Installation Instructions

Model ZIC-4A
Zone Indicating Card

Siemens Industry
Industry,, Inc.
P/N 315-033050-16 Building Technologies Di
echnologies vision
Division
CONTENTS

INTRODUCTION ............................................................................................... 3
Features............................................................................................................ 3
OPERATION ..................................................................................................... 4
Controls and Indicators ..................................................................................... 4
PRE-INSTALLATION ......................................................................................... 5
Output Zones ................................................................................................... 6
ZIC-4A Switch and Jumper Settings ................................................................. 7
Programming Options ...................................................................................... 7
WIRING ............................................................................................................ 8
Using Multiple Power Supplies ......................................................................... 9
INSTALLATION ............................................................................................... 10
ELECTRICAL RATINGS ................................................................................... 10
CONFIGURATIONS ........................................................................................ 11
Bell Follower ................................................................................................... 11
ZIC-4A Supervised Notification Appliance Wiring ........................................... 12
ZIC-4A Supervised Municipal Tie Wiring ......................................................... 13
ZIC-4A Leased Line Wiring ............................................................................. 13
ZIC-4A Releasing Service Wiring .................................................................... 14
ZIC-4A Releasing Service Wiring With PSC-12 Power Supply ......................... 15
ZIC-4A Bell Follower Circuit Wiring ................................................................. 16
ZIC-4A Two-Channel Audio Wiring................................................................... 17
ZIC-4A Single-Channel Audio Wiring ............................................................... 18
ZIC-4A Two-Channel Audio and Strobe Wiring ................................................ 19
ZIC-4A Single-Channel Audio and Strobe Wiring ............................................ 20
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
Releasing Logic .............................................................................................. 21
Installation Instructions
Model ZIC-4A
Zone Indicating Card
INTRODUCTION The Model ZIC-4A from Siemens Industry, Inc. is a zone
indicating card that provides notification appliance circuits
for the FireFinder-XLS/Desigo Fire Safety Modular/ ZIC-4A
Cerberus PRO Modular system. It has 4 outputs that can RESET

be configured for Class A or Class B and control of audible POWER


CARD FAIL
and visual notification appliances such as horns, speakers, CAN FAIL

bells, strobes etc. Its outputs can also be configured as HNET FAIL
GND FAULT
connection to Municipal Tie, Releasing Service per NFPA ZONE 1 ACTIVE
13 and 2001 or as a connection to a Leased Line remote TRBL
ZONE 2 ACTIVE
monitoring circuit. TRBL
ZONE 3 ACTIVE
Each zone can be configured independently for different TRBL
ZONE 4 ACTIVE
usages as programmed in the Zeus tool and can be TRBL
controlled automatically by program logic or manually
using the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo
Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular). During the initial power-up condition, each
zone on the ZIC-4A is configured as a steady NAC, Class
A configuration with 2A current limit. The ZIC-4A then
sends a message to the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3
(Cerberus PRO Modular) indicating that it is
unconfigured.

The ZIC-4A supports synchronized and non-synchronized


strobes. This selection is available in the Zeus tool under HUNDREDS

the detail properties for each ZIC-4A circuit. Synchroniza-


TENS
tion across multiple ZIC-4A cards is automatic as a part of
the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus ONES

PRO Modular operating characteristics. Refer to docu- HNET/CAN


ment P/N 315-096363 for a list of strobes that support
synchronization.

Features ZIC-4A features are as follows:

• Class A / Class B circuit configuration


• Zones can be configured independently
• Can have independent input source for each output Figure 1
• Zone input voltage supervision ZIC-4A Zone Indicating Card
• Zone output supervision
• Intelligent self-restoring power limiting
• Coded signal synchronization capability
• Card level Ground Fault detection
• Communicate H-Net protocol
• Uploadable firmware update
• Ability to pass through up to 3A per circuit
Siemens Industry
Industry,, Inc.
P/N 315-033050-15 Building Technologies Di
echnologies vision
Division
OPERATION The ZIC-4A contains four Class A circuits. Each circuit is rated at 3A at 24VDC and
has an input connected to the power source and an output where the NAC devices,
Municipal Tie, Releasing service and Leased Line remote monitoring device are
connected. The zone inputs are isolated from one another and are supervised for the
presence of power. This allows the use of different power sources with different
ground references. The zone output is supervised for open and short circuit condi-
tions while the zone is inactive and allows different combinations of output configura-
tions (Standard NAC, Releasing, etc.) per card. Each ZIC-4A card occupies any one
card slot in the CC-5 cardcage. The ZIC-4A also has the capability to detect ground
fault on its zone output as indicated by a diagnostic LED.

Controls and Indicators The front panel of the ZIC-4A contains one reset switch, thirteen LEDs, and three
HNET address switches as shown in Figure 1.

A reset switch is located on the top of the front panel. Pushing the reset switch
re-initializes the ZIC-4A operation.

The LEDs follow the reset switch and their functions are defined as follows:

POWER (Green) Normally ON. When illuminated, indi-


cates that power for the ZIC-4A is
applied to the card.

CARD FAIL (Yellow) Normally OFF. When illuminated, indi-


cates that the card microprocessor has
failed.

CAN FAIL (Yellow) Normally OFF. When illuminated, indicates


that the CAN communication with the
ZIC-4A has terminated and the card goes
into degrade mode (applicable only when
card resides in a CAN network). NOT
USED for FireFinder-XLS/Desigo Fire
Safety Modular/Cerberus PRO Modu-
lar applications.

HNET FAIL (Yellow) Normally OFF. When illuminated, indi-


cates that the HNET communication with
the ZIC-4A has terminated and the card
goes into degrade mode (applicable only
when card resides in the HNET network).

GND FAULT (Yellow) Normally OFF. When illuminated, indi-


cates that the ZIC-4A has detected either
a negative or positive ground fault on its
field wiring.

ZONE 1 ACTIVE (Red) Normally OFF. When illuminated, indi-


cates that Zone 1 is active.

TROUBLE (Yellow) Normally OFF. When illuminated, indi-


cates that the ZIC-4A has detected a
trouble on Zone 1 (open circuit or short
circuit).

ZONE 2 ACTIVE (Red) Normally OFF. When illuminated, indi-


cates that Zone 2 is active.
Siemens Industry, Inc. 4 P/N 315-033050-16
Building Technologies Division
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates that the ZIC-4A has detected a
trouble on Zone 2 (open circuit or short
circuit).

ZONE 3 ACTIVE (Red) Normally OFF. When illuminated, indi-


cates that Zone 3 is active.

TROUBLE (Yellow) Normally OFF. When illuminated, indi-


cates that the ZIC-4A has detected a
trouble on Zone 3 (open circuit or short
circuit).

ZONE 4 ACTIVE (Red) Normally OFF. When illuminated, indi-


cates that Zone 4 is active.

TROUBLE (Yellow) Normally OFF. When illuminated, indi-


cates that the ZIC-4A has detected a
trouble on Zone 4 (open circuit or short
circuit).

Three rotary dial switches at the bottom of the front panel are used to set the HNET
network address of the ZIC-4A.

PRE-INSTALLATION The following components must be set prior to inserting the card to the CC-5 (refer
to Figure 2):

S1 Primary Bell Follower Select Switch:


This switch selects Zone 1 as the Primary
Bell Follower. Toggle the S1 switch
towards the bottom of the board if Zone
1 is configured as a Primary Bell Follower; S3
RESET
SWITCH
otherwise toggle it to the top of the
board for normal operation (as shown in
Figure 2.)

S2, Leased Line Select Switches: These


switches select the zones configured for
Leased Line application. Toggle each
switch to the ON position if the corre- S2
1
sponding zone is configured as Leased 2
3
LEASED LINE
SELECT EXT 96 PIN DIN
Line. If the zone is not configured as a 4 S5 POWER PLUG CONNECTOR
On INPUT
Leased Line application, the correspond- POWER
SELECT
BP
ing zone switch must be set to the OFF POWER

position.
P4
6 5

During card failure, Zone 1 and Zone 2 4


2
3
1

outputs will activate if the FireFinder- S7


P3
XLS/Desigo Fire Safety Modular/Cerberus
6 5
4 3

NETWORK
PRO Modular Alarm bus is asserted,
2 1
S6 ADDRESS
ZONE INPUT
P2 SUPR ENABLE
Zone 3 outputs will activate the if the 6
4
5
3

FireFinder-XLS/Desigo Fire Safety S4


2 1

Modular/Cerberus PRO Modular Trouble P1


6 5
S1
Bus is asserted. You must configure each 4
2
3
1

zone to the proper Leased Line remote


monitoring circuit.

Silver line on S1 and jumpers P1 and


P4 indicates normal operation. Figure 2
ZIC-4A Switch Location
Siemens Industry, Inc. 5 P/N 315-033050-16
Building Technologies Division
S2-SW1: Set to ON if Zone 1 usage = Leased Line, Alarm Default only
S2-SW2: Set to ON if Zone 2 usage = Leased Line, Alarm Default only
S2-SW3: Set to ON if Zone 3 usage = Leased Line, Trouble Default only
S2-SW4: Set to OFF: Not Used

S3, Reset Switch: Momentarily Closed switch that when pressed will initiate a hard
reset to the ZIC-4A (similar to a cold boot).

S4, S6, S7 Network Address Switch: Set the three-digit HNET network address for
the ZIC-4A using the three rotary dial address switches located near the bottom of
the front panel. (Refer to Figure 1 for the location of the switches.) The address for
the ZIC-4A must be the same as the address selected for it in the Zeus Programming
Tool. To set the address, turn the pointers on each of the three dials to the numbers
for the selected address. For example, if the address is 123, set the pointer for the
HUNDREDS dial to “1”, set the pointer for the TENS dial to “2”, and set the pointer for
the ONES dial to “3”. The range of allowable addresses is from 001 to 251 (leading
zeros must be used).
HNET
S5 Input Power Select: This switch selects the source of voltage input to power the
ZIC-4A. BP Power indicates that the input is derived from the backplane of the CC-2/
CC-5 and EXT Power indicates that the input is derived from E5/E11 terminal of the
CC-2/CC-5, normally connected to non-power limited output of the PSC-12/PSX-12. It
is important to take into account the source of the voltage during battery calculations.

P1, P2, P3, P4 Shunt Headers, NAC Input Supervision Enable: These headers
select the NAC input zone supervision. If usage application is set for speaker func-
tion, place the shunt jumpers of the corresponding zone between 1—2 and between
5—6, otherwise place the shunt jumpers between 1—3 and 4—6.

P1 selects NAC input supervision for Zone 1 6 5


P2 selects NAC input supervision for Zone 2 4 3
P3 selects NAC input supervision for Zone 3
2 1
P4 selects NAC input supervision for Zone 4

Output Zones The ZIC-4A can be configured for the following usages:

Standard NAC Zone - Configurable as the following NAC zones:


Steady Strobe (Synchronized or Unsynchronized)
Zone Coding Temporal Code
Temporal 4, when used with Audible Base SBGA-34
March Time 120 March Time 60
March Time 30 Horn / Strobe
Releasing Zone - For release of FM-200, Halon, Pre-action & Deluge Sprinklers for
Canada or USA. Releasing zone requires an REL-EOL module for proper wire supervision.

Municipal Tie - Configurable as a supervised connection to municipal tie. Municipal


Tie usage application requires the LLM-1 interface module.

Leased Line - Configurable as a connection to a remote monitoring system. Leased


Line usage application requires LLM-1 interface module.

Bell Follower Primary - Configurable as a Bell Follower Primary (Zone 1 only).

Bell Follower Secondary - Configurable as a Bell Follower Secondary.


Siemens Industry, Inc. 6 P/N 315-033050-16
Building Technologies Division
ZIC-4A SWITCH AND JUMPER SETTINGS
ZONE USAGE S1 S2 HEADER POSITION
NAC Normal OFF 1 - 3, 4 - 6

Municipal Tie Normal OFF 1 - 3, 4 - 6

Releasing Zone Normal OFF 1 - 3, 4 - 6


Leased Line Normal SW (Zone) - ON 1 - 3, 4 - 6
Bell Follower - Primary
Off Normal OFF 1 - 3, 4 - 6
(Zone 1 Only)
Bell Follower - Secondary Normal OFF 1 - 3, 4 - 6
Zone Coding Normal OFF 1 - 3, 4 - 6
Coded Bells Normal OFF 1 - 3, 4 - 6
Speaker Zone Normal OFF 1 - 2, 5 - 6

Programming Options In order to perform its intended operation, the ZIC-4A card must be programmed
using the Zeus Programming Tool. The ZIC-4A card and its Out Ckt properties must
be set prior to normal operation.

In the Zeus Programming Tool, highlight the selected ZIC-4A card in the Physical
View and open the Detail View - Properties to modify and/or define the following
ZIC-4A card properties:

HNET Address This address must match the address


set in the ZIC-4A hardware.
Slot Location This defines the location where the
ZIC-4A is inserted in the CC-5.
Base Language Custom Message The message associated with the ZIC-4A
card.
Alternate Language Custom Message The message associated with the ZIC-4A
card in an alternate language.
ZIC Card 24V Power Source Select back plane or screw terminals.

Each ZIC-4A card is subdivided into four output circuits that can be programmed
independently of each other. In the Zeus Programming Tool, highlight the selected
ZIC-4A Output Ckt in the Physical View and open the Detail View - Properties to
modify and/or define the following ZIC-4A output circuit properties:

Device Address Shows preset address of ZIC card output.


Base Language Custom Message The message associated with the ZIC-4A
output circuit.
Alternate Language Custom Message The message associated with the ZIC-4A
output circuit in an alternate language.
Device Usage Signal
ZIC Circuit Usage Select usage required (see list).
NAC Steady Leased Line Alrm
NAC Coded Bell fol Primary
Horn Strobe Sync Bell fol Secondary
Sil. Horn Only (Horn Strobe) 25V Speaker
Strobe Sync 70V Speaker
Strobe UnSync 100V Speaker
Municipal Tie Releasing Zone

Degrade Mode Alarm Activation Determines if Degrade Alarm will activate


the ZIC-4A circuit when asserted.

Siemens Industry, Inc. 7 P/N 315-033050-16


Building Technologies Division
Silenceable Determines if the circuit is Silenceable or
Non-Silenceable.

Wiring Type Defines if the circuit is Class A or Class B


wiring type.

Total Current Drawn Select actual current load of output


circuit (see list).
0.0 Amp 1.5 Amp 3.0 Amp
0.5 Amp 2.0 Amp 3.5 Amp
1.0 Amp 2.5 Amp 4.0 Amp

If the zone usage is set in the Zeus Programming tool as “Sil Horn Only (Horn Strobe)”
,
the Silenceable Option is always set and is specific to the Horn of the Horn Strobe
device and the strobe is always Non-Silenceable.

Some restrictions apply to certain usage selections (for example, Municipal Tie can
only be configured as Class B wiring type) that are enforced by the Zeus tool during
Edit mode or Compile time.

Refer to the Zeus Quick Start Manual, P/N 315-033875, or the Zeus self-help index
for more information.

WIRING

Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)

All field wiring to the ZIC-4A is connected to


OUTPUTS SHOWN IN ACTIVE STATE
the terminal blocks of the CC-5 card cage
ZONE 1 ZONE 2
slot in which it is installed (Refer to Figure 3).
- - - -
+

CLASS A +

CLASS A +
CLASS A

CLASS A
To Connect External Wiring

1. Loosen the screw of the terminal


by turning it counterclockwise.
1 2 3 4 5 6 7 8
2. Insert the wire into the side of the
terminal block.
9 10 11 12 13 14 15 16

3. Tighten the screw of the terminal


+ CLASS A

CLASS A

+ CLASS A

CLASS A

block by turning it clockwise.


- - - -
+

The top terminals (1 through 8 and 9 ZONE 3 ZONE 4

through 16) are connected to the notifica- ONE SLOT OF CC-5


tion appliance devices such as bells, horns,
17 18 19 20 21 22 23 24
strobes, speakers, etc. Each zone has four
terminal connections: (+), Class A (+), (-),
Class A (-). These terminals are power
limited.
- - - -
+

The bottom terminals (17 through 24) are


ZONE 1 ZONE 2 ZONE 3 ZONE 4
connected to the input power source of the INPUT INPUT INPUT INPUT
NAC devices. Each zone has a (+) terminal
and (-) terminal. These terminals are not Figure 3
Wiring The 24VDC Power Lines To The
power limited. ZIC-4A Slot In The CC-5

Siemens Industry, Inc. 8 P/N 315-033050-16


Building Technologies Division
Care must be taken when installing the zone input and zone output field wiring to
prevent possible cross wiring.This can cause severe damage to the system
when powered up or when zone is activated.

The screw terminals can accommodate one 12-18 AWG or two 16-18 AWG.

If the total output of all 4 zones exceeds 12 amps, a single PSC-12 cannot be used to
supply the ZIC-4A. Refer to the PSC-12 Installation Instructions, P/N 315-033060 for
information when the total system load exceeds 12 amps.

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24 USING A SINGLE
- - - - PSC-12 TO

+
POWER A ZIC-4A

TO PSC-12, TB4 +

TO PSC-12, TB4 -

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24
USING A PSC-12 TO
- - - - POWER INPUTS 1-3
AND A PSX-12 TO
+

+
POWER INPUT 4

TO PSC-12, TB4 +

TO PSC-12, TB4 -

TO PSX-12, TB4 +

TO PSX-12, TB4 -

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24
USING A PSC-12 TO
- - - - POWER INPUTS 1-2
AND A PSX-12 TO
+

POWER INPUTS 3- 4

TO PSC-12, TB4 +

TO PSC-12, TB4 -

TO PSX-12, TB4 +

TO PSX-12, TB4 -
Figure 4
Using Multiple Power Supplies

Siemens Industry, Inc. 9 P/N 315-033050-16


Building Technologies Division
INSTALLATION The ZIC-4A plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin
DIN connectors and can occupy any slot in the card cage. (Refer to Figure 5.)

Insert the ZIC-4A card into the card guides right side up (lettering on the front panel
is legible).

Slide the card in until the card edge connectors contact the recep-
tacles on the motherboard.

Verify that the DIN connectors of the card and the card-cage aligned
properly. The card can only plug in one direction to the card cage, if it
does not align, DO NOT FORCE the card.

Place thumbs on the front panel adjacent to the captive screws and
gently apply even pressure on the card until the connectors seat in the
receptacles on the motherboard. Secure with the captive screws.

If the ZIC-4A is being powered from an external source, verify that E5 has the proper
Figure 5 voltage and proper terminal connections.
Installing The ZIC-4A

ELECTRICAL RATINGS
24V Back Plane or
See NOTE below
External Power Current
Screw Terminal 24V Current Total Device Current
6.2V Back Plane Current 0
24V Standby Current 89mA
NOTE: The 24V current is dependent on the usage and wiring type of each ZICCkt of the ZIC-4A.
Listed below are the required current draws for each zone usage and wiring type.

ZIC-4A Current Requirement


Output Current Class A Current
Zone Usage
Requirement Requirement
Not Used 0 0
NAC 17mA 6mA
Strobe - Sync. 17mA 6mA
Strobe - Unsync. 17mA 6mA
Municipal Tie - USA 34mA 0
Municipal Tie - Canada 17mA 0
Releasing Zone 17mA 0
Leased Line - Alarm 17mA 0
Leased Line - Trouble 17mA 0
Leased Line - Supv 17mA 0
Bell Follower - Primary 0 0
Bell Follower - Secondary 17mA 6mA
Speaker Zone 34mA 6mA
NAC - Coded 17mA 6mA

ZIC-4A Standby Current = 89mA

Siemens Industry, Inc. 10 P/N 315-033050-16


Building Technologies Division
To calculate the maximum current, the following equation should be used:
ZIC-4A Total Current = ZIC-4A Standby Current + [Zone 1 Usage Req. (See Table above) + Class A current (if Class A)]
+ [Zone 2 Usage Req. (See Table above) + Class A current (if Class A)]
+ [Zone 3 Usage Req. (See Table above) + Class A current (if Class A)]
+ [Zone 4 Usage Req. (See Table above) + Class A current (if Class A)]

Example 1: If a ZIC-4A has the following ZICCkt setting:


ZICCkt#1 — Speaker Zone, Class A
ZICCkt#2 — Speaker Zone, Class A
ZICCkt#3 — Speaker Zone, Class A
ZICCkt#4 — Speaker Zone, Class A

By applying the equation above, the maximum current requirement for this card will be determined.

Max Current = 89 + (34 + 6) +(34 + 6) +(34 + 6) +(34 + 6) = 249mA (worst case).

Example 2: If a ZIC-4A has the following ZICCkt setting:


ZICCkt#1 — NAC, Class B
ZICCkt#2 — Strobe Sync, Class A
ZICCkt#3 — NAC-Coded, Class B
ZICCkt#4 — Not Used

Max Current = 89 + (17 + 0) +(17 + 6) +(17 + 0) +(0 + 0) = 146mA.

CONFIGURATIONS The ZIC-4A zones can be configured for the following usages (Refer to Figures 6 - 16):

Notification Applicance (NFPA 72)


Municipal Tie (NFPA 72)
Leased Line (NFPA 72)
Releasing Service (NFPA 13 and NFPA 2001)
Bell Follower
Single-Channel and Two-Channel Audio
Single-Channel and Two-Channel Audio and Strobe

Bell Follower (Refer to Figure 11) When the ZIC-4A zones are configured as a bell follower, it
follows a signal that comes from another reverse polarity source. The zones can be
set as a Bell Follower-Primary or Bell Follower-Secondary.

The Bell Follower-Primary receives an input (it can be NAC output of another panel,
etc), converts it to a TTL signal and then sends it to the Bell Sync Bus of the CC-5
which is monitored by the card with Bell Follower-Secondary configuration. Bell
Follower-Primary can be configured on Zone 1 only. Once Zone 1 is configured as a
Bell Follower-Primary, its zone output is not used. There can only be one Bell Fol-
lower-Primary per enclosure. CC-5 Sync Bus transfers from card cage to card cage.

The ZIC-4A card monitors the Bell Sync Bus if any one of its zones is configured as
Bell Follower-Secondary. Once a HI is detected, the card activates the Bell Follower-
Secondary zone and continuously monitors this signal until it goes LO. Then the ZIC-
4A card de-activates the Bell Follower-Secondary. The zone inputs of the Bell Fol-
lower-Secondary are monitored for presence of input voltage (<20VDC) and its
output is supervised for short and open while the zone is in supervision.

Siemens Industry, Inc. 11 P/N 315-033050-16


Building Technologies Division
NOTES
1. All wiring must be in accordance with
Article 760 of NEC or local building
Current Max Line
codes. Wiring for each zone can either
Draw Resistance
be Class A or Class B.
2. All output circuits are power limited to 3.0A 0.8 ohms
NFPA 70 per NEC 760.
3. Electrical Ratings: Special Application 2.5A 1.0 ohms
24 VDC
4mA max @ Supervisory 2.0A 1.2 ohms
3A max @ Alarm
4. EOL resistor , 24k ohms , 1.5A 1.9 ohms
1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state. 1.0A 3.4 ohms
6. Maximum line resistance is dependent
upon the maximum current draw of 0.5A 7.9 ohms
connected notification appliances
when activated. The field wiring
resistance cannot exceed the
maximum line resistance specified for
any given NAC current draw. (See
Table) ZONE 1 ZONE 2
7. Sync and non-sync notification
appliances permitted. Sync is provided STYLE Z * 24K,
1W
STYLE Y
(CLASS A) 5% CLASS B
across all four tones. Sync is not
provided between ZIC-4A cards.
8. For a list of Compatible Notification
Appliances, refer to P/N 315-096363.
9. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB
(P/N 315-033009) Installation
Instructions for details on the
separation of power limited and
non-power limited wiring. * FOR CANADIAN APPLICATIONS,
USE EOL MODEL REL-EOL.
10. Positive or negative ground fault * 24K,
1W
OMIT THE DIODE.

detected at <40K ohms for 5%


- - -
NC NC
terminals 1-16.
+

+
+

STYLE Z 1 2 3 4 5 6 7 8 STYLE Y
(CLASS A) ZONE 3 ZONE 4 CLASS B

9 10 11 12 13 14 15 16
NC NC
* 24K, * 24K,
1W
1W
5%
5%

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24

- - - -
+

ZONE 1 ZONE 2 ZONE 3 ZONE 4


INPUT INPUT INPUT INPUT

Figure 6
ZIC-4A Supervised Notification Appliance Wiring

Siemens Industry, Inc. 12 P/N 315-033050-16


Building Technologies Division
MUNICIPAL LEASED LEASED LEASED LEASED
TIE LINE LINE LINE LINE

+
+
+
+
ZONE 1 ZONE 3 ZONE 1 ZONE 2 ZONE 4
- - - -

TB1
TB1
TB1

TB1
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

LLM-1 LLM-1 LLM-1 LLM-1

Siemens Industry, Inc.


1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

TB2
TB2
TB2

TB2

TB1

Building Technologies Division


1 2 3 4
+

+
LLM-1 NC NC NC NC
- -
1 2 3 4
NOTES

TB2
1. All wiring must be in
accordance with 1 2 3 4 5 6 7 8

Article 760 of NEC DO NOT USE

+
24K,
- -
or local building codes. 1W
5% 9 10 11 12 13 14 15 16
2. All output circuits are
+
+

NC NC NC NC
- -
not power limited.
1 2 3 4 5 6 7 8
3. Electrical Ratings:
Trip Coil: 14.5 ohms NOTES
Trip Current: 1. All wiring must be in accordance
9 10 11 12 13 14 15 16
220mA to 320mA DC with Article 760 of NEC or local
Supervisory Current: building codes. ONE SLOT OF CC-5
DO NOT USE
1mA DC 2. All output circuits are power

13
Voltage: 24V nominal limited. 17 18 19 20 21 22 23 24

4. EOL resistor, 24k ohms, 3. Leased Line circuit rating:


1 watt, 5%, P/N 140-820405. 24 VDC open circuit filtered
5. Polarity shown in active state. ONE SLOT OF CC-5 full wave
6. Supervised for open circuit only. 4. External circuit resistance:
7. LLM-1 module is required. The total 17 18 19 20 21 22 23 24 2k to 5k ohms
+
+
+

5. Rated Current: 3mA to 9mA,


- - -
loop resistance from the LLM-1 to
the Municipal Tie, including the alarm / supervisory.
ZONE 1 & 2 ZONE 3 ZONE 4
14.5 ohms in the Municipal Tie, 6. Polarity shown in active state. INPUT INPUT INPUT
should not exceed 22.5 ohms. 7. Lease Line circuits are not
8. Wire jumper must be connected supervised.

+
+
+
+
- - - -
between the positive terminals 8. LLM-1 module is required.
at the output. 9. Load must be compatible polarity reversal labeled
ZONE 1 ZONE 2 ZONE 3 ZONE 4
9. Any circuit may be used. INPUT INPUT INPUT INPUT Remote Station Receiver Unit.
10. Minimum Emergency Power: 10. Input voltage sources can be daisy-chained.
60 hours standby 11. Any circuit may be used.
5 minute alarm 12. Minimum Emergency Power:
11. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB 60 hours standby
(P/N 315-033009) Installation Instructions for details on the separation of 5 minute alarm
power limited and non-power limited wiring. 13. Intended for connection to a polarity reversal circuit of a remote station receiving unit having
12. Positive or negative ground fault detected at <40K ohms for terminals 1-16. compatible ratings.
14. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installa-
tion Instructions for details on the separation of power limited and non-power limited wiring.
Figure 7 Figure 8
ZIC-4A Supervised Municipal Tie Wiring ZIC-4A Leased Line Wiring

P/N 315-033050-16
NOTES
1. All wiring must be in accordance with
Article 760 of NEC or local building
codes. RELEASING ZONE RELEASING ZONE RELEASING ZONE RELEASING ZONE
2. Electrical Ratings: 24VDC ZONE 3
See Note 15
ZONE 1
See Note 14
ZONE 2
See Note 14
ZONE 4
See Note 16
2mA max @ Supervisory
3A max @ Alarm
3. All circuits are power limited to - - - -

+
NFPA 72 per NEC 760.
REL-EOL REL-EOL +
4. EOL resistor, 24k ohms,

-
REL-EOL 24K, MODULE 24K, MODULE 24K, REL-EOL
1 watt, 5%, P/N 140-820405. MODULE
+ * 1/2W
5% Disconnect
* 1/2W
5% Disconnect
* 1/2W
5%
MODULE

-
5. Polarity shown in active state for UL Circuit
- Circuit
-

+
+
compliant wiring only. NC NC NC NC
+
6. N/A 24K,
* 5%1/2W Disconnect
7. Releasing is wired for Class B only. Circuit

-
8. Any circuit may be used. 1 2 3 4 5 6 7 8
+
9. Input voltage sources can be daisy- Supervising Disconnect
chained. Module Switch

-
10. For Compatible Solenoids, refer to 9 10 11 12
- 13 14 15
-16

table at right.

+
Disconnect Circuit NC NC NC NC

11. Refer to Zeus Quick Start Guide (P/N


315-033875) for information about
* The REL-EOL ships
programming of releasing service. with three resistors.
12. Refer to CAB1/CAB1R (P/N 315- Use the 24K resistor
(P/N 140-034677)
0330007) and CAB2-BB/CAB3-BB (P/ with the ZIC-4A.
N 315-033009) Installation ONE SLOT OF CC-5

Instructions for details on


the separation of power 17 18 19 20 21 22 23 24

limited and non-power


limited wiring.
13. Positive or negative ground
fault detected at <40K ohms
for terminals 1-16.
- - -
14. For FM approved Pre-Action/
+

+
Deluge: All initiating devices
connected to the system ZONE 1 & 2 ZONE 3 ZONE 4
INPUT INPUT INPUT
must be wired CLASS A.
15. Wiring diagram shown for
24VDC solenoid.
16. Wiring diagram shown for
12VDC solenoids (2 units in Figure 9
series.) ZIC-4A Releasing Service Wiring
17. Wiring diagram shown for
6VDC solenoids (4 units in
series.)
18. The ZIC-4A circuit must be
configured as “NAC Steady”.
The “Releasing Zone” usage
in Zeus is only to be used
for legacy UL releasing
applications that did not
include the REL-EOL.
19. The ZIC-4A circuit must
include a UL864 listed
Releasing Disconnect
Switch such as Siemens
Model RSM-5, P/N S54339-
F1-A1. The switch position
must be monitored using an
input module such as the
HTRI-M using the second
set of contacts.

Refer to the Solenoid Compatibility List, Document ID


A6V11620059.

Initiating devices configured for supervisory signaling


are latching by default. If non-latching behavior is
required, check the self restoring supervisory checkbox
in the node properties for your Zeus configuration.
Siemens Industry, Inc. 14 P/N 315-033050-16
Building Technologies Division
NOTES
1. All wiring must be in accordance
with Article 760 of NEC or local
building codes.
2. All output circuits are power
limited to NFPA 70 per NEC 760.
ONE SLOT OF CC-5
3. Electrical Ratings: 24 VDC
2mA max @ Supervisory
3A max @ Alarm 17 18 19 20 21 22 23 24

4. Maximum line resistance: Refer - - - -

+
to table on pages 12 or 16.
5. Use only Pre-Action/Deluge
solenoids listed in tables on page
14.
6. For FM Approved Pre-Action/
Deluge: All initiating devices
conntected to the system must
be wired CLASS A.
7. Refer to Figure 9 for ZIC-4A
output soldenoid wiring for
Releasing Service. Connect the
zone ouput appropriately.
8. Inputs can be daisy-chained
provided that the power supply
TO PSC-12, TB4 +
can sustain the power require-
ment of the output when
activated.
9. Refer to Zeus Quick Start Guide TO PSC-12, TB4 -
(P/N 315-033875) for information
about programming of releasing
service.
10. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB
(P/N 315-033009) Installation
Instructions for details on the
separation of power limited and
non-power limited wiring.
11. 90 hour standby power is required
to meet FM Approved installation
requirements. Refer to PSC-12
Installation Instructions, P/N 315-
033060 for battery calculations.
Figure 10
ZIC-4A Releasing Service Wiring With PSC-12 Power Supply

FOR FM APPROVED INSTALLATION ONLY:

Double Interlock A sprinkler system comprised of two interlocks - an interlock which opens when
Pre-action Systems powered by a listed releasing panel and a second interlock which opens when a
pressure loss is experienced in the sprinkler pipes between the interlock and the
system’s sprinkler heads.

Both interlocks must be open at the same time to allow for the flow of water to initiate.

A specific sequence of operation is required with all Siemens panels with listed
releasing capabilities.

The FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular panel will


indicate an alarm if one detector detects an alarm condition. The system will not
energize the releasing circuit until an additional detector detects an alarm (any two
detectors in the same protection zone covering the sprinkler system) AND the panel
receives a low pressure indication from a pressure switch placed in the sprinkler
piping between the second interlock and that pipe system’s sprinkler heads (indi-
cates that the second interlock is in OPEN position). If this sequence is not followed
precisely, the correlating system design may not properly activate the double inter-
lock preaction sprinkler system, therefore, preventing the water from discharging
during a true fire incident.
Siemens Industry, Inc. 15 P/N 315-033050-16
Building Technologies Division
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local
building codes.
2. Only Zone 1 can be configured as Bell Follower-Primary. Any other
zone can be configured as Bell Follower-Secondary. There can only Current Max Line
be one Bell Follower-Primary per enclosure. Draw Resistance
3. Electrical Ratings:
Bell Follower-Primary: 3.0A 0.8 ohms
Input Alarm Current: 6mA max
Input Voltage: 24 VDC nominal 2.5A 1.0 ohms
No end of line resistor is used.
2.0A 1.2 ohms
Bell Follower-Secondary:
Input Voltage: 24 VDC nominal 1.5A 1.9 ohms
Output Supervision Current: 4mA max
Output Alarm Current: 3A max 1.0A 3.4 ohms
Output Voltage: 24 VDC nominal
4. Bell Follower-Primary is not supervised. BELL FOLLOWER - SECONDARY 0.5A 7.9 ohms
(CLASS B)
5. Bell Follower-Secondary is supervised for input voltage presence, ZONE 2
short and open on the output and is power limited. Bell Follower-
Secondary can be configured or Class A or Class B wiring. * 24K,
1W
6. The total output loop resistance must not 5%
exceed those stated in table to the right.
7. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB
(P/N 315-033009) Installation Instructions for details on the
separation of power limited and non-power limited wiring.
8. Positive or negative ground fault detected at <40K ohms for
terminals 1-16.
9. The use of sync strobes is not allowed on the secondary circuits.

NC NC NC NC NC NC
* FOR CANADIAN APPLICATIONS,
USE EOL MODEL REL-EOL.
OMIT THE DIODE.

-
+

BELL FOLLOWER - SECONDARY BELL FOLLOWER - SECONDARY


(CLASS A) 1 2 3 4 5 6 7 8 (CLASS B)
ZONE 3 ZONE 4
- - -
+

9 10 11 12 13 14 15 16
NC NC
* 24K, *24K,
1W
1W
5%
5%

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24
- - - -
+

BELL FOLLOWER
PRIMARY INPUT

FIRE ALARM PANEL


OR
BELL EXTENDER
+

NAC OUTPUT SHOWN TO PSC-12, TB4 -


IN ACTIVE STATE -
TO PSC-12, TB4 +

Figure 11
ZIC-4A Bell Follower Circuit Wiring

Siemens Industry, Inc. 16 P/N 315-033050-16


Building Technologies Division
Zone Wiring

ZONE 1 ZONE 2

24K,
STYLE Z 1W STYLE Y
CLASS A 5% CLASS B

24K,
1W NC NC
5%
- - -

+
+

STYLE Z 1 + 2 3 4 5 6 7 8
(CLASS A) ZONE 3
- - - STYLE Y
+

+
ZONE 4 (CLASS B)
9 10 11 12 13 14 15 16
NC NC
24K,
24K,
1W
1W
5%
5%

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24
+

+
CHANNEL A - - AUDIO FROM PREVIOUS
TO NEXT ZIC-4A OR FROM ZAC-40/
ZAM-180 TERMINALS
+

+
ZIC-4A
CHANNEL B - - 1A AND 1B OR 2A AND 2B

NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings:
Output Zone Supervisory: 4mA max
Output Zone Active: 96 Watts max / zone
4. EOL resistor, 24k ohms, 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of
power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Positive or negative ground fault detected at <40K ohms for
terminals 1-16.

Figure 12
ZIC-4A Two-Channel Audio Wiring

Siemens Industry, Inc. 17 P/N 315-033050-16


Building Technologies Division
NOTES
1. All wiring must be in accordance with
Article 760 of NEC or local building
codes. Wiring for each zone can
either be Class A or Class B.
2. All output circuits are power limited
to NFPA 70 per NEC 760.
3. Electrical Ratings:
Output Zone Supervisory:
4mA max
Output Zone Active:
96 Watts max / zone
4. EOL resistor, 24k ohms, ZONE 1 ZONE 2
1 watt , 5%, P/N 140-033771.
24K,
5. Polarity shown in active state. STYLE Z 1W STYLE Y
6. For a list of Compatible Notification CLASS A 5% CLASS B
Appliances, refer to P/N 315-096363.
7. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB (P/
N 315-033009) Installation Instruc-
tions for details on the separation of
power limited and non-power limited
wiring.
8. Positive or negative ground fault
detected at <40K ohms for
terminals 1-16.
24K,
1W NC NC
5%
- - + -
+

STYLE Z 1 2 3 4 5 6 7 8
(CLASS A) ZONE 3
- - - STYLE Y
+

ZONE 4 (CLASS B)
9 10 11 12 13 14 15 16
NC NC
24K, 24K,
1W 1W
5% 5%

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24

AUDIO FROM PREVIOUS


+

TO NEXT ZIC-4A - - ZIC-4A OR FROM ZAC-40/


ZAM-180 TERMINALS
1A AND 1B OR 2A AND 2B

Figure 13
ZIC-4A Single-Channel Audio Wiring

Siemens Industry, Inc. 18 P/N 315-033050-16


Building Technologies Division
Current Max Line
Draw Resistance

3.0A 0.8 ohms


ZONE 1 ZONE 2
2.5A 1.0 ohms
24K,
1W
STYLE Z 5% STYLE Y 2.0A 1.2 ohms
CLASS A CLASS B
1.5A 1.9 ohms

1.0A 3.4 ohms

0.5A 7.9 ohms

24K,
1W NC NC
5%
- - -

+
+

+
STYLE Z 1 2 3 4 5 6 7 8 STYLE Y
(CLASS A) ZONE 3 (CLASS B) ZONE 4
- - -
+

+
9 10 11 12 13 14 15 16
NC NC
* 24K, *24K,
1W
1W
5%
5%

* FOR CANADIAN APPLICATIONS,


USE EOL MODEL REL-EOL.
ONE SLOT OF CC-5 OMIT THE DIODE.

17 18 19 20 21 22 23 24
+

AUDIO FROM PREVIOUS CHANNEL A -


24V (-)
ZIC-4A OR FROM ZAC-40/ TO NEXT ZONE INPUT
24V (+)
+

ZAM-180 TERMINALS ZIC-4A


1A AND 1B OR 2A AND 2B CHANNEL B -

NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings For Speaker Application:
Output Zone Supervisory: 4mA max @ 24VDC
Output Zone Active: 96 Watts max / zone
Electrical Ratings For Special Application: 24 VDC (strobe)
Output Zone Supervisory: 4mA max
Output Zone Alarm: 3A max
4. EOL resistor, 24k ohms, 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of
power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated. The field wiring
resistance cannot exceed the maximum line resistance specified for any given NAC current draw. (See Table)
11. Zone Usage pair is interchangeable. Verify proper wiring.
12. Positive or negative ground fault detected at <40K ohms for terminals 1-16.

Figure 14
ZIC-4A Two-Channel Audio And Strobe Wiring

Siemens Industry, Inc. 19 P/N 315-033050-16


Building Technologies Division
ZONE 1 ZONE 2 Current Max Line
Draw Resistance
STYLE Z * 24K,
1W
STYLE Y
(CLASS A) 5%
(CLASS B) 3.0A 0.8 ohms

2.5A 1.0 ohms

2.0A 1.2 ohms

1.5A 1.9 ohms

1.0A 3.4 ohms

0.5A 7.9 ohms


* FOR CANADIAN APPLICATIONS,
USE EOL MODEL REL-EOL.
* 24K,
1W
OMIT THE DIODE.

5%
- - NC NC
-
+

+
+

- - + -
+

STYLE Z 1 2 3 4 5 6 7 8
(CLASS A) ZONE 3
- - - STYLE Y
+

ZONE 4 (CLASS B)
9 10 11 12 13 14 15 16
NC NC
24K, 24K,
1W 1W
5% 5%

ONE SLOT OF CC-5

17 18 19 20 21 22 23 24

AUDIO FROM PREVIOUS


+

ZONE - - ZIC-4A OR FROM ZAC-40/ TO NEXT


INPUT ZAM-180 TERMINALS ZIC-4A
1A AND 1B OR 2A AND 2B

NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings For Speaker Application:
Output Zone Supervisory: 4mA max @ 24VDC
Output Zone Active: 96 Watts max / zone
Electrical Ratings For Special Application: 24 VDC (strobe)
Output Zone Supervisory: 4mA max
Output Zone Alarm: 3A max
4. EOL resistor, 24k ohms,
1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of
power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Maximum line resistance is dependent upon the maximum current draw of connected notification appliances when activated. The field wiring
resistance cannot exceed the maximum line resistance specified for any given NAC current draw. (See Table)
11. Zone usage pair is interchangeable. Verify proper wiring.
12. Positive or negative ground fault detected at 40K ohms for terminals 1-16.

Figure 15
ZIC-4A Single-Channel Audio And Strobe Wiring

Siemens Industry, Inc. 20 P/N 315-033050-16


Building Technologies Division
GENERAL ALARM
ALARM NACs ACF1
P1 UC3
ALARM
ENABLE

Siemens Industry, Inc.


TRUE
E FIRST ALARM /
ST1 PRE DISCHARGE NAC

Building Technologies Division


START ACF2
PANEL G1 T TIMER O PRE-DISCHARGE P2 UC3
RESET 0 - 60s G2 P1 120PPM
PANEL RESET
C
PANEL CLR
CANCEL RESET CLK
Q DISCHARGE DISCHARGED NAC
G3 M G5 ACF3
TRUE D P1 SYNC STROBE
L1
HZM+AW-1

ABORT PRE DISCHARGE


M G4* LED1
LCM LED (Yellow)
SUPERVISORY
DISPLAY CAT. = ABORT SWITCH

21
DISCHARGED
LCM LED (Yellow) LED2
ENABLE TRUE
NOTE: SELECT SELF RESTORING SUPERVISORIES
AT THE NODE LEVEL IN ZEUS IF YOU WANT
ABORT EVENTS TO SELF-RESTORE. E
START
T TIMER O RELEASING NACs
30 - 60s
ST2 C
HZM+MH501 PANEL
CANCEL RESET
MANUAL ABORT LCM LED
(Yellow) LED3
RELEASE
*OPTIONAL: ABORT OVER-RIDES MANUAL RELEASE
ALARM ELIMINATE G4, CONNECT M TO M FOR DIRECT MANUAL RELEASE

NOTE: THE USE OF ALARM VERIFICATION IS NOT ALLOWED FOR DEVICES IN A CROSS ZONED INITIATING CIRCUIT.

Figure 16
FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular Releasing Logic

P/N 315-033050-16
CYBER SECURITY DISCLAIMER
Siemens provides a portfolio of products, solutions, systems and
services that includes security functions that support the secure
operation of plants, systems, machines and networks. In the field of
Building Technologies, this includes building automation and control,
fire safety, security management as well as physical security systems.

In order to protect plants, systems, machines and networks against


cyber threats, it is necessary to implement – and continuously
maintain – a holistic, state-of-the-art security concept. Siemens’
portfolio only forms one element of such a concept.

You are responsible for preventing unauthorized access to your


plants, systems, machines and networks which should only be
connected to an enterprise network or the internet if and to the
extent such a connection is necessary and only when appropriate
security measures (e.g. firewalls and/or network segmentation) are
in place. Additionally, Siemens’ guidance on appropriate security
measures should be taken into account. For additional information,
please contact your Siemens sales representative or visit https://
www.siemens.com/global/en/home/company/topicareas/future-of-
manufacturing/industrial-security.html.

Siemens’ portfolio undergoes continuous development to make it


more secure. Siemens strongly recommends that updates are
applied as soon as they are available and that the latest versions are
used. Use of versions that are no longer supported, and failure to
apply the latest updates may increase your exposure to cyber
threats. Siemens strongly recommends to comply with security
advisories on the latest security threats, patches and other related
measures, published, among others, under

https://www.siemens.com/cert/en/cert-security-advisories.htm.

Siemens Industry, Inc. 22 P/N 315-033050-16


Building Technologies Division
This page has been left intentionally blank.

Siemens Industry, Inc. 23 P/N 315-033050-16


Building Technologies Division
This page has been left intentionally blank.

For CE applications in Cerberus E100 systems refer to


Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).

Siemens Industry, Inc. Siemens Canada, Ltd. Siemens Gebäudesicherheit P/N 315-033050-16