GENERAL

1. ALL SANITARY WORKS SHALL CONFORM WITH PREVAILING REQUIREMENTS OF THE LOCAL
ORDINANCES AND NATIONAL LAWS

2. READ THE DRAWING IN CONNECTION WITH THE OTHER RELATED DRAWING AND SPECIFICATION. THE
ARCHITECT AND THE ENGINEER SHALL BE NOTIFIED FOR ANY DISCREPANCIES FOUND THEREIN

3. THE CONTRACTOR SHALL DETERMINE THE ACTUAL LOCATION, DEPTH AND INVERT ELEVATIONS OF
EXISTING PIPES AND STRUCTURES TO CONFORM WITH THE PROPOSED SANITARY UTILITIES.

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WALL AND WINDOW OPENINGS.

5. ALL PIPES SHALL BE INSTALLED AS INDICATED. ANY RELOCATION REQUIRED FOR PROPER EXECUTION
OF OTHER TRADES SHALL BE WITH PRIOR APPROVAL OF THE ARCHITECT AND THE ENGINEER.

6. ALL SLOPES FOR HORIZONTAL PIPES SHALL MAINTAIN 1% AS MIN. UNLESS OTHERWISE NOTED.

7. ALL FIXTURES SHALL BE VENTED UNLESS OTHERWISE NOTED.

8. ALL PIPES SIZES INDICATED ARE IN MILLIMETER (mm) UNLESS OTHERWISE SPECIFIED.

9. ALL UNDERGROUND WATER PIPES SHALL BE COATED WITH 2-COATS PF TAR OR CARBOLINE AND
WRAPPED WITH BURLAD.

10. REFER TO TECHNICAL SPECIFICATION FOR DETAIL AND EQUIPMENT SPECIFICATION. MATERIAL
SPECIFICATIONS

1. ALL DRAINS, WASTES AND VENT PIPES SHALL BE SANIMOLD BY MOLDEX OR APPROVED EQUAL

2. DOWNSPOUT AND INTERIOR DRAINAGE PIPE COLLECTOR SHALL BE SANIMOLD BY MOLDEX OR


APPROVED EQUAL.

3. EXTERIOR HORIZONTAL DRAINAGE LINE SHALL BE CONCRETE DRAINAGE PIPE 100mmØ UP TO 250mm
AND REINFORCED CONCRETE PIPE FOR 300MMØ OR LARGER.

4. WATERLINES FROM SERVICE CONNECTION FOR FIXTURE CONNECTION SHALL BE


POLYMUTAN/ECOSAN OR VESBO OR APPROVED EQUAL.

5. VALVES SHALL BE MANUFACTURED BY 'KITZ' OR APPROVED EQUAL.

6. FLOOR AND DECK DRAINS SHALL HAVE CAST IRON BODY FRAMES BY JAMAN METALCRAFT OR
APPROVED EQUAL.

7. EXPOSED GALVANIZED IRON PIPES SHALL BE PAINTED WITH ONE (1) COAT PRIMER AND TWO (2)
COATS OF ENAMEL PAINTS.

8. WATERLINES SHALL BE HYDROSTATICALLY TESTED FOR TWO (2) HOURS @ 200 PSI PRESSURE RATING.
9. WATERLINES SHALL BE POLYMUTAN/ECOSAN OR VESSEO OR APPROVED EQUAL.