DIgSILENT Print

You might also like

You are on page 1of 1

Transmission Example DIgSILENT Project:

PowerFactory
15.1.7 Date: 2/19/2021

Fault Locations with Feeders


Short-Circuit Calculation / Method : IEC 60909 3-Phase Short-Circuit / Max. Short-Circuit Currents
Asynchronous Motors Grid Identification Short-Circuit Duration
Always Considered Automatic Break Time 0.10 s
Fault Clearing Time (Ith) 1.00 s
Decaying Aperiodic Component (idc) Conductor Temperature c-Voltage Factor
Using Method B User Defined No User Defined No

Grid: Grid System Stage: Grid Annex: / 1


rtd.V. Voltage c- Sk" Ik" ip Ib Sb Ik Ith
[kV] [kV] [deg] Factor [MVA/MVA] [kA/kA] [deg] [kA/kA] [kA] [MVA] [kA] [kA]

S4_225kV
S4 BB 225.00 0.00 0.00 1.10 1086.84 MVA 2.79 kA -82.80 6.70 kA 2.68 1044.71 2.45 2.83
L_S2-S4_1 S2_225kV 248.32 MVA 0.64 kA 96.20 1.53 kA
L_S2-S4_2 S2_225kV 248.32 MVA 0.64 kA 96.20 1.53 kA
L_S3-S4_1 S3_225kV 170.72 MVA 0.44 kA 96.17 1.05 kA
L_S3-S4_2 S3_225kV 170.72 MVA 0.44 kA 96.17 1.05 kA
Tr_S4-S7_1 S7_90kV 124.67 MVA 0.32 kA 100.61 0.77 kA
Tr_S4-S7_2 S7_90kV 124.67 MVA 0.32 kA 100.61 0.77 kA
Rea_L_S2-S4_1 0.00 MVA 0.00 kA 0.00 0.00 kA
Rea_L_S2-S4_2 0.00 MVA 0.00 kA 0.00 0.00 kA
Rea_L_S3-S4_1 0.00 MVA 0.00 kA 0.00 0.00 kA
Rea_L_S3-S4_2 0.00 MVA 0.00 kA 0.00 0.00 kA

You might also like