Config 10 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
within the same colour dashed line. dimming from window row.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 11 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
within the same colour dashed line. dimming from window row.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 12 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
within the same colour dashed line. dimming from window row.

Switches and dims the whiteboard Upon exiting the space any luminaires
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 13 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

CH1 CH5 CH4


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
within the same colour dashed line. dimming from window row.

Switches and dims the whiteboard Upon exiting the space any luminaires
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 14 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
within the same colour dashed line. dimming from window row.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 15 – Classroom with luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Switch operates luminaires within the Luminaires daylight link – graduated Dimmable Luminaires
same colour dashed line. dimming from window row.
Main White- Emergency
Switches and dims the whiteboard Upon exiting the space any luminaires Switch board Lighting
luminaires independently within left on will switch off after an adjustable Switch Test
the same colour dashed line. time out period.
Config 16 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Detector/scene plate inputs


Main Switch Whiteboard Switch
Whiteboard

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Switch operates luminaires within the Luminaires daylight link – graduated Dimmable Luminaires
same colour dashed line. dimming from window row.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 17 – Classroom with luminaires working in absence mode. Whiteboard on channel 5.

Detector/scene plate inputs


Main Switch Whiteboard Switch
Whiteboard

CH1 CH5 CH4


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Switch operates luminaires within the Luminaires daylight link – graduated Dimmable Luminaires
same colour dashed line. dimming from window row.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 18 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – window row Dimmable Luminaires
within the same colour dashed line. only dimmable
SW1 SW2 SW3 Whiteboard Emergency
Switches and dims the whiteboard Switch Lighting
Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 19 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – window row Dimmable Luminaires
within the same colour dashed line. only dimmable
SW1 SW2 SW3 Whiteboard Emergency
Switch Lighting
Switches and dims the whiteboard Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 20 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires Luminaires daylight link – window row Dimmable Luminaires
within the same colour dashed line. only dimmable
SW1 SW2 SW3 Whiteboard Emergency
Switches and dims the whiteboard Switch Lighting
Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 21 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

CH1 CH5 CH4


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires Luminaires daylight link – window row Dimmable Luminaires
within the same colour dashed line. only dimmable
SW1 SW2 SW3 Whiteboard Emergency
Switches and dims the whiteboard Switch Lighting
Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 22 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Switch operates luminaires within the Luminaires daylight link – window row Dimmable Luminaires
same colour dashed line. only dimmable
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 23 – Classroom with luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Switch operates luminaires within the Luminaires daylight link – window row Dimmable Luminaires
same colour dashed line. only dimmable
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 24 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5

Detector/scene plate inputs


Main Switch Whiteboard Switch
Whiteboard

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Switch operates luminaires within the Luminaires daylight link – window row Dimmable Luminaires
same colour dashed line. only dimmable
Main White- Emergency
Switches and dims the whiteboard Upon exiting the space any luminaires Switch board Lighting
luminaires independently within left on will switch off after an adjustable Switch Test
the same colour dashed line. time out period.

Config 25 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Detector/scene plate inputs


Main Switch Whiteboard Switch
Whiteboard

CH1 CH5 CH4


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Switch operates luminaires within the Luminaires daylight link – window row Dimmable Luminaires
same colour dashed line. only dimmable
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 26 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – window row Daylight Switching
within the same colour dashed line. only daylight switching.
SW1 SW2 SW3 Whiteboard Emergency
Switches and dims the whiteboard Switch Lighting
Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 27 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – window row Daylight Switching
within the same colour dashed line. only daylight switching.
SW1 SW2 SW3 Whiteboard Emergency
Switch Lighting
Switches and dims the whiteboard Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 28 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires Luminaires daylight link – window row Daylight Switching
within the same colour dashed line. only daylight switching.
SW1 SW2 SW3 Whiteboard Emergency
Switch Lighting
Switches and dims the whiteboard Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 29 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

CH1 CH5 CH4


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires Luminaires daylight link – window row Daylight Switching
within the same colour dashed line. only daylight switching.
SW1 SW2 SW3 Whiteboard Emergency
Switch Lighting
Switches and dims the whiteboard Upon exiting the space any luminaires Test
luminaires independently within left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 30 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires within Luminaires daylight link – window row Daylight Switching
the same colour dashed line. only daylight switching.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 31 – Classroom with luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires within Luminaires daylight link – window row Daylight Switching
the same colour dashed line. only daylight switching.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 32 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Detector/scene plate inputs


Main Switch Whiteboard Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires within Luminaires daylight link – window row Daylight Switching
the same colour dashed line. only daylight switching.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 33 – Classroom with luminaires working in absence mode. Whiteboard on channels 5.

Detector/scene plate inputs


Main Switch Whiteboard Switch
Whiteboard

CH1 CH5 CH4


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1.
L

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Windows

Each switch operates luminaires within Luminaires daylight link – window row Daylight Switching
the same colour dashed line. only daylight switching.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 39 – Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1–3. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


SW1 SW2 SW3

GROUP 1 GROUP 2

SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH1 CH4 CH5
SC1 100%
SC2 OFF If using 2 PIRs instead of a microwave detector, the PIR
SC3 50% closest to the window will reference LUX and should be
SC4 25% GROUP 3 L
connected to Input 1.
Whiteboard

SC1 100% N
SC2 75% Switch inputs
SC3 50% E
SC4 25%
CH2 CH6
PL

GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Whiteboard Switch
Windows

SW1 SW2 SW3 White- Emergency


Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
board Lighting
within the same colour dashed line. dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard Upon exiting the space any luminaires
luminaires independently. left on will switch off after an adjustable
Scene 2 = Whiteboard fittings off. time out period.

Config 40 – classroom with 3 rows of fittings switched individually. Whiteboard row on channel 2. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


SW1 SW2 SW3

GROUP 1 GROUP 2

SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH1 CH4 CH5
SC1 100%
SC2 75% If using 2 PIRs instead of a microwave detector, the PIR
SC3 50% closest to the window will reference LUX and should be
SC4 25% GROUP 3 L
connected to Input 1.
Whiteboard

SC1 100% N
SC2 75% Switch inputs
SC3 50% E
SC4 25%
CH2 CH6
PL

GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Whiteboard Switch
Windows

SW1 SW2 SW3 White- Emergency


Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
board Lighting
within the same colour dashed line. dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard Upon exiting the space any luminaires
luminaires independently. left on will switch off after an adjustable
Scene 2 = Whiteboard fittings off. time out period.
Config 41 – Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1, 4 and 5. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

GROUP 1 GROUP 2

SC1 100%
SC2 OFF
SC3 50%
SC4 25%
CH1 CH4 CH5

If using 2 PIRs instead of a microwave detector, the PIR


closest to the window will reference LUX and should be
GROUP 3 L
connected to Input 1.

SC1 100% N
SC2 75% Switch inputs
SC3 50% E
SC4 25%
CH2 CH6
PL
SC1 100%
SC2 75%
SC3 50%
SC4 25% GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Windows

SW1 SW2 SW3 White- Emergency


Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
board Lighting
within the same colour dashed line. dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard
Upon exiting the space any luminaires
luminaires independently.
left on will switch off after an adjustable
Scene 2 = Whiteboard fittings off.
time out period.

Config 42 – Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 5. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Whiteboard Switch

GROUP 1 GROUP 2

SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH1 CH5 CH4
SC1 100%
SC2 75% If using 2 PIRs instead of a microwave detector, the PIR
SC3 50% closest to the window will reference LUX and should be
SC4 25% GROUP 3 L
connected to Input 1.

SC1 100% N
SC2 75% Switch inputs
SC3 50%
E
SC4 25%
CH2 CH6
PL

GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Windows

SW1 SW2 SW3 White- Emergency


Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
board Lighting
within the same colour dashed line. dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard
Upon exiting the space any luminaires
luminaires independently.
left on will switch off after an adjustable
Scene 2 = Whiteboard fittings off.
time out period.
Config 43 – Classroom with 3 rows switched together but with different dimming pre-set levels per row. Whiteboard channels 1–3.
Scene plate by teachers desk. Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


Main Switch

GROUP 1 GROUP 2

SC1 100%
SC2 OFF
SC3 50%
SC4 25%
CH1 CH4 CH5
SC1 100%
SC2 OFF If using 2 PIRs instead of a microwave detector, the PIR
SC3 50% closest to the window will reference LUX and should be
SC4 25% GROUP 3 L
connected to Input 1.
Whiteboard

SC1 100% Switch inputsN


SC2 75%
SC3 50% E
SC4 25%
CH2 CH6
PL

GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Whiteboard Switch
Windows

Main White- Emergency


Main Switch Luminaires daylight link – graduated Dimmable Luminaires
Switch board Lighting
dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard
luminaires independently. Upon exiting the space any luminaires
Scene 2 = Whiteboard fittings off. left on will switch off after an adjustable
time out period.

Config 44 – Classroom with all fittings switched together. Whiteboard on channels 2. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


Main Switch

GROUP 1 GROUP 2

SC1 100%
SC2 OFF
SC3 50%
SC4 25%
CH1 CH4 CH5
SC1 100%
SC2 75% If using 2 PIRs instead of a microwave detector, the PIR
SC3 50% closest to the window will reference LUX and should be
SC4 25% GROUP 3 L
connected to Input 1.
Whiteboard

SC1 100% Switch inputsN


SC2 75%
SC3 50% E
SC4 25%
CH2 CH6
PL

GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Whiteboard Switch
Windows

Main White- Emergency


Main Switch Luminaires daylight link – graduated Dimmable Luminaires
Switch board Lighting
dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard
luminaires independently. Upon exiting the space any luminaires
Scene 2 = Whiteboard fittings off. left on will switch off after an adjustable
time out period.
Config 45 – Classroom with all fittings switched together. Whiteboard on channels 1, 4 and 5. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


Main Switch Whiteboard Whiteboard Switch

GROUP 1 GROUP 2

SC1 100%
SC2 OFF
SC3 50%
SC4 25%
CH1 CH4 CH5

If using 2 PIRs instead of a microwave detector, the PIR


closest to the window will reference LUX and should be
GROUP 3 L
connected to Input 1.

SC1 100%
SC2 75%
Switch inputsN
SC3 50%
E
SC4 25%
CH2 CH6
PL
SC1 100%
SC2 75%
SC3 50%
SC4 25% GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Windows

Main White- Emergency


Main Switch Luminaires daylight link – graduated Dimmable Luminaires
Switch board Lighting
dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard
luminaires independently. Upon exiting the space any luminaires
Scene 2 = Whiteboard fittings off. left on will switch off after an adjustable
time out period.

Config 46 – Classroom with all fittings switched together. Whiteboard on channel 5. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


Main Switch Whiteboard Whiteboard Switch

GROUP 1 GROUP 2

SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH1 CH5 CH4
SC1 100%
SC2 75% If using 2 PIRs instead of a microwave detector, the PIR
SC3 50% closest to the window will reference LUX and should be
SC4 25% GROUP 3 L
connected to Input 1.

SC1 100%
SC2 75%
Switch inputsN
SC3 50%
E
SC4 25%
CH2 CH6
PL

GROUP 4
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH3 CH7

Windows

Main White- Emergency


Main Switch Luminaires daylight link – graduated Dimmable Luminaires
Switch board Lighting
dimming from window row, scene 1 only
Switch Test
Switches and dims the whiteboard
luminaires independently. Upon exiting the space any luminaires
Scene 2 = Whiteboard fittings off. left on will switch off after an adjustable
time out period.
Config 47 – Classroom with all fittings switched together. NO Whiteboard. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


Main Switch

GROUP 1
SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH1 CH5 CH4

If using 2 PIRs instead of a microwave detector, the PIR


closest to the window will reference LUX and should be
GROUP 2 connected to Input 1.

SC1 100% Switch inputs


SC2 50%
SC3 25% E
SC4 50%
CH2 CH6
PL

GROUP 3
SC1 100%
SC2 25%
SC3 25%
SC4 75%
CH3 CH7

Windows

Main Emergency
Main Switch Upon exiting the space any luminaires Switch Lighting
left on will switch off after an adjustable Test
Luminaires daylight link – graduated time out period.
dimming from window row, scene 1 only Dimmable Luminaires

Config 48 – Classroom with 3 rows of fittings switched individually. NO whiteboard. Scene plate by teachers desk.
Detector for LUX (scene 1 only) and absence.

Detector/scene plate inputs


SW1 SW2 SW3

GROUP 1

SC1 100%
SC2 75%
SC3 50%
SC4 25%
CH1 CH5 CH4

If using 2 PIRs instead of a microwave detector, the PIR


closest to the window will reference LUX and should be
GROUP 2 connected to Input 1.

SC1 100% Switch inputs


SC2 50%
SC3 25%
E
SC4 50%
CH2 CH6
PL

GROUP 3
SC1 100%
SC2 25%
SC3 25%
SC4 75%
CH3 CH7

Windows

SW1 SW2 SW3 Emergency


Each switch operates luminaires Upon exiting the space any luminaires
Lighting
within the same colour dashed line. left on will switch off after an adjustable
Test
time out period.
Luminaires daylight link – graduated
dimming from window row, scene Dimmable Luminaires
1 only
Config 51 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – graduated Dimmable Luminaires
within the same colour dashed line. dimming from window row.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 52 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Switch operates luminaires within the Luminaires daylight link – graduated Dimmable Luminaires
same colour dashed line. dimming from window row.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 53 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – window row Dimmable Luminaires
within the same colour dashed line. only dimmable.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 54 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Switch operates luminaires within the Luminaires daylight link – window row Dimmable Luminaires
same colour dashed line. only dimmable.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 55 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs


SW1 SW2 SW3

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Each switch operates luminaires Luminaires daylight link – window row Daylight Switching
within the same colour dashed line. only daylight switching.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 56 – Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs


Main Switch

CH1 CH4 CH5


If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH2 CH6 E

PL

CH3 CH7

Whiteboard Switch Windows

Switch operates luminaires within the Luminaires daylight link – window row Daylight Switching
same colour dashed line. only daylight switching.
Main White- Emergency
Switches and dims the whiteboard Switch board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 57 – Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently. .

Detector/scene plate inputs


SW1 SW2 SW3

CH1
If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L

Window
Whiteboard

Switch inputs N

CH5 CH2 E

PL

CH7 CH6 CH4 CH3

Whiteboard Switch Windows

Each switch operates luminaires Luminaires closest to the windows Dimmable Luminaires
within the same colour dashed line. daylight dim
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 58 – Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.

Detector/scene plate inputs


SW1 SW2 SW3

CH1
If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Window
Whiteboard

Switch inputs N

CH5 CH2 E

PL

CH7 CH6 CH4 CH3

Whiteboard Switch Windows

Each switch operates luminaires Luminaires closest to the windows Daylight Switching
within the same colour dashed line. daylight switch.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.
Config 59 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Switch

Window
CH7 CH1
If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L

Whiteboard
Switch inputs N

CH6 CH2 E

PL

CH5 CH4 CH3

Window
Windows

Each switch operates luminaires Luminaires closest to the windows Daylight Switching
within the same colour dashed line. daylight switch.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.

Config 60 – Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs


SW1 SW2 SW3 Whiteboard Switch
Window

CH7 CH1
If using 2 PIRs instead of a microwave detector, the PIR
closest to the window will reference LUX and should be
connected to Input 1. L
Whiteboard

Switch inputs N

CH6 CH2 E

PL

CH5 CH4 CH3


Window

Windows

Each switch operates luminaires Luminaires closest to the windows Dimmable Luminaires
within the same colour dashed line. daylight dim.
SW1 SW2 SW3 White- Emergency
Switches and dims the whiteboard board Lighting
Upon exiting the space any luminaires
luminaires independently within Switch Test
left on will switch off after an adjustable
the same colour dashed line. time out period.