You are on page 1of 16

EPC ISBL AND OSBL FOR THE

RDMP PROJECT RU V
BALIKPAPAN
Doc. No. : 26071-100-V1A-EWU0-00007 Rev. No. : 00A
Technical Data and Catalogue
Job No. : 26071 Page :1/1

General Comment
Please revise header form as per attached file.

Technical Data and Catalogue

PROJECT : Engineering, Procurement and Construction (EPC) Inside


Battery Limits (ISBL) and Outside Battery Limits (OSBL) for
the Refinery Development Master Plan (RDMP) Project
RU V Balikpapan
LOCATION : Refinery Unit V Balikpapan, East Kalimantan,Indonesia
OWNER : PT PERTAMINA (Persero)
PO NO. : 26071-100-POA-EWU0-00001

All items in BOQ to be included.


(MV/LV Splicing kit, Tape accessories for
Termination kit and etc..)

2021 02 01

D.H.Kang J.J.Park

00A 17 JUL 20 ISSUED FOR APPROVAL K.H.YANG G.S.GO S.J.PARK

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED

Tyco Electronics Raychem Korea Ltd.


COLD SHRINK
TERMINATION (CSTI/CSTO)
For Polymeric Insulated Cables
up to 42 kV

ENERGY /// COLD SHRINK TERMINATION (CSTI/CSTO)


COLD SHRINK TERMINATION (CSTI/CSTO)
For Polymeric Insulated Cables up to 42 kV

Raychem terminations CSTI/O cold shrink


terminations are made from a high performance,
liquid silicone material which is specially formulated
for excellent tracking and split resistance. The
extra-long, silicone stress cone is integrated within
the termination which ensures correct positioning.
Moisture sealing at the lug is integrated into the
termination body, eliminating the need for additional
sealing tapes.
They offer a reliable, fast and easy-to-install system to
ensure trouble free service and maintain high network
reliability. All key components are pre-expanded
on one holdout system, allowing neat installation in
compact environment on the prepared cable.
Raychem terminations CSTI/O are designed to cover
a wide range of applications and to accommodate
the variety of cable and conductor types used in the
networks. Range-taking, mechanical lugs ensuring
reliable installation and service can be supplied with
the kit.

Product Features Benefits

• Easy to install spiral holdout • Pre-expanded termination body with integrated


stress control deflector and sealing mastic
• Integrated sealing mastic
• Single piece silicone termination body with optimal
• Outstanding weathering, UV and Ozone Resistance
mechanical expansion ratio allows a wide application
• Chemically resistant range
• Resistant to fungi • The extra-long silicone stress cone is integrated with
• Excellent electrical properties, including good the termination and reduces positioning
tracking resistance and high dielectric strength • Moisture sealing at the lug is integrated
• Electrical stress control of the screen cut area using • Well-known and easy-to-install holdout system, rip
integrated conductive geometrical stress cones cord pulling direction towards the lug not the bottom
• Hydrophobic (water-repellent) of the termination

• Non-flammable • Easy to install in tight switchgear compartments

• Self-extinguishing • Accommodates mechanical shear bolt lug and


compression lug
• Retains performance over wide temperature range
±45 to +150°C
• Excellent resistance to splitting and permanent set
• Mechanical shear bolt lug and compression lug to IEC
61238-1 can be supplied
• CENELEC HD 629.1.S2, requirements which include
IEC, BS, VDE and other international specifications,
IEEE-48
• Manufacturing site ISO 9001 & ISO 14001 qualified

ENERGY /// COLD SHRINK TERMINATION (CSTI/CSTO)


Item 15.1.1 ~ 15.1.5
COLD SHRINK TERMINATION (CSTI/CSTO)
For Polymeric Insulated Cables up to 42 kV

Mechanical shear bolt connectors

Raychem terminations CSTI/O can be provided with


TE BLMT mechanical shear bolt lugs to ensure a
reliable connection for different conductor materials,
shapes and types used in today’s network. The pre-
set shear torque of the bolts ensures that the correct
contact pressure is always achieved. The specially
designed contact surface on the inside of the lug
breaks up any oxide layer and ensures reliable service
over the entire service life of the termination. Different
sizes of mechanical lugs with wide application ranges
are available. They have been tested in accordance
with IEC-61238-1 class A.
The installation shear-head bolts can be ruptured
manually by usage of ring spanner and or facilitated
by the usage of a cordless impact wrench supplied
(IT-1000-023).

Pre-expanded silicone termination body

The silicone termination body is delivered in a pre-


expanded condition on a spiral holdout system.
Silicone materials with excellent mechanical
properties allow high expansion forces and therefore
guarantee a wide application range. Integrated stress
control deflector and sealing mastic on the top end
of the termination provide exceptional electrical
performance. The termination body can be easily
removed from the spiral holdout with low release
forces, particularly designed for termination
applications.

Electrical stress control

Electrical stress control deflector is fully integrated


within the silicone termination body. Conductive cone
with an exactly defined geometrical design over the
screen cut area provide excellent electrical stress
control.

Technical data
VOLTAGE CLASS (kV) 6.35/11(12) 8.7/15(17.5) 12.7/22(24) 19/33(36) 20.8/36(42)
Cable Insulation Diameter (mm) 13.7 - 40.0 15.7 - 50.0 17.9 - 52.0 24.5 - 58.8 24.5 - 60.8
Cross Section Range (mm2) 25 - 630 25 - 630 25 - 630 50 - 1000 50 - 1000
Max System Voltage Um (kV) 12 17.5 24 36 42
Basic Impulse Level (kV) 95 95 125 195 200
Partial Discharge at 2 U0 (pC) <2 <2 <2 <2 <2
AC Voltage Withstand, 5 min (kV) 28.5 39 57 86 94
DC Voltage Withstand, 15 min (kV) 38 52 76 114 114

PAGE 3
COLD SHRINK TERMINATION (CSTI/CSTO)
For Polymeric Insulated Cables up to 42 kV

ORDERING INFORMATION
VOLTAGE CLASS KIT APPLICATION DIAMETER OVER DIAMETER OVER DIAMETER OVER
DESCRIPTION RANGE INSULATION MIN INSULATION MAX SHEATH MAX
6.35/11(12)kV (mm2) (mm) (mm) (mm)
Indoor CSTI-3122-ML-1-13 25 - 95 13.7 20.8 22
CSTI-3132-ML-4-13 95 - 240 20.8 28.4 34
CSTI-3142-ML-6-17 300 - 400 28.4 33.6 50
CSTI-3152-ML-7-17 500 - 630 34.0 40.0 58
Outdoor CSTO-3122-ML-1-13 25 - 95 13.7 20.8 22
CSTO-3132-ML-4-13 95 - 240 20.8 28.4 34
CSTO-3142-ML-6-17 300 - 400 28.4 33.6 50
CSTO-3152-ML-7-17 500 - 630 34.0 40.0 58
8.7/15(17.5)kV (mm2) (mm) (mm) (mm)
Indoor CSTI-4122 25 - 95 15.7 22.8 22
CSTI-4132 95 - 240 20.7 30.4 34
CSTI-4142 300 - 400 29.9 35.6 50
CSTI-4152 500 - 630 35.9 41.9 58
Outdoor CSTO-4122 25 - 95 15.7 22.8 22
CSTO-4132 95 - 240 20.7 30.4 34
CSTO-4142 300 - 400 29.9 35.6 50
CSTO-4152 500 - 630 35.9 41.9 58
12.7/22(24)kV (mm2) (mm) (mm) (mm)
Indoor CSTI-5122-ML-1-13 25 - 95 17.9 25.0 34
CSTI-5132-ML-4-13 95 - 240 25.0 32.0 50
CSTI-5142-ML-6-17 300 - 400 32.6 37.8 58
CSTI-5152-ML-7-17 500 - 630 42.6 49.2 58
Outdoor CSTO-5122-ML-1-13 25 - 95 17.9 25.0 34
CSTO-5132-ML-4-13 95 - 240 25.0 32.0 50
CSTO-5142-ML-6-17 300 - 400 32.6 37.8 58
CSTO-5152-ML-7-17 500 - 630 42.6 49.2 58
19/33(36)kV (mm2) (mm) (mm) (mm)
Indoor CSTI-6122-ML-1-13 50 - 70 24.5 28.4 42
CSTI-6132-ML-4-13 95 - 150 27.8 33.5 46
CSTI-6142-ML-6-17 185 - 400 32.4 42.8 56
CSTI-6152-ML-7-17 500 - 630 42.6 49.2 63
CSTI-6162-ML-8-21 800 - 1000 49.2 58.8 75
Outdoor CSTO-6122-ML-1-13 50 - 70 24.5 28.4 42
CSTO-6132-ML-4-13 95 - 150 27.8 33.5 46
CSTO-6142-ML-6-17 185 - 400 32.4 42.8 56
CSTO-6152-ML-7-17 500 - 630 42.6 49.2 63
CSTO-6162-ML-8-21 800 - 1000 49.2 58.8 75
20.8/36(42)kV (mm2) (mm) (mm) (mm)
Indoor CSTI-7122-ML-1-13 50 - 70 27.4 31.4 42
CSTI-7132-ML-4-13 95 - 150 29.9 36.5 48
CSTI-7142-ML-6-17 185 - 400 34.5 46.6 59
CSTI-7152-ML-7-17 500 - 630 44.8 51.2 65
CSTI-7162-ML-8-21 800 - 1000 50.6 60.8 73
Outdoor CSTO-7122-ML-1-13 50 - 70 27.4 31.4 42
CSTO-7132-ML-4-13 95 - 150 29.9 36.5 48
CSTO-7142-ML-6-17 185 - 400 34.5 46.6 59
CSTO-7152-ML-7-17 500 - 630 44.8 51.2 65
CSTO-7162-ML-8-21 800 - 1000 50.6 60.8 73

The application range given in the table is based on polymeric insulated cable according
to CENELEC HD 620 A2 (2004) standard with stranded circular conductors.
Trifurcation system available. Please contact your sales representative
FOR MORE INFORMATION:
Test reports
TE Technical Support Centers
The products are type tested in accordance with CENELEC HD629.1.S2:2009 and
CENELEC HD629.1.S3.draft:2015 specifications. USA: + 1 800 327 6996
Canada: + 1 (905) 475-6222
Mexico: + 52 (0) 55-1106-0800
te.com/energy Latin/S. America: + 54 (0) 11-4733-2200
©2017 TE Connectivity Ltd. family of companies. All Rights Reserved. EPP-2154-1/17 France: + 33 380 583 200
UK: + 44 0870 870 7500
Raychem, TE Connectivity and TE connectivity (logo) are trademarks. Other logos, product and/or company names might be Germany: + 49 896 089 903
trademarks of their respective owners. While TE has made every reasonable effort to ensure the accuracy of the information
in this brochure, TE does not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee Spain: + 34 916 630 400
that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information Italy: + 39 333 250 0915
contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information contained Benelux: + 32 16 351 731
herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose. The dimensions
in this catalog are for reference purposes only and are subject to change without notice. Specifications are subject to change Russia: +7 495-790 790 2-200
without notice. Consult TE for the latest dimensions and design specifications. China: + 86 (0) 400-820-6015

ENERGY /// COLD SHRINK TERMINATION (CSTI/CSTO)


CSTI/CSTO - COLD SHRINK TERMINATION
FOR POLYMERIC INSULATED CABLES UP TO 24 KV

KEY FEATURES TE Connectivity’s (TE) Raychem cold shrink terminations CSTI/O are
made from a high performance, liquid silicone material which is specially
• Pre-expanded termination
formulated for excellent tracking and split resistance.
body with integrated stress
control deflector and sealing They are easy to install thanks to the spiral holdout, have integrated
mastic sealing mastic and outstanding weathering, UV and ozone resistance.

• Easy-to-install holdout CSTI/O also present excellent electrical properties, including good
system, rib cord pulling tracking resistance and high dielectric strength. They retain performance
direction towards the lug not over wide temperature range –45 to +150°C.
the bottom of the termination

• Accommodates mechanical
shear bolt lug and
compression lug

• CENELEC HD 629.1.S3,
requirements which include
IEC, BS, VDE and other
international specifications

• ISO 9001, ISO 14001

Customers can count on consistent, high quality products, driven by TE’s


proven innovation and backed by our extraordinary customer support.

ENERGY /// CSTI/CSTO - COLD SHRINK TERMINATION FOR UP TO 42 KV


CSTI/CSTO - Cold Shrink Termination
for Polymeric Insulated Cables up to 24 kV

TECHNICAL DATA

Voltage class (kV) 6.35/11(12) 8.7/15(17.5) 12.7/22(24)


Cable insulation diameter (mm) 13.7 – 40.0 15.7 – 41.9 17.9 - 44.0
Cross section range (mm2) 25 – 630 25 – 630 35 – 630
Creepage distance indoor CSTI (mm) 465 - 495 465 - 495 465 - 495
Creepage distance outdoor CSTO (mm) 520 - 565 520 - 565 520 - 565
Installed length indoor CSTI (mm) 300 - 375 300 - 375 350 - 380
d
Installed length outdoor CSTO (mm) 355 -380 355 -380 355 -380
Installed diameter indoor CSTI (mm) 45 - 70 47 - 72 49 - 75
l Installed diameter outdoor CSTO (mm) 75 - 100 77 - 102 80 - 105
Number of sheds indoor CSTI (pC) 3 3 3
Number of sheds outdoor CSTO (pC) 4 4 4
Max system voltage Um (kV) 12 17.5 24
Basic impulse level (kV) 95 95 125
Partial discharge at 2 U0 (pC) <2 <2 <2
AC Voltage withstand, 5 min (kV) 28.5 39 57
Kit application range Designation
25 - 95 CSTI/CSTO 3122 4122 5122
95 - 240 CSTI/CSTO 3132 4132 5132
300 - 400 CSTI/CSTO 3142 4142 5142
500 - 630 CSTI/CSTO 3152 4152 5152

* based on the BLMT mechanical lugs


based on DIN VDE 0276 HD 620 A2 (2004)

Variations possible depending on cable dimensions and cable lug configuration.

Indoor Outdoor

FOR MORE INFORMATION:


TE Technical Support Centers
USA: + 1 800 327 6996
Canada: + 1 (905) 475-6222
Mexico: + 52 (0) 55-1106-0800
te.com/energy Latin/S. America: + 54 (0) 11-4733-2200
©2017 TE Connectivity Ltd. family of companies. All Rights Reserved. EPP-2203-1/17 France: + 33 380 583 200
UK: + 44 0870 870 7500
Raychem, TE Connectivity and TE connectivity (logo) are trademarks. Other logos, product and/or company names might be Germany: + 49 896 089 903
trademarks of their respective owners. While TE has made every reasonable effort to ensure the accuracy of the information
in this brochure, TE does not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee Spain: + 34 916 630 400
that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information Italy: + 39 333 250 0915
contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information contained Benelux: + 32 16 351 731
herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose. The dimensions
in this catalog are for reference purposes only and are subject to change without notice. Specifications are subject to change Russia: +7 495-790 790 2-200
without notice. Consult TE for the latest dimensions and design specifications. China: + 86 (0) 400-820-6015

ENERGY /// CSTI/CSTO - COLD SHRINK TERMINATION FOR UP TO 42 KV


CSTI/CSTO - COLD SHRINK TERMINATION
FOR POLYMERIC INSULATED CABLES UP TO 42 KV

KEY FEATURES TE Connectivity’s (TE) Raychem cold shrink terminations CSTI/O are
made from a high performance, liquid silicone material which is specially
• Pre-expanded termination
formulated for excellent tracking and split resistance.
body with integrated stress
control deflector and sealing They are easy to install thanks to the spiral holdout, have integrated
mastic sealing mastic and outstanding weathering, UV and ozone resistance.

• Easy-to-install holdout CSTI/O also present excellent electrical properties, including good
system, rib cord pulling tracking resistance and high dielectric strength. They retain performance
direction towards the lug not over wide temperature range –45 to +150°C.
the bottom of the termination

• Accommodates mechanical
shear bolt lug and
compression lug

• CENELEC HD 629.1.S3,
requirements which include
IEC, BS, VDE and other
international specifications

• ISO 9001, ISO 14001

Customers can count on consistent, high quality products, driven by TE’s


proven innovation and backed by our extraordinary customer support.

ENERGY /// CSTI/CSTO - COLD SHRINK TERMINATION FOR UP TO 42 KV


CSTI/CSTO - Cold Shrink Termination
for Polymeric Insulated Cables up to 42 kV

TECHNICAL DATA

Voltage class (kV) 19/33(36) 20.8/36(42)


Cable insulation diameter (mm) 24.5 – 53.4 24.5 – 53.4
Cross section range (mm2) 50 – 1000 50 – 1000
Creepage distance indoor CSTI (mm) 738 - 788 738 - 788
d Creepage distance outdoor CSTO (mm) 1138 - 1186 1138 - 1186
Installed length indoor CSTI (mm) 600* 600*
Installed length outdoor CSTO (mm) 600* 600*
Installed diameter indoor CSTI (mm) 73 - 100 73 - 100
Installed diameter outdoor CSTO (mm) 135 - 165 135 - 165
Number of sheds indoor CSTI (pC) 7 7
l
Number of sheds outdoor CSTO (pC) 8 8
Max system voltage Um (kV) 36 42
Basic impulse level (kV) 195 200
Partial discharge at 2 U0 (pC) <2 <2
AC Voltage withstand, 5 min (kV) 86 94
Kit application range Designation
50 - 70 CSTI/CSTO 6122 7122
95 - 150 CSTI/CSTO 6132 7132
185 - 400 CSTI/CSTO 6142 7142
500 - 630 CSTI/CSTO 6152 7152
800 - 1000 CSTI/CSTO 6162 7162

* based on the BLMT mechanical lugs


based on DIN VDE 0276 HD 620 A2 (2004)

Variations possible depending on cable dimensions and cable lug configuration.

Indoor Outdoor

FOR MORE INFORMATION:


TE Technical Support Centers
USA: + 1 800 327 6996
Canada: + 1 (905) 475-6222
Mexico: + 52 (0) 55-1106-0800
te.com/energy Latin/S. America: + 54 (0) 11-4733-2200
©2017 TE Connectivity Ltd. family of companies. All Rights Reserved. EPP-2850-1/17 France: + 33 380 583 200
UK: + 44 0870 870 7500
Raychem, TE Connectivity and TE connectivity (logo) are trademarks. Other logos, product and/or company names might be Germany: + 49 896 089 903
trademarks of their respective owners. While TE has made every reasonable effort to ensure the accuracy of the information
in this brochure, TE does not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee Spain: + 34 916 630 400
that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information Italy: + 39 333 250 0915
contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information contained Benelux: + 32 16 351 731
herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose. The dimensions
in this catalog are for reference purposes only and are subject to change without notice. Specifications are subject to change Russia: +7 495-790 790 2-200
without notice. Consult TE for the latest dimensions and design specifications. China: + 86 (0) 400-820-6015

ENERGY /// CSTI/CSTO - COLD SHRINK TERMINATION FOR UP TO 42 KV


Item 15.1.1 ~ 15.1.5
Copper Compression Connectors
Two-Hole Lugs - Heavy Duty
For Copper Conductor, Conductor Range 25 - 630 mm2

RLHV 2E

Characteristics
● HV Lugs are specially designed to witstand high voltage applica onsupto 33 KV.
● Stud hole spacing of RHLV 2E Lugs are as per NEMA standards.
● 2 Hole heavy duty lugs are best suited in applica on where two bolts are needed to avoid rota on or movement of the lugs.
● Annealed material op mizes material and crimping proper es
● Flat contact surface and precise stud holes as per the Metric standard

Material
● High Couduc vity ETP-Copper

Order Information
Also available with Inspection Window, Add Sufix
A – Without inspection hole
B – With D type window
C – With Rectangular notch

Finish
● Electro Tin Plated

Dimensions (mm)
Nominal
Stud Palm Stud Centre Barrel Total
Cross Section Bolt Size Catalouge Code Hole Barrel ID Barrel OD
Hole Width Distance Length Length
mm2 Spacing
ØE ØA ØC D G H B J
M6 RLHV 25 -2E-6 6.5 44.5 6.8 10.0 16.0 15.0 17.0 37.0 123.0
M8 RLHV 25 -2E-8 8.4 44.5 6.8 10.0 16.0 15.0 17.0 37.0 123.0
25
M10 RLHV 25 -2E-10 10.5 44.5 6.8 10.0 16.0 15.0 17.0 37.0 123.0
M12 RLHV 25 -2E-12 13.0 44.5 6.8 10.0 18.0 15.0 17.0 37.0 123.0
M6 RLHV 35 -2E-6 6.5 44.5 8.2 12.5 18.0 15.0 17.0 37.0 124.0
M8 RLHV 35 -2E-8 8.4 44.5 8.2 12.5 18.0 15.0 17.0 37.0 124.0
M10 RLHV 35 -2E-10 10.5 44.5 8.2 12.5 18.0 15.0 17.0 37.0 124.0
35
M12 RLHV 35 -2E-12 13.0 44.5 8.2 12.5 18.0 15.0 17.0 37.0 124.0
M14 RLHV 35 -2E-14 14.5 44.5 8.2 12.5 18.0 15.0 17.0 37.0 124.0
M16 RLHV 35-2E-16 17.0 44.5 8.2 12.5 18.0 15.0 17.0 37.0 124.0

- Blank Palm
Copper Compression Connectors
Dimensions (mm)
Nominal
Stud Palm Stud Centre Barrel Total
Cross Section Bolt Size Catalouge Code Hole Barrel ID Barrel OD
Hole Width Distance Length Length
mm2 Spacing
ØE ØA ØC D G H B J
M6 RLHV 50 -2E-6 6.8 44.5 9.5 14.5 20.0 14.0 16.0 39.5 124.0
M8 RLHV 50 -2E-8 8.4 44.5 9.5 14.5 20.0 14.0 16.0 39.5 124.0
M10 RLHV 50 -2E-10 10.5 44.5 9.5 14.5 20.0 14.0 16.0 39.5 124.0
50
M12 RLHV 50 -2E-12 13.0 44.5 9.5 14.5 20.0 14.0 16.0 39.5 124.0
M14 RLHV 50 -2E-14 14.5 44.5 9.5 14.5 20.0 14.0 16.0 39.5 124.0
M16 RLHV 50 -2E-16 17.0 44.5 9.5 14.5 20.0 14.0 16.0 34.0 124.0
M6 RLHV 70 -2E-6 6.5 44.5 11.0 16.0 23.0 14.0 16.0 42.0 126.0
M8 RLHV 70 -2E-8 8.4 44.5 11.0 16.0 23.0 14.0 16.0 42.0 126.0
M10 RLHV 70 -2E-10 10.5 44.5 11.0 16.0 23.0 14.0 16.0 42.0 126.0
70
M12 RLHV 70 -2E-12 13.0 44.5 11.0 16.0 23.0 14.0 16.0 42.0 126.0
M14 RLHV 70 -2E-14 14.5 44.5 11.0 16.0 23.0 14.0 16.0 42.0 126.0
M16 RLHV 70-2E 16 17.0 44.5 11.0 16.0 23.0 14.0 16.0 36.0 126.0
M8 RLHV 95 -2E-8 8.4 44.5 13.5 19.0 27.0 16.0 18.0 46.0 138.5
M10 RLHV 95 -2E-10 10.5 44.5 13.5 19.0 27.0 16.0 18.0 46.0 138.5
M12 RLHV 95 -2E-12 13.0 44.5 13.5 19.0 27.0 16.0 18.0 46.0 138.5
95 M14 RLHV 95 -2E-14 14.5 44.5 13.5 19.0 27.0 16.0 18.0 46.0 138.5
M16 RLHV 95 -2E-16 17.0 44.5 13.5 19.0 27.0 16.0 18.0 46.0 138.5
M18 RLHV 95 -2E-18 19.0 44.5 13.5 19.0 27.0 16.0 18.0 46.0 138.5
- RLHV 95 -2E-BL - 44.5 13.5 19.0 27.0 16.0 18.0 46.0 138.5
M8 RLHV 120 -2E-8 8.4 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
M10 RLHV 120 -2E-10 10.5 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
M12 RLHV 120 -2E-12 13.0 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
M14 RLHV 120 -2E-14 14.5 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
120
M16 RLHV 120 -2E-16 17.0 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
M18 RLHV 120 -2E-18 19.0 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
M20 RLHV 120 -2E-20 21.0 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
- RLHV 120 -2E-BL - 44.5 15.0 20.5 29.0 16.0 18.0 52.0 144.5
M8 RLHV 150 -2E-8 8.4 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
M10 RLHV 150 -2E-10 10.5 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
M12 RLHV 150 -2E-12 13.0 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
M14 RLHV 150 -2E-14 14.5 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
150
M16 RLHV 150 -2E-16 17.0 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
M18 RLHV 150 -2E-18 19.0 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
M20 RLHV 150 -2E-20 21.0 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
- RLHV 150 -2E-BL - 44.5 16.5 23.0 32.0 14.0 16.0 56.5 144.5
M8 RLHV 185 -2E-8 8.4 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0
M10 RLHV 185 -2E-10 10.5 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0
M12 RLHV 185 -2E-12 13.0 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0
M14 RLHV 185 -2E-14 14.5 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0
185
M16 RLHV 185 -2E-16 17.0 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0
M18 RLHV 185 -2E-18 19.0 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0
M20 RLHV 185 -2E-20 21.0 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0
- RLHV 185 -2E-BL - 44.5 18.5 24.0 34.0 16.0 18.0 65.0 156.0

- Blank Palm
Copper Compression Connectors
Dimensions (mm)
Nominal
Stud Palm Stud Centre Barrel Total
Cross Section Bolt Size Catalouge Code Hole Barrel ID Barrel OD
Hole Width Distance Length Length
mm2 Spacing
ØE ØA ØC D G H B J
M8 RLHV 240 -2E-8 8.4 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
M10 RLHV 240 -2E-10 10.5 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
M12 RLHV 240 -2E-12 13.0 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
M14 RLHV 240 -2E-14 14.5 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
240
M16 RLHV 240 -2E-16 17.0 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
M18 RLHV 240 -2E-18 19.0 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
M20 RLHV 240 -2E-20 21.0 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
- RLHV 240 -2E-BL - 44.5 21.0 26.5 38.0 16.0 20.0 65.0 160.0
M8 RLHV 300 -2E-8 8.4 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
M10 RLHV 300 -2E-10 10.5 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
M12 RLHV 300 -2E-12 13.0 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
M14 RLHV 300 -2E-14 14.5 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
300
M16 RLHV 300 -2E-16 17.0 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
M18 RLHV 300 -2E-18 19.0 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
M20 RLHV 300 -2E-20 21.0 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
- RLHV 300 -2E-BL - 44.5 23.5 32.0 45.0 17.0 19.0 79.5 175.0
M10 RLHV 400 -2E-10 10.5 44.5 27.0 38.0 53.0 17.0 19.0 81.0 182.5
M12 RLHV 400 -2E-12 13.0 44.5 27.0 38.0 53.0 17.0 19.0 81.0 182.5
M14 RLHV 400 -2E-14 14.5 44.5 27.0 38.0 53.0 17.0 19.0 81.0 182.5
400 M16 RLHV 400 -2E-16 17.0 44.5 27.0 38.0 53.0 17.0 19.0 81.0 182.5
M18 RLHV 400 -2E-18 19.0 44.5 27.0 38.0 53.0 17.0 19.0 81.0 182.5
M20 RLHV 400 -2E-20 21.0 44.5 27.0 38.0 53.0 17.0 19.0 81.0 182.5
- RLHV 400 -2E-BL - 44.5 27.0 38.0 53.0 17.0 19.0 81.0 182.5
M10 RLHV 500 -2E-10 10.5 44.5 30.3 41.0 57.0 20.0 20.0 85.5 194.5
M12 RLHV 500 -2E-12 13.0 44.5 30.3 41.0 57.0 20.0 20.0 85.5 194.5
M14 RLHV 500 -2E-14 14.5 44.5 30.3 41.0 57.0 20.0 20.0 85.5 194.5
500 M16 RLHV 500 -2E-16 17.0 44.5 30.3 41.0 57.0 20.0 20.0 85.5 194.5
M18 RLHV 500 -2E-18 19.0 44.5 30.3 41.0 57.0 20.0 20.0 85.5 194.5
M20 RLHV 500 -2E-20 21.0 44.5 30.3 41.0 57.0 20.0 20.0 85.5 194.5
- RLHV 500 -2E-BL - 44.5 30.3 41.0 57.0 20.0 20.0 85.5 194.5
M10 RLHV 630 -2E-10 10.5 44.5 33.4 43.0 61.0 20.0 20.0 95.5 206.5
M12 RLHV 630 -2E-12 13.0 44.5 33.4 43.0 61.0 20.0 20.0 95.5 206.5
M14 RLHV 630 -2E-14 14.5 44.5 33.4 43.0 61.0 20.0 20.0 95.5 206.5
630 M16 RLHV 630 -2E-16 17.0 44.5 33.4 43.0 61.0 20.0 20.0 95.5 206.5
M18 RLHV 630 -2E-18 19.0 44.5 33.4 43.0 61.0 20.0 20.0 95.5 206.5
M20 RLHV 630 -2E-20 21.0 44.5 33.4 43.0 61.0 20.0 20.0 95.5 206.5
- RLHV 630 -2E-BL - 44.5 33.4 43.0 61.0 20.0 20.0 95.5 206.5

- Blank Palm
BOOTS

ELASTOMERIC INSULATING BUSHING BOOT


(RCAB)
FOR TERMINATIONS UP TO 17.5KV

KEY FEATURES TE Connectivity (TE)’s Raychem elastomeric insulating boots are


moulded parts which fit over the connection between the cable lug
•T
 ool free application
and the inline or right-angled equipment bushing to improve phase-to-
•H
 igh-performance insulation phase and phase-to-ground insulation. They are used in switchgear and
material transformer cable boxes, where the air clearances are insufficient for
normal operation, or to protect against flashover due to rodents or high
•E
 xcellent track and erosion humidity.
resistance
The non-tracking elastomeric housing has excellent erosion resistance,
•R
 emovable and reinstallable dielectric properties and environmental resistance, giving superb
performance in areas of high humidity and electrical stress.
•Q
 uick and easy installation
TE’s Raychem RCAB boots work in combination with all Raychem
• Unlimited shelf life termination product lines including both elastomeric and traditional heat
shrink technology.
•C
 onnection can be
energized directly after TE’s Raychem RCAB boots are quick and easy to install and do not
installation require any taping of the bushing or the termination. The boot can easily
be removed and reinstalled without the need for additional material or
• One product for inline and
tooling, allowing access to the bushing connection for test purposes.
right angle application

Customers can count on consistent, high quality products, driven by TE’s


proven innovation and backed by our extraordinary customer support.

ENERGY /// ELASTOMERIC INSULATING BUSHING BOOT 17.5 KV (RCAB)


Elastomeric Insulating Bushing Boot 17.5 kV (RCAB)

Technical information RCAB 4110 RCAB 4120


Maximum system voltage 17.5 kV 17.5 kV
Basic impulse level 95 kV 95 kV
Collar size No. 1 none
Bushing diameter 31 – 45 mm 46 – 70 mm
Bushing types: to DIN, CENELEC, ANSI – 400/630 A
Cable cross section 35 – 400 mm2 35 – 400 mm2
­

Ordering information

Each kit contains elastomeric insulating boots, collars (if required)


for three phases and installation instructions.

Related Product Information

Test report PPR 1336

The universal screw EXRM-1366 is supplied on request

FOR MORE INFORMATION:


TE Technical Support Centers
USA: + 1 800 327 6996
Canada: + 1 (905) 475-6222
Mexico: + 52 (0) 55-1106-0800
te.com/energy Latin/S. America: + 54 (0) 11-4733-2200
© 2017 TE Connectivity. All Rights Reserved. EPP-0788-0517 France: + 33 380 583 200
UK: + 44 0870 870 7500
RAycehm, TE, TE Connectivity and TE connectivity (logo) are trademarks. Other logos, product and/or company names Germany: + 49 89 6089 903
might be trademarks of their respective owners. While TE has made every reasonable effort to ensure the accuracy of the
information in this data sheet, TE does not guarantee that it is error-free, nor does TE make any other representation, warranty Spain: + 34 916 630 400
or guarantee that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the Italy: + 39 333 250 0915
information contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information Benelux: +32 16 508 695
contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose.
The dimensions in this data sheet are for reference purposes only and are subject to change without notice. Specifications are Russia: +7 495-790 790 2-200
subject to change without notice. Consult TE for the latest dimensions and design specifications. China: + 86 (0) 400-820-6015

ENERGY /// ELASTOMERIC INSULATING BUSHING BOOT 17.5 KV (RCAB)


IronwoodPremium_243201_Catalog-On-Demand.QXD 7/10/2013 7:50 PM Page 163

Item 15.2.6 ~ 15.2.7

3M™ Cold Shrink Splice Kits

3M™ Cold Shrink Connector Insulators 8420 and 8430 Series

Low Voltage Splices, 1000 V or less


3M™ Cold Shrink Connector Insulators 8420 and 8430 Series are designed using 3M’s proprietary cold shrink delivery system. Products are supplied
prestretched on a removable core for efficiency and ease of installation. Removal of the core (unwinding) after positioning the splice allows the product to
shrink into position forming a moisture-tight seal. The live memory action of the specially formulated EPDM material promotes a permanent, durable
environmental seal and insulation, with a typical operating temperature range from -40–194°F (-40–90°C).
The 8420 insulator meets requirements of ANSI C119-1 and Western Underground Guide 2.14 for secondary splices rated up to 1 kV.
Important: Use insulation jacket or connector O.D. for final ordering criteria.
* Mastic pads included for cable O.D. build-up. ** Kit contains adapters. *** These sizes are listed for availability only and are not designed to be used as
primary insulation. These tubes are for conduit sealing and breakouts. ****Maximum connector length: 5.625"
"Point of Purchase" packaging designated by "P". Example: 8423-6P

Voltage 1000 V or less


Number of Conductors Single Conductor
Low Voltage Single Conductor
Cable Type
Insulated Cable
Splice Type Cold Shrink
Primary electrical insulation for all
solid dielectric (rubber and plastic)
insulated wire and cable splicing rated
Applications to 1000 V. Good for repairs and envi-
ronmental sealing for communication
and other non-electrical applications.
RoHS 2011/65/EU Yes
Agency Approvals ANSI C1191.1

Min. Cable Dia. Max. Dia. Insulator Cable or Connector Max. Connector Relaxed Tube Case
Order No. UPC Typical Conductor Size
for Seal Covers Length Length Qty.
8423-6 054007-42146 6-4 AWG 0.31" (7,8 mm) 0.56" (14,2 mm) 2.0" (50,8 mm) 6.0" (152,4 mm) 10
(14-16 mm²)
8423-6P 054007-42864 6-4 AWG 0.31" (7,8 mm) 0.56" (14,2 mm) 2.0" (50,8 mm) 6.0" (152,4 mm) 10
(14-16 mm²)
8424-8** 054007-42390 10-1/0 AWG 0.10" (2,5 mm) 0.82" (20,9 mm) 3.0" (76,2 mm) 8.0" (203,2 mm) 10
(6-16 mm²)
8424-8P 054007-42865 10-1/0 AWG 0.10" (2,5 mm) 0.82" (20,9 mm) 3.0" (76,2 mm) 8.0" (203,2 mm) 10
(6-16 mm²)
8425-8 054007-42391 2-1/0 AWG 0.40" (10,1 mm) 0.82" (20,9 mm) 3.0" (76,2 mm) 8.0" (203,2 mm) 10
(35-50 mm²)
8425-8P 054007-42866 2-1/0 AWG 0.40" (10,1 mm) 0.82" (20,9 mm) 3.0" (76,2 mm) 8.0" (203,2 mm) 10
(35-50 mm²)
8426-9 054007-34457 2/0 AWG-250 kcmil 0.55" (13,9 mm) 1.18" (30,1 mm) 5.0" (127,0 mm) 9.0" (228,6 mm) 10
(70-125 mm²)
8426-9M* 054007-43436 2-4/0 AWG 0.40" (10,1 mm) 1.18" (30,1 mm) 5.0" (127,0 mm) 9.0" (228,6 mm) 10
(30-90 mm²)
8426-9P 054007-42867 2/0 AWG–250 kcmil 0.55" (13,9 mm) 1.18" (30,1 mm) 5.0" (127,0 mm) 9.0" (228,6 mm) 10
(70-125 mm²)
8426-11 054007-34458 2/0 AWG-250 kcmil 0.55" (13,9 mm) 1.18" (30,1 mm) 7.0" (177,8 mm) 11.0" (279,4 mm) 10
(70-125 mm²)
8427-6*** 054007-09915 - 0.67" (16,8 mm) 1.38" (35,1 mm) 2.0" (50,8 mm) 6.0" (152,4 mm) 10
8427-12 054007-34459 250-400 kcmil 0.67" (16,8 mm) 1.38" (35,1 mm) 8.0" (203,2 mm) 12.0" (304,8 mm) 10
(125-200 mm²)
8427-12P 054007-42868 250-400 kcmil 0.67" (16,8 mm) 1.38" (35,1 mm) 8.0" (203,2 mm) 12.0" (304,8 mm) 10
(125-200 mm²)
8427-16 054007-34460 250-400 kcmil 0.67" (16,8 mm) 1.38" (35,1 mm) 12.0" (304,8 mm) 16.0" (406,4 mm) 10
(125-200 mm²)
8428-6*** 054007-09916 - 0.95" (24,1 mm) 1.94" (49,2 mm) 2.0" (50,8 mm) 6.0" (152,4 mm) 10

PHONE: 800-245-3573 www.3M.com/Electrical 163


IronwoodPremium_243201_Catalog-On-Demand.QXD 7/10/2013 7:50 PM Page 164

3M™ Cold Shrink Splice Kits

3M™ Cold Shrink Connector Insulators 8420 and 8430 Series (continued)
Min. Cable Dia. Max. Dia. Insulator Cable or Connector Max. Connector Relaxed Tube Case
Order No. UPC Typical Conductor Size
for Seal Covers Length Length Qty.
8428-6M 051128-53828 450-800 kcmil 0.95” (24,1 mm) 1.94” (49,2 mm) 2.0” (50,8 mm) 6.0” (152,4 mm) 50
(240-400 mm²)
8428-8 051128-53711 500-800 kcmil 0.95" (24,1 mm) 1.94" (49,2 mm) 3.0" (76,2 mm) 8.0" (203,2 mm) 25
(300-400 mm²)
8428-12 054007-09056 500-800 kcmil 0.95" (24,1 mm) 1.94" (49,2 mm) 8.0" (203,2 mm) 12.0" (304,8 mm) 10
(300-400 mm²)
8428-12M 054007-43746 500-800 kcmil 0.95" (24,1 mm) 1.94" (49,2 mm) 8.0" (203,2 mm) 12.0" (304,8 mm) 10
(300-400 mm²)
8428-12P 054007-42869 500-800 kcmil 0.95" (24,1 mm) 1.94" (49,2 mm) 8.0" (203,2 mm) 12.0" (304,8 mm) 10
(300-400 mm²)
8428-18 054007-34461 500-800 kcmil 0.95" (24,1 mm) 1.94" (49,2 mm) 14.0" (355,6 mm) 18.0" (457,2 mm) 10
(300-400 mm²)
8429-6*** 054007-09917 - 1.27" (32,2 mm) 2.67" (67,8 mm) 2.0" (50,8 mm) 6.0" (152,4 mm) 10
8429-9**** 054007-09931 900-1000 kcmil 1.27" (32,2 mm) 2.67" (67,8 mm) 5.0" (127,0 mm) 9.0" (228,6 mm) 10
(500 mm²)
8429-9M 054007-42018 900-1000 kcmil 1.27” (32,2 mm) 2.67” (67,8 mm) 5.0” (127,0 mm) 9.0” (228,6 mm) 10
(500 mm²)
8429-12 054007-42389 900-1000 kcmil 1.27" (32,2 mm) 2.67" (67,8 mm) 8.0" (203,2 mm) 12.0" (304,8 mm) 10
(500 mm²)
8429-15 054007-44198 900-1000 kcmil 1.27" (32,2 mm) 2.67" (67,8 mm) 11.0" (279,4 mm) 15.0" (381,0 mm) 10
(500 mm²)
8429-18 054007-34462 900-1000 kcmil 1.27" (32,2 mm) 2.67" (67,8 mm) 14.0" (355,6 mm) 18.0" (457,2 mm) 10
(500 mm²)
8430-9*** 054007-42147 1250-2000 kcmil 1.68" (42,6 mm) 3.69" (93,7 mm) 5.0" (127,0 mm) 9.0" (228,6 mm) 10
8430-18 054007-42388 1250-2000 kcmil 1.68" (42,6 mm) 3.69" (93,7 mm) 14.0" (355,6 mm) 18.0" (457,2 mm) 10
Low Voltage Splices, 1000 V or less