You are on page 1of 1

Valve Regulated Lead Acid Battery (AGM)

HIGH RATE SERIES


CCB 12HD-270 (12V270Watts/Cell@15Min Rate)

FEATURES
*Absorbent Glass Mat (AGM) technology for efficient
gas recombination of up to 99% and freedom from
electrolyte maintenance.
*Computer-generated grid design optimized for high
power density.
*Float/ Cycle Use
*Low Self Discharge Rate
*Safety Valve
*Lead Calcium Alloy
*Useable In Any Position
*UL-recognized component
*Available Flame Retardant Material(Optional)

VRLA 12HD-270 Specifications


Nominal Voltage Rated Capacity (20hr rate) @77 F(25 C) Max. Discharge-5sec. Internal Resistance Terminal

12V 75Ah 700Amps 5.6milliohms St7/St6

Dimensions & Weight


Length Width Height Total Height Weight

260mm(10.24inches) 169mm(6.65inches) 208mm(8.19inches) 213mm(8.38inches) 25.0Kg(55.1Ibs)

Discharging
Discharge Temp. Range Cap.@104 F (40 C) Cap.@32 F (0 C) Cap.58 F ( -15 C) Self-Discharge@77 F (25 C)

-4 F (-20 C) to + 140 F (60 C) 102% 85% 65% -3% of capacity per month

Charging
Charge Temp. Range Max. Charge Current Constant Volt. (Cycle use) Constant Volt. (Trickle use)

14 F (-10 C) to + 122 F (50 C) 22.5Amps 14.4-14.7V @77 F (25 C) -30mV/ C 13.6-13.8V @77 F (25 C) -20mV/ C

Battery Charging Characteristics Battery Life Characteristics of Cyclic Use


140 0.21 15.0

120 0.18 14.0 Charge voltage 120


Charge current(CA)

Retention Capacity(%)
Charge volume(%)

Charge voltage(V)

100 0.15 13.0 vo lu m e 100


C ha rg e

80 0.12 12.0 80

1 Discharge
60 100%(0.1CAx10h)
0.09 11.0 60
---50%(0.1CA x5h) 100% 50% 30%
2 Constant voltage charging
Charge voltage:2.275V/cell
(Depth of discharge) (D.O.D.) (D.O.D.)
40 0.06 10.0 40
Charge current:0.1CA
3 Temperature 20 C(68 F)
~
~
20 0.03 20

Charge current ~
~
0 0 0 0
0 5 10 15 20 25 0 300 600 900 1200 1500
Charge Time (hr) Number of cycles

Constant current discharge characteristics at 25 C/77 F Constant power discharge characteristics at 25 C/77 F

Discharge time(Hr) 31.4 Discharge time(Min)


End Voltage
0.5 1 2 3 5 8 10 20 5 10 15 30 45 60 120 180
VPC Per Bat.
Battery output current(Amp) Battery output power(W)

1.85V 78.8 43.8 25.9 18.3 12.0 8.02 6.63 3.70 1.75V 379 304 256 157 114 89.0 50.9 36.4

1.80V 81.5 45.7 26.5 19.0 12.5 8.35 6.85 3.75 1.70V 404 316 263 160 117 91.8 51.4 36.6

1.75V 83.7 46.9 26.8 19.2 12.6 8.43 6.91 3.79 1.65V 422 322 270 162 118 93.1 51.7 36.6