Professional Documents
Culture Documents
Manual
Manual
0)
Product Description
ZXDU58 B121(V2.0) Product Description
Table of Contents
1 Overview.................................................................................................................................. 1
1.1 Application ..................................................................................................................... 1
1.2 Features .......................................................................................................................... 1
1.3 Technical Specifications ................................................................................................ 2
2 Structure and Principle.......................................................................................................... 4
2.1 System Structure and Principle ...................................................................................... 4
2.1.1 System Composition ............................................................................................ 4
2.1.2 Operating Principles of the System...................................................................... 4
2.2 Integrated Chassis .......................................................................................................... 5
2.3 Power Distribution Unit ................................................................................................. 6
2.3.1 Operating Principles of AC Distribution Unit ..................................................... 6
2.3.2 Operating Principles of DC Distribution Unit ..................................................... 6
2.3.3 Front Panel ........................................................................................................... 7
2.3.4 Backplane............................................................................................................. 8
2.4 Rectifier.......................................................................................................................... 8
2.4.1 Structure Description ........................................................................................... 8
2.4.2 Performance Indices............................................................................................. 9
2.4.3 Status Display .................................................................................................... 10
2.4.4 Interfaces............................................................................................................ 11
2.5 Monitor Unit................................................................................................................. 11
2.5.1 Appearance ........................................................................................................ 11
2.5.2 Functions of the Monitor Unit ........................................................................... 13
2.6 Monitor Networking Mode .......................................................................................... 14
Tables
Table 1 Integrated chassis Specification................................................ 2
Table 2 AC power distribution Specification ........................................ 2
Table 3 DC power distribution Specification ........................................ 2
Table 4 Environment Specification ....................................................... 3
Table 5 measurement accuracy of the monitor unit............................... 3
Table 6 Composition of the ZXDU58 B121 System ............................. 4
Table 7 Installation Slots of the Rectifiers and the Monitor Unit.......... 5
Table 8 Components on the Power Distribution Unit Front Panel ........ 7
Table 9 Backplane of the Distribution Unit........................................... 8
Table 10 Rectifier Component Names and Functions ............................. 9
Table 11 Performance Parameters of the ZXD1500 (V4.0) .................... 9
Table 12 Meanings of the Rectifier Indicators ...................................... 10
Table 13 Definitions of Pins of Input/Output Integrated Socket ........... 11
Table 14 Indicators of the Monitor Unit ................................................ 12
Table 15 Data Collection and Processing .............................................. 13
Table 16 Alarm reporting management and protection ......................... 13
1 OVERVIEW
This chapter describes the application, features and technical parameters of the
ZXDU58 B121 system.
1.1 Application
The ZXDU58 B121 system is a 30A rectifier and -48 VDC power supply system. It
has such functions as centralized monitor and battery maintenance & management
and allows no attendance. The ZXDU58 B121 can be mounted into the cabinet of
the powered equipment.
ZXDU58 B121 adopts advanced rectifier conversion technologies in the world. It is
applicable to provide power supply for access network equipment, remote switch
offices, mobile communication devices, transmission equipment, ground satellite
transceiver stations, and microwave communication devices.
1.2 Features
The ZXDU58 B121 system offers the following features:
1. Advanced power control technologies and components and following the latest
trend in DC power supply.
2. Uses modular design, automatic current equalization technology, and capable
of N+1 backup and easy expansion.
3. Good electromagnetic compatibility.
4. Intelligent design with a centralized monitor unit capable of “3-remote”
functions (remote measurement, remote information and remote control) and
PC-based management. The monitor unit can communicate with the remote
monitor center so that no human attendance is needed on site. This complies
with the requirement of modern communications technology development.
5. Combination of power control and computing technologies to monitor and
control the parameters and status of rectifiers and AC/DC power distribution
unit in real time.
6. Single-phase AC input and wide range of input voltage, which enables the
system to be used in areas with unstable voltage.
7. Flexible configuration: allowing a maximum of four rectifiers, which are hot-
pluggable.
8. Automatic battery management: The monitor unit measures the charge and
discharge current automatically and enables floating charge and equalized
charge mode of battery.
9. LVD (low voltage disconnect) function: The system will generate audible and
visible alarms when the battery voltage is too low. According to the importance,
loads are divided to two groups. Less important load are powered off firstly to
ensure that important loads can work longer.
10. Multi-class lightning protection assures high reliability of the whole system.
11. Intelligent air cooling with low noise.
12. High reliability with MTBF ≥ 2.2×105 h.
13. Compact structure: Various units, including AC/DC power distribution unit,
rectifiers and the monitor unit, are built in one chassis.
6. Monitor unit
Local monitoring: The monitor unit of the system has LCD and operation panel,
which enable the user to set system parameters and query system operation data.
Background monitoring: The system provides the RS232/RS485 interface to be
connected to a PC, where the monitor software serves to monitor the ZXDU58 B121
system. Or the system can be connected to a remote PC through modem or others; in
this way, the monitor software in the PC serves to monitor the system remotely.
Note: Please refer to ZTE Background Power Supply Monitor Software (V3.21)
User’s Manual for details.
The table below gives the measurement accuracy of the monitor unit.
Table 5 measurement accuracy of the monitor unit
Item Accuracy
AC voltage ±1%
Battery current and output current ±1%
Battery voltage and output voltage ±0.5%
Temperature ±3°C
Humidity ±5%
Boolean value 100%
3
4
4
5
7
6
8
2. Four input/output integrated sockets are equipped on the inner wall of the
integrated chassis, as shown in Figure 3. All electrical connections between the
rectifiers and ZXDU58 B121 are realized through these sockets.
Battery 1 Air switch of battery 1 To turn on/off battery 1 and battery 2 branch with
2.3.4 Backplane
The backplane of the distribution unit is at the back of the cabinet, as shown in
Figure 7.
1
2 3
2.4 Rectifier
When fully configured, a ZXDU58 B121 system can contain four ZXD1500 (V4.0)
rectifiers to form a power system up to 120A.
3
ZXD1500
4 5 7
Section indicator
0 30A
IN OUT CL ALM
2.4.4 Interfaces
The input/output integrated socket is used for connecting with the power system,
with the interfaces arrangement shown in Figure 10.
26 28
1 3
5 8 11 14 17 20 23
6 9 12 15 18 21 24 27 29
2 4
7 10 13 16 19 22 25
1
2
3
4
5
6
7
8
9
DC distribution unit DC output voltage, battery voltage, battery current, total load current,
status of load output air switch, status of DC contactors and DC
arrester status
Rectifier Power-on/off control of rectifier, recharge status control and in-
position and fault detection
been discharged for a period long enough (to be set by users). In this case,
the system automatically charges a storage battery.
2) Battery protection function
When the mains supply is cut off, the battery supplies the power. The
alarm is generated when the voltage of the battery decreases to a certain
degree (adjustable).
When the voltage of the battery decreases to the protection voltage of
primary power-off, cut off the secondary load first. When the further
discharge of battery reaches the protection voltage of the secondary
power-off, cut off the primary load, to prevent the battery from being
damaged due to discharge.
This ensures that the basic load is maintained for a long period of standby
time even after power failure, that the battery is not damaged due to any
over-discharge.
6. Control
Control the power-on, power-off, equalized charging and float charging of the
rectifier through the control instruction of the foreground man-machine interaction
operation or background computer. Adjust the output voltage of the rectifier (-42 V
~ -58 V adjustable continuously) according to the requirements of the user.