2 Guide de diagnostic
“maintenance” message and red indicator on
Symptoms Possible causes Remedies
c Sepam displays the maintenance The parameters have been altered. c replace the customer cartridge by the
message, There may be several causes for the TSM 2005 final testing cartridge and read
c the red indicator is on, alteration: the internal fault using the TSM 2001 (see
c the TSM 2001 pocket terminal is not c the memory cartridge has been TSM 2005 manual, chapter on reading
operational, inadvertently plugged in or pulled with internal faults).
c the Sepam 2000 is not working; the power on.
the watchdog has dropped out. c Sepam 2000 self-testing has detected an without the TSM 2005
internal fault which prevents it fromcarrying c to locate the fault, replace the cartrige by
out its functions. another one (made for use in the same
model). If the fault disappears, it came from
the cartridge: reprogram it with LOGIPAM
using the reprogram settings option,
c if necessary, replace the faulty cartridge,
c if the fault persists, replace the power
supply card,
c if the fault persists, replace Sepam 2000.
Guide de diagnostic 3
Sepam 2000 diagnosis guide (cont’d)
“CARTRIDGE” message
Symptoms Possible causes Remedies
c Sepam displays the cartridge message, c the cartridge does not match the Sepam c ensure that the cartridge has not been
c the red indicator is on. model, mixed up with another Sepam 2000
c the TSM 2001 pocket terminal is not c boards needed for Sepam 2000 cartridge,
working, operation are missing, c check the number of ESTOR I/O boards.
c Sepam 2000 is not working; the watchdog c the boards have been switched around, It should be greater than or equal to the
relay has dropped out. c 2 different ECM boards are pluged number of boards needed for the control
in Sepam. logic program,
c check that the cartridge is installed in the
correct model of Sepam: the Sepam model
in which the cartridge should be inserted
appears in line 1 of the label on the front
of the cartridge.
Example :
a cartridge labeled S25 LX M01 should be
inserted in a model 2025 LX Sepam,
c the Sepam model appears in the label
stuck to its side. Check that the boards
present in the rear compartment of that
model comply with the board position
table in the appendix,
c check that ECM boards have the same
sérial number (03143179 or 3122288).
4 Guide de diagnostic
Everything off except for green and red indicators
Symptoms Possibles causes Remedies
c the green on indicator is on, c the cartridge is missing, c check for the cartridge behind the shutter,
c the red inidicator is off, c there may be a programming fault in the c replace the cartridge by a cartridge that is
c the TSM 2001 pocket terminal is not cartridge, presumed to be a good one (intended for
communicating, its screen is blank, c the control logic part is not programmed, the same model of Sepam 2000). If the fault
c the 3 indicators I on, O off, trip and the c power supply board fault. disappears, the fault came from the
display unit are off, cartridge: replace or reprogram it,
c the blinking cursor is displayed on the c if the fault persists, change the Sepam
TSM 2001 pocket terminal but the terminal 2000 power supply board,
is not working. c if the fault persists, change Sepam 2000.
Display of dashs
Symptoms Possible causes Remedies
c a line of dashs is displayed: c pressing a key on the front which is not c none. This is not a fault.
--------------, used (e.g. V/Hz key on a Sepam which does
c this message may appear in normal not contain voltage measurement
operating conditions. functions),
c pressing the alarm key (to display the
stored messages) when no messages have
been stored,
c when stored messages are being read
(after the user has pressed the alarm key),
the dashs appear to indicate the end of the
list of messages (they appear after the
oldest message).
Guide de diagnostic 5
Sepam 2000 diagnosis guide (cont’d)
6 Guide de diagnostic
The voltage measurements are false
Symptoms Possible causes Remedies
c the difference between the expected c the microswitches on the back of the c check the setting of the microswitches on
measurement and the measurement 3U+Vo board are not set correctly, the 3U+Vo board; refer to installation
indicated by Sepam 2000 may be between c one of the parameters in the status menu manual,
10% and 500%, is not set correctly. c check that the Unp and Uns settings
c the protections do not trip at the expected (status menu, phase VT heading) match
setting, the VTs being used; refer to use/
c the green on indicator is on, commissioning manual,
c the red indicator is off, c check that the network frequency has
c the display unit is lit up, been selected correctly (50 or 60 Hz,
c the TSM 2001 pocket terminal is working status menu).
normally.
With TSM 2005
c use the TSM 2005 to test the 3U+Vo
boards (see TSM 2005 manual, chapter on
testing 3U+Vo boards).
Guide de diagnostic 7
Sepam 2000 diagnosis guide (cont’d)
8 Guide de diagnostic
A protection does not trip at the expected set point
Symptoms Possible causes Remedies
c one or more protections do not trip at the c the causes may be same as when the c check the setting of the microswitches on
expected set points. current or voltage measurements are false; the 3U+Vo and the ECM (or ECA) boards;
microswitches or status parameter set refer to installation manual,
incorrectly, c check that the frequency, Unp and Uns
c a protection set point is outside the range settings (status menu, phase VT heading)
accepted by Sepam 2000 after a match the VTs being used;
modification of In, Ib, Unp or Uns, refer to use/commissioning manual,
c the control logic omits the protection c check that the In setting (status menu,
(see control logic operation further on), CT ratio) matches the rating of the CTs
c the protection is set to 999. or CSP sensors used.
See user commissioning manual;
c using the TSM 2001 pocket terminal,
review the list of protections (protections
menu) and check that none of them is
blinking. If that is the case, reset it.
Generally speaking, it is recommended to
set all the parameters in the status menu
before setting the protections,
c check the control logic.
“connector” message
Symptoms Possible causes Remedies
c the display unit indicates connector, c detection of unplugged connector. c check that all connectors are plugged into
c pressing key A (for example) makes the rear of device,
message disappear momentarily, c check that the detection of plugged
c the green on indicator is on, connectors bridge (marked DPC) is present
c the red indicator is off, on terminals 5 and 6 of the 6-pin
c the display unit is lit up, connectors; terminals 7 and 8 on the 8-pin
c the TSM 2001 pocket terminal is working connectors and terminals 20 and 21 on the
normally. 21-pin connectors.
N.B. The BNC, power supply and
communication connectors are not equipped
with the plugged connector detection
system.
Guide de diagnostic 9
Sepam 2000 diagnosis guide (cont’d)
10 Guide de diagnostic
The red communication indicator stays on
Symptoms Possible causes Remedies
c the red communication indicator is on, c Sepam 2000 communication coupler c change the communication kit (2 boards).
c this indicator (communication watchdog) blockage,
is located on the back of Sepam 2000, near c communication coupler failure.
the communication inlet, on the CE40 power
supply board. It is normal for it to light up for
a few seconds when the power is switched
on. When the device is operating normally, it
should be off,
c this indicator may light up even if the
remote monitoring and control system is not
operating or is not connected.
Guide de diagnostic 11
Sepam 2000 diagnosis guide (cont’d)
12 Guide de diagnostic
Sepam 2000 appendix
slot 8 7 6 5 4 3 2 1
S26 or S25 models
LS ESTOR(2) ESTOR ESB SONDE ECM(1) CE40
(2)(4) (4)
LT ESTOR ESTOR ESB 3U+Vo ECM(1) CE40
LX ESTOR(2)(4) ESTOR(4) ESB nothing ECM(1) CE40
XT ESTOR(2) ESTOR ESB 3U+Vo nothing CE40
S36 or S35 models
KR ESTOR(3) ESTOR(2) ESTOR ESB nothing ECM ECM(1) CE40
KZ SONDE ESTOR(2) ESTOR ESB nothing ECM ECM(1) CE40
(3) (2) (1)
YR ESTOR ESTOR ESTOR ESB nothing nothing ECM CE40
ZR ESTOR(3) ESTOR(2) ESTOR ESB nothing SONDE ECM(1) CE40
LR ESTOR(3) ESTOR(2) ESTOR ESB 3U+Vo ECM ECM(1) CE40
LS SONDE ESTOR(2) ESTOR ESB 3U+Vo ECM ECM(1) CE40
(3) (2) (1)
SR ESTOR ESTOR ESTOR ESB 3U+Vo SONDE ECM CE40
SS SONDE ESTOR(2) ESTOR ESB 3U+Vo SONDE ECM(1) CE40
XR ESTOR(3) ESTOR(2) ESTOR ESB 3U+Vo nothing ECM(1) CE40
TR ESTOR(3) ESTOR(2) ESTOR ESB 3U+Vo 3U+Vo ECM(1) CE40
(3) (2)
CR ESTOR ESTOR ESTOR ESB nothing ECMD ECMD CE40
CC(5) ESTOR(3) ESTOR(2) ESTOR ESB ECMD ECMD ECMD CE40
TS(5) SONDE ESTOR(2) ESTOR ESB 3U+Vo 3U+Vo ECM(1) CE40
Notes
(1)
or ECA for CSP sensor,
(2)
the ESTOR 2 board may be installed, depending on the application,
(3)
option for the ESTOR board,
(4)
For SX1 and SX2 applications the ESTOR boards are not installed in Sepam,
(5)
available with S36 only.
Guide de diagnostic 13
9644
Sepam 1000 diagnosis guide
14 Guide de diagnostic
The current measurements are false
Symptoms Possible causes Remedies
c the difference between the expected c the microswitches on the back of the EM c check the setting of the microswitches on
measurement and the measurement (or EA) board are not set correctly, the EM (or EA) board;
indicated by Sepam 1000 may be between c one of the parameters in the status loop refer to installation manual,
10% and 500%, is not set correctly. c check that the In setting (status loop)
c the green on indicator is on, matches the rating of the CTs or CSP
c the red indicator is off, sensors being used; refer to use/
c the display unit is working. commissioning manual,
c check that the network frequency has
been selected correctly
(50 or 60 Hz, status loop).
Guide de diagnostic 15
Sepam 1000 diagnosis guide (cont’d)
16 Guide de diagnostic
A protection does not trip at the expected set point
Symptoms Possible causes Remedies
c one or more protections do not trip at the c the causes may be same as when the c check the setting of the microswitches on
expected set points. current or voltage measurements are false; the ET and the EM (or EA) boards; refer to
microswitches or status parameter set installation manual,
incorrectly, c check that the Unp and Uns settings
c a protection set point is outside the range (status loop) match the VTs being used,
accepted by Sepam 1000 after a c check that the In setting (status loop)
modification of In, Ib, Unp or Uns, matches the rating of the CTs or CSP
c case of residual current protection: sensors being used;
core balance CT connection error refer to use/commissioning manual,
(2 A , 30 A rating or CT). c check that the network frequency setting
has been selected correctly (50 or 60 Hz,
status loop),
c review the list of parameters and check
that none of them are blinking. If that is the
case, set the parameters again. Generally
speaking, it is recommended to set all the
parameters in the status menu before
setting the protections,
c residual current: check the core balance
CT connection.
Check that the core balance CT is a CSH.
Guide de diagnostic 17
Sepam 1000 diagnosis guide (cont’d)
Acknowledgement is impossible
Symptoms Possible causes Remedies
c the reset key is disabled, c the fault at the origin of tripping is still c check for the presence of the fault
acknowledgement is impossible. present. (current, voltage, frequency):
v think of undervoltage protections which
trip when there is zero voltage,
v also remember the thermal overload and
starts per hour protections which remain in
tripped status even when there is no
current. In such cases, wait for the
conditions which caused tripping to
disappear.
18 Guide de diagnostic
Sepam 1000 appendix
Guide de diagnostic 19
3140758A-E
Schneider Electric SA Postal address As standards, specifications and designs change from This document has been
F-38050 Grenoble cedex 9 time to time, please ask for confirmation of the information printed on ecological paper.
Tel: 33 (0)4 76 57 60 60 given in this publication.
Telex: merge 320842 F
http://www.schneider-electric.com
Publishing: Schneider Electric SA
Design, production: Idra
Rcs Nanterre B 954 503 439 Printing:
3140758E-E
ART.75436 02 / 1998