1. Normal range parameter of a BOILER WATER

Categories Normal Ranges Best action to do if


out of range
P. Alkalinity 100 to 300 ppm COMBITREAT
uses for raising the
alkalinity which you
just have to use 40l
grams per tons and a
10kg may raise it by
50ppm.

Chlorides maximum of 200 Formation of


ppm chlorides can be
controlled by
manipulating the
amount and time of
boiler blow down.
Categories Normal Ranges Best action to do if
out of range
pH Boiler 9.5 to 11 To control ph, you
have to either
remove water
impurities or by
adding chemicals to
neutralize the
condition
pH condensate 8.3 to 11 Maintain condensate
ph to neutralize acids
by using volatile
amine

2. Normal range parameters of a Engine Cooling water


Categories Normal Ranges Best action to do if
out of range
Nitrite 100 to 300 ppm To raise the nitrite
level, you will have
to add 2 kg of
DIESELGUARD per
tonne of water ,
which a 500 grams
can raise the nitrite
level, or 9 liters of
ROCOR NB
LIQUID per tonnes
of water that a 2.1
liters per tonne of
water can raise the
water level.

Chlorides maximum of 50 To maintain the


ppm chloride level,
manufactures
suggested to use the
distilled water for
suggestions.
Categories Normal Ranges Best action to do if
out of range
pH 8.3 to 11 N.B. buffering
agents in
NALFLEET
ROCOR NB can
maintain pH values