. Working medium of oil ejector is
steam turbine oil, and oil ejector operates
when turbine reaches or approaches rated
speed.
1、Specifications for Lubricating oil System
Oil Cooler
There are two sets of oil
coolers in the Lubricating oil
system, with the stainless steel
plate heat exchangers type, that
one use and the other standby.
Using circulating water as the
cooling medium, it takes away
the heat resulted from the friction
of bearing.
1、Specifications for Lubricating oil System
Switching valve
H2 block device
#1 #2
H2 block device
#1 #2
H2 block device
#1 #2
H2 block device
JACKING
#1 #2 OIL DEVICE
1、The maintenance work of the lubricating oil system is over and the work ticket has
been terminated. Pipes and equipment are intact.
2、Each control power supply and signal power supply are well energized.
3、The insulation of each equipment is acceptable, the grounding wire is intact, and the
power is energized.
4、The each primary and secondary meters in the system are opened, the oil level gauge
is put into normal, all the oil drain valves are closed, and the measuring and monitoring
protection alarms are well enabled.
2、Preparation before the Lube oil System put into operation
Inspection and preparation
5、The inlet valve of the main lubricating oil tank exhaust fan is opened, one exhaust
fan for operation, one for standby.
8、The main oil tank is cleaned and the oil return filter is installed.
9、check the oil cooler, one side for operation, one side for standby.
10、Check the filter, one side for operation, one side for standby.
2、Preparation before the Lube oil System put into operation
11、Start the oil purification system and use the lubricating oil transfer pump to fill
the oil tank to a high oil level. During the oil filling process, check that the actual oil
level of the oil tank matches the oil level gauge indication. And the oil level alarm
value shall be correct.
12、The jacking oil pump inlet and outlet valves are opened and the filter screen is
cleaned.
13、Lubricating oil and sealing oil systems have been inspected according to the
Valve Inspection Card and all valves are in normal state before startup
3 Lubricating Oil System Startup and Shutdown
3、Lube oil System Startup and Shutdown
Put lube oil system into operation
1、When the oil temperature of the oil tank is lower than 10 ℃ , it is forbidden to
start the oil pump. When the oil temperature of the oil tank is lower than 21℃ , it is
forbidden to start the turning gear, and electric heater shall be put into operation, and
when the oil temperature is greater than 35 ℃ , the electric heater can be stopped.
2、 Start the operation of one exhaust fan of the main oil tank, adjust the inlet damper
of the exhaust fan, maintain the slight vacuum in the main oil tank at 0.248~0.762KPa,
check that the exhaust fan is operating normally, and open the inlet damper of the
other exhaust fan, enable interlock.
3、Lube oil System Startup and Shutdown
Put lube oil system into operation
3、Select a water cooler and put it into operation, open the water side vent valve for
exhaust, and turn it off when there is continuous water flow.
4、Confirm that the oil system is ready. The AC and DC lubricating oil pumps
starting conditions are met, start the AC lubricating oil pump, check that the pump
outlet oil pressure is normal, and the lubricating oil main pipe pressure should be
>0.15MPa.
5、Check that the oil level in the oil tank is normal. The system has no leakage and
the bearing return oil temperature is normal.
3、Lube oil System Startup and Shutdown
6、Check and open the oil side vent valve of the oil cooler to exhaust, and observe
the continuous oil flow and then close it.
7、According to the regulations, carry out the AC and DC lubricating oil pump
interlock test, and then the DC lubricating oil pump is automatically interlocked and
put into operation.
8、 After the unit is fixed at a constant speed, the lubricating oil pressure should be
>0.15MPa, closely monitor the oil level of the main oil tank, and input the lubricating
oil cooler according to the oil temperature to maintain the lubricating oil temperature
of 45~50 ℃ .
3、Lube oil System Startup and Shutdown
Put lube oil system into operation
8、After the unit is fixed at a constant speed, and the main oil pump works
normally, the AC oil pump can be stopped and the interlock shall be put into
operation.
3、Lube oil System Startup and Shutdown
Lube oil system shutdown
1、Confirm that the turning gear, the jacking oil pump and the generator sealing oil
system have been stopped. The metal temperature of the inner wall of the high
pressure cylinder is lower than 121 ℃ , and the metal temperature of each bearing is
within the normal range, the AC lubricating oil pump can be stopped.
4、Disable the interlock of the standby exhaust fan, and stop the operation of the
exhaust fan.
4 Operation Adjustment and Troubleshooting of Lube Oil
System
4、Operation Adjustment and Troubleshooting of Lube oil System
Start-up State
1、Before the start-up of system, it is necessary to confirm whether the oiliness meets
the start-up cleanliness requirement for start-up cleanliness, the oil level in the oil tank
is at the highest oil level and make sure the instruments and meters adjusted properly.
2、Close the cooling water valve for the oil cooler. Heat the oil and start the AC
lubricant pump when the oil temperature meets the start-up requirements for the oil
pump.
3、Open the smoke discharge fan to forcibly circulate the lubricant. When the oil
temperature reaches 35℃ , Stop the electric heater (it is forbidden to start the electric
heater in the process of normal operation).
4、Operation Adjustment and Troubleshooting of Lube oil System
Start-up State
4、Start the cooling water valve of oil cooler to get the oil cooler engaged, then start
the oil pump of shaft jacking up device and adjust the jacked up height of each bearing
neck to the designed valve.
5、After these, it is ready to put the spin gearing into operation. When the unit speed
reaches 1200 r/min, the shaft jacking up device can be removed. During the period of
raising speed, the AC lubricant pump shall work normally and provide lubricant to the
unit.
6、When the unit reaches 3000 r/min and gets stable, the AC lubricant pump can be
stopped. Self-reliance type pressure regulator began to work, to maintain the system
oil pressure is normal.
4、Operation Adjustment and Troubleshooting of Lube oil System
1、During normal operation, all the high pressure oil in the system is supplied by
the main oil pump located in the front bearing housing. The high pressure oil from
the main oil pump serves as the dynamic oil source of oil ejector.
2、The oil ejector sucks the oil from the oil tank. #1 oil ejector provides the oil
source for the main oil pump while #2 oil ejector supplies oil to each bearing and
generator hydrogen seal system for the purposes of Lubricating oil, cooling and
sealing.
4、Operation Adjustment and Troubleshooting of Lube oil System
3、During normal operation, it is necessary to adjust the cooling water flow of oil
cooler according to the oil temperature of lubricant main pipe so as to control the
inlet oil temperature of bearing within the set valve.
4、During normal operation, the oil processing system should be launched regularly,
in order to ensure the normal operation of turbine oil meet the requirements.
4、Operation Adjustment and Troubleshooting of Lube oil System
1、When shutting down the unit under normal or emergent (tripping) condition, the
AC lubricant pump shall be started before the speed of steam turbine drops to 2850
r/min;
2、When it drops to 1200 r/min, the shaft jacking up device shall be started.
3、If the AC lubricant pump fails to react, the DC emergency oil pump shall be
combined to ensure safe shut down. During the barring, the shaft jacking up device
and AC lubricant pump can only be stopped after the spin gearing is stopped.
4、Operation Adjustment and Troubleshooting of Lube oil System
1、During normal operation, the normal outlet oil pressure of main oil pump is
1.8±0.05MPa. When it drops to 1.65MPa, the AC lubricant pump shall be started.
The root cause shall be investigated and make the equipment be ready to shut down.
3、After AC lubricant pump runs, if the pressure drop of lubricant continues, the
brake shall be switched off. During the shutdown, when the lubricant pressure
reduces to 0.07MPa,the DC emergency oil pump shall be started. Every half month,
the test of interlock protection with low oil pressure shall be performed.
4、The unit bearing requires the inlet lubricant temperature to be 45℃ ~50℃ and
the temperature of return oil of bearing shall be less than 65℃ . During normal
operation, the cooling water flow for the oil cooler shall be adjusted according to
the lubricant main pipe to ensure the inlet oil temperature.
4、Operation Adjustment and Troubleshooting of Lube oil System
5、Before operating, according to the oil level requirement on the drawing of main
oil tank, the middle position between the highest and lowest oil levels shall be set
as the zero position as the normal oil level for the oil level indicator. During normal
operation, the highest oil level is +250mm, lowest -250mm, stop oil level -330mm.
6、Before the normal start-up, the oil level in the oil tank is at the highest oil level.
When normal operation, the oil level should between the highest and the lowest oil
level, not be allowed under the lowest.
4、Operation Adjustment and Troubleshooting of Lube oil System
(1) When the lubricating oil pressure drops, check the meter immediately, find
out the cause, pay attention to monitor the changes of oil pressure, metal temperature
of each bearing, oil return temperature, vibration and other parameters. It was found
that the oil flow was interrupted or the bearing temperature was abnormally
increased, if the limits were reached, emergency shut down the unit and break the
vacuum.
(2) When the oil pressure drops to 0.115MPa, the AC lubricating oil pump starts
automatically. When the oil pressure drops to 0.07MPa, the DC lubricating oil pump
starts automatically, otherwise it shall be manually start, and shut down the unit and
put turning gear into operation. The turning gear is stopped when oil pressure drops
to 0.03Mpa.
4、Operation Adjustment and Troubleshooting of Lube oil System
(1) When the oil level is high, it should be checked whether the oil quality is
emulsified, and whether the turbine steam seal has leakage. If water enters the oil,
the oil purifying device shall be put into operation for continuous purification.
(2) When the oil level is low, check whether the oil system pipeline and
equipment are leaking. If it leaks, contact maintenance personnel. If it can be isolated,
it should be isolated. If it cannot be isolated and cannot be handled during operation,
start lubricating oil transfer pump to make up the oil in the oil tank, pay attention to
the oil level change, and report the issue to leader and ask for shutdown.
4、Operation Adjustment and Troubleshooting of Lube oil System
The differential pressure between the inlet and outlet of the oil cooler outlet
filter is big (>0.05MPa), the oil quality shall be tested. Put the standby filter into
operation, and disable the filter with big differential pressure.
When confirming the high temperature of the lubricating oil, check the cooling
water pressure of the oil cooler, whether the flow rate is normal, whether the air at
oil, water side of the oil cooler is well exhausted, and whether the oil cooler is dirty
or not, problems should be solved in time when it is found.
5 The Interlocking and Protection of Lubricating
oil System
5、The Interlocking and Protection of Lubricating oil System
Allow to start:
◇The jacking oil pump A inlet oil pressure is not low >0.03Mpa
Interlock start:
◇Main oil tank exhaust fan B trips, 3s pulse
5、The Interlocking and Protection of Lubricating oil System
Turning gear
Allowed to start:
◇Lubricating oil main pipe pressure is greater than 0.115Mpa
◇Any one of the jacking oil pumps is in operation and the outlet oil
pressure is not lower than 7Mpa
◇Jacking oil pump main pipe pressure is not lower than 9.8Mpa
◇The bearing jacking pressure is not lower than 3.43Mpa
◇Steam turbine speed is less than 2 rpm, delay 30 seconds
◇The turning gear is well engaged.
5、The Interlocking and Protection of Lubricating oil System
Turning gear
Protection stop:
◇Jacking oil pumps are fully stopped, delay 2 seconds
◇Jacking oil pump main pipe pressure is lower than 9.8Mpa, delay 2
seconds.
◇Lubricating oil pressure is lower than 0.07Mpa
◇Bearing jacking pressure is lower than 3.43Mp.
◇Turbine speed is greater than 200 rpm