Professional Documents
Culture Documents
\*
MERGE
FORMA
M&V Plan 6.2- Phase Change Material Temperature Control
b) Drafts from poor air sealing cause infiltration related discomfort. This uncontrolled
infiltration is a cause of excessive heating energy consumption. As a remedy a contagious
vapor permeable air barrier will be installed.
a) Temperature fluctuations from the outdoor environmental conditions cause the building
indoor temperatures to not meet thermostatic set points causing occupant discomfort.
These indoor temperature fluctuations cause excessive heating, cooling and fan energy
consumption. As a remedy the Infinite R Phase Change Material product will be applied
to the bottom of the attic and as an integrated layer within the CMU block wall during the
installation of an ascetic clip on metal wall finishing system.
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
M&V GUIDELINE AND OPTION
This project will use an abridged methodology including option B, all perimeter measurement,
option C while building regression analysis of utility bills and option D, calibrated simulation.
determine long annual values by means of calibration with short term sensor data
collection.
c) Electric energy savings will be determined from current transducer measurements from
baseline and performance periods. Annual baseline energy consumption will be
determined by means of empirical regression analysis of historical utility bills. Per
option D, a calibrated simulation will be used to determine long annual values by means
of calibration with short term sensor data collection.
e) Historical utility bill data will be corrected for variation of occupancy related internal
loads and outdoor weather conditions related thermal loads.
f) An Energy Plus thermal simulation will be calibrated to available data and ran for a
typical meteorological year for the location and serve as the annual baseline.
c) Uncontrolled infiltration.
that the occupants will “feel” more comfortable with higher cooling and lower heating
setpoints that follow california title 24 standards.
e) All other inputs will remain the same as the Baseline
3.3 CALCULATIONS
Sample formulas:
The Heat flux method can be used to determine the energy savings of installed PCM without
measurement of HVAC system energy or demand by calculating the total absorbed heat
(cooling) and rejected heat (heating). Also the heat flux method can be used to confirm energy
savings resulting from measurement of HVAC system energy by comparing the trends of energy
or demand savings to the reduced HVAC loads. The formula to calculate the heat absorbed or
released with a Heat Flux sensor is: HeatFlux [W/m2] x AREA= numerically Positive THEN x AREA
x PCM Thermal Capacity = kWh Heating Energy Saved ELSE/IF numerically Negative THEN x
AREA x PCM Thermal Capacity = kWh Cooling Energy Saved.
The following depiction highlights the use measurement of heat flux as a method to plit a
standard phase change diagram as would be typically be done using DSC tests in a laboratory,
but on the building scale. Placing the temperature measurement at the PCM on the X axes and
total stored heat measured by the heat flux sensor at the PCM in the Y axis, The Phase Change
material thermal energy storage as a function of temperature can be diagramed, similar to the
phase change region in the generic example below.
In order to verify this heat flux behavior, the following process will be followed:
● Heat flux sensors shall be thermoelectric generator type with amplification and a total
accuracy of no more than 0.4 W/m2 and no less than 1 W/m2.
● Measured data shall be in 15 minute or smaller time steps and averaged hourly.
● Temperature and heat flux data shall be correlated and processed in order to show total
heat absorbed, stored and released by the PCM in relative terms as compared to the
control area.
● The measured heat flux energy at the PCM shall then be used in data analysis to locate
and confirm the cooling and heating effects of PCM in the measured energy consumption
and demand from the HVAC system.
Overview:
This project aims to measure and verify the energy absorption of phase change
materials within a small office building. The intent of the study is to demonstrate the
annual cooling and heating energy savings, peak electrical demand reduction and
comfort improvement to the building.
The thermal zone has a single office with a thermostat. The spaces within the zone
contain multiple primary uses ranging from: single office, to main lobby, to conference
room. Due to this use variance, and fact of one thermostat location; throughout the day,
offices and conference rooms frequently become overheated or undercooled. Offices
have been known to overheat during the day when there are solar gains from the south
glazing and/or when there is high occupancy during company meetings in conference
rooms or in offices.
Presently, to address temperature fluctuations the occupants have set the thermostats
to 72F. California Energy Commission thermostat setting are 75F for cooling and 68F
for heating will be used during the performance period and the PCM will be used to
maintain comfort temperatures.
period.
● RTU amperage, current and power factor for baseline and performance period.
● Directional heat flux will be measured for short term during performance period.
2. Zone air temperature, attic floor temperature and external wall are measured in Office #1
3. Current transducers and energy meter is attached to the power box located in the MECH
room and connected to the cell gateway.