Professional Documents
Culture Documents
L2 L2
L3 L3
2F5-MDP2-MCC3
QM
KM1 KM2
FR1 FR2
QM0
KM3 KM4
XT1-12 XT1-13 XT1-14 XT1-15 XT1-12 XT1-13 XT1-14 XT1-15
U V W PE U V W PE U1 V1 W1 PE U1 V1 W1 PE
M1 M1a M7 M8
R S T PE 3Ø 3Ø 3Ø 3Ø
Unilever RFM
Ice Cream Inc.
L1 L1
L2 L2
L3 L3
L1 L2 L3
QM11 QM12
KM7 KM8 FR3
XT1-1 XT1-2 XT1-3 XT1-4 XT1-5 XT1-6 XT1-7 XT1-4 XT1-5 XT1-6 XT1-7 XT1-4 XT1-5 XT1-6 XT1-7 XT1-4 XT1-5 XT1-6 XT1-7
U1 V1 W1 U2 V2 W2
M2
3Ø
01 02 03 04
Booster Pump 2 Outgoing Supply Outgoing Supply Outgoing Supply Hard Water Station Soft Water-Booster Pump 2
going to 2F5-MDP2-MCC1 going to 2F5-MDP2-MCC5 going to 2F5-MDP2-MCC6
18.5kW / 32.5A 3Ø,440VAC, 60Hz 3Ø,440VAC, 60Hz 1Ø,220VAC, 60Hz 1Ø,220VAC, 60Hz
3Ø,440VAC, 60Hz
SOFT WATER STATION BOOSTER PUMPS Rain Water Recovery Pump Sump Pit Pump Control Circuit Supply
Unilever RFM
Ice Cream Inc.
01 101 101
STOP M1 / 1a
SB1
SB0 VFD1 SS1
VSD1 SS1
KM1 KM2
ACKNOWLEDGE
OFF
MOTOR
1A
STARTER KM1 SB4
1
SA2
VSD
OFF
SS
SA1
KM2
02 02
idle
E-Stop VSD1 ready SS1 ready M1 run M1a run M1 fault M1a fault
M1 & M1a
Hard Water Pump Station : Booster Pump M1 and M1a
Unilever RFM
Ice Cream Inc.
101 L1
START M7 START M8
SB6 KM5 SB8 KM6
02 L3
Unilever RFM
Ice Cream Inc.
03 103 103
STARTER
VSD
SB00
OFF
KA5
Y-Δ
SA3 FR3 VSD2
KA3 KA4
KM7
VSD2 FR3
STOP M2
SB9
KA3 KA4
START M2
SB10 KA5
KM9
KA4 KA3
KT1 KT1
KM11 KM10
SB9
KA3 KA4 KA5 KM7 KM8 HL5 KM9 HL6 KT1 KM10 KM11 -HL HL7
GN GN RD YL
04 04
VSD2 run main run timer: 3sec delta wye idle fault
E-Stop VSD ready Y-Δ ready M2 start / stop signal
Booster Pump M2 : VSD Booster Pump M2 : Y-Δ M2
Soft Water Pump Station
Unilever RFM
Ice Cream Inc.
WIRE DUCT 75X100mm
E-STOP E-STOP
SS1 VFD2
TERMINAL BLOCKS
Unilever RFM
Ice Cream Inc.
2F5-MDP2-MCC1
(SOFT WATER MCC)
2F5-MDP2-MCC3
(BOOSTER PUMP 1
VFD1 MCC)
NEW
2F5-MDP2
BOOSTER PUMP MCC
(WATER GEN. MDP)
2F5-MDP2-MCC5
(RAIN WATER REC. MCC)
2F5-MDP2-MCC6
(SUMP PIT PUMP MCC)
Unilever RFM
Ice Cream Inc.
Designation: NEW WATER GENERATION CONTROL PANEL Mounting: Floor Standing
System: 3Ø, 440V, 60Hz, 3 Wire (Line) + 1 Wire (G) Enclosure: NEMA 3, STAINLESS
Minimum I.C.: Feed From: 2F5-MDP2
Location: New Boiler Control Room
Name Plate Rating Computed Ratings Circuit Breaker / OCP Overload Conductors
No. Load Desription FLA/VFD Starter Controller Setting
kW HP Voltage 3Ø Current CB(AT) OL(A) Type Poles AT AF (A) x3 (L) +1 (G)
(kW)
1 VFD 162.5 55 n/a MCCB 3 175 250 n/a 80 8.0
Booster Pump Motor 1 or 1a 55 75 440 89 130 Soft
2 162.5 55 n/a MCCB 3 175 250.0 n/a 80 8.0
Starter
3 Booster Pump Motor 7 15 20 440 24.9 27 DOL 67.5 15 29 MCCB 3 70 100 29 5.5 5.5
4 Booster Pump Motor 8 15 20 440 24.9 27 DOL 67.5 15 29 MCCB 3 70 100 29 5.5 5.5
VFD 46.9 18.5 n/a MCCB 3 75 100 n/a 14 5.5
5 Booster Pump Motor 2 18.5 25 440 32.5 49.6
Y-Δ 70.7 18.5 22 MCCB 3 75 100 22 14 5.5
6 2F5-MDP2-MCC1 (SOFT WATER) 41 57 440 71 80 n/a n/a n/a n/a MCCB 3 200 250 0 80 8
2F5-MDP2-MCC5 (Rain Water
7 n/a n/a n/a n/a MCCB 3 50 100 n/a 8 5.5
Recovery Pump) 10 440 18 18
2F5-MDP2-MCC6 (Sump Pit
8 3.0 440 6 6 n/a n/a n/a n/a MCCB 3 40 100 n/a 3.5 3.5
Pump)
Total 158 197 440 266 338