You are on page 1of 20

Protection

and control

Sepam range
Sepam 2000
Sepam 1000
Diagnosis guide
Sepam 2000 diagnosis guide

Contents page
Sepam 2000 diagnosis guide 2
Sepam 2000 appendix 13
Sepam 1000 diagnosis guide 14
Sepam 1000 appendix 19

c the symptoms column describes the fault


observed, together with the possible
consequences.
c the possible causes column describes
what could have caused the fault.
c the remedies column describes the tests
to be performed or operations to be carried
out to correct the situation (they are not
necessarily given opposite the causes
discussed).

All indicators off


Symptoms Possibles causes Remedies
c all the indicators and the display unit c the Sepam 2000 is not being supplied c check the voltage on the power supply
are off, with power, connector,
c the TSM 2001 terminal is not c the device has been switched on rapidly c disconnect the power supply for a few
communicating, the screen is blank. several times in a row, causing internal minutes,
tripping of the CE40 power supply. c if the fault persists, change the Sepam
2000 power supply board. The CE40 board
is fitted with an internal fuse; never replace
it (since other power supply components are
damaged when the fuse blows).

2 Guide de diagnostic
“maintenance” message and red indicator on
Symptoms Possible causes Remedies
c Sepam displays the maintenance The parameters have been altered. c replace the customer cartridge by the
message, There may be several causes for the TSM 2005 final testing cartridge and read
c the red indicator is on, alteration: the internal fault using the TSM 2001 (see
c the TSM 2001 pocket terminal is not c the memory cartridge has been TSM 2005 manual, chapter on reading
operational, inadvertently plugged in or pulled with internal faults).
c the Sepam 2000 is not working; the power on.
the watchdog has dropped out. c Sepam 2000 self-testing has detected an without the TSM 2005
internal fault which prevents it fromcarrying c to locate the fault, replace the cartrige by
out its functions. another one (made for use in the same
model). If the fault disappears, it came from
the cartridge: reprogram it with LOGIPAM
using the reprogram settings option,
c if necessary, replace the faulty cartridge,
c if the fault persists, replace the power
supply card,
c if the fault persists, replace Sepam 2000.

Before re-energizing the Sepam,


check the complete parameter setting
of the Sepam:
c status,
c protection settings,
c control logic parameters:
bistables, time delays...

“maintenance” message and red indicator off


Symptoms Possible causes Remedies
c Sepam displays the maintenance c the microswitches are in a prohibited c check the setting of the microswitches on
message, setting, the ECM (or ECA) and 3U+Vo boards
c the red indicator is off, c Sepam 2000 internal self-testing has (installation manual),
c the TSM 2001 pocket terminal is detected an internal fault which does not c for S25 and S35 Sepam, an error code
operational, prevent Sepam 2000 from momentarily can be read with the pocket terminal in the
c Sepam 2000 is working, performing its functions. About Sepam menu, SFT 2800 heading; it
c the maintenance message disappears appears in line 4 of the screen, on the right :
when a key on the front of the device is v code 0400: change the ECM (ECA) board
pressed, but comes back again after a few (slot 2),
seconds. v code 1000: change the 3U+Vo board,
v code 0800: change the additional ECM
(ECA) board (slot 3),
v codes 2000, 8000: change the RTD
boards,
v other codes or if the fault persists:
replace Sepam 2000.

With TSM 2005


c replace the customer cartridge by the
TSM 2005 final testing cartridge and read
the internal fault using the TSM 2001 (see
TSM 2005 manual, chapter on reading
internal faults).

Guide de diagnostic 3
Sepam 2000 diagnosis guide (cont’d)

“CARTRIDGE” message
Symptoms Possible causes Remedies
c Sepam displays the cartridge message, c the cartridge does not match the Sepam c ensure that the cartridge has not been
c the red indicator is on. model, mixed up with another Sepam 2000
c the TSM 2001 pocket terminal is not c boards needed for Sepam 2000 cartridge,
working, operation are missing, c check the number of ESTOR I/O boards.
c Sepam 2000 is not working; the watchdog c the boards have been switched around, It should be greater than or equal to the
relay has dropped out. c 2 different ECM boards are pluged number of boards needed for the control
in Sepam. logic program,
c check that the cartridge is installed in the
correct model of Sepam: the Sepam model
in which the cartridge should be inserted
appears in line 1 of the label on the front
of the cartridge.
Example :
a cartridge labeled S25 LX M01 should be
inserted in a model 2025 LX Sepam,
c the Sepam model appears in the label
stuck to its side. Check that the boards
present in the rear compartment of that
model comply with the board position
table in the appendix,
c check that ECM boards have the same
sérial number (03143179 or 3122288).

With TSM 2005


c replace the customer cartridge by the
TSM 2005 final testing cartridge and read
the internal fault using the TSM 2001
(see TSM 2005 manual, chapter on reading
internal faults).

“M.CARTRIDGE” message and red indicator on


Symptoms Possible causes Remedies
c Sepam displays the M.CARTRIDGE c cartridge memory fault, with possible c replace the cartridge.
message, altered parameters. Before re-energizing the Sepam, check
c the red indicator is off, the complete parameter setting of the
c the TSM 2001 pocket terminal is not Sepam:
working , c status,
c the Sepam 2000 is not working; the c protection settings,
watchdog has dropped out. c control logic parameters:
bistables, time delays...

“M.CARTRIDGE” message and red indicator off


Symptoms Possible causes Remedies
c Sepam displays the M.CARTRIDGE c incorrect status setting, c check whether the STATUS menu
message, c the maximum number of cartridge parameters are blinking. Blinking
c the red indicator is off, memory entries has been reached parameters should be reprogrammed,
c the TSM 2001 pocket terminal is working, c for S25 and S35 Sepam, an error code is
c the Sepam 2000 is working, read using the pocket terminal in the About
c the M.CARTRIDGE message disappears Sepam menu, item SFT 2800; it appears in
when a key on the front of the device is line 4 of the screen, on the right:
pressed, but comes backagain after a few v code 0040 : replace the cartridge.
seconds.

4 Guide de diagnostic
Everything off except for green and red indicators
Symptoms Possibles causes Remedies
c the green on indicator is on, c the cartridge is missing, c check for the cartridge behind the shutter,
c the red inidicator is off, c there may be a programming fault in the c replace the cartridge by a cartridge that is
c the TSM 2001 pocket terminal is not cartridge, presumed to be a good one (intended for
communicating, its screen is blank, c the control logic part is not programmed, the same model of Sepam 2000). If the fault
c the 3 indicators I on, O off, trip and the c power supply board fault. disappears, the fault came from the
display unit are off, cartridge: replace or reprogram it,
c the blinking cursor is displayed on the c if the fault persists, change the Sepam
TSM 2001 pocket terminal but the terminal 2000 power supply board,
is not working. c if the fault persists, change Sepam 2000.

Display of dashs
Symptoms Possible causes Remedies
c a line of dashs is displayed: c pressing a key on the front which is not c none. This is not a fault.
--------------, used (e.g. V/Hz key on a Sepam which does
c this message may appear in normal not contain voltage measurement
operating conditions. functions),
c pressing the alarm key (to display the
stored messages) when no messages have
been stored,
c when stored messages are being read
(after the user has pressed the alarm key),
the dashs appear to indicate the end of the
list of messages (they appear after the
oldest message).

The TSM 2001 display is blank


Symptoms Possible causes Remedies
c the TSM 2001 pocket terminal screen is c the TSM 2001 pocket terminal display unit c turn the dial on the right-hand side of the
dark, or blank except for the blinking cursor, contrast adjustment has been modified, TSM 2001 pocket terminal,
c the green on indicator is on, c the pocket terminal is out of order. c test the pocket terminal on another
c lthe red indicator is off, Sepam 2000 to determine whether the fault
c the Sepam 2000 display unit is working comes from the terminal or Sepam 2000.
and the keys on the front are operational. If the fault is located in Sepam 2000,
replace it.

Guide de diagnostic 5
Sepam 2000 diagnosis guide (cont’d)

The current measurements are false


Symptoms Possible causes Remedies
c the difference between the expected c the microswitches on the back of the ECM c check the setting of the microswitches on
measurement and the measurement (or ECA) board are not set correctly, the ECM (or ECA) board;
indicated by Sepam 2000 may be between c one of the parameters in the status menu refer to installation manual,
10% and 500%, is not set correctly. c check that the In setting (status menu,
c the green on indicator is on, phase CT heading) matches the rating of
c the red indicator is off, the CTs or CSP sensors being used;
c the display unit is lit up, refer to use/commissioning manual,
c the TSM 2001 pocket terminal is working c check that the network frequency has
normally. been selected correctly (50 or 60 Hz,
status menu).

With TSM 2005


c use the TSM 2005 to test the ECM or ECA
current boards (see TSM 2005 manual,
chapter on testing ECM or ECA boards).

The residual current measurement is false


Symptoms Possible causes Remedies
c reading < 50% of injected current. cthe core balance CT is not compatible. c replace the core balance CT by a CSH,
c check that the core balance CT is wired to
the core balance CT input and not to the CT
input.

I2 current measurement does not appear


Symptoms Possible causes Remedies
c the I2 measurement is missing. It does not c the number of phase CTs selected in the c check the number of CTs indicated in the
appear on the display or on the TSM 2001 status menu is 2 instead of 3. status menu, phase CT heading. Set it to 3.
pocket terminal, If this is the case, Sepam is unaware of the
c the phase 1 and 3 currents are correct. presence of the phase 2 CT.

One of the 3 phase current measurements is zero


Symptoms Possible causes Remedies
c one of the measurements indicates a c there are only 2 CTs in the cubicle, c Sepam connected to a 1A/5A CT: ensure
value of zero or close to zero, c one CT is not wired, that there is current in the CT secondary
c the other 2 phase current measurements c the ECM (or ECA) current input board is circuit which reaches the CCA 660 or
are working normally. The indications are faulty, CCA 650 connector,
the same on the display and on the TSM c the current measured is less than 1.5% of c replace the ECM board,
2001 pocket terminal, In. c Sepam connected to a CSP sensor:
c the green on indicator is on momentarily reverse the connections (BNC
c the red indicator is off, connector) on the ECA board: if the fault
c the display unit is lit up, disappears, the problem is an external one;
c the TSM 2001 pocket terminal is working if the fault persists, replace the ECA board.
normally.
With TSM 2005
c use the TSM 2005 to test the ECM or ECA
current boards (see TSM 2005 manual,
chapter on testing ECM or ECA boards).

6 Guide de diagnostic
The voltage measurements are false
Symptoms Possible causes Remedies
c the difference between the expected c the microswitches on the back of the c check the setting of the microswitches on
measurement and the measurement 3U+Vo board are not set correctly, the 3U+Vo board; refer to installation
indicated by Sepam 2000 may be between c one of the parameters in the status menu manual,
10% and 500%, is not set correctly. c check that the Unp and Uns settings
c the protections do not trip at the expected (status menu, phase VT heading) match
setting, the VTs being used; refer to use/
c the green on indicator is on, commissioning manual,
c the red indicator is off, c check that the network frequency has
c the display unit is lit up, been selected correctly (50 or 60 Hz,
c the TSM 2001 pocket terminal is working status menu).
normally.
With TSM 2005
c use the TSM 2005 to test the 3U+Vo
boards (see TSM 2005 manual, chapter on
testing 3U+Vo boards).

One or two phase voltage measurements do not appear


Symptoms Possible causes Remedies
c the U13 (and U32) measurement is c the phase VTs selected in the status c check the number of VTs indicated in the
missing. It does not appear on the display menu are U21(and U32). If this is the case, status menu, phase VT heading. Set it to 3.
or on the TSM 2001 pocket terminal, Sepam is unaware of the presence of the
c the other voltages are correct. other VTs.

A voltage measurement is zero


Symptoms Possible causes Remedies
c one of the phase-to-phase voltage c there are only one or two VTs in the c ensure that the wiring to Sepam 2000
measurements indicates a value of zero or cubicle, is correct,
close to zero. The indications are the same c the 3U+Vo voltage input board is faulty, c replace the 3u+Vo board.
on the display and on the TSM 2001 pocket c the voltage measured is less than 1.5%
terminal, of Un. With TSM 2005
c the green on indicator is on, c use the TSM 2005 to test the 3U+Vo
c the red indicator is off, voltage boards (see TSM 2005 manual,
c the display unit is lit up, chapter on testing 3U+Vo voltage boards).
c the TSM 2001 pocket terminal is working
normally.

Guide de diagnostic 7
Sepam 2000 diagnosis guide (cont’d)

The power measurements and accumulated energy readings are false


Symptoms Possible causes Remedies
c the power indicated may be totally false c inversion of CT wiring to Sepam 2000 c check the wiring. Comply with the given
or almost zero, current inputs if the frequency is correct, order of phases.
c the power factor indicated may be a c inversion of VT cabling to Sepam voltage
deviant value, inputs if the frequency is displayed by
c otherwise, the current and voltage dashs.
measurements are correct.

The current measurement is zero and the accumulated energy increments


Symptoms Possible causes Remedies
c the accumulated energy increments for a c the load is low and the current is less than c normal operation.
displayed current of zero. 1.5% of In (e.g. no-load transformer).

The frequency measurement is not displayed or is given as dashs


Symptoms Possible causes Remedies
c no display of frequency measurement, c inversion of VT wiring to Sepam 2000 c check the wiring.
c otherwise, the current and voltage voltage inputs, Comply with the given order of phases.
measurements are correct, c direction of phase rotation is incorrect,
c the power indicated and the power factor c the frequency is not measured if voltage
are correct. U21 < 40%,
c the frequency is outside the tolerance
range
45 < F < 55 for 50 Hz
55 < F < 65 for 60 Hz.

8 Guide de diagnostic
A protection does not trip at the expected set point
Symptoms Possible causes Remedies
c one or more protections do not trip at the c the causes may be same as when the c check the setting of the microswitches on
expected set points. current or voltage measurements are false; the 3U+Vo and the ECM (or ECA) boards;
microswitches or status parameter set refer to installation manual,
incorrectly, c check that the frequency, Unp and Uns
c a protection set point is outside the range settings (status menu, phase VT heading)
accepted by Sepam 2000 after a match the VTs being used;
modification of In, Ib, Unp or Uns, refer to use/commissioning manual,
c the control logic omits the protection c check that the In setting (status menu,
(see control logic operation further on), CT ratio) matches the rating of the CTs
c the protection is set to 999. or CSP sensors used.
See user commissioning manual;
c using the TSM 2001 pocket terminal,
review the list of protections (protections
menu) and check that none of them is
blinking. If that is the case, reset it.
Generally speaking, it is recommended to
set all the parameters in the status menu
before setting the protections,
c check the control logic.

“connector” message
Symptoms Possible causes Remedies
c the display unit indicates connector, c detection of unplugged connector. c check that all connectors are plugged into
c pressing key A (for example) makes the rear of device,
message disappear momentarily, c check that the detection of plugged
c the green on indicator is on, connectors bridge (marked DPC) is present
c the red indicator is off, on terminals 5 and 6 of the 6-pin
c the display unit is lit up, connectors; terminals 7 and 8 on the 8-pin
c the TSM 2001 pocket terminal is working connectors and terminals 20 and 21 on the
normally. 21-pin connectors.
N.B. The BNC, power supply and
communication connectors are not equipped
with the plugged connector detection
system.

A logic input generates a fault in cabling outside Sepam


Symptoms Possible causes Remedies
c the logic input is working normally but it c wiring error on the connector of the c check wiring,
creates interference in the outside circuit related board, c replace the faulty ESB or ESTOR board.
(e.g. monitoring of tripping circuit c the ESB or ESTOR board is faulty.
continuity),
c the green on indicator is on,
c the red indicator is off,
c the display unit is lit up,
c the TSM 2001 pocket terminal is working
normally.

Guide de diagnostic 9
Sepam 2000 diagnosis guide (cont’d)

The standard control logic does not operate as expected


Symptoms Possible causes Remedies
c the standard control logic does not c the control logic time delays are not set c if Sepam 2000 is equipped with the
operate as expected, correctly, standard control logic, refer to the
c case in which Sepam 2000 is equipped c the Kp parameters, set via the pocket use/commissioning manual. Check:
with standard control logic. The standard terminal, are not set correctly. They mainly v control logic time delay settings,
control logic is recognized by the presence define the control logic operating modes v Kp parameters (control logic contacts set
of the CAT label which is read on the TSM according to the type of switchgear, with the TSM 2001 pocket terminal).
2001 pocket terminal, in the About Sepam c fault in wiring outside Sepam 2000, c control logic with undervoltage release:
menu, program logic heading, c ESB or ESTOR board faulty. check the open order input I13 wiring
c the green on indicator is on, (normally set to 1),
c the red indicator is off, c generator control logic: check the
c the display unit is lit up, emergency shutdown input I22 wiring
c the TSM 2001 pocket terminal is working (normally set to 1).
normally.
With TSM 2005
c use the TSM 2005 to test the ESB
or ESTOR logic input/output boards
(see TSM 2005 manual, chapter on testing
ESB and ESTOR boards).

Without TSM 2005


c in case of doubt regarding the operation
of a logic input, check that there is voltage
on the input, and set it to 1; to do so check
the input status (1 or 0) using the TSM 2001
pocket terminal (program logic menu,
logic input heading). In the event of a
discrepancy, change the faulty board,
c when in doubt regarding the operation of
a relay output, check that the relay is
activated when Sepam sets the output to 1;
to do so check the input status (1 or 0)
using the TSM 2001 pocket terminal
(program logic menu, logic input
heading). In the event of a discrepancy,
change the faulty board.

Control logic does not operate as expected


Symptoms Possible causes Remedies
c the control logic does not operate as c error in the control logic program, c if there is no CAT label, it is essential to
expected, c time delays or Kp internal bits obtain the customized control logic program
c case in which Sepam 2000 is equipped incorrectly set, in order analyze it and detect the source of
with customized control logic, c defect in cabling outside Sepam 2000, the fault,
c the green on indicator is on, c faulty ESB or ESTOR board. c when in doubt regarding the operation of
c the red indicator is off, logic outputs, refer to the paragraph above.
c the display unit is lit up,
c lthe TSM 2001 pocket terminal is working
normally.

10 Guide de diagnostic
The red communication indicator stays on
Symptoms Possible causes Remedies
c the red communication indicator is on, c Sepam 2000 communication coupler c change the communication kit (2 boards).
c this indicator (communication watchdog) blockage,
is located on the back of Sepam 2000, near c communication coupler failure.
the communication inlet, on the CE40 power
supply board. It is normal for it to light up for
a few seconds when the power is switched
on. When the device is operating normally, it
should be off,
c this indicator may light up even if the
remote monitoring and control system is not
operating or is not connected.

The green Jbus indicator does not blink


Symptoms Possible causes Remedies
c the green communication indicator does c the remote monitoring and control system c refer to Jbus communication documents
not blink, is not in service or is not sending messages and check the following:
c the green indicator is located on the back throught the line, v check the direction of line cabling to
of Sepam 2000, near the communication c the line is cut, terminals 1 to 4 of all the CCA609 units in
inlet, on the CE40 power supply board. c the L+ and L- network wires are reversed, the network,
If the remote monitoring and control system c polarization or impedance matching of the v check that the line has been polarized.
is connected, the indicator should blink to RS 485 line are incorrect. This should be at one point only.
indicate that there is electrical activity in the v check that line impedance has been
line. If it does not blink, it means that the matched at both ends.
Sepam communication input is electrically
deactivated, With TSM 2005
c the red coupler indicator is off, c use the TSM 2005 and a PC to test
c the rest of Sepam 2000 is working the communication system (refer to
normally. communication kit manual.

Guide de diagnostic 11
Sepam 2000 diagnosis guide (cont’d)

The Jbus communication CPT2 diagnosis counter increments


Symptoms Possible causes Remedies
c the CPT2 counter increments, c one of the communication parameters has c use the TSM 2001 pocket terminal to set
c the counter is accessed via the TSM 2001 not been set correctly: rate or parity, the communication rate and parity in
pocket terminal, status menu, c impedance matching and/or accordance with the remote monitoring
communication heading. It counts the communication network polarization are and control system (status menu,
errors in the communication frames. When incorrect, communication heading),
the device is operating normally, it should c there is noise on the line c if this is not sufficient, check polarization
not increment, N.B. The frames which contain errors are and line impedance matching
c the green coupler indicator is blinking (so detected by Sepam 2000 which does not (see Jbus communication manual),
the line is not cut). The red coupler indicator process them. Overall Sepam/remote c check that the CCA 609 clamps are
is off, monitoring and control system operation is tightened onto the cable shielding and not
c the rest of Sepam 2000 is working not generally affected and the number of onto the insulating material. The clamps
normally. frames with errors remains limited (a few). earth the cable shielding,
c check the earthing of the CCA 609 (green-
yellow wire),
c check that the CCA 602 cable connecting
Sepam and the CCA 609 unit is plugged in
and locked at both ends. It contributes to
shielding continuity,
c check that the communication network
does not cross through zones with high
levels of electrical pollution.

With TSM 2005


c use the TSM 2005 and a PC to test
the communication system
(refer to communication KIT manual).

The JBUS communication CPT9 diagnosis counter does not increment


Symptoms Possible causes Remedies
c the CPT9 counter does not increment, c the remote monitoring and control system c use the TSM 2001 pocket terminal to set
c the counter is accessed via the TSM 2001 never addresses this Sepam, the communication speed, salve number
pocket terminal, status menu, c one of the communication parameters is and parity in accordance with the remote
communication heading. It counts the not set correctly: monitoring and control system
errors in the communication frames. When rate, slave number or parity, (status menu, communication heading),
the device is operating normally, it should c communication network impedance c if this is not suficient, check polarization
not increment, matching or polarization is incorrect. and impedance matching
c the green coupler indicator is blinking (see Jbus communication manual).
(so the line is not cut).
The red coupler indicator is off,
c the rest of Sepam 2000 is working
normally.

12 Guide de diagnostic
Sepam 2000 appendix

Table of rear compartment


board positions
c The table below indicates the position of the boards
in the rear compartment according to the different
Sepam 2000 models.
c If the board poisitions are not complied with, Sepam
2000 will not start up and will display maintenance
or cartridge.

slot 8 7 6 5 4 3 2 1
S26 or S25 models
LS ESTOR(2) ESTOR ESB SONDE ECM(1) CE40
(2)(4) (4)
LT ESTOR ESTOR ESB 3U+Vo ECM(1) CE40
LX ESTOR(2)(4) ESTOR(4) ESB nothing ECM(1) CE40
XT ESTOR(2) ESTOR ESB 3U+Vo nothing CE40
S36 or S35 models
KR ESTOR(3) ESTOR(2) ESTOR ESB nothing ECM ECM(1) CE40
KZ SONDE ESTOR(2) ESTOR ESB nothing ECM ECM(1) CE40
(3) (2) (1)
YR ESTOR ESTOR ESTOR ESB nothing nothing ECM CE40
ZR ESTOR(3) ESTOR(2) ESTOR ESB nothing SONDE ECM(1) CE40
LR ESTOR(3) ESTOR(2) ESTOR ESB 3U+Vo ECM ECM(1) CE40
LS SONDE ESTOR(2) ESTOR ESB 3U+Vo ECM ECM(1) CE40
(3) (2) (1)
SR ESTOR ESTOR ESTOR ESB 3U+Vo SONDE ECM CE40
SS SONDE ESTOR(2) ESTOR ESB 3U+Vo SONDE ECM(1) CE40
XR ESTOR(3) ESTOR(2) ESTOR ESB 3U+Vo nothing ECM(1) CE40
TR ESTOR(3) ESTOR(2) ESTOR ESB 3U+Vo 3U+Vo ECM(1) CE40
(3) (2)
CR ESTOR ESTOR ESTOR ESB nothing ECMD ECMD CE40
CC(5) ESTOR(3) ESTOR(2) ESTOR ESB ECMD ECMD ECMD CE40
TS(5) SONDE ESTOR(2) ESTOR ESB 3U+Vo 3U+Vo ECM(1) CE40
Notes
(1)
or ECA for CSP sensor,
(2)
the ESTOR 2 board may be installed, depending on the application,
(3)
option for the ESTOR board,
(4)
For SX1 and SX2 applications the ESTOR boards are not installed in Sepam,
(5)
available with S36 only.

c 3U+Vo: voltage inputs and residual voltage input,


Functions of rear c SONDE: 6 PT100 RTD inputs,
compartment boards c ESB: 2 logic inputs, 2 output relays and watchdog relay
3 versions available: 24/30 VDC, 48/127 VDC and 220/250 VDC,
c CE40 c ESTOR: 8 logic inputs and 4 output relays 3 versions available: 24/30 VDC,
Power supply: 3 versions available: 24/30 VDC, 48/127 VDC and 220/250 VDC.
48/127 VDC and 220/250 VDC.
c INT RS 485 :
Communication interface. It is located behind the
metal plate on the power supply board.
c ECM
Current inputs for 1 A or 5 A seonsor and CSH core
balance CT input for residual current measurement.
Sepam TC type.
c ECA
current inputs for CSP sensor or CSH core balance
CT input for residual current measurement. This
board in installed in place of the ECM board for
Sepam 2000 CS type.

Guide de diagnostic 13

9644
Sepam 1000 diagnosis guide

All indicators off


Symptoms Possible causes Remedies
c all the indicators and the display unit c the Sepam 1000 is not being supplied with c check the voltage on the power supply
are off. power. connector,
c if the fault persists, change the Sepam
1000 AS' power supply board. The AS'
board is fitted with an internal fuse; never
replace it (since other power supply
components are damaged when the fuse
blows).

Everything off except for green and red indicators


Symptoms Possible causes Remedies
c the green on indicator is on, c the self-tests have detected an internal c change the Sepam AS' power supply
c the red indicator is on, fault, board,
c the trip indicator and display unit are off, c power supply board fault. c if the fault persists, replace the
c the watchdog has dropped out. Sepam 1000.

display of the “check settings” message


Symptoms Possible causes Remedies
c the display unit shows the message: c Sepam 1000 has detected a parameter c switch to parameter setting mode and
check settings, setting faults (outside range, incompatible change the settings of all the parameters
c the values of some parameters are settings, set point modified after a change which are blinking on the display unit.
blinking, of In, etc.).
c the protections are working normally.

The -, + and enter keys are disabled


Symptoms Possible causes Remedies
c the -, + and enter keys are disabled. c Sepam is not in parameter setting mode. c switch to parameter setting mode by
pressing for a second on the P key on the
back of Sepam.

Display of the “fault” message


Symptoms Possible causes Remedies
c internal fault. c internal fault. c replace Sepam.

14 Guide de diagnostic
The current measurements are false
Symptoms Possible causes Remedies
c the difference between the expected c the microswitches on the back of the EM c check the setting of the microswitches on
measurement and the measurement (or EA) board are not set correctly, the EM (or EA) board;
indicated by Sepam 1000 may be between c one of the parameters in the status loop refer to installation manual,
10% and 500%, is not set correctly. c check that the In setting (status loop)
c the green on indicator is on, matches the rating of the CTs or CSP
c the red indicator is off, sensors being used; refer to use/
c the display unit is working. commissioning manual,
c check that the network frequency has
been selected correctly
(50 or 60 Hz, status loop).

One of the phase current measurements is zero


Symptoms Possible causes Remedies
c a measurement indicates a value of zero c there are only 2 CTs in the cubicle, c Sepam connected to a 1A/5A CT: ensure
or close to zero, c one CT is not wired, that there is current in the CT secondary
c the 2 other phase current measurements c the EM (or EA) current input board is circuit which reaches the CCA 660 or
are working normally, faulty. CCA 650 connector,
c the green on indicator is on, c replace the EM board,
c the red indicator is off, c Sepam connected to a CSP sensor:
c the display unit is working. momentarily reverse the connections (BNC
connector) on the EA board: if the fault
disappears, the problem is an external one;
if the fault persists, replace the EA board.

The voltage measurements are false


Symptoms Possible causes Remedies
c the difference between the expected c the microswitches on the back of the ET c check the setting of the microswitches on
measurement and the measurement board are not set correctly, the ET board; refer to installation manual,
indicated by Sepam 1000 may be between c one of the parameters in the status loop c check that the Unp and Uns settings
10% and 500%, is not set correctly. (status loop) match the VTs being used;
c the protections do not trip at the expected refer to use/commissioning manual,
setting, c check that the network frequency has
c the green on indicator is on, been selected correctly (50 or 60 Hz, status
c the red indicator is off, loop).
c the display unit is working.

Guide de diagnostic 15
Sepam 1000 diagnosis guide (cont’d)

The U32 and U13 phase voltage measurements do not appear


Symptoms Possible causes Remedies
c the U32 and U13 measurements are c the VT's parameter in the status loop is c check the VT's parameter (status loop).
missing, set to U21, in which case Sepam is unaware Set it to U21U32.
c the U21 voltage measurement is correct. of the value of the other voltage
measurements.

A voltage measurement channel indicates zero


Symptoms Possible causes Remedies
c one of the phase-to-phase voltage c there are only one or two VTs in the c ensure that the VT secondaries are wired
measurements indicates a value of zero or cubicle or not all the VTs are cabled, to Sepam 1000,
close to zero, c the ET voltage input board is faulty. c replace the ET board.
c the green on indicator is on,
c the red indicator is off,
c the display unit is working.

16 Guide de diagnostic
A protection does not trip at the expected set point
Symptoms Possible causes Remedies
c one or more protections do not trip at the c the causes may be same as when the c check the setting of the microswitches on
expected set points. current or voltage measurements are false; the ET and the EM (or EA) boards; refer to
microswitches or status parameter set installation manual,
incorrectly, c check that the Unp and Uns settings
c a protection set point is outside the range (status loop) match the VTs being used,
accepted by Sepam 1000 after a c check that the In setting (status loop)
modification of In, Ib, Unp or Uns, matches the rating of the CTs or CSP
c case of residual current protection: sensors being used;
core balance CT connection error refer to use/commissioning manual,
(2 A , 30 A rating or CT). c check that the network frequency setting
has been selected correctly (50 or 60 Hz,
status loop),
c review the list of parameters and check
that none of them are blinking. If that is the
case, set the parameters again. Generally
speaking, it is recommended to set all the
parameters in the status menu before
setting the protections,
c residual current: check the core balance
CT connection.
Check that the core balance CT is a CSH.

A protection does not trip


Symptoms Possible causes Remedies
c a protection does not trip. c inhibition of the protection by a 999 type c check the set points,
setting, c check the output addressing. Make sure in
c incorrect addressing of the protection particular that the ES1 board is included if
output, relays AUX1, AUX3 and AUX4 are
c residual current protection: supposed to be used,
microswitches not set correctly. c residual current protection: if the sum of
the phase currents i used, check that the
setting of the SW1 microswitches on the EM
or EA board is as follows:
SW1.

Guide de diagnostic 17
Sepam 1000 diagnosis guide (cont’d)

Acknowledgement is impossible
Symptoms Possible causes Remedies
c the reset key is disabled, c the fault at the origin of tripping is still c check for the presence of the fault
acknowledgement is impossible. present. (current, voltage, frequency):
v think of undervoltage protections which
trip when there is zero voltage,
v also remember the thermal overload and
starts per hour protections which remain in
tripped status even when there is no
current. In such cases, wait for the
conditions which caused tripping to
disappear.

Frequency measurement and functions do not work


Symptoms Possible causes Remedies
c the frequency measurement is displaying c incorrect wiring, c check the wiring
hyphens, c U21 or forward voltage too low. (direction of phase rotation),
c the frequency protections do not trip. c check voltage amplitude: U21 voltage
should be greater than 30% of Unp and
forward voltage should be greater than 20%
of Vnp.

The logic input does not work


Symptoms Possible causes Remedies
c the logic input remains at zero, whether it c wiring error on the ES1 board connector, c check the wiring and voltage on the input
is supplied with power or not, c ES1 board microswitch setting error, in terminals,
c the green on indicator is on, the case of use with 24/30 VDC. c if the input is used with 24/30 VDC, the
c the red indicator is off, microswitches on the ES1 board must be
c the display unit is working. set as follows: SW1,
c if the fault persists,
replace the ES1 board.

18 Guide de diagnostic
Sepam 1000 appendix

Table of rear compartment Functions of rear compartment boards


board positions c EM: current inputs for 1 A or 5 A sensor and CSH core balance CT input for
residual current measurement,
c the table below indicates the position of the boards c EA: current inputs for CSP sensor and CSH core balance CT input for residual
in the rear compartment according to the different current measurement,
Sepam 1000 models. c ET: voltage inputs and residual voltage input,
c failure to use the correct board positions is liable to c AS’: power supply and 2 outputs 4 versions available:
damage Sepam 1000. v 24/30 VDC,
v 48/125 VDC,
v 220/250 VDC and 100/127 VAC,
v 220/240 VAC,
c ES1: 1 logic input and 3 output relays and watchdog relays
single multi-voltage version available.
slot 3 2 1 0
S05 model
LX EM AS’ ES1
1 A / 5 A CT sensor (option)
LX EA AS’ ES1
CSP sensor (option)
TX ET AS’ ES1
(option)

Guide de diagnostic 19
3140758A-E

Schneider Electric SA Postal address As standards, specifications and designs change from This document has been
F-38050 Grenoble cedex 9 time to time, please ask for confirmation of the information printed on ecological paper.
Tel: 33 (0)4 76 57 60 60 given in this publication.
Telex: merge 320842 F
http://www.schneider-electric.com
Publishing: Schneider Electric SA
Design, production: Idra
Rcs Nanterre B 954 503 439 Printing:
3140758E-E
ART.75436 02 / 1998