Safety Cautions

Read the entire “Instruction Manual” carefully for important information about safety, handling,
installation, operation, maintenance, and parts replacements.
This equipment is designed and built in accordance with applicable safety standard in effect on
the date of manufacture. Unauthorized modifications will void warranty and can result in severe
injury, death and property damage. Do not make any modifications to the equipment.
Only qualified persons are to install, operate or service this equipment according to all applicable
codes and established safety practices.
Use only genuine Toshiba replacement parts and accessories. Improper components could cause
the equipment malfunction.
Do not install this equipment in areas where unusual service conditions exist. Using this
equipment in other than usual service conditions can result in equipment failure.
Do not exceed the ratings specified on the equipment nameplate or system accessories.
Underrated equipment can fail during operation causing fire, explosion, severe injury, death, and
property damage.

CV-6GAL/6HAL
7.2kV-200/400A-6.3kA

TRANSMISSION DISTRIBUTION & INDUSTRIAL SERVICES COMPANY


1-1, SHIBAURA 1-CHOME, MINATO-KU, TOKYO 105-8001, JAPAN
PHONE +81-3-3457-4898 FAX +81-3-5444-9169

http://www3.toshiba.co.jp/sic/english/swgr/products.htm

The data given in this catalog are subject to change without notice.

KSP-E2412 AD 4 Printed in Japan


2008-12 (1.5)
Excellent Breaking Performance
Since the higher interrupting capacity and short-time
withstand capability, Toshiba Vacuum Contactors are
appropriate to fuse combination for large capacity load,
and to high-speed breaking.

Since the introduction of the first Vacuum Interrupter in 1962,


Toshiba has been continuously improving and developing Vacuum Compact and Lightweight
Compact and slim design contactors can be applied to
Technology. either two-tier motor starters or slim starters per IEC
Over 3 millions Vacuum interrupters have been produced for various 60470 (2000).
The Contactors CV-6GA(L) and CV-6HA(L) have the same
types of vacuum apparatus such as contactors, circuit breakers and outline and mounting dimensions, as well as dual voltage No Surge Protection Required
ratings (3.6/7.2kV). Special main contact materials minimize chopping current.
switches which are now widely used as result of their outstanding No surge suppressor/arrester is required except for special
applications.
performance.
Toshiba has become a leading Japanese manufacturer that has
attained a record exceeding 230 thousands Low and High voltage
Low Power Consumption
Vacuum Contactors produced. The control device adopts an electronic circuit, the control
voltage either AC or DC can be easily changed by
Consistent with its dedication to the most advanced vacuum switches in the circuit board without changing the coil
technology, Toshiba offers new series of High-voltage vacuum and/or other parts. Since the economizing resistors are Conformity to Industrial Standard
eliminated, the power consumption in holding condition Conforming to latest international standards such as IEC,
contactors. has been reduced. BS, AS and JEM, being certified by class NK and TUV,
Toshiba Vacuum Contactors can be used widely all over
By adopting an electronics controlled circuit and being designed the world.
compactly to ensure reliability, handling ease and safety, the new
series of High-voltage Vacuum Contactors are suitable for Motor
starters, Transformer feeders and Capacitor switching applications.
3
Class NK certificate (Marine application)
4
1 TIMER
5
2 52
CC
OSCILLATION POWER
6
SWITCHING

Fig. 1 Configuration of drive-unit


TUV certificate

Ratings Type Operating mechanism Application Standard


Standard 7.2/3.6kV 200A 6.3kA CV-6GA Non-Latched Type General IEC, JEM, Class NK
CV-6GAL Latched Type General
400A 6.3kA CV-6HA Non-Latched Type General
CV-10HA(L) CV-6HAL Latched Type General
15/12kV-400A-4/5kA 720A 8.0kA CV-6KA1 Non-Latched Type General
CV-10HB(L) CV-6KAL1 Latched Type General
12kV-400A-5kA 12kV 400A 5.0kA CV-10HB Non-Latched Type Capacitor IEC
CV-6KA1 CV-10HBL Latched Type Capacitor
7.2kV-720A-8kA 15/12kV 400A 4.0/5.0kA CV-10HA Non-Latched Type Motor/Transformer IEC, NEMA
CV-10HAL Latched Type Motor/Transformer

Ratings Type Operating mechanism Application Standard


Special 7.2/3.6kV 400A 6.3kA CV-6HA-2 Non-Latched Type General IEC, JEM
Main CV-6HAL-2 Latched Type General
Terminals 12kV 400A 5.0kA CV-10HB-1 Non-Latched Type Capacitor IEC
(Rear side of CV-10HA) CV-10HBL-1 Latched Type Capacitor
15/12kV 400A 4.0/5.0kA CV-10HA-1 Non-Latched Type Motor/Transformer IEC, NEMA
CV-10HAL-1 Latched Type Motor/Transformer

1 2
Excellent Breaking Performance
Since the higher interrupting capacity and short-time
withstand capability, Toshiba Vacuum Contactors are
appropriate to fuse combination for large capacity load,
and to high-speed breaking.

Since the introduction of the first Vacuum Interrupter in 1962,


Toshiba has been continuously improving and developing Vacuum Compact and Lightweight
Compact and slim design contactors can be applied to
Technology. either two-tier motor starters or slim starters per IEC
Over 3 millions Vacuum interrupters have been produced for various 60470 (2000).
The Contactors CV-6GA(L) and CV-6HA(L) have the same
types of vacuum apparatus such as contactors, circuit breakers and outline and mounting dimensions, as well as dual voltage No Surge Protection Required
ratings (3.6/7.2kV). Special main contact materials minimize chopping current.
switches which are now widely used as result of their outstanding No surge suppressor/arrester is required except for special
applications.
performance.
Toshiba has become a leading Japanese manufacturer that has
attained a record exceeding 230 thousands Low and High voltage
Low Power Consumption
Vacuum Contactors produced. The control device adopts an electronic circuit, the control
voltage either AC or DC can be easily changed by
Consistent with its dedication to the most advanced vacuum switches in the circuit board without changing the coil
technology, Toshiba offers new series of High-voltage vacuum and/or other parts. Since the economizing resistors are Conformity to Industrial Standard
eliminated, the power consumption in holding condition Conforming to latest international standards such as IEC,
contactors. has been reduced. BS, AS and JEM, being certified by class NK and TUV,
Toshiba Vacuum Contactors can be used widely all over
By adopting an electronics controlled circuit and being designed the world.
compactly to ensure reliability, handling ease and safety, the new
series of High-voltage Vacuum Contactors are suitable for Motor
starters, Transformer feeders and Capacitor switching applications.
3
Class NK certificate (Marine application)
4
1 TIMER
5
2 52
CC
OSCILLATION POWER
6
SWITCHING

Fig. 1 Configuration of drive-unit


TUV certificate

Ratings Type Operating mechanism Application Standard


Standard 7.2/3.6kV 200A 6.3kA CV-6GA Non-Latched Type General IEC, JEM, Class NK
CV-6GAL Latched Type General
400A 6.3kA CV-6HA Non-Latched Type General
CV-10HA(L) CV-6HAL Latched Type General
15/12kV-400A-4/5kA 720A 8.0kA CV-6KA1 Non-Latched Type General
CV-10HB(L) CV-6KAL1 Latched Type General
12kV-400A-5kA 12kV 400A 5.0kA CV-10HB Non-Latched Type Capacitor IEC
CV-6KA1 CV-10HBL Latched Type Capacitor
7.2kV-720A-8kA 15/12kV 400A 4.0/5.0kA CV-10HA Non-Latched Type Motor/Transformer IEC, NEMA
CV-10HAL Latched Type Motor/Transformer

Ratings Type Operating mechanism Application Standard


Special 7.2/3.6kV 400A 6.3kA CV-6HA-2 Non-Latched Type General IEC, JEM
Main CV-6HAL-2 Latched Type General
Terminals 12kV 400A 5.0kA CV-10HB-1 Non-Latched Type Capacitor IEC
(Rear side of CV-10HA) CV-10HBL-1 Latched Type Capacitor
15/12kV 400A 4.0/5.0kA CV-10HA-1 Non-Latched Type Motor/Transformer IEC, NEMA
CV-10HAL-1 Latched Type Motor/Transformer

1 2
3.6kV/7.2kV High-voltage Vacuum Contactors 3.6kV/7.2kV High-voltage Vacuum Contactors
Type CV Type CV
Standard 6GA 6HA 6GAL 6HAL Form 6KA1 6KAL1
Form
Upper front terminal - 6HA-2 - 6HAL-2 Operating Mechanism Non-Latched Latched
Operating Mechanism Non-Latched Latched Rated Voltage (Ur) 3.6/7.2kV
Rated Voltage (Ur) 3.6/7.2kV Rated Operational Current (Ie) 720A 720A
Rated Operational Current (Ie) 200A 400A 200A 400A Thermal Current (Ith) 800A 800A
Thermal Current (Ith) 300A 450A 300A 450A Rated Frequency 50/60Hz
Rated Frequency 50/60Hz Rated Short-time Withstand Current (Ik) 8000A - 1s
Rated Short-time Withstand Current (Ik) 6300A - 1s 6300A - 2s 6300A - 1s 6300A - 2s Rated peak Withstand Current (Ip) 20kA
Rated peak Withstand Current (Ip) 15.8kA Short-circuit Making and Breaking Current 8000A
Short-circuit Making and Breaking Current 6300A (Duty) "O" - 3min. - "CO" - 3min. - "CO"
(Duty) "O" - 3min. - "CO" - 3min. - "CO" Making Current (100times) AC4 7200A 7200A
Making Current (100times) AC4 2000A 4000A 2000A 4000A Breaking Current (25times) AC4 5760A 5760A
Breaking Current (25times) AC4 1600A 3200A 1600A 3200A Withstand Overload Current 4320A-30s 4320A-30s
Withstand Overload Current 1200A-30s 2400A-30s 1200A-30s 2400A-30s 6 times of Ie - 30s
6 times of Ie - 30s 15 times of Ie - 1s 10800A-1s 10800A-1s
4000A-4s 4000A-12s 4000A-4s 4000A-12s
15 times of Ie - 1s 6300A-2s 6300A-1s 6300A-2s Coordination with Current-limiting Fuses Prospective Short-circuit Current 40kA
6300A-1s
Coordination with Current-limiting Fuses Prospective Short-circuit Current 40kA Cut-off Current (Peak) 85kA
Cut-off Current (Peak) 55kA 85kA 55kA 85kA Rated Power Frequency Withstand Voltage 22kV - 1 min. *1
Rated Power Frequency Withstand Voltage 22kV-1min. *1 Insulation Level Impulse Withstand voltage 60kV
Insulation Level Impulse Withstand voltage 60kV Switching Frequency 600 operating cycles/hr 300 operating cycles/hr
Switching Frequency 1200 operating cycles/hr 300 operating cycles/hr Mechanical Life 1.0 million operations 0.2 million operations
Endurance
Mechanical Life 2.5 million operations 0.25 million operations Electrical Life (AC3) 0.2 million operations 0.2 million operations
Endurance
Electrical Life (AC3) 0.25 million operations 0.25 million operations Closing 100-240VAC / 100-220VDC
Rated Control Voltage
Closing 100-110, 115-120, 200-220, 230-240VAC / 100-110, 200-220VDC Tripping - 100-110, 200-220VDC
Rated Control Voltage
Tripping 24, 32, 48, 100-110, 200-220VDC Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage
Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage Operating Current Closing 7.5A (Peak)
Operating Current Closing 4.5A (Peak) (at 100V) Holding/Tripping 0.19A (Average) 4.0A (Peak)
(at 100V) Holding/Tripping 0.1A (Average) 4.0A (Peak) Closing Time 80 - 100ms
Closing Time 65 - 80ms Opening Time 55 - 65ms
Opening Time 20 - 30ms Contact arrangement 3NO-3NC 2NO-2NC
Contact arrangement 3NO-3NC 2NO-2NC Operational voltage Max. 480V, Min. 48V
Operational voltage Max. 480V, Min. 48V Ratings of Auxiliary Contact Thermal Current 10A
Ratings of Auxiliary Contact Thermal Current 10A AC Capacity 700VA (PF. 0.35)
AC Capacity 700VA (PF. 0.35) DC Capacity 60W (L/R 150ms)
DC Capacity 60W (L/R 150ms) Installation Floor Mount Vertical Installation
Installation Floor Mount Vertical Installation Altitude 1000m or lower
Altitude 1000m or lower Ambient air temperature -5 to 40OC
Ambient air temperature -5 to 40OC Application Condition Relative humidity 45 to 85%
Application Condition Relative humidity 45 to 85% Vibration Max. 20Hz 1G
Vibration Max. 20Hz 1G Shock Max. 30G
Shock Max. 30G Motor 2500/5000kW
Motor (kW) 750/1500 1500/3000 750/1500 1500/3000 Maximum Load Transformer 3500/7000kVA
Maximum Load Transformer (kVA) 1000/2000 2000/4000 1000/2000 2000/4000 Capacitor 2000/2000kvar
Capacitor (kvar) 1000/2000 2000/2000 1000/2000 2000/2000 Weight 27kg 28kg
Weight 19.0kg 19.5kg 19.5kg 20.0kg Standard IEC60470 (2000)
Standard IEC60470 (2000) JEM1167 (1990)
*2 JEM1167 (1990) *1 : Special withstand voltage (32kV-1min.) will be available by request.
*1 : Special withstand voltage (32kV-1min.) will be available by request.
*2 : CE marking can be available by request.
3 4
3.6kV/7.2kV High-voltage Vacuum Contactors 3.6kV/7.2kV High-voltage Vacuum Contactors
Type CV Type CV
Standard 6GA 6HA 6GAL 6HAL Form 6KA1 6KAL1
Form
Upper front terminal - 6HA-2 - 6HAL-2 Operating Mechanism Non-Latched Latched
Operating Mechanism Non-Latched Latched Rated Voltage (Ur) 3.6/7.2kV
Rated Voltage (Ur) 3.6/7.2kV Rated Operational Current (Ie) 720A 720A
Rated Operational Current (Ie) 200A 400A 200A 400A Thermal Current (Ith) 800A 800A
Thermal Current (Ith) 300A 450A 300A 450A Rated Frequency 50/60Hz
Rated Frequency 50/60Hz Rated Short-time Withstand Current (Ik) 8000A - 1s
Rated Short-time Withstand Current (Ik) 6300A - 1s 6300A - 2s 6300A - 1s 6300A - 2s Rated peak Withstand Current (Ip) 20kA
Rated peak Withstand Current (Ip) 15.8kA Short-circuit Making and Breaking Current 8000A
Short-circuit Making and Breaking Current 6300A (Duty) "O" - 3min. - "CO" - 3min. - "CO"
(Duty) "O" - 3min. - "CO" - 3min. - "CO" Making Current (100times) AC4 7200A 7200A
Making Current (100times) AC4 2000A 4000A 2000A 4000A Breaking Current (25times) AC4 5760A 5760A
Breaking Current (25times) AC4 1600A 3200A 1600A 3200A Withstand Overload Current 4320A-30s 4320A-30s
Withstand Overload Current 1200A-30s 2400A-30s 1200A-30s 2400A-30s 6 times of Ie - 30s
6 times of Ie - 30s 15 times of Ie - 1s 10800A-1s 10800A-1s
4000A-4s 4000A-12s 4000A-4s 4000A-12s
15 times of Ie - 1s 6300A-2s 6300A-1s 6300A-2s Coordination with Current-limiting Fuses Prospective Short-circuit Current 40kA
6300A-1s
Coordination with Current-limiting Fuses Prospective Short-circuit Current 40kA Cut-off Current (Peak) 85kA
Cut-off Current (Peak) 55kA 85kA 55kA 85kA Rated Power Frequency Withstand Voltage 22kV - 1 min. *1
Rated Power Frequency Withstand Voltage 22kV-1min. *1 Insulation Level Impulse Withstand voltage 60kV
Insulation Level Impulse Withstand voltage 60kV Switching Frequency 600 operating cycles/hr 300 operating cycles/hr
Switching Frequency 1200 operating cycles/hr 300 operating cycles/hr Mechanical Life 1.0 million operations 0.2 million operations
Endurance
Mechanical Life 2.5 million operations 0.25 million operations Electrical Life (AC3) 0.2 million operations 0.2 million operations
Endurance
Electrical Life (AC3) 0.25 million operations 0.25 million operations Closing 100-240VAC / 100-220VDC
Rated Control Voltage
Closing 100-110, 115-120, 200-220, 230-240VAC / 100-110, 200-220VDC Tripping - 100-110, 200-220VDC
Rated Control Voltage
Tripping 24, 32, 48, 100-110, 200-220VDC Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage
Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage Operating Current Closing 7.5A (Peak)
Operating Current Closing 4.5A (Peak) (at 100V) Holding/Tripping 0.19A (Average) 4.0A (Peak)
(at 100V) Holding/Tripping 0.1A (Average) 4.0A (Peak) Closing Time 80 - 100ms
Closing Time 65 - 80ms Opening Time 55 - 65ms
Opening Time 20 - 30ms Contact arrangement 3NO-3NC 2NO-2NC
Contact arrangement 3NO-3NC 2NO-2NC Operational voltage Max. 480V, Min. 48V
Operational voltage Max. 480V, Min. 48V Ratings of Auxiliary Contact Thermal Current 10A
Ratings of Auxiliary Contact Thermal Current 10A AC Capacity 700VA (PF. 0.35)
AC Capacity 700VA (PF. 0.35) DC Capacity 60W (L/R 150ms)
DC Capacity 60W (L/R 150ms) Installation Floor Mount Vertical Installation
Installation Floor Mount Vertical Installation Altitude 1000m or lower
Altitude 1000m or lower Ambient air temperature -5 to 40OC
Ambient air temperature -5 to 40OC Application Condition Relative humidity 45 to 85%
Application Condition Relative humidity 45 to 85% Vibration Max. 20Hz 1G
Vibration Max. 20Hz 1G Shock Max. 30G
Shock Max. 30G Motor 2500/5000kW
Motor (kW) 750/1500 1500/3000 750/1500 1500/3000 Maximum Load Transformer 3500/7000kVA
Maximum Load Transformer (kVA) 1000/2000 2000/4000 1000/2000 2000/4000 Capacitor 2000/2000kvar
Capacitor (kvar) 1000/2000 2000/2000 1000/2000 2000/2000 Weight 27kg 28kg
Weight 19.0kg 19.5kg 19.5kg 20.0kg Standard IEC60470 (2000)
Standard IEC60470 (2000) JEM1167 (1990)
*2 JEM1167 (1990) *1 : Special withstand voltage (32kV-1min.) will be available by request.
*1 : Special withstand voltage (32kV-1min.) will be available by request.
*2 : CE marking can be available by request.
3 4
12kV/15kV High-voltage Vacuum Contactors
Supplied Not supplied
Type CV CV-6GA/6HA CV-6KA1 CV-10HA/10HB
Standard 10HA 10HAL 10HB 10HBL Name of parts Remarks
From Non-Latched Latched Non-Latched Latched Non-Latched Latched
Vertical terminals 10HA-1 10HAL-1 10HB-1 10HBL-1
Operating Mechanism Non-Latched Latched Non-Latched Latched Wipe gauge For checking contact wear
Rated Voltage (Ur) 12/15kV 12kV Trip rod For latched type only
Rated Operational Current (Ie) 400A 400A
Control wire With plug (1.25mm 2 X 1m)
Thermal Current (Ith) 450A 450A
Rated Frequency 50/60Hz
Rated Short-time Withstand Current (Ik) 5000A - 1s 5000A - 1s
Wipe gauge
Wipe gauge
Rated peak Withstand Current (Ip) 12.5kA 12.5kA The wipe gauge can be used for checking
t=0.5 CV-6GA/6HA

28
contact wear of vacuum interrupters. Refer to the
Short-circuit Making and Breaking Current 5000/4000A 5000A t=1.0 CV-6KA1/CV-10
instruction manual for using this gauge. 120
(Duty) "O"-3min.-"CO"-3min.-"CO" "O"-3min.-"CO"-3min.-"CO"
Making Current (100 times) AC4 4000A 4000A

DIA 7
Trip rod
Breaking Current (25 times) AC4 3200A
Trip rod
3200A
The trip rod may be used for manual tripping for
Withstand Overload Current 2400A-30s 2400A-30s
60
latched contactor and combination unit, however
6 times of Ie - 30s
8000A-1s 8000A-1s this operation shall be maintenance purpose or
15 times of Ie - 1s CONNECTOR WIRE
emergency case only.
Coordination with Current-limiting Fuses Prospective Short-circuit Current 50kA Control wire
Cut-off Current (Peak) 36kA

63

55
Control wire
Rated Power Frequency Withstand Voltage 28kV - 1 min. *1 The control wire with plug is provides on CV-10
Insulation Level Impulse Withstand voltage 75kV series contactor, however the additional wire will 14 23 1000

Switching Frequency 300 op./hr 120 op./hr 300 op./hr 120 op./hr be available on request.
Mechanical Life 0.25 mill. 0.25 mill. 0.25 mill. 0.25 mill. Fig. 2 Standard accessories
Endurance
Electrical Life (AC3) 0.10 mill. 0.10 mill. 0.10 mill. 0.10 mill.
Closing 100-240VAC / 100-220VDC
Rated Control Voltage
Tripping 100-110, 200220VDC
Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage
Supplied Not supplied
Operating Current Closing 6.0A (Peak) CV-6GA/6HA CV-6KA1 CV-10HA/10HB
(at 100V) Holding/Tripping 0.13A (Av.) 4.0A (Peak) 0.13A (Av.) 4.0A (Peak) Name of parts
Non- Non- Non- Remarks
Latched Latched Latched
Closing Time 120-145ms 120-145ms 120-145ms 120-145ms Latched Latched Latched
Opening Time 80-90ms 30-40ms 80-90ms 30-40ms LC9 100/110VAC for 100-110V coil
For
Capacitor
Contact arrangement 4NO-2NC 2NO-1NC 4NO-2NC 2NO-1NC LC10 Latched 200/220VAC for 200-220V coil
trip device
Operational voltage Max. 480V, Min. 48V type
CIT-10Q 100/200VAC for 100-110V coil
Ratings of Auxiliary Contact Thermal Current 10A CR Surge suppressor NV60K304T1, NV95K304T1 (See Page 13)
AC Capacity 700VA (PF. 0.35)
Mechanical interlock (See Fig. 9)
DC Capacity 60W (L/R 150ms)
Installation Floor Mount Vertical Installation
Capacitor trip device
Altitude 1000m or lower
The capacitor trip device will be used for latched contactor when DC power source is not available. The device charges
Ambient air temperature -5 to 40OC
Application Condition from AC power, and supplies DC power to the trip coil at trip command. The alarm contact is provided on CIT-10Q.
Relative humidity 45 to 85%
Vibration Max. 20Hz 1G Surge suppressor
Shock Max. 30G The three phase type NV60K304T1 for 3.6/7.2kV and NVK95K304T1 for 12/15kV are available.
Motor 3500kW -
Mechanical interlock
Maximum Load Transformer 4500kVA -
The mechanical interlock shall be used in the reversing starter to prevent mechanically from c l o sing the fo rward
Capacitor - 5000kvar and reverse contactors simultaneously.
Weight 40kg 41kg 40kg 41kg The following vertical pitch interlocks are available for contactors.
Standard IEC60470 (2000) Vertical pitch 450 mm and 550mm for CV-6GA(L)/CV-6HA(L)
*1 : Special withstand voltage (42kV-1min.) will be available by request. Vertical pitch 600mm for CV-6KA(L)1

5 6
12kV/15kV High-voltage Vacuum Contactors
Supplied Not supplied
Type CV CV-6GA/6HA CV-6KA1 CV-10HA/10HB
Standard 10HA 10HAL 10HB 10HBL Name of parts Remarks
From Non-Latched Latched Non-Latched Latched Non-Latched Latched
Vertical terminals 10HA-1 10HAL-1 10HB-1 10HBL-1
Operating Mechanism Non-Latched Latched Non-Latched Latched Wipe gauge For checking contact wear
Rated Voltage (Ur) 12/15kV 12kV Trip rod For latched type only
Rated Operational Current (Ie) 400A 400A
Control wire With plug (1.25mm 2 X 1m)
Thermal Current (Ith) 450A 450A
Rated Frequency 50/60Hz
Rated Short-time Withstand Current (Ik) 5000A - 1s 5000A - 1s
Wipe gauge
Wipe gauge
Rated peak Withstand Current (Ip) 12.5kA 12.5kA The wipe gauge can be used for checking
t=0.5 CV-6GA/6HA

28
contact wear of vacuum interrupters. Refer to the
Short-circuit Making and Breaking Current 5000/4000A 5000A t=1.0 CV-6KA1/CV-10
instruction manual for using this gauge. 120
(Duty) "O"-3min.-"CO"-3min.-"CO" "O"-3min.-"CO"-3min.-"CO"
Making Current (100 times) AC4 4000A 4000A

DIA 7
Trip rod
Breaking Current (25 times) AC4 3200A
Trip rod
3200A
The trip rod may be used for manual tripping for
Withstand Overload Current 2400A-30s 2400A-30s
60
latched contactor and combination unit, however
6 times of Ie - 30s
8000A-1s 8000A-1s this operation shall be maintenance purpose or
15 times of Ie - 1s CONNECTOR WIRE
emergency case only.
Coordination with Current-limiting Fuses Prospective Short-circuit Current 50kA Control wire
Cut-off Current (Peak) 36kA

63

55
Control wire
Rated Power Frequency Withstand Voltage 28kV - 1 min. *1 The control wire with plug is provides on CV-10
Insulation Level Impulse Withstand voltage 75kV series contactor, however the additional wire will 14 23 1000

Switching Frequency 300 op./hr 120 op./hr 300 op./hr 120 op./hr be available on request.
Mechanical Life 0.25 mill. 0.25 mill. 0.25 mill. 0.25 mill. Fig. 2 Standard accessories
Endurance
Electrical Life (AC3) 0.10 mill. 0.10 mill. 0.10 mill. 0.10 mill.
Closing 100-240VAC / 100-220VDC
Rated Control Voltage
Tripping 100-110, 200220VDC
Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage
Supplied Not supplied
Operating Current Closing 6.0A (Peak) CV-6GA/6HA CV-6KA1 CV-10HA/10HB
(at 100V) Holding/Tripping 0.13A (Av.) 4.0A (Peak) 0.13A (Av.) 4.0A (Peak) Name of parts
Non- Non- Non- Remarks
Latched Latched Latched
Closing Time 120-145ms 120-145ms 120-145ms 120-145ms Latched Latched Latched
Opening Time 80-90ms 30-40ms 80-90ms 30-40ms LC9 100/110VAC for 100-110V coil
For
Capacitor
Contact arrangement 4NO-2NC 2NO-1NC 4NO-2NC 2NO-1NC LC10 Latched 200/220VAC for 200-220V coil
trip device
Operational voltage Max. 480V, Min. 48V type
CIT-10Q 100/200VAC for 100-110V coil
Ratings of Auxiliary Contact Thermal Current 10A CR Surge suppressor NV60K304T1, NV95K304T1 (See Page 13)
AC Capacity 700VA (PF. 0.35)
Mechanical interlock (See Fig. 9)
DC Capacity 60W (L/R 150ms)
Installation Floor Mount Vertical Installation
Capacitor trip device
Altitude 1000m or lower
The capacitor trip device will be used for latched contactor when DC power source is not available. The device charges
Ambient air temperature -5 to 40OC
Application Condition from AC power, and supplies DC power to the trip coil at trip command. The alarm contact is provided on CIT-10Q.
Relative humidity 45 to 85%
Vibration Max. 20Hz 1G Surge suppressor
Shock Max. 30G The three phase type NV60K304T1 for 3.6/7.2kV and NVK95K304T1 for 12/15kV are available.
Motor 3500kW -
Mechanical interlock
Maximum Load Transformer 4500kVA -
The mechanical interlock shall be used in the reversing starter to prevent mechanically from c l o sing the fo rward
Capacitor - 5000kvar and reverse contactors simultaneously.
Weight 40kg 41kg 40kg 41kg The following vertical pitch interlocks are available for contactors.
Standard IEC60470 (2000) Vertical pitch 450 mm and 550mm for CV-6GA(L)/CV-6HA(L)
*1 : Special withstand voltage (42kV-1min.) will be available by request. Vertical pitch 600mm for CV-6KA(L)1

5 6
OUTLINE DIMENSIONS OPERATING CIRCUITS
Non-Latched type
RECOMMENDED
PARTITION
High-Voltage Vacuum Contactors P or R
E OFF
30 368 30 202 REMOTE
DISTANCE SWITCH
The typical operating circuit is shown in Fig. 5 E
13 69 115 115 69 31 2 15
*2
indicating type CV-6GA/6HA contactor. *1
E E ON
VMC
30

4
Make sure to use the "NO" contacts of quick 4 COS
16 15 14 13 12 11

100-110VAC/DC
200-220VAC/DC
3 1 4
START
operating relay (4) self-holding circuit. Do not use INTERLOCK
FRONT COVER 30 5
the "NO" auxiliary contacts of vacuum contactor, STOP

6
INTERLOCK DU
26 25 24 23 22 21
INTERRUPTERS this may cause the welding of main contacts 52CC 52CC
MAIN CIRCUIT TERMINALS when the start (ON) button is pushed 2E-RY

124
6
12 DIA-6 HOLES GL RL

INDICATOR incompletely. (refer to the marked 1 in figure) 2


N or T
Make sure to switch the closing coil on DC side.
400

VMC : Vacuum contactor

371
6
OFF
TRIP LEVER 30 Should the coil be switched on AC side, a 52CC : Closing coil
ON
DU : Drive unit
(FOR LATCHED TYPE)
TRIPPING HOLE
MAIN CIRCUIT TERMINALS discharging circuit will be formed by rectifiers 4 : Control relay

217
(DIA 9) Fig. 5 Non-Latched type operating circuit
87654321

against coil, resulting in prolonged opening time.


180

DIA 15

(REAR)
128

AUXILIARY +1
345-
SWITCH (refer to the marked 2 in figure)
166 179

10 195 10
Latched type

195-+ 1
13 300 60
166 134 REMOTE SWITCH
18 373 21 219 11 DIA - 4 HOLES

EARTHING CONTROL MOUNTING HOLES 300-+1 High-Voltage Vacuum Contactors P


TERMINAL TERMINAL (FRONT) E ON E E E OFF 2E-RY
(M8 BOLT) COUNTER LATCH MECHANISM The typical operating circuits are shown in Fig. 6
(OPTION) (FOR LATCHED TYPE) DETAIL OF MOUNTING
HOLES (TOP VIEW) and Fig. 7 indicating type CV-6GAL/6HAL COS VMC
START 4 11 15 14 13 12
INTERLOCK
Fig. 3 Types CV-6GA(L)/CV-6HA(L) contactor. 3 1 4

1 0 0 -1 10V DC
2 0 0 -2 20V DC
The electrical trip free circuit must be furnished in 5
16
control circuit. (outside of contactor) DU 21
25 24 23 22
26 D 52CC 52CC 52TC
A stable DC power source such as battery is
6
RECOMMENDED
recommended for control circuit. If the DC power 4
GL RL
202
PARTITION source is not available, employ the AC closing and
30 368 30 DISTANCE 60 13
2 7
N
13 69 115 115 69 31 2 capacitor trip device (CTD) for tripping. VMC : Vacuum contactor
15
52CC: Closing coil
Make sure to use the "NO" auxiliary contacts (11- 52TC : Trip coil
30

MAIN CIRCUIT DU : Drive unit


TERMINALS 21) of vacuum contactor in trip circuit, and "Late 4 : Control relay

FRONT COVER Opening NC" auxiliary contacts (16-26) of vacuum Fig. 6 Latched type operating circuit (Shunt trip)
30
contactor for control relay circuit.
INTERRUPTERS
MAIN CIRCUIT TERMINALS
6

12 DIA-3 HOLES
M10 SCREW
124

REMOTE SWITCH
10 30
INDICATOR
R
400

371
6

OFF
ON
TRIP LEVER (REAR) E ON E E E OFF 2E-RY
(FOR LATCHED TYPE)
345-+1
TRIPPING HOLE
217

VMC
87654321

(DIA 9) COS
180

DIA-15

166 179 4 11 15 14 13 12

100/110VAC
200/220VAC
START CTD
128

AUXILIARY SWITCH INTERLOCK 3 1 4


P U
195-+ 1

10 N V
166 134
11 DIA-4 HOLES 16 5
DU 21
13 300 60 10 195 10 25 24 23 22
300-+1 26 D 52CC 52CC 52TC
18 373 21 215
(FRONT) 4 6
GL RL
EARTHING CONTROL LATCH MECHANISM MOUNTING HOLES 2 7
DETAIL OF MOUNTING
TERMINAL TERMINAL (FOR LATCHED TYPE) HOLES (TOP VIEW) T
(M8 BOLT)
VMC : Vacuum contactor
52CC: Closing coil
Fig. 4 Types CV-6HA(L)-2 52TC: Trip coil
DU : Drive unit
4 : Control relay
CTD : Capacitor trip device
Fig. 7 Latched type operating circuit (Capacitor trip)
OUTLINE DIMENSIONS OPERATING CIRCUITS
Non-Latched type
RECOMMENDED
PARTITION
High-Voltage Vacuum Contactors P or R
E OFF
30 368 30 202 REMOTE
DISTANCE SWITCH
The typical operating circuit is shown in Fig. 5 E
13 69 115 115 69 31 2 15
*2
indicating type CV-6GA/6HA contactor. *1
E E ON
VMC
30

4
Make sure to use the "NO" contacts of quick 4 COS
16 15 14 13 12 11

100-110VAC/DC
200-220VAC/DC
3 1 4
START
operating relay (4) self-holding circuit. Do not use INTERLOCK
FRONT COVER 30 5
the "NO" auxiliary contacts of vacuum contactor, STOP

6
INTERLOCK DU
26 25 24 23 22 21
INTERRUPTERS this may cause the welding of main contacts 52CC 52CC
MAIN CIRCUIT TERMINALS when the start (ON) button is pushed 2E-RY

124
6
12 DIA-6 HOLES GL RL

INDICATOR incompletely. (refer to the marked 1 in figure) 2


N or T
Make sure to switch the closing coil on DC side.
400

VMC : Vacuum contactor

371
6
OFF
TRIP LEVER 30 Should the coil be switched on AC side, a 52CC : Closing coil
ON
DU : Drive unit
(FOR LATCHED TYPE)
TRIPPING HOLE
MAIN CIRCUIT TERMINALS discharging circuit will be formed by rectifiers 4 : Control relay

217
(DIA 9) Fig. 5 Non-Latched type operating circuit
87654321

against coil, resulting in prolonged opening time.


180

DIA 15

(REAR)
128

AUXILIARY +1
345-
SWITCH (refer to the marked 2 in figure)
166 179

10 195 10
Latched type

195-+ 1
13 300 60
166 134 REMOTE SWITCH
18 373 21 219 11 DIA - 4 HOLES

EARTHING CONTROL MOUNTING HOLES 300-+1 High-Voltage Vacuum Contactors P


TERMINAL TERMINAL (FRONT) E ON E E E OFF 2E-RY
(M8 BOLT) COUNTER LATCH MECHANISM The typical operating circuits are shown in Fig. 6
(OPTION) (FOR LATCHED TYPE) DETAIL OF MOUNTING
HOLES (TOP VIEW) and Fig. 7 indicating type CV-6GAL/6HAL COS VMC
START 4 11 15 14 13 12
INTERLOCK
Fig. 3 Types CV-6GA(L)/CV-6HA(L) contactor. 3 1 4

1 0 0 -1 10V DC
2 0 0 -2 20V DC
The electrical trip free circuit must be furnished in 5
16
control circuit. (outside of contactor) DU 21
25 24 23 22
26 D 52CC 52CC 52TC
A stable DC power source such as battery is
6
RECOMMENDED
recommended for control circuit. If the DC power 4
GL RL
202
PARTITION source is not available, employ the AC closing and
30 368 30 DISTANCE 60 13
2 7
N
13 69 115 115 69 31 2 capacitor trip device (CTD) for tripping. VMC : Vacuum contactor
15
52CC: Closing coil
Make sure to use the "NO" auxiliary contacts (11- 52TC : Trip coil
30

MAIN CIRCUIT DU : Drive unit


TERMINALS 21) of vacuum contactor in trip circuit, and "Late 4 : Control relay

FRONT COVER Opening NC" auxiliary contacts (16-26) of vacuum Fig. 6 Latched type operating circuit (Shunt trip)
30
contactor for control relay circuit.
INTERRUPTERS
MAIN CIRCUIT TERMINALS
6

12 DIA-3 HOLES
M10 SCREW
124

REMOTE SWITCH
10 30
INDICATOR
R
400

371
6

OFF
ON
TRIP LEVER (REAR) E ON E E E OFF 2E-RY
(FOR LATCHED TYPE)
345-+1
TRIPPING HOLE
217

VMC
87654321

(DIA 9) COS
180

DIA-15

166 179 4 11 15 14 13 12

100/110VAC
200/220VAC
START CTD
128

AUXILIARY SWITCH INTERLOCK 3 1 4


P U
195-+ 1

10 N V
166 134
11 DIA-4 HOLES 16 5
DU 21
13 300 60 10 195 10 25 24 23 22
300-+1 26 D 52CC 52CC 52TC
18 373 21 215
(FRONT) 4 6
GL RL
EARTHING CONTROL LATCH MECHANISM MOUNTING HOLES 2 7
DETAIL OF MOUNTING
TERMINAL TERMINAL (FOR LATCHED TYPE) HOLES (TOP VIEW) T
(M8 BOLT)
VMC : Vacuum contactor
52CC: Closing coil
Fig. 4 Types CV-6HA(L)-2 52TC: Trip coil
DU : Drive unit
4 : Control relay
CTD : Capacitor trip device
Fig. 7 Latched type operating circuit (Capacitor trip)
OUTLINE DIMENSIONS OPERATING CIRCUITS
RECOMMENDED
PARTITION Non-Latched type
DISTANCE
25 390 25 239 High-Voltage Vacuum Contactors P or R
E OFF REMOTE
SWITCH
19 80 115 115 80 18 5 205 20 The typical operating circuit is shown in Fig. 10 E 4
25

indicating type CV-6KA1 contactor. *1


E E ON VMC
A1
2 15 Make sure to use the "NO" contacts of quick 16 15 14 13 12 11

100-110VAC/DC
200-220VAC/DC
FRONT COVER 4 COS

operating relay (4) self-holding circuit. Do not use START


INTERLOCK
30 T1
the "NO" auxiliary contacts of vacuum contactor, STOP
INTERLOCK DU
26 25 24 23 22 21
INTERRUPTERS this may cause the welding of main contacts 52CC 52CC

10
DIA 13
2E-RY
when the start (ON) button is pushed GL RL

120
MAIN TERMINALS T2
15 4 A2
DIA 13 incompletely. (refer to the marked 1 in figure)

10
N or T
VMC : Vacuum contactor
30
468

DU : Drive unit

433
4 : Control relay
OFF TRIP LEVER
ON (FOR LATCHED TYPE) Fig. 10 Non-Latched type operating circuit

273
DIA 15
190

TRIPPING HOLE
160

(DIA 9) AUXILIARY

105
SWITCH
24

REMOTE SWITCH
3

CONTROL
CONTROL MOUNTING
Latched type P
TERMINAL MOUNTING HOLES
High-Voltage Vacuum Contactors
MOUNTING E ON E E E 2E-RY
FOR TRIPPING TERMINAL HOLES
HOLES FOR CLOSING 48 29 154 25 4
11 DIA-4 HOLES 122
EARTHING 208 COS
10 368 TERMINAL The typical operating circuits are shown in Fig. 10 A1 OFF T4 VMC
START
(M8 BOLT) 226
20 388 and Fig. 11 specifying type CV-6KAL1 contactor. INTERLOCK

100-110VDC
200-220VDC
15 14 13 12
11
T1
LATCH MECHANISM The electrical trip free circuit must be furnished in
(FOR LATCHED TYPE) 16
control circuit. (outside of contactor) DU
Fig. 8 Types CV-6KA1/CV-6KAL1 26
D 52CC 52CC 21
A stable DC power source such as battery is 25 24 23 22
52TC
CV-6KA1 recommended for control circuit. If the DC power 4
T2 GL RL
CV-6KAL1 A2 T3
source is not available, employ the AC closing and N
ARM capacitor trip device (CTD) for tripping. VMC: Vacuum contactor
ELLIPSE OFF 52CC: Closing coil
ON Make sure to use the "NO" auxiliary contacts (11- 52TC: Trip coil
DU : Drive unit
21) of vacuum contactor in trip circuit, and "NC" 4 : Control relay
COUPLING
VMC : OFF auxiliary contacts (16-26) of vacuum contactor for Fig. 11 Latched type operating circuit (Shunt trip)
SHAFT (VMC)
control relay circuit.

ADJUTING NUTS (M8)


REMOTE SWITCH
COUPLING ROD
R
ADJUTING NUTS (M8)
PITCH BETWEEN CONTACTORS

E ON E E E OFF 2E-RY
4
ARM
COS A1 T4 VMC
COUPLING START 11 15 14 13 12 CTD

100-110VAC
200-220VAC
ON INTERLOCK
P U
P

OFF
T1 N V
16
468

M8 BOLTS FOR FIXING DU 21


SHAFT (VMC) INTERLOCK UNIT 25 24 23 22
VMC : OFF 26 D 52CC 52CC 52TC

4 T2 T3
A2 GL RL
160

DETAIL OF INTERLOCKING MECHANISM


T
VMC : Vacuum contactor
52CC: Closing coil
128 10 52TC: Trip coil
MOUNTING 25 154 29 38 368 10 DU : Drive unit
HOLES 266 435 4 : Control relay
11 DIA-4 HOLES CTD : Capacitor trip device

Fig. 12 Latched type operating circuit (Capacitor trip)


Fig. 9 Mechanical Interlock on CV-6KA(L)1

9 10
OUTLINE DIMENSIONS OPERATING CIRCUITS
RECOMMENDED
PARTITION Non-Latched type
DISTANCE
25 390 25 239 High-Voltage Vacuum Contactors P or R
E OFF REMOTE
SWITCH
19 80 115 115 80 18 5 205 20 The typical operating circuit is shown in Fig. 10 E 4
25

indicating type CV-6KA1 contactor. *1


E E ON VMC
A1
2 15 Make sure to use the "NO" contacts of quick 16 15 14 13 12 11

100-110VAC/DC
200-220VAC/DC
FRONT COVER 4 COS

operating relay (4) self-holding circuit. Do not use START


INTERLOCK
30 T1
the "NO" auxiliary contacts of vacuum contactor, STOP
INTERLOCK DU
26 25 24 23 22 21
INTERRUPTERS this may cause the welding of main contacts 52CC 52CC

10
DIA 13
2E-RY
when the start (ON) button is pushed GL RL

120
MAIN TERMINALS T2
15 4 A2
DIA 13 incompletely. (refer to the marked 1 in figure)

10
N or T
VMC : Vacuum contactor
30
468

DU : Drive unit

433
4 : Control relay
OFF TRIP LEVER
ON (FOR LATCHED TYPE) Fig. 10 Non-Latched type operating circuit

273
DIA 15
190

TRIPPING HOLE
160

(DIA 9) AUXILIARY

105
SWITCH
24

REMOTE SWITCH
3

CONTROL
CONTROL MOUNTING
Latched type P
TERMINAL MOUNTING HOLES
High-Voltage Vacuum Contactors
MOUNTING E ON E E E 2E-RY
FOR TRIPPING TERMINAL HOLES
HOLES FOR CLOSING 48 29 154 25 4
11 DIA-4 HOLES 122
EARTHING 208 COS
10 368 TERMINAL The typical operating circuits are shown in Fig. 10 A1 OFF T4 VMC
START
(M8 BOLT) 226
20 388 and Fig. 11 specifying type CV-6KAL1 contactor. INTERLOCK

100-110VDC
200-220VDC
15 14 13 12
11
T1
LATCH MECHANISM The electrical trip free circuit must be furnished in
(FOR LATCHED TYPE) 16
control circuit. (outside of contactor) DU
Fig. 8 Types CV-6KA1/CV-6KAL1 26
D 52CC 52CC 21
A stable DC power source such as battery is 25 24 23 22
52TC
CV-6KA1 recommended for control circuit. If the DC power 4
T2 GL RL
CV-6KAL1 A2 T3
source is not available, employ the AC closing and N
ARM capacitor trip device (CTD) for tripping. VMC: Vacuum contactor
ELLIPSE OFF 52CC: Closing coil
ON Make sure to use the "NO" auxiliary contacts (11- 52TC: Trip coil
DU : Drive unit
21) of vacuum contactor in trip circuit, and "NC" 4 : Control relay
COUPLING
VMC : OFF auxiliary contacts (16-26) of vacuum contactor for Fig. 11 Latched type operating circuit (Shunt trip)
SHAFT (VMC)
control relay circuit.

ADJUTING NUTS (M8)


REMOTE SWITCH
COUPLING ROD
R
ADJUTING NUTS (M8)
PITCH BETWEEN CONTACTORS

E ON E E E OFF 2E-RY
4
ARM
COS A1 T4 VMC
COUPLING START 11 15 14 13 12 CTD

100-110VAC
200-220VAC
ON INTERLOCK
P U
P

OFF
T1 N V
16
468

M8 BOLTS FOR FIXING DU 21


SHAFT (VMC) INTERLOCK UNIT 25 24 23 22
VMC : OFF 26 D 52CC 52CC 52TC

4 T2 T3
A2 GL RL
160

DETAIL OF INTERLOCKING MECHANISM


T
VMC : Vacuum contactor
52CC: Closing coil
128 10 52TC: Trip coil
MOUNTING 25 154 29 38 368 10 DU : Drive unit
HOLES 266 435 4 : Control relay
11 DIA-4 HOLES CTD : Capacitor trip device

Fig. 12 Latched type operating circuit (Capacitor trip)


Fig. 9 Mechanical Interlock on CV-6KA(L)1

9 10
OUTLINE DIMENSIONS OPERATING CIRCUITS
RECOMMENDED
Non-Latched type
PARTITION
DISTANCE High-Voltage Vacuum Contactors P or R
E OFF
REMOTE 4
E
The typical operating circuit is shown in Fig. 15 SWITCH
T5 T6 T7 T8 T9 T10
T1 VMC
E E ON
indicating type CV-10HA/10HB contactor. *1 AUS
137 37

100-110VAC/DC
200-220VAC/DC
65 475 65 4
165 165 Make sure to use the "NO" contacts of quick COS 11 9 7 5 3 1
110

8 165 165 8 15 1
START
INTERRUPTERS 30 operating relay (4) self-holding circuit. Do not use INTERLOCK 5 12 10 8 6 4 2

6
LIFTING HOLES
the "NO" auxiliary contacts of vacuum contactor, STOP
INTERLOCK
DU 52CC 52CC

(20 DIA -2 HOLES) 6


this may cause the welding of main contacts 2
MAIN CIRCUIT 2E-RY
INSULATION
when the start (ON) button is pushed

206
BARRIER TERMINALS
15 13 DIA- 6 HOLES 4
T11 T15 T16 T17 T18 T19 T20
incompletely. (refer to the marked 1 in figure) N or T

6
VMC : Vacuum contactor
52CC : Closing coil
565

DU : Drive unit
METAL COVER 4 : Control relay
474

Fig. 15 Non-Latched type operating circuit

320
INDICATOR
63
200

CONTROL
COUNTER (OPTION) 170
CONNECTOR TRIPPING HOLES REMOTE SWITCH
(DIA 9)
MOUNTING HOLES
24 146 23
Latched type
P
(14 DIA-4 HOLES)
E ON E 4 E E OFF 2E-RY
13 500 13 193
526 235 High-Voltage Vacuum Contactors COS T1 T6 T7 T8 T3 VMC

The typical operating circuits are shown in Fig. 16 START


INTERLOCK
AUS
9 7 5 3 1

100-110VDC
200-220VDC
Fig. 13 Types CV-10HA(L)/CV-10HB(L) and Fig. 17 specifying type CV-10HAL/10HBL T5
11 1
contactor. 5
10 8 6 4 2

The electrical trip free circuit must be furnished in 12


DU D 52CC 52CC
52TC
6
RECOMMENDED PARTITION DISTANCE control circuit. (outside of contactor) T15
4
2
4
A stable DC power source such as battery is T11 T16 T17 T18 T13
N
recommended for control circuit. If the DC power VMC : Vacuum contactor
52CC: Closing coil
65 475 65 75 140 source is not available, employ the AC closing and 52TC : Trip coil
165 165
137 17 DU : Drive unit
115

capacitor trip device (CTD) for tripping.


15

8 165 165 8 30 4 : Control relay


6
Make sure to use the "NO" auxiliary contacts (1-2 Fig. 16 Latched type operating circuit (Shunt trip)
INTERRUPTERS
and 3-4) of vacuum contactor in trip circuit
LIFTING HOLES
91

(20 DIA-2 HOLES) (connected in contactor), and "NC" auxiliary


MAIN CIRCUIT
245

INSULATION TERMINALS contacts (11-12) of vacuum contactor for control REMOTE SWITCH
BARRIER 6 13 DIA-6 HOLES
relay circuit.
R
E ON E
4 E E OFF 2E-RY
606

15

30 COS T1
METAL COVER T6 T7 T8 T3 VMC
474

START AUS
INTERLOCK
1

100-110VAC
200-220VAC
9 7 5 3 CTD
346

T5
11 1 P U
INDICATOR 10 8 6 4 2 N V
63 5
200

COUNTER (OPTION)
170

DU D 52CC 52CC
12 52TC
CONTROL TRIPPING HOLES 6
CONNECTOR (DIA 9) T15
2 4
4
13 500 13 24 146 23 T11 T16 T17 T18 T13
T
526 193 VMC : Vacuum contactor
52CC: Closing coil
MOUNTING HOLES 215 52TC: Trip coil
(14 DIA-4 HOLES) DU : Drive unit
4 : Control relay
CTD : Capacitor trip device
Fig. 14 Types CV-10HA(L)-1/CV-10HB(L)-1
Fig. 17 Latched type operating circuit (Capacitor trip)

11 12
OUTLINE DIMENSIONS OPERATING CIRCUITS
RECOMMENDED
Non-Latched type
PARTITION
DISTANCE High-Voltage Vacuum Contactors P or R
E OFF
REMOTE 4
E
The typical operating circuit is shown in Fig. 15 SWITCH
T5 T6 T7 T8 T9 T10
T1 VMC
E E ON
indicating type CV-10HA/10HB contactor. *1 AUS
137 37

100-110VAC/DC
200-220VAC/DC
65 475 65 4
165 165 Make sure to use the "NO" contacts of quick COS 11 9 7 5 3 1
110

8 165 165 8 15 1
START
INTERRUPTERS 30 operating relay (4) self-holding circuit. Do not use INTERLOCK 5 12 10 8 6 4 2

6
LIFTING HOLES
the "NO" auxiliary contacts of vacuum contactor, STOP
INTERLOCK
DU 52CC 52CC

(20 DIA -2 HOLES) 6


this may cause the welding of main contacts 2
MAIN CIRCUIT 2E-RY
INSULATION
when the start (ON) button is pushed

206
BARRIER TERMINALS
15 13 DIA- 6 HOLES 4
T11 T15 T16 T17 T18 T19 T20
incompletely. (refer to the marked 1 in figure) N or T

6
VMC : Vacuum contactor
52CC : Closing coil
565

DU : Drive unit
METAL COVER 4 : Control relay
474

Fig. 15 Non-Latched type operating circuit

320
INDICATOR
63
200

CONTROL
COUNTER (OPTION) 170
CONNECTOR TRIPPING HOLES REMOTE SWITCH
(DIA 9)
MOUNTING HOLES
24 146 23
Latched type
P
(14 DIA-4 HOLES)
E ON E 4 E E OFF 2E-RY
13 500 13 193
526 235 High-Voltage Vacuum Contactors COS T1 T6 T7 T8 T3 VMC

The typical operating circuits are shown in Fig. 16 START


INTERLOCK
AUS
9 7 5 3 1

100-110VDC
200-220VDC
Fig. 13 Types CV-10HA(L)/CV-10HB(L) and Fig. 17 specifying type CV-10HAL/10HBL T5
11 1
contactor. 5
10 8 6 4 2

The electrical trip free circuit must be furnished in 12


DU D 52CC 52CC
52TC
6
RECOMMENDED PARTITION DISTANCE control circuit. (outside of contactor) T15
4
2
4
A stable DC power source such as battery is T11 T16 T17 T18 T13
N
recommended for control circuit. If the DC power VMC : Vacuum contactor
52CC: Closing coil
65 475 65 75 140 source is not available, employ the AC closing and 52TC : Trip coil
165 165
137 17 DU : Drive unit
115

capacitor trip device (CTD) for tripping.


15

8 165 165 8 30 4 : Control relay


6
Make sure to use the "NO" auxiliary contacts (1-2 Fig. 16 Latched type operating circuit (Shunt trip)
INTERRUPTERS
and 3-4) of vacuum contactor in trip circuit
LIFTING HOLES
91

(20 DIA-2 HOLES) (connected in contactor), and "NC" auxiliary


MAIN CIRCUIT
245

INSULATION TERMINALS contacts (11-12) of vacuum contactor for control REMOTE SWITCH
BARRIER 6 13 DIA-6 HOLES
relay circuit.
R
E ON E
4 E E OFF 2E-RY
606

15

30 COS T1
METAL COVER T6 T7 T8 T3 VMC
474

START AUS
INTERLOCK
1

100-110VAC
200-220VAC
9 7 5 3 CTD
346

T5
11 1 P U
INDICATOR 10 8 6 4 2 N V
63 5
200

COUNTER (OPTION)
170

DU D 52CC 52CC
12 52TC
CONTROL TRIPPING HOLES 6
CONNECTOR (DIA 9) T15
2 4
4
13 500 13 24 146 23 T11 T16 T17 T18 T13
T
526 193 VMC : Vacuum contactor
52CC: Closing coil
MOUNTING HOLES 215 52TC: Trip coil
(14 DIA-4 HOLES) DU : Drive unit
4 : Control relay
CTD : Capacitor trip device
Fig. 14 Types CV-10HA(L)-1/CV-10HB(L)-1
Fig. 17 Latched type operating circuit (Capacitor trip)

11 12
OPERATING COIL EXCITATION CAPACITOR APPLICATION
The current limiting fuses shall be combined for capacitor switching application.
Non-Latched The series reactor shall be connected, especially back-to-back application.
Mainly applied to frequent switching operation such as motor.
(Continuous Excitation) Service life of capacitor switching
T h e s w i t c h i n g , o p e n i n g a n d c l o s i n g , o f c a p a c i t o r p r o d u c e s s e v e r e c o n d i t i o n f o r c o n t a c t o r, s u c h a s
Mainly applied to non-frequent switching operation and/or to the important load which h i g h frequency inrush current and interpole recovery voltage higher than twice of normal voltage.
Latched
(Instantaneous Excitation) require to be contact closed even by power loss. The criteria of maximum number of capacitor switching are shown in the figure below. The vacuum interrupters should
be replaced when the number of switching operations reached to point shown in figure.

PROTECTION COORDINATION
The protection coordination with upper/lower stream relay shall be evaluated by considering total system and load
characteristics.
100
The single-phase protection shall be performed which may be occurred by power fuses.
(Apply 2E-relay or fuse blown detection which is provided on combination unit as standard.)

Switching Life
50
APPLICATION GUIDE TO SURGE

(Thousand Op.)
40
No surge protection is required except for special application, however the insulation coordination shall be evaluated by following
table. 30

20
Load Protection Notice

The surge suppressor shall be installed for machine rated at


55kW or below, and/or be subject to inching operation. 10
The surge suppressor shall be installed between starting
Rotating Machine Not required contactor and autotransformer for machine started by
autotransformer. 20 30 50 100 200 300 400
The suppressor shall be installed for machine which has Sw itchi n g Curre nt ( A)
inferior insulation.
Fig. 18 Capacitor Switching Life (with 6% reactor)
The surge arrester shall be installed for transformer rated at
Dry-type Transformer Not required
150kVA or below and exciting inrush is interrupted.

The installation of suppressor and insulation coordination shall


Oil-immersed Transformer Not required be evaluated when the low surge level apparatus are connected Ordering Information
on secondary circuit of transformer.
Non-Latched Type Vacuum Contactor Latched Type Vacuum Contactor
Capacitor Not required Refer to the clause for capacitor application. 1. Type-Form CV- 1. Type-Form CV-
2. Quantity Set(s) 2. Quantity Set(s)
The surge suppressor is composed of capacitor and series resistor, and is one of the most excellent protection mediums. The 3. Ratings
3. Ratings
device features suppression as well as a decrease of surge generation. Particularly being free from limitation on the number Voltage(Ur) kV
of operating times, this device is suitable for protecting motors and transformer required performing frequent operations. Voltage(Ur) kV
Current (Ie) A
The surge arrester has no effect of suppressing the surge generation, this suppresses overvoltage to within a fixed level. Current (Ie) A
Short-circuit Making &
Short-circuit Making &
Breaking Current kA
CONTROL TRANSFORMER Breaking Current kA 4. Operating voltage
The contactor can be operated with following burden of control transformer. 4. Operating voltage VDC or AC Closing VDC or AC
Type Form (Contactor) Control Transformer VT 5. Options, Accessories, Spare Parts Tripping VDC
CV-6GA(L), 6HA(L) 400VA or more 6. Special Operating Condition 5. Options, Accessories, Spare Parts
CV-6KA(L)1 600VA or more 100VA 10P10 6. Special Operating Condition
CV-10HA(L), 10HB(L) 500VA or more

13 14
OPERATING COIL EXCITATION CAPACITOR APPLICATION
The current limiting fuses shall be combined for capacitor switching application.
Non-Latched The series reactor shall be connected, especially back-to-back application.
Mainly applied to frequent switching operation such as motor.
(Continuous Excitation) Service life of capacitor switching
T h e s w i t c h i n g , o p e n i n g a n d c l o s i n g , o f c a p a c i t o r p r o d u c e s s e v e r e c o n d i t i o n f o r c o n t a c t o r, s u c h a s
Mainly applied to non-frequent switching operation and/or to the important load which h i g h frequency inrush current and interpole recovery voltage higher than twice of normal voltage.
Latched
(Instantaneous Excitation) require to be contact closed even by power loss. The criteria of maximum number of capacitor switching are shown in the figure below. The vacuum interrupters should
be replaced when the number of switching operations reached to point shown in figure.

PROTECTION COORDINATION
The protection coordination with upper/lower stream relay shall be evaluated by considering total system and load
characteristics.
100
The single-phase protection shall be performed which may be occurred by power fuses.
(Apply 2E-relay or fuse blown detection which is provided on combination unit as standard.)

Switching Life
50
APPLICATION GUIDE TO SURGE

(Thousand Op.)
40
No surge protection is required except for special application, however the insulation coordination shall be evaluated by following
table. 30

20
Load Protection Notice

The surge suppressor shall be installed for machine rated at


55kW or below, and/or be subject to inching operation. 10
The surge suppressor shall be installed between starting
Rotating Machine Not required contactor and autotransformer for machine started by
autotransformer. 20 30 50 100 200 300 400
The suppressor shall be installed for machine which has Sw itchi n g Curre nt ( A)
inferior insulation.
Fig. 18 Capacitor Switching Life (with 6% reactor)
The surge arrester shall be installed for transformer rated at
Dry-type Transformer Not required
150kVA or below and exciting inrush is interrupted.

The installation of suppressor and insulation coordination shall


Oil-immersed Transformer Not required be evaluated when the low surge level apparatus are connected Ordering Information
on secondary circuit of transformer.
Non-Latched Type Vacuum Contactor Latched Type Vacuum Contactor
Capacitor Not required Refer to the clause for capacitor application. 1. Type-Form CV- 1. Type-Form CV-
2. Quantity Set(s) 2. Quantity Set(s)
The surge suppressor is composed of capacitor and series resistor, and is one of the most excellent protection mediums. The 3. Ratings
3. Ratings
device features suppression as well as a decrease of surge generation. Particularly being free from limitation on the number Voltage(Ur) kV
of operating times, this device is suitable for protecting motors and transformer required performing frequent operations. Voltage(Ur) kV
Current (Ie) A
The surge arrester has no effect of suppressing the surge generation, this suppresses overvoltage to within a fixed level. Current (Ie) A
Short-circuit Making &
Short-circuit Making &
Breaking Current kA
CONTROL TRANSFORMER Breaking Current kA 4. Operating voltage
The contactor can be operated with following burden of control transformer. 4. Operating voltage VDC or AC Closing VDC or AC
Type Form (Contactor) Control Transformer VT 5. Options, Accessories, Spare Parts Tripping VDC
CV-6GA(L), 6HA(L) 400VA or more 6. Special Operating Condition 5. Options, Accessories, Spare Parts
CV-6KA(L)1 600VA or more 100VA 10P10 6. Special Operating Condition
CV-10HA(L), 10HB(L) 500VA or more

13 14
Safety Cautions
Read the entire “Instruction Manual” carefully for important information about safety, handling,
installation, operation, maintenance, and parts replacements.
This equipment is designed and built in accordance with applicable safety standard in effect on
the date of manufacture. Unauthorized modifications will void warranty and can result in severe
injury, death and property damage. Do not make any modifications to the equipment.
Only qualified persons are to install, operate or service this equipment according to all applicable
codes and established safety practices.
Use only genuine Toshiba replacement parts and accessories. Improper components could cause
the equipment malfunction.
Do not install this equipment in areas where unusual service conditions exist. Using this
equipment in other than usual service conditions can result in equipment failure.
Do not exceed the ratings specified on the equipment nameplate or system accessories.
Underrated equipment can fail during operation causing fire, explosion, severe injury, death, and
property damage.

CV-6GAL/6HAL
7.2kV-200/400A-6.3kA

TRANSMISSION DISTRIBUTION & INDUSTRIAL SERVICES COMPANY


1-1, SHIBAURA 1-CHOME, MINATO-KU, TOKYO 105-8001, JAPAN
PHONE +81-3-3457-4898 FAX +81-3-5444-9169

http://www3.toshiba.co.jp/sic/english/swgr/products.htm

The data given in this catalog are subject to change without notice.

KSP-E2412 AD 4 Printed in Japan


2008-12 (1.5)

You might also like