Combustion Filter Calculation

Donaldson Viledon Viledon Faist Faist


Description Unit Canisters MX-98 MX-100 FV-F9-R FVX-E11
(Original) (Existing) (Existing) (Retrofit) (Retrofit)

Synthetic + Micro-glass fiber Micro-glass fiber Water resistance Water resistance


Media type mtrl
Nanofibres paper paper Micro-glass Micro-glass
ID 660 x 445
Dimension mm 592 x 592 x 292 592 x 592 x 292 592 x 592 x 292 592 x 592 x 440
OD 660 x 476
Filter grade to En779-2012 F8 F9 E11 F9 E11
3
Flow Combustion m /h 390.772 390.772 390.772 390.772 390.772
Surface area m2 21 18 18 20 32
No. of filter combustion (final filter) pcs 112 160 160 120 112
No. of filter ventilation (final filter) pcs
Total no. of filter set (final filter) pcs 112 160 160 120 112
No. of prefilter pcs 160 160 160 160 160
Nominal air flow for combustion m3/h 3.489 2.442 2.442 3.256 3.489
Nominal media velocity m/h 166 136 136 163 109

Total media area m2 2.352 2.880 2.880 2.400 3.584


Initial Dp at air flow for combustion Pa 170 80 135 100 150
Realistic final Dp Pa 650 650 650 450 450