ADAM-5017UH 8-ch Ultra High Speed Analog Input

Module

ADAM-5018 7-ch Thermocouple Input Module

ADAM-5018P 7-ch Thermocouple Input Module


with Independent Input Range

RoHS RoHS RoHS


ADAM-5017UH COMPLIANT
2002/95/EC
ADAM-5018 COMPLIANT
2002/95/EC
ADAM-5018P COMPLIANT
2002/95/EC

Specifications Specifications Specifications


General General General
ƒƒ Certification CE ƒƒ Certification CE, FM ƒƒ Certification CE, FCC class A
ƒƒ Connectors 1 x Plug-in screw terminal ƒƒ Connectors 1 x Plug-in screw terminal
(# 14 ~ 22 AWG) ƒƒ Connectors 1 x Plug-in screw terminal (# 14 ~ 22 AWG)
ƒƒ Enclosure ABS+PC (# 14 ~ 22 AWG) ƒƒ Enclosure ABS+PC
ƒƒ Power Consumption 2.2 W (max.) ƒƒ Enclosure ABS+PC ƒƒ Power Consumption 0.63 W (max.)
ƒƒ Power Consumption 0.63 W (max.)
Analog Input Thermocouple Input
ƒƒ Accuracy ±0.1% or better Thermocouple Input ƒƒ Accuracy Voltage mode: ±0.1% or
ƒƒ Bandwidth 200 kHz better
ƒƒ Channels 8 differential
ƒƒ Accuracy ±0.1% or better Current mode: ±0.2% or
ƒƒ Differential Non-linear ±1 LSB ƒƒ Bandwidth 13.1 Hz @ 50 Hz better
ƒƒ Input Impedance Voltage: 2 MΩ 15.72 Hz @ 60 Hz ƒƒ Bandwidth 13.1 Hz @ 50 Hz
Current: 120 Ω (Build-in) ƒƒ Channels 7 differential 15.72 Hz @ 60 Hz
ƒƒ Integral Non-linear ±1 LSB ƒƒ Channels 7 (differential, each channel
ƒƒ CMR @ 50/60 Hz 92 dB min
ƒƒ Input Range ±10 V, +0 ~ 10 V, can be configured with
0 ~ 20 mA, +4 ~ 20 mA ƒƒ Input Impedance 2 MΩ different range)
ƒƒ Low pass filter Configured by User ƒƒ lnput Range ±15 mV, ±50 mV, ±100 mV, ƒƒ CMR @ 50/60 Hz 92 dB min
ƒƒ Resolution 12-bit ±500 mV, ƒƒ Input Impedance 20 MΩ. (Build-in 120 Ω
ƒƒ Sampling Rate Depends on base unit ±1 V, ±2.5 V, ±20 mA Register for Current Input)
ADAM-5000/485 & 5000E: ƒƒ lnput Range and Types
100 Samples/sec max (Total): one ADAM-5017UH ƒƒ lnput Type mV, V, mA, thermocouple Thermocouple
installed ƒƒ Resolution 16-bit J 0 ~ 760°C
ADAM-5000/TCP & 5000L/TCP: ƒƒ Sampling Rate 10 samples/sec. (total) K 0 ~ 1,370°C
100 Samples/sec max (Total) :one ADAM-5017UH ƒƒ Span Drift ±25 PPM/ °C T -100 ~ 400°C
installed E 0 ~ 1,000°C
ADAM-5510 : ƒƒ Zero Drift ±6 μV/ °C R 500 ~ 1,750°C
200K Samples/sec max (Single Channel): one ADAM- ƒƒ T/C Type and Temperature Range S 500 ~ 1,750°C
5017UH installed J 0° ~ 760°C B 500 ~ 1,800°C
ADAM-5550 & ADAM-5560: K 0° ~ 1,370°C Current ±20 mA, 4 ~ 20 mA
1K Samples/sec max(single channel): one ADAM- T -100° ~ 400°C Voltage ±15 mV (0.2%), ±50 mV,
5017UH installed ±100 mV, ±500 mV
E 0° ~ 1,000°C
*Depending on the performance of client server or ±1 V, ±2.5 V
controller R 500° ~ 1,750°C ƒƒ Resolution 16-bit
ƒƒ Signal Input 200 kHz for both voltage S 500° ~ 1,750°C ƒƒ Sampling Rate 10 samples/sec. (total)
Bandwidth and current inputs B 500° ~ 1,800°C ƒƒ Span Drift ±25 PPM/°C
ƒƒ Zero Drift ±6 μV/°C
Protection Protection ƒƒ High Common Mode 200 VDC
ƒƒ Isolation Voltage 3,000 VDC ƒƒ Fault and Withstands overvoltage up
Note: Protection
Overvoltage to ±35 V
1) The voltage difference between any two pins must not Protection ƒƒ Fault and Withstands overvoltage up
exceed 15 V Overvoltage to ±35 V
ƒƒ Isolation Voltage 3,000 VDC Protection
2) Distinct range settings allowed on each channel
ƒƒ Isolation Voltage 3,000 VDC
Note: Not support ADAM-5510KW series
Ordering Information ƒƒ Filter function Yes
ƒƒ Built-in TVS/ESD Protection
Ordering Information ƒƒ ADAM-5018 7-ch Thermocouple Input Note: Not support ADAM-5510KW series
Module
ƒƒ ADAM-5017UH 8-ch Ultra High Speed
Analog Input Module ƒƒ ADAM-5018SK ADAM-5018 with CJC kit/
external
Ordering Information
ƒƒ ADAM-5018P 7-ch Thermo. Input Module
w/ Ind. Input Range

Programmable Automation Controllers


All product specifications are subject to change without notice Last updated : 28-Aug-2013
Mouser Electronics