Professional Documents
Culture Documents
BS 5306-0-2020 - (2021-02-02 - 08-57-28 PM)
BS 5306-0-2020 - (2021-02-02 - 08-57-28 PM)
The BSI copyright notice displayed in this document indicates when the document was last issued.
ICS 13.220.10
Contents Page
Foreword iii
Introduction 1
Section 1: Preliminaries 2
1 Scope 2
2 Normative references 2
3 Terms and definitions 3
Section 2: Key concepts and initial considerations 9
4 Initial considerations and assessment of factors influencing protection design 9
4.1 General 9
4.2 Determining the protection objectives 9
4.3 Determining the firefighting ambition 10
4.4 Additional motivation for installing protection 11
4.5 Nature of the hazard(s) to be mitigated 12
4.6 Extent of protection 12
4.7 Fixed firefighting system reliability and performance 12
5 Interested parties and key stakeholders 13
Section 3: Method of selection 15
6 Identifying a suitable fixed firefighting system option 15
7 Method A: Simplified selection method 15
Figure 1 — Selection method flow chart 16
Table 1 — Method A: Typical examples of fixed firefighting system by building occupancy (or part
thereof) — by common purpose groups (1 of 2) 17
Table 1 — Method A: Typical examples of fixed firefighting system by building occupancy (or part
thereof) — by common purpose groups (2 of 2) 18
Table 2 — Method A: Fixed firefighting system by special application — by application
types (1 of 4) 19
Table 2 — Method A: Fixed firefighting system by special application — by application
types (2 of 4) 20
Table 2 — Method A: Fixed firefighting system by special application — by application
types (3 of 4) 21
Table 2 — Method A: Fixed firefighting system by special application — by application
types (4 of 4) 22
8 Method B: Innovative, engineered or otherwise non‑standard solutions 23
Section 4: Compendium of supporting information 26
9 Types of fixed systems and other firefighting equipment 26
9.1 Fixed automatic systems 26
Figure 2 — Typical automatic sprinkler system 27
Table 3 — Classes of sprinkler system for different hazard classifications 28
Figure 3 — Typical water spray system for limited area of risk 29
Figure 4 — Gaseous system — Example of single‑zone system 32
Figure 5 — Gaseous system — Example of multi‑zone system 33
Figure 6 — Carbon dioxide total flooding system protecting a turbo‑generator with initial and
extended discharge over the whole volume 35
Figure 7 — Carbon dioxide local application system protecting quench tank 36
Figure 8 — Typical pre‑mixed foam system protecting a specific hazard 37
Figure 9 — Typical low‑expansion foam deluge system using open foam nozzles 38
Figure 10 — Typical low‑expansion foam deluge system using aspirating foam sprinklers 38
Figure 11 — Typical high‑expansion foam system for total flooding of a warehouse or storage 40
Summary of pages
This document comprises a front cover, and inside front cover, pages i to vi, pages 1 to 75, an inside back cover and
a back cover.
Foreword
Publishing information
This part of BS 5306‑0 is published by BSI Standards Limited, under licence from The British
Standards Institution, and came into effect on 31 August 2020. It was prepared by Technical
Committee FSH/18, Fixed fire fighting systems. A list of organizations represented on this committees
can be obtained on request to the committee manager.
Supersession
This part of BS 5306 supersedes BS 5306‑0:2011, which is withdrawn.
1)
Systems that can be used as an alternative to halon are covered by the BS EN 15004 series.
Presentational conventions
The guidance in this standard is presented in roman (i.e. upright) type. Any recommendations are
expressed in sentences in which the principal auxiliary verb is “should”.
Commentary, explanation and general informative material is presented in smaller italic type, and
does not constitute a normative element.
Where words have alternative spellings, the preferred spelling of the Shorter Oxford English
Dictionary is used (e.g. “organization” rather than “organisation”).
2)
1 bar = 105 N/m2 = 100 kPa.
Introduction
There is a wide range of different types of firefighting systems and equipment available that suppress,
control and, in some cases, extinguish fire. These systems utilize different firefighting media and, in
some cases, apply such media in varying ways to suit different applications. The whole range of media
and systems means that virtually all types of fire in a wide range of combustible materials can be
tackled reliably and effectively.
The fire suppression industry has developed substantial experience and expertise over many years.
With the results obtained from real fires, as well as exhaustive testing of systems and their individual
components, a high degree of reliability and effectiveness can be claimed.
This part of BS 5306 is intended to assist those charged with selecting and specifying fixed
firefighting systems to determine the most appropriate medium and method of application. This is
not the simple process that is sometimes thought. Care is needed to ensure that characteristics of the
fire hazard in relation to the building and its contents are properly assessed. This needs to include
the nature of the fuel and its configuration, whether the objective is to suppress or extinguish the
fire, and the consequences in use in relation to safety of persons, extent of fire damage and scope for
secondary damage from the medium itself or by‑products of its use.
Design and installation standards are available for all the individual systems and equipment
referenced in this part of BS 5306. These standards are primarily aimed at giving recommendations
or specifying requirements for the design, installation, operation and maintenance of such systems
and equipment. These standards are not concerned with the relative merits of particular systems
or equipment, nor do they compare these to other systems which might be available or focus on
the limitations of such systems and equipment for any given application. That is the purpose of this
part of BS 5306.
This part of BS 5306 is aimed at aiding the selection of the most effective firefighting medium and
type of system or equipment by describing the characteristics and most suitable applications of
each, as well as identifying limitations or safety aspects which need to be taken into account by
stakeholders.
Section 1: Preliminaries
1 Scope
This part of BS 5306 gives guidance on the selection, use and application of automatic water
sprinkler, water spray, water mist, gaseous, foam, condensed aerosol, wet chemical and powder
firefighting systems and oxygen reduction systems. It also gives guidance on installed equipment for
fire and rescue service use, and on portable fire extinguishers.
This part of BS 5306 does not cover firefighting systems for the following applications:
• use on ships, in aircraft, on vehicles and mobile fire appliances;
• use below ground in the mining industry;
• explosion suppression systems.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes provisions of this document3). For dated references, only the edition cited
applies. For undated references, the latest edition of the referenced document (including any
amendments) applies.
BS 4422, Fire – Vocabulary4)
BS 5306‑1, Code of practice for fire extinguishing installations and equipment on premises –
Part 1: Hose reels and foam inlets5)
BS 5306‑3, Fire extinguishing installations and equipment on premises – Part 3: Commissioning and
maintenance of portable fire extinguishers – Code of practice
BS 5306‑4, Fire extinguishing installations and equipment on premises – Part 4: Specification for carbon
dioxide systems6)
BS 5306‑5, Fire extinguishing installations and equipment on premises – Part 5: Halon systems
BS 7273‑1, Code of practice for the operation of fire protection measures – Part 1: Electrical actuation
of gaseous total flooding extinguishing systems7)
BS 7273‑2, Code of practice for the operation of fire protection measures – Part 2: Mechanical actuation
of gaseous total flooding and local application extinguishing systems
BS 7273‑3, Code of practice for the operation of fire protection measures – Part 3: Electrical actuation
of pre‑action watermist and sprinkler systems
BS 7273‑5, Code of practice for the operation of fire protection measures – Part 5: Electrical actuation
of watermist systems (except pre‑action systems)
BS 8458, Fixed fire protection systems – Residential and domestic watermist systems – Code of practice
for design and installation
3)
Documents that are referred to solely in an informative manner are listed in the Bibliography.
4)
This standard also gives informative reference to BS 4422:2005.
5)
This standard also gives informative reference to BS 5306-1:2006.
6)
This standard also gives informative reference to BS 5306-4:2001+A1:2012.
7)
This standard also gives an informative reference to the BS 7273 series.
BS 8489‑1, Fixed fire protection systems – Industrial and commercial watermist systems – Code of
practice for design and installation8)
BS 8663‑1, Fixed fire protection systems – Components for watermist systems – Part 1: Specification and
test methods for watermist nozzles
BS EN 54‑4, Fire detection and fire alarm systems – Part 4: Power supply equipment
BS EN ISO 13943, Fire safety – Vocabulary
3.24 halon
halogenated hydrocarbon used as an extinguishing medium
NOTE Halon is no longer used or widely available, except for a limited number of critical applications as defined
in EC Regulation No. 744/2010 [1].
3.42 surfactant
compound that lowers the surface tension (or interfacial tension) between two liquids, between a gas
and a liquid, or between a liquid and a solid
NOTE Surfactants can act as detergents, wetting agents, emulsifiers, foaming agents and dispersants.
3.46 voltages
3.46.1 extra low voltage (ELV)
voltage of <50 V AC or <120 V DC
All fixed firefighting systems require a degree of ongoing inspection, testing and maintenance to
help ensure their continued satisfactory operation. Any “change of use” or “change of circumstances”
(i.e. change of any significant underpinning design assumptions) is a critical aspect of continued
satisfactory performance (see Clause 10).
Protection objectives are sometimes discussed in terms of, for example, the factors described in 4.2.2
to 4.2.4. In assessing the protection objectives, it is possible that this might reveal that there are
multiple objectives. The overall objective should always be based on the highest required.
4.2.3 Property protection, business continuity, loss control and organizational resilience
The effects of a fire on the continuing viability of a business can be substantial, and, depending on the
clients’ or insurers’ objectives, methods to minimize the damage to the following should be assessed:
a) the structure and fabric of the building;
b) the building contents;
c) the critical asset(s);
d) the ongoing business viability; and
e) the corporate reputation.
Users of buildings should determine whether the expectations they place on others (the anticipated
fire and rescue services response, equipment users, etc.) are reasonable.
Firefighting systems and their components should be suitable for their intended application
in terms of:
a) suitability for the application and objectives;
b) the degree and suitability of quality assurance measures provided;
c) fire testing as required by the design and installation standard, or bespoke application where
there is no relevant standard;
d) design in accordance with the relevant design and system standard;
e) incorporating components conforming to the relevant component standard as set out in the
applicable design and installation standard;
f) compatibility of components used in the same system;
g) compatibility of firefighting media;
h) compliance with the manufacturer’s design, installation, operation and maintenance
requirements;
i) installation in accordance with the relevant installation standard; and
j) maintenance in accordance with the relevant maintenance standard.
Product certification/inspection/testing. Users of fixed firefighting systems are advised to consider
the desirability of third‑party testing, inspection and certification of conformity to the relevant
standards (see Clause 9) by bodies certified to:
• BS EN ISO/IEC 17025 for the competence of testing and calibration laboratories; the scope of
accreditation needs to include the applicable test protocols;
• BS EN ISO/IEC 17065 for the competence of certification bodies (products and services); the scope
of accreditation needs to include the applicable product or system standards;
• BS EN ISO/IEC 17024 for the competence of certification bodies (persons); the scope of
accreditation needs to include the applicable competency area; and/or
• BS EN ISO/IEC 17021 for the audit and certification of management systems; the scope of
accreditation needs to include the applicable standards.
Method A, which should be used in its entirety, comprises the steps set out in:
a) Clause 4 and Clause 5;
b) Figure 1;
c) Table 1 and/or Table 2 (as applicable); and
d) supplementary clauses as applicable.
Table 1 gives typical examples of scenarios where fixed firefighting systems are used in buildings.
Table 2 gives typical examples of applications for which fixed firefighting systems are used.
Users are cautioned not to “cherry‑pick” or modify solutions offered by design standards or the
material in this part of BS 5306.
Where a fixed firefighting system is specified using Method A, it should be in full compliance with the
applicable standard.
Some situations might require more than one firefighting system type to be installed to meet the
protection objectives. In such cases it might be necessary to apply Method A multiple times to suit
each circumstance. Alternatively, Method B might be more appropriate.
NOTE 1 This could be a case where regulatory compliance and/or cases where additional protection is
identified as being necessary (see Clause 4).
NOTE 2 Equipment identified by the risk assessment (see Clause 4), e.g. mission‑critical equipment and high
fire risk equipment.
NOTE 3 Are there any items of high risk equipment, areas or processes in the building, e.g. equipment
identified by the risk assessment (see Clause 4), such as mission‑critical equipment and high fire
risk equipment?
Domestic
Residential
Residential (mixed
use e.g. residential
+ commercial)
Hotel
Ofice
School and
educational
Warehouse
Data centre
Laboratory or
cleanroom
Places of assembly
or recreation
Licenced premises
(bars and
restaurants)
Retail
Hospital
Factory or process
facility
A) BS EN 12845 could be used and might be more suitable for certain more challenging areas and in certain scenarios e.g. very tall buildings, common parts, plant rooms,
car parks, higher than usual risk proile, bin stores, mixed use buildings, or where property protection is sought.
B) Bed and breakfast accommodation only.
C) Might be suitable for small unlicensed B&Bs. Not suitable for bars, clubs, restaurants, etc.
BS 5306-0:2020
D) Fire test evidence alone is insuficient to demonstrate itness for purpose. Third-party approval (see 4.7) of critical system components, design and installation is
considered normal industry good practice. Users are cautioned that many systems of this type might not meet this expectation and therefore thorough checks should be
made. See also 9.1.1.3.
E) Usually BS 8458 should be used for residential parts. BS 8489-1 might be more suitable for certain scenarios beyond the scope of BS 8458.
F) Might be suitable for small licenced B&Bs. Not suitable for bars, clubs, restaurants, etc.
G) Data centres require complex protection strategies. Gaseous extinguishing systems can be employed to offer the highest level of protection to the equipment, and
sprinkler systems can be employed to protect the buildings. Sprinkler systems can be pre-action in areas particularly sensitive to water damage. See also
BS EN 50600-2-5.
H) Laboratories and cleanrooms might require complex protection strategies. Gaseous extinguishing systems can be employed to offer the highest level of protection to the
equipment in certain parts, and sprinkler systems can be employed to protect the buildings. Sprinkler systems can be pre-action in areas particularly sensitive to water
damage.
I) Suitable for special hazards within this occupancy type, e.g. server room or other critical infrastructure. See Table 2.
J) Might be suitable for protecting some parts of the building. e.g. apartments beyond the scope of BS 8458, low ire load common parts, ofice areas or other parts within
the scope and Table 1 of BS 8489-1:2016.
K) Bedrooms and corridors only. The rest of the building should be protected by a sprinkler system conforming to BS EN 12845, or a Method B solution (see Clause 8).
L) Might only be suitable for protecting some parts of the building. e.g. low ire load areas and other parts within the scope and Table 1 of BS 8489-1:2016. Might not be
suitable for storage or plant areas, where a sprinkler system conforming to BS EN 12845, or a Method B solution (see Clause 8) might be more suitable.
M) Classrooms only. Other parts should be protected with other solutions such as a sprinkler system conforming to BS EN 12845, or a Method B solution (see Clause 8).
N) In full compliance with FM 5560:2016 [9], Annex M and Annex N, and FM datasheet 5-32 [10].
Clause 11)
BS 5306-4 CO2 total lood
protection: deep seated (BS
5306-4:2012, 10.1b and Table 3)
protection: surface (BS 5306-
4:2012, Clause 10 and 3.17)
BS 8489-1 Water mist
BS EN 12416- 1+2 Powder
BS EN 12845 Sprinkler
BS EN 13565-1+2 Foam
BS EN 15004-1 Halocarbon total
lood surface protection
BS EN 15004-1 Inert gas total
systems [8]
LPS 1666 in-cabinet systems [14]
lood
BS EN 15276-1+2 Aerosol
BS EN 16750 Oxygen reduction
DD CEN/TS 14816 Water spray
LPS 1223 [12]/UL300 [13]/
prEN 17446/BS EN 16282-7
Kitchen systems
LPS 1655 Personal protection
Dust collector
Electrical cabinet
(extra low voltage and low voltage)
◐E) ◐M)
Electrical rooms
(extra low voltage and low voltage)
A) A) ◐ Q) ◐E)
Electrical rooms
(high voltage)
A) A) ◐E) ◐R)
Engine test cells A) A) ◐E)
Exhaust/extract duct ◐P) ◐P) ◐P) ◐P) ◐P) ◐P)
A) Normally unoccupied areas only; CO2 systems require particularly careful consideration of health and safety effects upon occupants (see 14.3.5.4).
B) For mobile racking refer to BS EN 16893:2018 (e.g. BS EN 16893:2018, 6.5.8).
C) Generally, not suitable for buildings with frequent air changes (e.g. caused by large openings, frequent ingress/egress, high rates of air change due to ventilation and
cooling, buildings with low integrity or poor access control).
BS 5306-0:2020
D) Low oxygen atmospheres require particularly careful consideration of health and safety effects upon occupants (see 14.8.2).
E) Aerosol systems can generate hazards for personnel and should be used only in normally unoccupied or unoccupiable spaces. Use of such systems requires particularly
careful consideration of health and safety effects upon occupants (see 14.6.2).
F) An emerging challenge is very large/complex storage facilities. If the ire and rescue service cannot effectively perform inal extinguishment, the system can deplete its
power or water supply and a large loss can still be incurred.
G) The fuels and geometry of the hazard and enclosure should be assessed. A Method B solution (see Clause 8) might be more suitableǤ
H) Car stackers vary greatly in design. A Method B solution (see Clause 8) based upon BS EN 12845 might be suitable.
I) Certain chemicals (e.g. hydroscopic compounds) can only be tackled with powder.
J) A Method B solution (see Clause 8) based upon BS 5306-4 might be suitable.
K) Gas or oxygen reduction systems in a computer room, data processing area or server room will afford protection to the equipment. Such areas might also require
sprinkler protection. Water mist in computer rooms, data processing areas or server rooms, depending upon how it is implemented, might be suitable to afford a
degree of protection to the equipment and/or the building. See also Table 1, Note G.
L) A Method B solution (see Clause 8) based on the BS 8489 series and FM 5560:2016 [9], Annex M and Annex N, might be suitable.
M) To be used according to the limitations of LPS 1666 [14] and conditions of approval.
N) Conveyor belts may be protected by a sprinkler system, but a Method B solution (see Clause 8) based upon BS EN 12845 might be suitable. Further measures such as
interlocks and detection might be required.
O) Some modern storage buildings are larger, taller and/or more complex than was ever envisaged by ixed ireighting sy stem standards. It might be unrealistic to expect
ire and rescue services to enter such buildings to ight a ire if no lives are at risk. Whilst such thresholds are not speciied or deined, users should determine whether
the ixed ireighting system combined with reasonable ire and rescue service action would give rise to the desired protection outcome.
In order to develop an innovative, engineered or otherwise non‑standard solution, the following steps
should be followed:
i) It should be ascertained that a fully standardized solution really is not suitable.
ii) The circumstances of the fire safety or protection challenge should be properly understood,
documented and analysed (see Clause 4), as follows.
• The motivation for the protection should be clearly defined.
• The protection objective(s) should be stated.
• The firefighting ambition should be stated.
• The nature of the hazard(s) to be mitigated should be stated.
• The extent of protection should be defined.
• The target level of system reliability (see Clause 12) and measures to achieve it
should be stated.
• The interested stakeholders should be identified and engaged in a meaningful process of
consultation (see Clause 5).
iii) Relevant fire and loss experience should be analysed to direct the development of the innovative,
engineered or otherwise non‑standard solution. The relevance and relationship of the fire and
loss experience to the engineering of the solution should be fully justified.
iv) The benefits of standardization and the supporting frameworks should be employed as far as is
possible (e.g. as far as is applicable, use existing standards, proven components and concepts) in
order to de‑risk the innovative, engineered or otherwise non‑standard solution.
v) Realistic scale fire testing should be undertaken by competent test laboratories, in all reasonably
foreseeable permutations (e.g. variations in fire loading, scale, obstructions, ignition scenarios,
geometric presentation, ventilation and operating conditions) to verify that the system
performance concept is effective. The applicability of the fire testing to the application should
be justified.
NOTE 1 Due to the complex nature of fire and firefighting phenomena (e.g. multiple interactions of chaotic
regimes), CFD modelling and/or scaling are generally not considered reliable means to provide evidence of
satisfactory performance.
vi) Critical components should be designed and subject to rigorous evaluation of their whole‑life
suitability for the application.
NOTE 2 Users of this part of BS 5306 are advised to consider the desirability of third‑party evaluation
of components.
vii) The components and the system selected should be subject to robust change and revision
control measures.
viii) The competent person should identify where engineering judgment is applied as part of
the substantiation of a proposed engineered solution. It is often important to understand
how judgement has been applied, especially in cases where test data, guidance from
published standards, or other information is being extrapolated in support of the proposed
engineering solution.
ix) All significant aspects of the development and use of the derived solution should be documented.
Documentation should be available to any party with a legitimate interest. Documentation
should cover in detail all the preceding points in this list.
A number of design, installation and maintenance standards also include guidance on developing fire
test protocols.
NOTE 3 As can be seen above, developing fire test protocols is only a small part of the challenge of designing an
innovative, engineered or otherwise non‑standard fixed firefighting system.
Each sprinkler is capable of opening individually in response to the heat from a fire and of
discharging a spray of water onto the fire below, whilst also initiating an alarm. In response to the
development of high‑bay warehouses, sprinkler systems have been developed to suppress fires in
these high‑hazard environments, either by roof or ceiling sprinklers alone or by a combination of roof
and ceiling sprinklers with in‑rack sprinkler protection. Only small numbers of sprinklers operate in
the event of a fire, limiting fire and water damage to the immediate fire site and its surroundings.
9)
Available at https://www.fmglobal.com/research-and-resources/fm-global-data-sheets.
For some warehouse storage systems involving plastic storage tote boxes or plastic pallets,
foam‑enhanced sprinkler protection can be the most effective form of fire protection. For these
hazards, relatively low concentrations of foam additive are used, and although the run‑off should be
contained and disposed of safely, no depth of foam is created within the area of discharge.
Sprinklers were intended primarily to suppress and contain class A fires. In many instances they
not only extinguish this class of fire but can also be adapted to deal with class B fires, either within
general sprinkler systems or by the addition of the special water spray systems described in 9.1.1.2.
In a typical sprinkler system, each sprinkler head has a temperature rating and water discharge
capacity which is appropriate to the fire load within the protected compartment. The spacing
between each sprinkler head is also determined by the compartment’s fire load.
NOTE 2 Figure 2 shows the layout of a typical automatic sprinkler system.
Key
1 Sprinkler head 6 Main distribution pipe
2 Riser 7 Control valve set
3 Design point 8 Riser
4 Distribution pipe spur 9 Range pipes
5 Arm pipe 10 Drop
Each class and subclass is linked to a design density, and an area over which the design density is
achieved, as given in Table 3.
Key
1 Compressed air supply
2 Spray nozzles
3 Detectors
4 Automatic deluge valve
5 Water supply
Actuation of such systems is normally enabled by the use of heat‑sensitive devices, often sprinkler
heads fitted to a separate set of air‑pressurized pipes (the “detection line”), installed in parallel
with the water discharge pipes around the object or area to be protected. While conventional heat
detection can be used to operate water spray or deluge systems, the detection line approach is
popular because of its inherent simplicity, reliability and ruggedness for use outdoors.
NOTE 1 For applications where there is no risk of freezing, a water‑charged detection line could be used.
2) medium‑velocity water spray systems for use against fires in water‑immiscible liquids of low fire
points, or in fires in water‑miscible liquids, e.g. alcohols;
3) deluge systems sometimes using an early limited discharge of foam, for large flammable liquid
spillages, e.g. in aircraft hangars and tanker refuelling bays. Medium‑velocity nozzles are used to
cover all parts of the fire hazard or a specific zone of the hazard in which the fire is occurring;
4) deluge systems to protect fuel storage tanks against heat radiation from an adjacent fire. These
can employ medium‑velocity spray nozzles, or nozzles specially selected to give a uniform
distribution over the protected surface; and
5) deluge systems, or water spray systems, used to protect apertures in fire‑resisting compartment
walls. Such apertures might be small, e.g. a hole for electrical conduits, or very large,
e.g. connecting doorways between different areas of a factory or storage, capable of being closed
by sliding or folding shutter doors but kept open for transit of goods during working hours.
NOTE 2 CEN is in the process of preparing a water mist standard series, currently identified as prEN 14972. This
series is not included in this part of BS 5306 at this time because it is still a work in progress and subject to change,
and the UK has serious concerns about the series, which are on record.
NOTE 3 BRE have published a document [18] which provides further guidance on the selection and deployment of
these systems.
There are normally two main types of operating system used in water mist: automatic systems and
open nozzle systems. Automatic systems are generally used for applications for hazards involving
materials associated with class A fires. Open nozzle systems are generally used for applications for
hazards associated with class B or class F fires.
Fire test evidence alone is insufficient to demonstrate fitness for purpose.
The use of components that have been tested and approved in accordance with appropriate
component specifications for fire protection applications is also important for system performance
and reliability.
Water mist nozzles should be in accordance with BS 8663‑1.
All other critical system components should be tested and listed specifically for the intended fire
protection application.
Users are cautioned that many systems of this type might not utilize tested and approved
components, and therefore thorough checks should be made of both component and water
supply robustness.
Automatic nozzle systems include thermal actuation devices, and the general arrangement of the
full system is similar to that of an automatic sprinkler system shown in Figure 2. Where the water
in these systems can be maintained at ambient temperatures above freezing, the pipework is
permanently charged with water. Where water temperatures might be below freezing, the pipework
is empty of water until the control valve is actuated. In automatic nozzle systems, only the nozzles in
the immediate vicinity of the fire are expected to operate to control and suppress a fire.
Open nozzle systems are designed such that water mist discharges from all nozzles when the system
control valve is actuated. The general arrangement of the full system is the same as that of a water
spray system shown in Figure 3. These systems can be deployed to protect complete enclosures and/
or to provide local application protection for designated equipment within an enclosure.
For both types of water mist system, designs are based upon the results from representative fire
tests which establish the type and quantities of nozzles needed to control, suppress and extinguish
fire. Factors of safety (which are given in the appropriate British Standard) are then applied to these
results to establish the design basis. All results are unique and specific to each supplier of nozzles.
Automatic nozzle systems have been tested and validated for residential and domestic occupancies,
offices, hotels and similar accommodation hazards. Open nozzle systems have been tested for a
variety of hazards involving flammable liquids, such as turbines, engines and fuel/lube oil hazards.
As water mist systems discharge small quantities of water through small orifice nozzles, system
cleanliness is important. Water mist systems use a range of materials in their pipework, including
stainless steel and copper. Water mist heads are usually fitted with filters to prevent clogging of
nozzles which would hinder discharge.
The water supplies for water mist systems can be provided either by pumps with dedicated water
storage tanks, or from containers where the water is propelled by gas under pressure. For hazards
involving materials associated with class A fires (other than in domestic or residential premises),
a 60 min water supply duration is required, whereas for some hazards involving flammable liquids,
the supply duration could be as little as 10 min because rapid fire extinguishment and post‑fire
cooling are achieved. The available water supply should provide for a minimum discharge of 10 min.
NOTE 2 BRE/LFB have published a document [19] which provides further guidance on the selection and
deployment of these systems.
Key
1 Main control panel 8 Discharge nozzle – room
2 Manual release 9 Discharge nozzle – floor void
3 Hold‑off button (normally inside) 10 Detector – ceiling void
4 Discharge pressure switch 11 Detector – room
5 Agent containers 12 Detector – floor void
6 Audio/visual pre‑discharge alarms 13 Distribution pipework
7 Discharge nozzle – ceiling void 14 Vent
Key
1 Main control panel 7 Discharge nozzle
2 Manual release 8 System state indicator c/w auto/manual changeover switch
3 Hold‑off button (normally inside) 9 Detector
4 Discharge pressure switch 10 Pressure relief vent (as required)
5 Agent containers 11 Selector valve
6 Audio/visual pre‑discharge alarms
Figure 6 — Carbon dioxide total flooding system protecting a turbo‑generator with initial and extended discharge
over the whole volume
Key
1 System actuator (electrical) 9 Initial discharge nozzle
2 Pilot loop 10 Discharge pressure switch
3 Container valve and actuator 11 Initial discharge containers
4 Turbine 12 Extended discharge containers
5 Generator 13 Extended discharge feed pipe
6 Vertical cooler (horizontal type similarly protected) 14 Initial discharge feed pipe
7 Extended discharge nozzle 15 Exciter
8 Heat detector
Key
1 CO2 container 7 Heat actuated detector
2 System controller 8 Pit
3 Manual release 9 Quench tank
4 Pressure trip 10 Oven
5 Local application nozzles 11 Hood
6 Pressure switch 12 Damper
9.1.5.1.1 General
There is a wider range of methods used for applying low‑expansion foams than for any other medium.
This is because the properties at risk often vary enormously in size and complexity. The range of
methods is described in 9.1.5.1.2 to 9.1.5.1.7.
NOTE A basic system might consist of a simple pressure vessel containing foam solution under gas pressure, and
discharging when a fire on, for example, a dip tank causes a heat‑sensitive sprinkler to operate. An example of a
complex system would be a fully‑fledged automatic foam‑generating system feeding a foam deluge system in an
aircraft hangar.
Key
1 Heat retaining plate 6 Pressure switch to alarm bell
2 Heat detector 7 Tank for premixed foam solution
3 Link line anchor 8 Manual discharge control
4 Foam sprinkler 9 Bund wall
5 Discharge pipe 10 Twin cylinders of carbon dioxide or nitrogen
Figure 9 — Typical low‑expansion foam deluge system using open foam nozzles
Key
1 Heat detectors 6 Water
2 Open foam nozzles 7 In‑line foam generator
3 Control box 8 Foam liquid
4 Alarm 9 Pump
5 Foam proportioner
Figure 10 — Typical low‑expansion foam deluge system using aspirating foam sprinklers
Key
1 Self‑aspirating foam sprinklers
2 Foam proportioner
Figure 11 — Typical high‑expansion foam system for total flooding of a warehouse or storage
Key
1 Foam generators 5 Automatic valve
2 Automatic vent 6 Proportioner
3 Foam liquid storage tank 7 Control panel
4 Water line 8 Heat actuated devices
e) the integrity of the enclosed volume and determination of the need for venting; and
f) contract arrangements.
Figure 12 — Typical hydrant system hose reel and foam inlet installed in building
Key
1 Landing valve 5 Connection to building water supply
2 Dry fire main 6 Foam inlet
3 Hose reel 7 Foam nozzle
4 Dry fire main inlet 8 Oil‑fired heating appliance
• BS 5306‑9;
• BS 5306‑10;
• BS EN 3 series.
These standards cover topics including but not limited to:
a) guidance on the types of extinguishers available and their suitability for use in the different
classes of fire;
b) type, quality and firefighting performance;
c) inspection, maintenance and testing recharging and remedial action;
d) guidance on the competence and training of servicing engineers;
e) test‑fire rating schemes for extinguishers (requirements and guidance).
NOTE 1 Where powder‑filled portable fire extinguishers are to be used, it is necessary to take into account:
Subclause 14.5 and the standards referenced earlier in this clause give specific guidance on these issues.
NOTE 2 There are other types of portable fire extinguisher on the market (e.g. water mist). Manufacturers of such
devices might have conducted assessments and declare certain performance characteristics for their products.
These extinguishers might be suitable against a range of fire hazards.
A fixed firefighting system might have been installed as part of a building’s original fire strategy.
Therefore, when a building fitted with a fixed firefighting system is to be taken over, no decision
should be taken to abandon or remove the system without contacting the relevant insurers and
ascertaining any views which might be expressed by the authorities having jurisdiction.
• critical components;
Statistical data shows overall reliability for sprinkler systems for all building types is 88% [21]
or 94.3% [22].
In using such data, at least the following factors should be taken into account:
a) occupancy type;
b) country of origin (i.e. system design, installation and maintenance standards and other
factors); and
c) size and robustness of study (e.g. appropriateness of the statistical techniques employed).
The paper “A review of sprinkler system effectiveness studies” [23] is recommended further reading
for anyone considering using such figures and for those wishing to gain a deeper insight into fixed
firefighting system performance evaluation methods (e.g. by measurement or modelling).
e) action by the fire and rescue service (including use of their own equipment and installed
equipment such as hydrants, wet and dry risers, fire mains and foam inlets); and
f) smoke ventilation systems; generally, the use of fixed firefighting systems requires ventilation
systems to be shut down upon detection of a fire (see 13.2).
NOTE 1 Attention is drawn to the need in some instances to shut down sources of heat, energy, motion and
ventilation in the case of many fixed firefighting system types.
NOTE 2 For a full description of fire strategy, see BS 9999:2017, 8.3, and BS 9991.
NOTE 3 Gaseous fires require special attention because, if the flow of gas is not quickly stopped after extinguishing
the fire, a serious danger of explosion could arise. The primary consideration in gaseous fires is to isolate the leak
and, if necessary, protect adjacent hazards.
The degree of importance of each element, and the extent of interdependency, varies with the type
of installed system and the characteristics of the hazard. The need for a particular element might be
reduced or eliminated by the success of others, but in some cases all the elements might be required.
14 Firefighting media
14.1 General
This clause provides information on the general properties of firefighting media and the effects of
firefighting media on people, property and the environment.
The firefighting media available are:
a) water (see 14.2);
b) gaseous media, including inert gases, halocarbon agents and carbon dioxide (see 14.3);
c) foams (see 14.4);
d) powders (see 14.5);
e) condensed aerosols (see 14.6);
f) wet chemicals (see 14.7); and
g) oxygen reduction systems (14.8).
NOTE Reduced oxygen (hypoxic air) systems use an inert gas, nitrogen, to continually maintain a level of oxygen
lower than that needed to support sustained flaming combustion.
It is assumed that occupants will be instructed to leave any area covered by a fixed firefighting system
involved in fire to limit their exposure to products of combustion.
The environmental considerations in 14.3.7, 14.4.7, 14.5.7, 14.6.4, 14.7.4 and 14.8.4 address the
firefighting media themselves, but do not analyse the considerable impact of fire on the environment,
which should not be ignored.
It is essential that a system discharged within one occupancy does not adversely affect the interests,
livelihood or safety of persons within an adjacent occupancy, and this should always be taken into
account when selecting the firefighting system to meet a particular fire hazard. A summary of
possible adverse effects, which need to be avoided, is given in 14.2.4, 14.3.8, 14.4.8, 14.5.9, 14.6.5,
14.7.5 and 14.8.5.
14.2 Water
14.2.1 General properties
Water, which is applied for wetting and surface cooling, is the most widely used firefighting medium
and is likely to remain so because of the following properties.
a) It is inexpensive and usually readily available.
b) It has a high heat capacity, absorbing large amounts of heat as a liquid and even greater amounts
by its conversion to steam. Therefore, it is an effective medium:
1) in jet, spray (e.g. sprinklers) or mist form, for suppressing class A fires, even when these
fires are deep‑seated. It is also capable of extinguishing class A fires;
NOTE 1 As fires in these materials represent the majority of fire hazards, the applications of water in jet
or spray form are profuse.
NOTE 2 Residential and domestic sprinkler systems rely for their effectiveness on the wall‑wetting effect
of the sprinkler discharge as a method of inhibiting fire spread.
NOTE 3 Some test evidence suggests that water mist might be less effective against deep‑seated class A
fires where the initial fire is not hot enough to generate steam.
2) in spray or mist form, for use against class B fires, particularly those of a high flash point
(around 65 °C and above), e.g. diesel oil, transformer oil and lubricating oil;
3) in mist form, for use against fires involving petrol and alcohols;
4) in jet, spray or mist form, for achieving cooling. It is particularly effective:
i) as a spray in cooling exposed building elements or process equipment, such as doors
and windows, subject to radiant heat from an adjacent fire, or fuel storage tanks which
are adjacent to a fire;
ii) as a mist in cooling the fire and its surroundings as well as blocking radiant
heat transfer.
Water can be applied to fires indoors, or just as readily outdoors in circumstances where a fixed
system can be used. When water is delivered as a mist, often at low water delivery rates, the
increased surface area of the water droplets means that it can provide effective protection. The use
of water mist should be limited to applications included in the scope of BS 8458 and BS 8489‑1, or
where supported by fire testing.
For certain types of fuels, the effectiveness of water‑based systems can be increased by the use of
additives, e.g. foam (see 14.4).
When using water, other considerations include:
1) the possibility of electrical conductivity. This is particularly relevant to water when
applied as a jet;
NOTE 4 Fixed high‑velocity water spray systems are used extensively and successfully for the protection of
steam and gas turbine power‑generating equipment and in oil‑filled transformers and switchgear.
14.3.5.1 General
The precautions to be taken when using the gaseous media are covered in detail in the subsequent
parts of BS 5306, BS EN 15004, and the Halon Alternatives Group (HAG) report [25], as appropriate.
The gaseous media do not conduct electricity and do not present a danger of shock if they are
discharged against high‑voltage equipment, provided that the recommended system component
clearance gaps are observed. However, discharge of these media can sometimes be accompanied by a
loud noise and, in some circumstances, brief obscuration of vision.
Protected spaces for gas systems specified in BS EN 15004 can be occupied while the system is in
automatic mode, if the achieved concentration of gas is within safe limits. Special protection measures
are required for CO2, which is toxic at design concentrations. Where concentrations are not within
safe limits or CO2 is used, such systems need to be in the manual mode when the room is occupied
and, in some circumstances, fitted with a lock‑off device. In all cases, there should be an audible and
visible warning that a discharge is about to take place. There should be a delay to facilitate evacuation
prior to discharge. In some circumstances, a hold‑off device that allows occupants to manually
delay the discharge should be fitted. Guidance on the electrical control and actuation of gaseous
extinguishing systems is given in BS 7273‑1.
environmental use restrictions. Carbon dioxide used as a fire‑extinguishing agent is also not subject
to any environmental controls.
NOTE Table 5 gives values for the ODP, GWP and ATL of the commonly used inert gases and halocarbon agents.
14.4 Foams
14.4.1 General
Foams consist essentially of a bubble structure formed by aerating and agitating a solution of a foam
concentrate in water.
Protein foams are made from concentrates based on proteinaceous products alone and with the
addition of fluorinated additives to give fluoroprotein foams. Hydrocarbon and fluorinated surfactant
materials can also be mixed with stabilizers to form aqueous film‑forming foam (AFFF) type
concentrates. These are used for the extinction of fires in hydrocarbons and other water‑immiscible
flammable liquids.
Modifications of fluoroprotein and AFFF foams have been developed that are suitable for use on fires
in water‑miscible flammable liquids, alcohols and ketones. These are the alcohol‑resistant (AR or
AFFF/AR) foams or general‑purpose foams.
Other types of foam currently used are:
a) film‑forming fluoroprotein (FFFP) foam, which is a fluoroprotein foam concentrate with the
ability to form an aqueous film on the surface of some hydrocarbons;
b) fluorine‑free foam (F3), which does not contain fluorinated surfactants; and
c) class F foam for use on oil- and grease‑bearing kitchen equipment.
Foams are classified by their expansion ratio (expansion) – the ratio of the volume of the made foam
to the volume of the solution from which it is made – as follows:
1) low‑expansion foams, with expansions between 1 and 20 (see 14.4.2);
2) medium‑expansion foams, with expansions between 21 and 200 (see 14.4.3); and
3) high‑expansion foams, with expansions between 201 and 1 000 (see 14.4.4).
High‑expansion foams are effective on LNG spills by forming a vapour suppression blanket without
significant degradation by cryogenic LNG liquid.
14.5 Powders
14.5.1 General
Powders are finely divided chemicals with a controlled range of particle sizes, which are used in the
extinction of fires in flammable liquids, gases and solids. They are manufactured in the following
four main types:
a) for use on class B and class C fires (BC powders; see 14.5.2);
b) for use on class B and class C fires [BC (foam‑compatible) powders; see 14.5.2)];
c) for use on class A, class B and class C fires (ABC powders; see 14.5.3); and
d) for use on class Fires (D powders; see 14.5.4).
14.5.4 D powders
D powders are suitable for use on flammable metals. These powders might be subdivided into those
suitable for radioactive metals and those for use on general industrial metals.
They are usually formulated with a specific range of metals in mind, and hence they vary widely in
their characteristics.
All appliances or foodstuffs utilizing or incorporating oils or fats, as well as extract ventilation
systems, are potential fire hazards, regardless of the amount of oil/fat being used in the cooking
process. The following are examples of hazards that should be protected:
a) deep oil/fat fryers;
b) griddles/range tops;
c) gas, electric, lava, pumice, synthetic rock, charcoal, wood, upright and chain broilers;
d) woks;
e) hoods;
f) ducts; and
g) plenums.
It is essential that the wet chemical system is tested for suitability to protect the specific appliances.
It is also important that the fuel supply is shut off prior to or during system activation.
b) They provide a continuous level of fire prevention, rather than a discharge of extinguishing agent
once a fire has been detected.
c) There is no residual clean‑up or damage to goods or equipment within the protected space.
d) Although not required to actuate the oxygen reduction system, separate aspirating smoke
detection systems would normally be provided to warn of the presence of pyrolysis and
smouldering combustion.
e) Oxygen reduction systems require detailed risk assessments with regard to occupants likely
to enter the protected space. As oxygen levels reduce, it becomes increasingly important
that adequate provision is in place to protect the health and safety of all people within the
oxygen‑reduced (hypoxic) space, in particular those who are predisposed to be adversely
affected by reduced oxygen levels, such as pregnant women or those with certain medical
conditions (see 9.1.8).
Oxygen reduction systems may be used where:
1) the enclosure is normally unoccupied;
2) the enclosure to be protected has sufficient integrity to retain the reduced‑oxygen atmosphere at
the requisite level; and
3) the fabrics of construction and contents of the enclosure are within the limits of the capability of
the oxygen reduction fire prevention approach.
Particular attention should be paid to the effects of such systems upon the health and safety
of occupants.
NOTE 2 Attention is drawn to the Confined Spaces Regulations 1997 [31].
10)
See https://www.bafsa.org.uk/water-firefighting-electricity/ for further information.
Where separate fire detection, control and actuation systems are used, they can be mechanical,
pneumatic, explosive or electrical. Recommendations relating to these systems can be found in the
BS 7273 series. Specific additional provisions are set out in BS 6266 covering electronic equipment
installations.
They can also be arranged to provide signals of “fire” and “system operation” to an alarm receiving
centre, which can be connected to the fire and rescue service if required.
Foam‑enhanced sprinkler protection operates on similar principles to low expansion foam systems
where a complete sprinkler system, sprinkler installation or part of an installation might include
foam enhancement.
A common type of low‑expansion foam system, larger than the simple type described, is similar in its
control to a sprinkler system. When one or more of the heat‑sensitive closed spray heads is opened by
the heat from a fire, the ensuing drop of pressure in the trunk main causes a pressure‑sensitive switch
to switch in the pump. This then forces the water to flow through a suitable type of proportioning
device where the foam concentrate is injected, and thence to the now‑open spray heads.
NOTE 2 Where a pre‑mixed foam solution is used, the proportioning device is not required.
Another type of full‑scale automatic foam system includes a fire detection system which relays a
signal to a control and annunciation panel. This panel gives audible and visual alarms and also sends
a signal to start a water pump that supplies water and opens the foam system control valve. The flow
of water induces another flow of foam concentrate in the correct proportion, and the two streams mix
to form a foam solution. The foam solution is delivered through hydraulically designed pipework to a
series of open nozzles, from which it is discharged.
Other types of foam system, e.g. protection of storage tanks by fixed pourers or monitors or
by sub‑surface application, are usually operated manually on receipt of an alarm given by a
heat‑sensitive or other form of fire detection system.
Medium- and high‑expansion foam systems can be operated by point or linear system fire detection
devices suitable for the fire and hazard being addressed. The detection and control panel also has a
manual/automatic selector switch and a time delay facility to allow occupants to leave the area after
the warning is given. The time delay can be up to 30 s.
enclosure(s). It should be possible to stop the further reduction of the oxygen‑reduced environment,
from outside the protected enclosure.
The control panel should include, as a minimum:
a) a continuous display of the oxygen concentration level measured in each protected space;
b) alarm indications at oxygen alarm levels measured on any of the oxygen sensors in the
protected area;
c) oxygen sensor fault and fault status indication;
d) online/offline status controlled by a secure switch;
e) control of the range of oxygen concentration levels acceptable for each protected space and the
associated alarms, with safeguards so that levels cannot be accidentally adjusted; and
f) a power supply conforming to BS EN 54‑4, with sufficient battery backup for 24 h in the event of
mains failure.
An abnormally low oxygen concentration level (the lower alarm threshold) alarm should trigger
automatic shutdown to stop the further reduction of the oxygen‑reduced environment.
18.2 Fire mains (including hydrants), hose reels and foam inlets
Field experience shows that maintenance of these systems is often overlooked, and therefore good
practice recommendations are highlighted in this subclause.
It is recommended that the following maintenance instructions are provided to the owners or
occupiers of the building.
a) All fire hydrants should be inspected at least once a year by a competent person to verify that
pressure and flow are satisfactory, that there are no obstructions and that all isolating valves are
locked in the open position.
b) All dry fire mains should be checked every six months to verify that all valves are fully
serviceable, and a wet pressure test should be carried out annually to verify that there
is no leakage.
c) All wet fire mains should be similarly checked, and, in addition, water storage tanks and booster
pumps should be checked for operational serviceability.
d) All hose reels should be checked regularly to verify that there are no leaks, the valves operate
satisfactorily, the nozzle outlet is not choked, and the nozzle can be moved between “jet” and
“spray” positions without difficulty. The hose should be run out fully at least once a year and
subjected to operational water pressure. At the same time, the booster pumps may be checked,
and the flow rate of each hose reel measured to check that it is not less than the minimum
recommended in BS 5306‑1.
e) Defects in equipment should be rectified as soon as possible by a competent person. If delay
ensues, the fire and rescue service should be warned, and warning notices should be posted in
the building at the appropriate place. The fire and rescue service should be informed as soon as
the equipment is serviceable again.
Further guidance is given in BS 9990, BS 5306‑1 and BS EN 671‑3.
Annex A (informative)
Glossary of terms
NOTE This annex provides a glossary with details of document types and bodies referred to in this part of
BS 5306. Other similar bodies might also exist.
A.1.4 BS specification
type of British Standard giving a coherent set of absolute requirements, each of which is
objectively verifiable
Annex B (informative)
Environmental considerations for certain
halocarbon agents
NOTE Attention is drawn to the following regulations in respect of the legal requirement for companies and
personnel involved in activities associated with halon and certain fluorinated greenhouse gases to be certificated:
B.1 Halon
B.1.1 Halon manufacture
Under the 1987 Montreal Protocol [34] on substances that deplete the ozone layer, the production
of halons identified as ozone‑depleting compounds was banned in developed countries
from 31 December 1993. This ban was implemented and enforced in the European Community
through EC Regulation No. 3093/94 [35], which is enacted in the Environmental Protection (Controls
on Ozone‑Depleting Substances) Regulations 2002 [36], which prohibit the production of halons, and
controls their supply and use. The use of halon 1211 and 1301 is restricted to the “critical uses” listed
in the EC Regulation No. 3093/94 [35].
B.2.2 Regulations
Under EU Regulations, some restrictions exist in respect to the use of HFCs and PFCs in fire
protection. EC Regulation No. 842/2006 [38] set in place certain requirements that were captured
through additional Regulations:
• EC Regulation No. 1493/2007 [39] – reporting by producers, importers and exporters;
• EC Regulation No. 1494/2007 [40] – labelling;
• EC Regulation No. 1497/2007 [41] – leakage checking requirements; and
• EC Regulation No. 304/2008 [42] – certification of companies and personnel.
EC Regulation No. 842/2006 [38] banned the use of PFCs in fire protection (systems and
extinguishers) from 4 July 2007.
EC Regulation No. 842/2006 [38] was repealed in 2014 and replaced by EU Regulation
No. 517/2014 [24], which introduced some additional requirements in relation to labelling
and leakage.
EU Regulation No. 517/2014 [24] introduced quotas for the quantity (based on the total
CO2 equivalency) of fluorinated greenhouse gases that are allowed to be imported into the EU, based
on 100% of the quantity imported in 2015, reducing to 21% by 2030. The quotas apply to fluorinated
greenhouse gases as a group of chemicals and does not automatically represent a specific reduction
in the quantity of HFCs that may be imported or used in fire protection, since quota reduction from
importers can be achieved by reductions across a range of fluorinated greenhouse gases.
EU Regulation No. 517/2014 [24] introduced a ban in the use (placing on the market) of HFC‑23 for
fire protection from 1 January 2016.
Bibliography
Standards publications
For dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
BS 0, A standard for standards – Principles of standardization
BS 5306‑8, Fire extinguishing installations and equipment on premises – Selection and positioning of
portable fire extinguishers – Code of practice
BS 5306‑9, Fire extinguishing installations and equipment on premises – Part 9: Recharging of portable
fire extinguishers – Code of practice
BS 5306‑10, Fire extinguishing installations and equipment on premises – Part 10: Colour coding to
indicate the extinguishing media contained in portable fire extinguishers – Code of practice
BS 5908 (all parts), Fire and explosion precautions at premises handling flammable gases,
liquids and dusts
BS 6266, Fire protection for electronic equipment installations – Code of practice
BS 7974, Application of fire safety engineering principles to the design of buildings – Code of practice
BS 9251, Fire sprinkler systems for domestic and residential occupancies – Code of practice
BS 9990:2015, Non automatic fire‑fighting systems in building – Code of practice
BS 9991, Fire safety in the design, management and use of residential buildings – Code of practice
BS 9992, Fire safety in the design, management and use of rail infrastructure – Code of practice
BS 9999, Fire safety in the design, management and use of buildings – Code of practice11)
BS EN 2, Classification of fires12)
BS EN 3 (all parts), Portable fire extinguishers13)
BS EN 671‑3, Fixed firefighting systems – Hose systems – Maintenance of hose reels with semi‑rigid hose
and hose systems with lay‑flat hose
BS EN 12094 (all parts), Fixed firefighting systems – Components for gas extinguishing systems.
BS EN 12259 (all parts), Fixed firefighting systems – Components for sprinkler and water spray systems
BS EN 12416‑1, Fixed firefighting systems – Powder systems – Requirements and test methods
for components
BS EN 12416‑2, Fixed firefighting systems – Powder systems – Design, construction and maintenance
BS EN 12845, Fixed firefighting systems – Automatic sprinkler systems – Design, installation and
maintenance14)
BS EN 13565‑1, Fixed firefighting systems – Foam systems – Part 1: Requirements and test methods
for components
BS EN 13565‑2, Fixed firefighting systems – Foam systems – Design, construction and maintenance
BS EN 15004 (all parts), Fixed firefighting systems – Gas extinguishing systems15)
11)
This standard also gives a dated reference to BS 9999:2017.
12)
This standard also gives a dated reference to BS EN 2:1992.
13)
This standard also gives a dated reference to BS EN 3-7:2004+A1:2007.
14)
This standard also gives dated references to BS EN 12845:2015.
15)
This standard also gives a dated reference to BS EN 15004-1:2019.
16)
This standard also gives a dated reference to BS EN 16750:2017.
17)
This standard also gives a dated reference to DD CEN/TS 14816:2008.
18)
In preparation.
[23] FRANK. K., GRAVESTOCK, N., SPEARPOINT, M. et al. A review of sprinkler system effectiveness
studies. In: Fire Science Reviews, 2013, Volume 6, No. 2.
[24] EUROPEAN COMMISSION. Commission Regulation (EU) No. 517/2014 of 16 April 2014 on
fluorinated greenhouse gases and repealing Regulation (EC) No. 842/2006. Luxembourg:
Office for Official Publications of the European Communities, 2014.
[25] HALON ALTERNATIVES GROUP. A review of the toxic and asphyxiating hazards of clean agent
replacements for halon 1301. Petersfield: The Halon Users National Consortium, 2003.
[26] JOHNSON CONTROLS. Impact of sound on computer hard disk drives and risk mitigation
measures. Milwaukee, WI: Johnson Controls, 2018.20)
[27] SIEMENS. Silent extinguishing – Disruptions to hard disk drives caused by inert gas extinguishing
systems – Analysis and measures for the safe operation of storage systems. Zug: Siemens
Switzerland Ltd, 2015.21)
[28] INTERGOVERNMENTAL PANEL ON CLIMATE CHANGE. IPCC fifth assessment report: Climate
change 2014. Geneva: IPCC, 2014.
[29] GREAT BRITAIN. Groundwater Regulations 1998. London: The Stationery Office.
[30] EUROPEAN PARLIAMENT, COUNCIL OF THE EUROPEAN UNION. Regulation (EU)
No. 2019/1021 of the European Parliament and of the Council of 20 June 2019 on
persistent organic pollutants. Luxembourg: Office for Official Publications of the European
Communities, 2019.
[31] GREAT BRITAIN. Confined Spaces Regulations 1997. London: The Stationery Office.
[32] GREAT BRITAIN. Ozone Depleting Substances (Qualifications) Regulations 2006.
London: The Stationery Office.
[33] EUROPEAN COMMISSION. Commission Regulation (EC) No. 304/2008 of the European
Parliament and of 2 April 2008 establishing, pursuant to Regulation (EC) No. 842/2006 of
the European Parliament and of the Council, minimum requirements and the conditions for
mutual recognition for the certification of companies and personnel as regards stationary fire
protection systems and fire extinguishers containing certain fluorinated greenhouse gases.
Luxembourg: Office for Official Publications of the European Communities, 2008.
[34] UNITED NATIONS ENVIRONMENT PROGRAMME. Montreal Protocol on substances that deplete
the ozone layer. New York: United Nations, 1987.
[35] COUNCIL OF THE EUROPEAN UNION. Council Regulation (EC) No. 3093/94
of 15 December 1994 on substances that deplete the ozone layer. Luxembourg: Office for
Official Publications of the European Communities, 1994.
[36] GREAT BRITAIN. Environmental Protection (Controls on Ozone‑Depleting Substances)
Regulations 2002 and subsequent amendments. London: The Stationery Office.
[37] EUROPEAN PARLIAMENT, COUNCIL OF THE EUROPEAN UNION. Regulation (EC)
No. 2037/2000 of the European Parliament and of the Council of 29 June 2000 on substances
that deplete the ozone layer. Luxembourg: Office for Official Publications of the European
Communities, 2000.
A6V10699087_hq-en.pdf?mandator=ic_bt&segment=HQ&fct=downloadasset&pos=download&id1=A6V10699087.
• A single paper copy may be printed for personal or internal company use only.
Knowledge Centre
Standards purchased in hard copy format: Tel: +44 20 8996 7004
• A British Standard purchased in hard copy format is for personal or internal Email: knowledgecentre@bsigroup.com
company use only.
Copyright and Licensing
• It may not be further reproduced – in any format – to create an additional copy. Tel: +44 20 8996 7070
This includes scanning of the document.
Email: copyright@bsigroup.com
If you need more than one copy of the document, or if you wish to share the
document on an internal network, you can save money by choosing a subscription BSI Group Headquarters
product (see ‘Subscriptions’).
389 Chiswick High Road London W4 4AL UK