Professional Documents
Culture Documents
is known, the quantity of condensing medium convert from pounds per minute to cubic feet
circulated through the condenser in pounds per minute, viz:
per hour can be determined by applying M(lb/hr) x v(cu ft/lb)
Equation 14-4. Likewise, if the quantity cfm =- .
circulated is known, the temperature rise 60 m m
through the con denser can be computed by Assuming the specific volume of the air to be
applying Equation 14-5. the specific volume of standard air (13.34 cu
Average specific heat values for air and ft/ lb), incorporation of these conversion
water are 0.24 Btu/lb and 1 Btu/lb, factors into Equation 14-7 results in the
respectively. By substituting the appropriate following:
value for C, Equations 14-4 and 14-5 can be . Q, x 13.34 cu ft/lb
written to apply specifically to either water or cfm ... 0.24 x 60 x b.T
air, viz: or, combining constants (13.34/0.24 x 60 =
I
Condensing temperature
t
1100·
!
Mean effective l
Flt• 14-1. Water temperature temperature J Leaving waier temperature 92°-.Water out
difference ,· - ----------
(13.84")
,
rise through condenser. _t -.- Average water temperature L86.1 •
I , .
Temper ture
nse m
1 condenser
i
1
Water in Entenng water temperature 1a•
amount of condensing surface required for a increases. If the flow rate is increased beyond
given condensing temperature decreases as the a certain point, the increase in the power
flow rate of the condensing medium increases. required to circulate the condensing medium
will more than offset the reduction in the
With regard to the latter statement, this power require ments of the compressor
means in effect that the same condensing accruing from the increased flow rate.
temperature can be maintained with either a · Therefore, the quantity of condensing medium
small condensing surface and a high flow rate which can be economically circulated is
or a large condensing surface and a low flow limited by the power requirements of the fan,
rate. However, it should be recogni7.ed that blower, or pump.
the flow rate of the condensing medium is Obviously, the optimum flow rate for the
fixed within certain limits by the size and condensing medium is the one which will
design of the condenser. If the flow rate result in the lowest over-all operating costs for
through the condenser is too low, flow will be the system. This will vary somewhat with the
streamlined rather than turbulent and a low conditions of the individual installation, being
transfer coeffi cient will.result. On the other influenced by the type of application, the size
hand, if the flow rate is too high, the pressure and type of condenser used, fouling rates, and
drop through the condenser becomes the design conditions for the region, along
excessive, with the result that the power with such practical considerations as the cost
required to circulate the con densing medium and availability of water, utility costs, local
also becomes excessive. codes and restrictions, etc. For example, since
Since the design entering temperature of the good system efficiency prescribes lower
condensing medium is usually fixed by condi condensing temperatures for low temperature
tions beyond the control of the system applications than for high temperature
designer, it follows that the size and design of applications, it follows that for the same
the con denser and the flow rate of the condenser load the optimum condensing
condensing medium are determined almost medium flow rate will usually be higher for a
entirely by the design condensing temperature. low temperature appli cation than for a high
Although low condensing temperatures are temperature application. Too, where the
desirable in that they result in high compressor entering temperature of the condensing
efficiency and low horsepower requirements medium is relatively high, larger condensing
for the compressor, this does not necessarily surfaces and higher flow rates are required
mean that the use of a large condensing to provide reasonable condensing
surface and a high flow rate in order to temperatures than where the entering tempera
provide a low con densing temperature will ture of the condensing medium is lower.
always result in the most practical and 14-6. Air-Cooled Condensers. The circula
economical installation. Other factors which tion of air over an air-cooled condenser may
must be taken into account and which tend to
be either by natural convection or by action
limit the size of the condenser and/or the
of a fan or blower. Where air circulation is
quantity of condensing medium circulated
by natural convection, the air quantity
are initial cost, available space, and the power
requirements of the fan, blower., or pump circulated over the condenser is low and a
circulating the condensing medium. Too, relatively large condensing surface is
where water is used as the condensing required. Because of their limited capacity
medium and the water leaving the condenser natural convection con densers arc used only
is wasted to the sewer (see Section 14-9), the on small applications, principally domestic
availability and cost of the water must also be refrigerators and freez.ers. Natural convection
considered. The limitations imposed on condensers employed on domestic
condenser size by the factors of initial cost refrigerators are usually either plate surface
and available space are self-evident. As for or finned tubing. When finned tubing is used,
the power requirements of the fan, blower, the fins are widely spaced so that little or no
or pump circulating the condensing medium, resistance is offered to the free circulation of
it has already been stated that the power air. Too, wide fin spacing reduces the
required to circulate the con densing medium possibility of the condenser being fouled with
increases as the flow rate dirt and lint.
The plate-type condenser is mounted on the
CONDENSERS AND COOLING TOWERS 249
back of the refrigerator in such a way that an limitation in physical size, chassis-mounted
air flue is formed to increase air circulation.
condensers of the type shown in Fig. 6-12 are
Finned tube condensers are mounted either on
rarely found in capacities larger than 2 tons.•
the back of the refrigerator or at an angle
Another disadvantage of the chassis-mounted
underneath the refrigerator. Regardless of
air-cooled condenser is their susceptibility to
condenser type or location, it is essential that
fouling. Since most condensing units are
the refrigerator be so located that air is
mounted on the floor, the condenser air tends
permitted to circulate freely through the
to sweep across the floor so that dirt, lint, and
condenser at al} times. Too, warm locations,
other foreign materials are picked up from the
such as one adjacent to an oven, should be
floor and carried to the surface of the
avoided when ever possible.
condenser, thereby "clogging" the condenser
A number of domestic free7.er
and restricting
manufacturers uti1ilize the outer shel1 of the
the air flow.
freezer (outside wal1 surface) as a condensing
Too, on "open-type" air-cooled condensing
surface. This is accomplished by bonding
units the condenser fan is usually mounted on
bare tubing to the inside surface of the outer
the shaft of the compressor driver (Fig. 6-12).
sheU so that the entire outer shell becomes a
Natural1y this limits both the size and the
plate-type heat transfer surface. The use of
location of the fan so that the quantity of air
these "wrap around" condensers permits a
circulated over the condenser is always less
considerable reduction in the size of the
than that which would produce maximum
freezer (6 to 8 in. on both length and width),
efficiency at fu]] load conditions. Notice also
not only because it eliminates the space
that, because of the fan location, the distri
ordinarily required for the condenser but also
bution of the air over the condenser surface is
because it allows the use of
very uneven, being much greater on the end of
3 to 4 in. of insulation in the walls where
the condenser directly in front of the fan.
normal1y 6 to 8 in. is required in order to
Remote air-cooled condensers are used in •
prevent moisture from condensing on the
sizes from 1 ton up to 100 tons or more and
outside surface of the freezer. The slightly
may be mounted either indoors or outdoors.
higher operating costs which accrue as a result
When located indoors, provisions must be
of reducing the amount of wan insulation is
made for an adequate supply of outside air to
more than offset by the savings in space that
the condenser (Fig. 14-2). If the condenser is
this practice makes possible.
installed in a warm location, such as in an attic
Air-cooled condensers employing fans or
or boiler room, ducts should be used to carry
blowers to provide "forced-air" circulation can
the air into the condenser and back to the
be divided into two groups according to the
outside. Because of the large quantity of air
location of the condenser: (1) chassis-mounted
required, only the smaller sizes are mounted
and (2) remote.
indoors.
A chassis-mounted air-cooled condenser is
When located outdoors, the air-cooled con
one that is mounted on a common chassis with
denser may be mounted on the ground, on the
the compressor and compressor driver so that
roof, or on the side of a wall, with roof
it is an integral part of the air-cooled "con
locations being the most popular. Typical wall
densing unit" (Fig. 6-12). Although chassis
and roof installations are shown in Figures 14-
mounting of the air-cooled condenser makes
3 and 14-4, respectively. In all cases, the
possible a very compact, completely self
condenser should be so oriented that the
contained condensing unit which is ideally
prevailing winds for the area in the
suited for use on smal1 commercial fixtures,
summertime will aid rather than retard the
this arrangement has certain inherent
action of the fan. In the event that such
disadvan tages which make chassis-mounting
orientation is not possible, wind deflectors
impractical in larger applications.
should be installed on the discharge side of the
The principal disadvantage of chassis
mounted air-cooled condensers is that the condenser (Fig. 14-5).
physical size of the condenser is limited to • This is the approximate condenser
the dimensions of the chassis. Because of the capacity required on a 3 hp, commercial, air-
cooled '-.m densing. Approximately 25% of the
motor horse power is required to drive the fan.
Naturally, this reduces the horsepower available to
the compressor.
CONDENSERS AND COOLING TOWERS 250
Ceilin Purge
g valve
D
D
Air
flo
D v:-
D Fl1. 10-2, Indoor installation of
air-cooled condenser. (Cour
tesy Kramer Trenton Com
pany.)
One significant outgrowth of the remote air type is rapidly gaining in popularity and is now
cooled condenser has been the development of available in almost any desired capacity.
a new type of air-cooled condensing unit which 14-7. Air Quantity and Velocity. For an
is designed specifically for remote installation. air-cooled condenser there is a definite relation
The air-cooled condensing unit illustrated in ship between the size (face area) of the con
Fig. 14-6 is typical of these newer designs. This denser and the quantity of air circulated in that
the velocity of the air through the condenser is
critical within certain limits. Good design pre
scribes the minimum air velocity that will pro
duce turbulent flow anda high transfer
coefficient. Increasing the air velocity beyond
this point causes an excessive pressure drop
through the condenser and results in an
unnecessary increase in the power requirements
of the fan or blower circulating the air.
The velocity of the air passing through an air
cooled condenser is a function of the free face
area of the condenser and the quantity of air
circulated. The relationship is given in the
following equation:
. . Air quantity (cfm)
Air velocity (fpm) =F reef ace area( sqf
)t
Fis. 14-4. Remote air-cooled condensers mounted on roof. (Courtesy Dunham-Bush, Inc.)
Fl1, 14-6, Air-cooled condensln& unit designed for remote Installation. Notice generous size of condenser.
(Courtesy Kramer Trenton Company.)
most air-cooled condensers come equipped In order to select a condenser from the
with fans or blowers, the quantity of air rating tables, the following design data must be
circulated over the condenser is also fixed so known:
that the average temperature of the air passing (1) The design suction and condensing tem
over the condenser depends only on the dry peratures
bulb tem perature of the entering air and the (2) The compressor capacity in Btu/hr
load on the condenser. Obviously, then, in (3) The design outdoor dry bulb temperature
such cases, the capacity of thecondenser is (use values in Table 10-6A. Round off
directly proportional to the temperature to next highest multiple of 5)
difference between the dry bulb temperature of
the entering air and the condensing Example 14-8. From Table R-13, select
temperature. This temperature differential is an air-cooled condenser for a compressor
having a capacity of 75,000 Btu/hr if the
often referred to as the "tempera ture split" in design evaporating and condensing
order to distinguish it from the mean effective temperatures arc 20° F and 110° F,
temperature differential.• respectively, and the outdoor design dry bulb
Table R-13 is a typical manufacturer's for the region is 90° F.
rating table for air-cooled condensers. The Solution. From Table
basic ratings given in Table R-I 3A arc based R-13B, the correction
on 90° F fac- tor for 20° F suction
tem
ambient air temperature, 120° F condensing perature = 0.95
temperature, and 40° F evaporating tempera From Table R-12C,
ture. For other design conditions multiply the the correction factor for
basic rating from Table R-13A by the con- densing
temperature of 110° F
correction factors for variation in evaporating and entering air = 0.665
temperatures (Table R-13B) and for variation temperature of 90° F
in entering air and condensing temperatures Required capacity of 75,000
(Table R-13C). condenser at basic rating =.,.....,,..,,.........,..,c,c
0.95 X 0.665
• The temperature split is always proportional conditions = 118,700 Btu/hr
to the METD.
CONDENSERS ANO COOLING TOWERS 2S3
From Table R-13A, select condenser Model
#BDlOOO which has a capacity of 120,000 shown that, in general, a water flow rate of
Btu/hr at the basic rating conditions. between 2.5 and 3 gal per minute per ton
usually provides the most economical balance
Experience has shown that as a general rule between compressor horsepower and pump
selecting an air-cooled condenser on the basis horsepower. In some instances, the water
of a condensing temperature of 110° F will supply for a waste-water system is taken from
result in the most economical condenser size. a well or from some nearby body of water,
Hence, the actual size of the condenser such as a river, lake, pond, etc., in which case
selected will depend upon the outdoor design both the cost of the water and the pumping
dry bulb temperature for the region in horsepower must be considered in
question. The higher the dry bulb determining the optimum water
temperature, the larger the condenser required. flow rate.
For example, for a con densing temperature of To a large extent, the quantity of water cir
110° F, if the dry bulb temperature is 85° F, culated through the condenser determines the
the condenser can be selected for a 25° F design of the water circuit in the condenser.
temperature split, whereas if the dry bulb Since heat transfer is a function of time, it
temperature is 90° F, the con denser must be follows that where low water quantities
selected for a 20° F temperature split, which necessi tate a high temperature rise in the
will require a larger size. condenser, the water must remain in contact
14-9. Water-Cooled Condenser Systems. with the con densing refrigerant for a longer
Systems employing water-cooled condensers period than when the water flow rate is high
can be divided into two general categories: (I) and the tem perature rise required is smaller.
waste-water systems and (2) recirculated Hence, where the water flow rate is low, the
water systems. In waste-water systems the number of water circuits through the
water supply for the condenser is usually condenser are few and the circuits are long so
taken from the city main and wasted to the that the water will remain in the condenser for
sewer after passing through the condenser enough time to permit the required amount of
(Fig. 14-7). In recirculated water systems the heat to be absorbed. On the other hand, when
water leaving the condenser is piped to a water the flow rate is high and the temperature rise
cooling tower where its temperature is low, more circuits are used and the circuits are
reduced to the entering temperature, after shorter in order to reduce the pressure drop to
which the water is recircu lated through the a minimum. This is illu strated in Figs. 14-9a
condenser (Fig. 14-8). and 14-9b. In Fig. 14-9a, the two water circuits
Naturally, where the condenser water is through the condenser are connected in series
wasted to the sewer, the availability and cost for a low flow rate and a high temperature rise.
of the water are important factors in The water enters through opening A and
determining the quantity of water circulated leaves through opening C. Opening B is
per unit of con denser load. As a general rule, capped. In Fig. 14-9b, the two water circuits
an economical balance between water and are connected in parallel for a high flow rate
power costs pre scribes a water flow rate of and a low temperature rise. The water enters
approximately 1.5 gal per minute per ton of through opening B and leaves through
capacity. openings A and C.
The high cost of water, along with limited In designing the condenser water circuit
sewer facilities and recurring water shortages particular attention must be given to the water
in many regions, bas tended to limit waste-
water systems to very small sizes. Too, many Waterreaulatingn
cities have placed severe restrictions on waste- warm water out ,-+
water systems, particularly where the water to sewer
-
supply is taken from the city main and wasted Cold water in
to the sewer. from city ll1lin
When the condenser water is recirculated
the power required to circulate the water Liquid to control
through the water system must be taken into
account in determining the water flow rate. Fl1. 14-7. Waste water system.
Experience has
CONDENSERS AND COOLING TOWERS 25S
Cooling
"Bleed
tower
off" line
"Make-up"
water
"By
L C_on_d_e_ns_e_r....J--='-
liquid out tilo---"""'pass"
Pump
Condensed
refrigerant out
scale factor of 0.0005 should always be used. chassis-mounted air-cooled condensers during
Under no circumstances should a condenser periods of peak loading. Since the water valve
be selected on the basis of clean tubes. can be adjusted to open and allow water to
However, when the condensing temperature is flow through the condenser only when the
low (leaving water temperature less than 100° con densing pressure rises to some
F) and the condenser tubes are to be cleaned predetermined level, the amount of water used
frequently, the fouling factor from Table 14-1 is relatively small in comparison to the
may be reduced to the next lowest value. The savings in power afforded by the increased
use of scale factors will be illustrated later in compressor effi ciency.
the chapter. The shell-and-coil condenser is made up of
1-4-11. Water-Cooled Condensers. Water one or more bare-tube or finned-tube coils
cooled condensers are of three basic types: enclosed in a welded steel shell (Fig. 14-9).
(1) double-tube, (2) shell-and-coil, and (3) The condensing water circulates through the
shell and-tube. coils while the refrigerant is contained in the
As its name implies, the double-tube con shell surrounding the coils. Hot refrigerant
denser consists of two tubes so arranged that vapor enters at the top of the shell and
one is inside of the other (Fig. 14-10). Water condenses as it comes in contact with the
is piped through the inner tube while the water coils. The con densed liquid drains off
refrig erant flows in the opposite direction in the coils into the bottom of the shell, which
the space between the inner and outer tubes. often serves also as _the receiver tank. Care
With should be taken not to
CON DENSE:RS AND COOLING TOWE 257
R.5
Fl1r- 1<4-11, Double-pipe a)l:ldensers with mechanlally cleanable t1.1bci. (CootttS)' Hatuead and MttcheU.)
o n::harge the system with refrigerant since from one end to the olher before leaving the
an exCC:Ssive aocumulation of liquid in the condcnr..er. The number of passes may he all
con. denser will k:nd to cover too much of the: few as two or- as many a, twenty.
con• deru;ing i;urfa{;e. and cause an increa:ie in For any given totaJ riumber of tubes., the
lhe discharge temperature and pressure. number of tu'boe:J per pass varie<i inversely
Most shell-and-wil. condenstn1 s:re equ,ipped with lM number of passes. For example.
with a split water circuit. The two parts of assuming that a condenser has a total of forty
the circuit are connected in series for waste- tubes, jf lherti are two passes, the nwnbi!:r of
water sy tcm:s (Fig. 14-9b) and in parallel for tub:s per pa js twenty. whereas if there are
rcc:ircu
four '
]ati ng systems (Fig. l4-9a). As a general lhe number of Lubes per pass fa ten.
rule, me11.:.and-coil condensers arc used ooly It fa important to notice that for the same
for small installation:s; up to approximatt:ly 10 ton total number of tubes and the samt:; water
capacity, quantity. the velocity of the water and the
SheH-and--t:oi1 condensers are cleaned by pressure drop through thecondenser wiU be four
cir cufotir1g an approved chcmkaJ through times as great for a four.pass condenser u for
the water coil . a two-pass condenser. Because of the high r
TI1c sbeU-and.tubc condenser consists. of a \'clo city the transfer coefficient will be higher
cy1indrical stct:l she:H in which 11. numbec or far lhe
straight tubes are arranged in parallet and held four-pass condenser and n smaller CQndens.ing
in place at lhe ends by ube sheel.3. Construc surface will be required for a gt,..en heat transfer
tion is almost identical ta that of the flooded capacity. However, 011 the other hand,
type shell-and-tube liquid chiller, The con· because of the Jiigh pressure drop, the p=r
denslng water is circulated through the tubes, required to circulate the water- will be greater.
which may be ehher steel or copper, bare or Hence. for a wa!lti:-water system, the four pasi.
elltended surface. The rerrigerant is contained condenser fa probably the best selection,
in the steeJ hell between. ll1c tube sheets. Water whereas for a reel rcula ling sys[.Cm, lhe two-
circulates in lh..: ilr1Ilular spaces hi:\ween the pass condenser .is probably lhe beuer of the
tube sheets and lhe md-platcs, the end-plates two.•
being baffled to act as manifolds to guide the Sfu::U.and-tube condensers an: avaifable io
wa Ltt now lhrough lhe tubes. The arrangemcnl of capacities ranging from 2 tons up to severa1
the cnd-plale baffiing determines the number
• This example i intended only lo illusttiu.e
of passes the water makes through the Ute: priqclple:s of design and sboL1ld not be
condenser cons.trued to mean that rour•p;i.ss condensc111 a!(!
undesirable for rcufating sysreru.
CON DENSE:RS AND COOLING TOWE 257
R.5
R11, 14-ll. Typical dm,1hle-pip1!! c.afld 11 r r11lg ndot15. MTramoone ront'lgt.1!'11,tlo11-. (b} Helix: conf1gura
tlon. (Courtesy Edwanh En n l!,dn:i:; Corpor;a.t[oP.)
-
Fl1. 14-14. Small Induced
draft-cooling tower. ==-=-:--- == ->"<:a-:;.;:.,,.-=3 Air out
---------- Decking $' _
Air in
: :: .-. = -- = ;;>,". = 20:
= = f == ==
-water outi--- -- -Ba-s-in------------------i
CONDENSERS AND COOLING TOWERS 262
Air out
\tttttttt!(1 Spray
SSS%%SSSS<,ss<-,ss<H,SSSSSSSSSSSSS%SSSSSS eliminators
Water in
Water
out
Btu/min/ton. Nominal tower ratings are based Example 14-14. It is desired to cool 90 gpm
on a 3 mi per hour wind velocity, and 80° F from 96° F to 86° F when the design wet bulb is
design wet bulb temperature, and a water flow 78° F. Select the proper tower from Table
rate over the tower of 4 gpm per ton. Tower R-16.
performance at conditions other than those
listed in the table can be determined by using
Solution
the rating correction chart that accompanies the Tower range = 96 - 86 = 10°
table. Tower approach = 86 - 78 = 8°
To select the proper tower from the rating
table, the following data must be known: From rating correc-
tion chart, range-ap
I. Desired tower capacity in tons (compressor proach factor = I.I
capacity) From wet bulb cor
2. Design wet bulb temperature rection chart, wet bulb
factor = 1.04
3. Desired leaving water temperature (con
denser entering water temperature or tower
Nominal gpm = 90 x 1.1 x 1.04
approach)
= 103 gpm
From Table R-16, for 103 gpm nominal,
or select tower, Model #SA-68.
I. Desired flow rate over the tower (gpm)
2. Design wet bulb temperature Example 14-15. It is required to cool water
3. Desired entering and leaving water tem for 30 tons at 5 gpm/ton to a 5° F approach of
peratures (tower cooling range and tower an 80° F wet bulb. Select the proper tower from
approach) Table R-16.
Example 14-13. From Table R-16, select a
cooling tower to meet the following conditions: Solution
I. Required tower capacity = 20 tons Total gpm required
2. Design wet bulb for 30 tons at 5 gpm/
temperature = 78° F ton = 30 X 5 = 150 gpm
3. Desired leaving water From rating cor
temperature = 86° F tion chart, rating cor
rection factor for 5
Solution. From Table R-16, select tower, gpm/ton and 5° ap
Model #CSA-66, which has a capacity of 20.7 proach = 1.15
tons at the desired conditions when the flow
rate over the tower is 3 gpm per ton. Hence, for From wet bulb
20-tons capacity, a total of 60 gpm (20 x 3) correction chart, wet
must be circulated over the tower. As shown in bulb correction factor = 1.0
the table, the entering water temperature will be Nominal gpm = 150 X 1.15 X 1.0
approximately 96° F. = 172.6gpm
CONDENSERS AND COOLING TOWERS 263
Fl1. I•U 6. Schematlc di,gram or enpc,ntlvi:- n manufacturer and depends to a large extent on
den i-. the llm.ount of air and water circulated.
Generally. the capacity of the evaporative
condenser increases as the quantity or air cir
l◄-18, Evaporative Cond nsen. An evapo· cuhHcd thrnugh the condenser i.ncR:ases. As a
rative coodenser is esscnlill.lily a watet constr practical matter. the maximum quantity of air
vation device and is, in effect, a condenser and
a cooling tower combined into a .singie unit, A
diagram of a typical evaporntive condenser i.s
shown in Fig. l 4-16.
As pnwiously stated, both air and water are
emplo)·ed in the. evaporative condenser. The
waler, pumped from the st1mp up to the spray
header, sprajiS down over the refrigetant coils
and returns. to the sump. The air is dr.twn in
rrom the outside at the bottom of lhe condcm.cr
by action of the blower and fa dlschargcd back
to t.he outside at the top of the condenser. In
some cases. both pump and btower are, driven
by the same motor. In others, s.eparatc motors
nre u$ed. The eliminators installed irt the air
stream above the spray header arc to prevent
entrained water rrom being carried over intQ
tbe blower. An alternate arran ment, with the
blower located on the entering air side of the
condenser, j5 shown in Fig. 14--17.
Although the actual Ut<.rmody.namlc proT
cesses taking place in lhc evaporative con-
denser 11re somewhat complex., the fundalll.Cntal Fig. 14-17. Cuu.wa:, vlew or "l>rl-hn'' ewa rad
process is that or evaporative cooling. Wat« is conderinr. Fun.nel-thaped o"' rflow dr'1In providM
1-u(t:1niatlt blel!d--ofl'. tCo rte,i;y Ref •,i= •tlon. En.gl
evapo ratedfron1 thespmy and from the wetted
l'l t1edng, Inc·. A proprlt1tary dt1sT&ri of Rt1frilll!
surface
ratfo11 Engln.eerl ng, Inc.)
CONDENSERS AND COOLING TOWERS 16S
which can be circulated through the condenser
is limited by the horsepower requirements of 6-ton evaporator load (Refrigerant-12)
the fan and by the maximum air velocity that 20° evaporator temperature
can be permitted through the eliminators 78° entering wet bulb temperature
without the carry over of water particles. I05° F condensing temperature
The quantity of water circulated over the Solution. Since the rating table is in terms of
condenser should be sufficient to keep the evaporator load at 40° F, it is necessary to
tube surface thoroughly wetted in order to correct for other evaporator temperatures by
using a correction factor from R-l7B as
obtain follows: Tons x evaporator correction factor
maximum efficiency from the tube surface and
to
minimize the rate of scale formation. However, -= Rating table tons
a water flow rate in excess of the amount Therefore, 6 x 1.05 6.3 tons.
=
required for adequate wetting of the tubes will • McQuay Products.
only increase the power requirements of the
pump without materially increasing the con
denser capacity.
Assuming a condenser load of lS,000 Btu
per hour per ton, the water lost by evaporation
is approximately I5 lb (2 gal) per hour per ton
(15,000/1000). In addition to the water lost by
evaporation, a certain amount of water is lost
by drift and by bleed-off. The amount of
water lost by drift and by bleed-off is
approximately
1.5 to 2.5 gal per hour per ton, depending
upon the design of the condenser and the
quality of water used. Hence, total water
consumption for an evaporative condenser is
between 3 and 4 gal per hour per ton.
Some evaporative condensers are available
equipped with desuperheating coils, which are
usually installed in the leaving air stream. The
hot gas leaving the compressor passes first
through the desuperheating coils where its
tem perature is reduced before it enters the
con densing coils. The desuperheating coils
tend to increase the over-all capacity of the
condenser and reduce the scaling rate by
lowering the temperature of the wetted tubes.
Too, often the receiver tank is located in the
sump of the evaporative condenser in order to
iricrcase the amount of liquid subcooling.
14-19. Rating and Selection of Evaporative
Condensers. Table .R-17 is a typical evapo
rative condenser rating table. Notice that the
ratings are based on the temperature
difference between the condensing
temperature and the design wet bulb
temperature. The following sample selection
is reprinted directly from the manufacturer's
catalog data:•
Example 14-17. Select an evaporative con
denser for the following conditions:
Referring to Table R-l7A, the E-135F has a
capacity of only 5.6 tons at 78° F entering
wet bulb and 105° F condensing temperature.
It does, however, have the required capacity of
6.3 tons at between 105° F and 110° F
condensing temperature.
The compressor ratings should then be
checked to see if the compressor originally
selected has the required capacity at between
105° F and 110° F condensing temperature.
If not, it will be necessary to select the next
larger size evaporative condenser or
compressor to do the job.
The next larger size evaporative condenser,
the E-270F, has a capacity of I1.2 tons at the
given conditions; however, the required
capa city of 6.3 tons will be obtained at a
condensing temperature between 90 and 95°
F. The com pressor selection should then be
made for these conditions.
14-20. Water Regulating Valves. The water
flow rate through a water-cooled condenser on
a waste water system is automatically
controlled by a water regulating valve (Fig.
14-18). The valve is installed on the water
line at the inlet of the condenser and is
actuated by the compressor discharge (Fig.
I4-7). When the compressor is in operation,
the valve acts to modulate the flow of water
through the condenser in response to changes
in the condensing pressure. An increase in
the condensing pressure tends to collapse the
bellows further and open the valve wider
against the tension of the range spring,
thereby increasing the water flow rate
through the condenser. Likewise, as the
condensing pressure decreases, the valve
moves toward the closed position so that the
flow rate through the condenser is reduced
accordingly. Although the regulating valve
tends to maintain the con densing pressure
constant within reasonable limits, the
condensing pressure will usually be
considerably higher during periods of peak
loading than during those of light loading.
2" PRlNCIPLES OF IU;fRIGERATION
.fl1, 14-IA. Typlt;il thre:ii.i:l.i:.:1- yp,e w1tet t g1.r!atin,11 ,,,.,J,,.e, bqjl!f sh.es 11.re 11:ll le wlth fbflge co11nectl0ns.
(a) CrosM ctianal vrew howlng· prh,clp .1 parts. { ) E:xtctltir vi(!_w, (Courtesy Pen.n Contrab, Tnt.}
in some cases, overloading of the compressor capacity of the condenser during periods when
driver and/or serious damage to the the ambient temperature is low and/or the
compressor itself. refrig erating load is light. Although the
An abnormally low condensing methods employed to control the capacity of
temperature, on the other hand, will cause an the con denser vary somewhat with the type of
insufficient pressure differential across the con denser used, all involve reducing either
refrigerant con trol (condensing pressure to the quantity of condensing medium circulated
vaporizing pres sure), which reduces the or the amount of effective condensing surface.
capacity of the control and results in starving Condenser capacity control devices are
of the evaporator and general unbalancing of usually actuated by pressure or temperature
the system. controls which respond to condensing
As a general rule, low condensing tempera pressure or temperature.
tures result from either one or both of two With regard to air-cooled condensers, the
principal causes: (I) low ambient temperatures condensing temperature is maintained within
and (2) light refrigerating loads. Naturally, the the desired limits by varying the air quantity
problem of low condensing temperatures is through the condenser or by causing a portion
more acute in the wintertime when the of the condenser to become filled with liquid
ambient temperature and the refrigerating load so as to reduce the amount of effective
are both apt to be low. condensing surface.
To maintain the condensing temperature at The air quantity through the condenser is
a sufficiently high level, it is necessary to varied by cycling the fan or blower or by the
make some provision for reducing or use
controlling the
r
compound, many of which are available in
either liquid or powder form. After the tower
Tower or condenser sump has been drained, deaned,
static and filled with fresh water, the cJeaning com
head pound can be added directly to the sump
water. The pump is then started and the
cleaner is circulated through the system until
the system is clean, at which time the sump is
again drained, flushed, and filled with cJean
Additio
static head.._
nal
water before the system is placed in normal
L . , tank
Indo
or
operation.
It should be pointed out that dcsca1ing com
pounds have an acid base and should not be
allowed to contact grass, shrubs, or painted
surfaces. Therefore, it is usually advisable to
remove the cooling tower spray nozzles, if
any, in order to minimize the danger of
damaging shrubs or painted surfaces with drift
from the tower.
Conden When rapid descaJing of the condenser tubes
ser is required, an inhibited solution {18%) of
muriatic acid may be used. However, muriatic
acid should be used only on the condenser
Fl1. 14-24. Protected Indoor tank. tubes. The system pump should not be used to
circu late the acid. A small pump having an
acid resistant impeller (brass or nylon) may be
fan blades and condensing surface should be used for this purpose (see Fig. 14-25). After
inspected occasionally for the accumulation of the condenser is clean, it should be flushed
dust and other foreign materials. These parts with clean water or with an acid neutrali7.er as
should be kept clean in order to obtain high recommended by the manufacturer.
efficiency from the condenser. Corrosion is usually greatest in areas near
Any type of condenser employing water is salt water or in industrial areas where relative
subject to scaling of the condenser tubes,
corro sion, and the growth of algae and
bacterial slime on all wetted surfaces. The
latter is con trolled by frequent cleaning of the
infected parts and by the use of various
algaccides which arc available commercially.
As previously stated, the scaling rate
depends primarily upon the condensing
temperature and the quality of water used.
The scaling rate will be relatively low where
the condenser leaving water temperature is
below 100° F. Too, the importance of
providing for the recommended amount of
.bleed-off'cannot be ovcremphasiud with
regard to keeping the scaling rate at a
minimum. In addition, a number of chemical
companies have products which when added
to the sump water considerably reduce the
scaling rate.
Scale can be removed from the condenser Fl1. 14-25. Apparatus for descalin1 condenser.
large concentrations of sulfur and other indus trial fumes are found in the atmosphere. Corro sion damage is
minimi7.Cd by regular cleaning and painting of the affected parts and by application of protective coatings of
various types.
PROBLEMS
1. An R-12 system is operating at an evaporator temperature of 0° F and a condensing tempera ture of 100° F.
From Chart 14-1, determine the heat load on the condenser in Btu per minute per ton of refrigeration. Ans. 251
Btu/min/ton
2. An R-22 system operating with a 40° F evaporator and a I l0° F condenser has an evaporator load of IO tons.
Determine the heat load on the condenser in Btu/hr.
Ans. 141,000Btu/hr
3. The heat rejected to a water-cooled con denser is 120,000 Btu/hr. How many square feet of effective tube
surface must this condenser have if the U factor of the condenser is I 00 Btu/hr/sq ft/° F and the METD is 5° F at
the desired gpm? Ans. 240 sq ft
4. The heat load on the evaporator of an air conditioning system is 60,000 Btu/hr. If the coefficient of
performance of the system is 4 : 1, what is the heat load on the condenser in Btu/hr?
Ans. 75,000 Btu/hr
5. An R-12 waste water system operating at a 40° F suction temperature and a 105° F con densing temperature
has an evaporator load of 5 tons. If the condenser is selected for a 12° F water temperature rise, how many gpm
must be circulated through the condenser?
Ans. 11.5 gpm
6. Seventy-two gallons of water per minute are circulated through a water-cooled condenser. If the temperature
rise of the water in the con denser is 14° F, what is the heat load on the condenser? Ans. 504,000 Btu/hr
7. An R-12 air conditioning system operating with an evaporator temperature of 40° F and a condensing
temperature of 120° F has an evaporator load of 60,000 Btu/hr. 4500 cfm of air arc circulated over the
condenser. If the temperature of the air entering the condenser is 90° F, compute: (a) the leaving air temperature
and (b) the METD.
Ans. (a) 104.6° F (b) 21.89° F
8. If the air-cooled condenser in Problem 7 has a free face area of 5.5 sq ft, what is the velocity of the air through
the condenser?
Ans. 818 fpm
9. From Table R-12, select an air-cooled con denser for a compressor having a capacity of 42,000 Btu/hr if the
design suction and discharge temperatures are 40° F and 130° F, respectively, and the outdoor design dry bulb
temperature for the region is 95° F.
10. Select a shell-and-tube water-cooled con denser for an R-12 system to meet the following conditions:
Refrigeration load and eva-
porator 60 tons
Evaporator temperature 40° F
Condensing temperature 110° F
Water quantity 2.5 gpm/ton Untreated cooling tower water enters con-
denser at 85° F.
11. Rework Problem 10 using a condensing temperature of 120° F.
12. A cooling tower and a water-cooled con denser (with by-pass) are operating with a condenser load of
240,000 Btu/hr. Forty-eight gpm are circulated through the condenser and 32 gpm are by-passed. The ambient
wet bulb temperature is 78° F and the tower approach is 7° F. Determine:
(a) The temperature of the water entering the condenser. Ans. 85° F
(b) The temperature of the water leaving the condenser. Ans. 95° F
(c) The temperature of the water entering the cooling tower. Ans. 91° F
(d) The tower range. Ans. 6° F
13. A compressor on a Refrigerant-12 system has a capacity of 50 tons. The design wet bulb temperature is 78°
F. The desired condenser water entering temperature is 85° F and the desired temperature rise through the
condenser is 12° F. Select a cooling tower from Table R-15 and determine:
(a) The total gpm circulated over the tower
(b) The temperature of the water entering the tower
(c) The temperature of the water leaving the
condenser
(d) The tower range
(e) The gpm circulated through the condenser (/) The gpm by-passed
14. Select an evaporative condenser for the following conditions:
Refrigcrant-12 system
Evaporator load-10 tons Evaporator temperature-40° F
Wet bulb temperature of entering air-78° F Condensing temperature-105° F