Professional Documents
Culture Documents
User manual
VW3A3501SYNCSE
Revision 21
Comply with ATV71 Sync software V3.0.0
Disclaimer
The software described in this manual is sold or licensed “as is”. Should the program prove defective neither Schneider
Electric nor the distributor is responsible for the cost of any servicing, repair incidental or consequential damages resulting
from any defect in the software. Further, Schneider Electric reserves the right to revise this publication and to make changes
from time to time in the contents hereof without obligation to notify any person of such revision or changes.
One drive is the Master and the remaining drives are Slaves. The Master drive is
given the desired command and speed reference from a PLC controller. The basic
function of the Slave drive is to follow the speed of the master, but if a positioning
error is detected the speed is automatically adjusted to maintain position
synchronism.
The Master drive consists of a standard ATV71 variable speed drive with one
encoder card, one Controller Inside card with the ATV71 Position Synchronizer
application loaded and one fieldbus communication card.
The Slave drive is a standard ATV71 with only an encoder card.
The Position Synchronizer handles the communication to the Slave drive so the PLC
Controller is only connected on the communication link to the Master drive.
The PLC Controller has 8 specific I/O exchange words in the Com Scanner I/O
dedicated to command and monitor the Slave drives.
2.3 POWER UP
After first power up it’s advised to make for all axis a Homing to a reference switch
before the position synchronizing is started. It’s up to the PLC Controller to handle
this procedure.
Refer to the “Graphic Display Terminal” section of the ATV 71 Programming Manual
for instructions on how to navigate the display and for information on any standard
ATV71 screen which will not be described in this manual.
Here you can monitor the important objects for the Synchronizer application.
Example the CANopen sync bus status, control and statuswords for all of the drives,
position error, direction of encoder rotation etc.
See chapter “CANopen States and Errors” for more information on CAN faults.
With the Oscilloscope you can monitor graphically four important parameters
simultaneously to validate the behavior of the machine. You choose the slave and
channels to record and the update time for the oscilloscope. There is no problem to
make a record longer than the y-axis of the oscilloscope. When you stop the
recording there is a scrollbar to go back and forwards on the Y-axis. You can also
compress the Y-axis to display the whole recording in the same screen.
From the drop down menu “Programs” in Sync Commissioning Tool you have the
possibilities to start the program Gear Calc.
Gear Calc is a PC-software to help calculate complex gear ratios.
You specify the number of teeth for each stage of the gears inside the gearbox and
then the same for the mechanical parts after the gearbox.
All slaves are handled from one file. The finished file is saved in a standard text file.
From the menu “File” in Sync Commissioning Tool it’s then possible to import the
final Gear Calc file.
Terminal Description
24V Power supply for ATV71 Synchronizer card, logic output and analog output.
Current consumption
Power: 24Vdc (min. 19, max. 30)
Max: 2A
No load: 80 mA
If allowed by the power consumption table (for example if outputs are not used), the
ATV71 Synchronizer card can be powered by the 24V power supply in the drive.
This ground and electrical 0V are common with the drive ground and electrical 0V.
There is therefore no point in connecting this terminal to the 0V terminal on the
drive control terminals.
LI, LO, Not in use with ATV71 Synchronizer application.
AI, AO
Use a straight connector (catalog number TSX CAN KCDF 180T) to connect the card
to the CANopen bus.
This connector integrates a line terminator that must be activated if the card is at one
end of the CANopen bus.
The 9-way SUB-D connector on the card is linked to the card ground and the drive
ground. The shielding must be connected to the connector ground.
The CANopen signals on the card are isolated.
NOTE: For drives bigger than 18,5kW use the reference VW3 CAN KCDF180T
Otherswise it’s difficult to close the protection plate for I/O terminals.
For all drive the baud rate and transmission speed must be configured at the first
commissioning. Access to CANopen parameters from the graphical terminal menu
[1.9 COMMUNICATION] / CnO – [CANopen] or from the Powersuite software folder
Communication / CANopen configuration.
Description:
CAN fault – General CANopen fault on.
0 – No errors.
1 – One or more CAN errors active.
CAN Stack Err. – Error number reported from CANopen master port on Sync card.
See “Table of CAN error numbers” for more information.
CAN Error no. – Error number on the CANopen port on the drive.
See “Table of CAN error numbers” for more information.
Number of Slaves
Description Number of Slaves
Range 1 12
Default 1
Units
Function Serves to set the number of Slave drives connected to Master
drive.
KPp GAIN
Description Position loop proportional gain
Range 0 200
Default 15
Units
Function Speed adjustment = GAIN KPp * position inc Error / 100
Increase if the Slave takes to long time to get in position.
Reduce if the Slave is instable and makes to big speed
adjustments.
GEARnum_1
Description Gear numerator step 1
Range
Default 1
Units
Function Serves to set the predefined Gear ratio between Master and Slave
A sign GEARnum value results in reversed rotation on the Slave.
GEARdenom_2
Description Gear denominator step 2
Range Use GearCalc for complex values
Default 1
Units
Function Use GearCalc for complex gear ratios
MaxSpeedCorr
Description Maximum speed correction
Range 0 32767
Default 200
Units rpm
Function Serves to give the maximum speed correction out from the position
controller.
Offset
Description Offset value for the slave
Range -32768 32767
Default 0
Units Encoder increments
Function To make and offset between Master and Slave axis after the sync
have been activated. The parameter can be adjusted under
running.
MaxError
Description Maximum positional error allowed
Range 0 32767
Default 1024
Units Encoder increment
Function Set maximum allowed positional error. If the limit is reached a
warning is activated.
bit15 bit14 bit13 bit12 Bit11 Bit10 Bit9 Bit8 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 bit0
N/A N/A N/A N/A @12 @11 @10 @9 @8 @7 @6 @5 @4 @3 @2 @1
@x = Slave number
The Ethernet cards does not use the ATV71 internal I/O Scanner table.
So to get the right words to and from the PLC controller from the Ethernet card we
have to setup the Ethernet I/O Scanner table inside the Ethernet card itself.
You can do this with Powersuite software or a standard web browser.
If the SYNC bit is active the Slave drive switches automatically the internal ramps
from Ramp setup 1 (ACC/DEC) to Ramp setup 2 (AC2/DE2). The Ramp Setup 1 is
user configured and it’s in use when we not are in sync operation. If we are in sync
operation the Ramp setup 2 values is in use. Ramp setup 2 values are written by the
sync application automatically.