SYMBOL DESIGNATION SYMBOL DESIGNATION SYMBOL DESIGNATION SYMBOL DESIGNATION SYMBOL DESIGNATION
PIPING PARTS OTHER EQUIPMENTS GENERAL SYMBOL FOR MEASURING MEASURING AND INTERFACES, LIMITS
POINT CONTROL (I&C)
INTERFACE POINTER TO / FROM OTHER P&ID
VENT LINE STEAM TRAP /AUTOMATIC LIQUID DRAIN KIND OF MEASUREMENT GROUP1 - GROUP2
GENERAL SYMBOL FOR MEASURING POINT
-CODE LETTERS FOR I&C (ACCORDING ISO 3511/2) XY 69018/000xx XY : COORDINATES ON OTHER P&ID
11HAD10 CL001 -CONTACT DRAWING NUMBER
First letter -KKS DESIGNATION OF MEASURING POINT
Y STRAINER -SUPPLIER DRAWING NUMBER
FLEXIBLE HOSE STRAINER P PRESSURE LOCALLY MOUNTED TP

XX LIMIT OF SUPPLY
T TEMPERATURE CMI Others
FUNNEL CONDENSING POT
Z POSITION 7
7

SIGNAL SENT TO DCS


11 HAD11 BR101 PIPING DESIGNATION KKS F FLOW INTERFACE POINTER TO/FROM OTHER P&ID
DN350-1C PIPING NOMINAL DIAMETER (mm)-CMI PIPING SPECIFICATION FLOW VORTEX OUT OF CMI SUPLY
L LEVEL
Y VIBRATION SIGNAL SENT TO CONTROL ROOM
POCKET (THERMOWELL OR SAMPLING PROBE) FLOW MEASURING DEVICE, GENERAL
Q QUALITY

BUTTWELD CONNECTOR FLOW NOZZLE S SPEED, ROTATION


CODE LETTERS FOR KKS
Second letter OF MEASUREMENTS
(or third)
QUICK COUPLING CONNECTOR FLOW SWITCH
CF FLOW MEASUREMENT
T TRANSMITTER (LOCAL INDICATION OR FLOW SWITCH)
ORIFICE FLOW METER I INDICATOR (WITH GRADUATION) 6
REDUCER CL LEVEL MEASUREMENT
6

PRESSURE REDUCING ORIFICE E PRIMARY ELEMENT


D CP PRESSURE MEASUREMENT
FLANGE DIFFERENCE
S SWITCH CT TEMPERATURE MEASUREMENT
EXHAUST PIPE SILENCER
BLIND CAP CG LIMIT SWITCH

DUCT SILENCER CQ ANALYSIS NOTES :


HEAT TRACING --------------------------------------------------------------------------------------------------------------------------------------------------------------------
BT CONDENSATE POT
HEAT EXCHANGER - GENERAL NOTES :
CY VIBRATION MEASUREMENT
VALVES, ACTUATORS - REFER TO :
69018_20E21 FOR PIPE LIST
69018_23E21 FOR VALVE LIST
69018_49E21 FOR EQUIPMENT LIST
GLOBE VALVE OR TANK, DRUM 69018_71E21 FOR INSTRUMENTATION LIST
69018_49E22 FOR TERMINAL POINT LIST 5
5

69018_20E23 FOR SITE DISSIMILAR WELDING


BALL VALVE HEAT EXCHANGER HEADER 69018_10C06 FOR WATER/STEAM LAYOUT
69018_94D45 FOR SAFETY VALVES SETTING

NORMALLY CLOSED (GENERAL) CENTRIFUGAL PUMP


- SEE P&ID 69018_00021 FOR THE GENERAL
NOTE ABOUT ASME LIMITATION.
CHECK VALVE
AGITATOR - INSTRUMENT NUMBERS BETWEEN 800 AND 899 ARE USED FOR PERFORMANCE TEST AND TEMPORARY
MEASUREMENTS ONLY
STOP CHECK VALVE
OPENED DRAIN - FOR ALL MANUAL DRAINS AND VENTS, IF THERE IS CMI SPECIFICATION CHANGE,
THE TRANSITION IS DONE AFTER THE LAST VALVE.
GATE VALVE
WELDED CAP
VALVE WITH PROGESSIVE
ADJUSTMENT CHARASTERISTIC CCC
CHEMICAL CLEANING CONNECTION 4
THREE WAYS VALVE
4

PRESSURE RELIEF PP
PRESSURE PORT
VALVE FOR CONSTRUCTION VR ER IW 27-10-16 D
UPDATED KVH SJ IW 25-08-16 C
DELIMITATION OF THE SYSTEM IDENTIFICATION IN THE FIRST UPDATED VR ER IW 02-06-16 B
SELF PRESSURE REDUCING VALVE BREAKDOWN LEVEL ( F1 F F F )
2 3 N
FIRST ISSUE VR ER IW 20-04-16 A
Modifications D raft. C heck . E ngin. DATE REV

DESUPERHEATING VALVE DELIMITATION OF THE PIPING IDENTIFICATION OR BR NUMBER


IN THE SECOND BREAKDOWN LEVEL ( AN )
CHECK VALVE WITH HOLE
MINIMUM FLOW CASING LIMIT
PNEUMATICALLY OPERATED VALVE 3
3

SOLENOIDE VALVE
ELECTRIC MOTOR ACTUATED VALVE
ANGLE VALVE
FENCHUGANJ
KUSHIARA CCPP
LOCkABLE GLOBE VALVE 1x1x1 GE9E.03
NEEDLE VALVE

PRESSURE AND DIFFERENTIAL PRESSURE MEASUREMENTS

MOVDIG : MOTORIZED OPERATED ON/OFF VALVE 2


2

DP TRANSMITTER P TRANSMITTER P INDICATOR MOVPOS : MOTORIZED OPERATED POSITIONABLE VALVE


MOVCTRL : MOTORIZED OPERATED CONTROL VALVE STATUS REVISIONS
(*) (*) PRELIMINARY A B C Material Weight Unit.
FOR LAYOUT B004E/00069
POVDIG : PNEUMATIC OPERATED ON/OFF VALVE FOR CONSTRUCTION D ORDER N° ISO
FOR CONSTRUCTION EXCEPT HOLD
PROCESS PROCESS POVPOS : PNEUMATIC OPERATED POSITIONABLE VALVE AS BUILT
5 WAYS POVCTRL : PNEUMATIC OPERATED CONTROL VALVE Engineer WEBER
2 WAYS VALVE
MANIFOLD MANIFOLD DIN 16272 Destination Checker RADERMECKER

FSC : FAIL SAFE CLOSE (ON INSTRUMENTATION AIR FAILURE)


FENCHUGANJ Draftman RIZZO
DR / TEST
DP DR / TEST DR / TEST
FSO : FAIL SAFE OPEN (ON INSTRUMENTATION AIR FAILURE) KUSHIARA CCPP N ame Signature
P P FSL : FAIL SAFE LAST POSITION Designation
(*) CONDENSING POT IN CASE OF STEAM CONNECTION
LSO : LIMIT SWITCH OPEN HRSG SYMBOLS
LSC : LIMIT SWITCH CLOSE 1
P&I Diagram
1

Draw
This drawing and the design it covers are the property of C.M.I.. This drawing and the design it covers are the property of C.M.I..
They are merely loaned and on the borrower ' s express agreement that They are merely loaned and on the borrower ' s express agreement that 69018_00001
they will not be reproduced , copied , loaned , exhibited or used , except they will not be reproduced , copied , loaned , exhibited or used , except

N
in the limited way and private use permitted by any written consent in the limited way and private use permitted by any written consent
given by C.M.I. to the borrower . given by C.M.I. to the borrower . Scale : A1 Sheet : 1 1
P O N M L K J I H G F E D C B A

You might also like