PROJECT;-
SUBJECT : TRANSFORMER RECTIFIER UNIT CLCULATION GROUP : ELECTRICAL
OBJECTIVE
PRIMARY CURRENT= [SECONDARY VOLTAGE X SECONDARY CURRENT X DERATING FACTOR] / [RUTE2 X PRIMARY VOLTAGE]
TRANSFORMER UNIT RATING = TOTAL COLLECTION AREA IN Sq.M X current density in mA/Sq.M
NO OF FIELDS
TOTAL DUST COLLECTION AREA = 13839.3 Sq.M
CURRENT DENSITY IN Sq.M = 0.275 Ma
NO OF FIELDS = 4
TRANSFORMER SIZEING CAPACITY = 951.45188 mA
SO TRANSFORMER SELECTED 1000mA
NOTE : SAMPLE CALCULATION IS ENCLOSED. THIS CAN BE USED FOR OTHER PROJECTS BY CHANGING THE
SHADED VALUES AS APPLICABLE TO THE PROJECT.
CHECKED BY AK 11.10.2010
APPROVED BY 11.10.2010
PROJECT;-TKII-BIDCO
SUBJECT : TRANSFORMER RECTIFIER UNIT LOAD CURRENT CLCULATION GROUP : ELECTRICAL
NO OF TRANSFORMERS = 4 Nos.
TRANSFORMER SECONDARY CURRENT = 1000 mA
TRANSFORMER SECONDARY VOLTAGE (PEAK) = 110 KV(P)
DERATING FACTOR = 1.3
PRIMARY VOLTAGE = 415 VOLT AC
PRIMARY CURRENT = 243.69 Amp
FORM NO
TRANSFORMER RECTIFIER UNIT CALCULATION
CALCULATION DOCUMENT NO. :
ISSUE : 14/09/2010
SHEET: 3
PROJECT;- TKII-BIDCO
SUBJECT : TRANSFORMER RECTIFIER UNIT LOAD CURRENT CLCULATION GROUP : ELECTRICAL
The three-phase syste have three coils fixed at 120° to each other; thus three
voltages, that are 120° out of phase with each other, are produced in three separate circuits (figure)
The phases are normally called red (R), yellow (Y) and blue (B) or line 1 (L1), line 2 (L2) and
line 3 (L3),
when connected in parallel, single-phase system present difficulties which do not occur with
three phase system
P = 3VP X IP cos
But,
VL= VP , IL= √3IP IP= IL / √3
P = √3VL X IL cos
TRANSFORMER RECTIFIER UNIT CALCULATION
CALCULATION DOCUMENT NO. :
PROJECT;-
SUBJECT : TRANSFORMER RECTIFIERUNIT LOAD CURRENT CLCULATION GROUP : ELECTRICAL
Power Factor = Phase angle different between Line voltage & line current
Ref; Below fig.
In a three phase Delta connected system Phase angle different between Line current & Phase current =30
Phase current and line voltage phase angle difference =33
Phase angle different between Line voltage & line current @ R Phase
Phase angle = 63
cos (63) = 0.45, The cos factor value suitable for first transformer of the Table Si.No -1
TRANSFORMER RECTIFIER UNIT CALCULATION
CALCULATION DOCUMENT NO. :
PROJECT;- TKII-BIDCO
SUBJECT : TRANSFORMER RECTIFIER UNIT LOAD CURRENT CLCULATION GROUP : ELECTRICAL
Power Factor = Phase angle different between Line voltage & line current
Ref; Below fig.
In a three phase Delta connected system Phase angle different between Line current & Phase current =30
Phase current and line voltage phase angle difference =21
Phase angle different between Line voltage & line current @ R Phase
Phase angle = 51
cos (51) = 0.63, , The cos factor value suitable for secondt transformer of the Table Si.No -2
TRANSFORMER RECTIFIER UNIT CALCULATION
CALCULATION DOCUMENT NO. :
PROJECT;- TKII-BIDCO
SUBJECT : TRANSFORMER RECTIFIER UNIT LOAD CURRENT CLCULATION GROUP : ELECTRICAL
Power Factor = Phase angle different between Line voltage & line current
Ref; Below fig.
In a three phase Delta connected system Phase angle different between Line current & Phase current =30
Phase current and line voltage phase angle difference =45
IYp = Irms GREATER THAN (0-120)
Phase angle different between Line voltage & line current @ R Phase
Phase angle = (75-120)
cos (45) = 0.70, , The cos factor value suitable for Third transformer of the of the Table Si.No -3
TRANSFORMER RECTIFIER UNIT CALCULATION
CALCULATION DOCUMENT NO. :
PROJECT;- TKII-BIDCO
SUBJECT : TRANSFORMER RECTIFIER UNIT LOAD CURRENT CLCULATION GROUP : ELECTRICAL
Power Factor = Phase angle different between Line voltage & line current
Ref; Below fig.
In a three phase Delta connected system Phase angle different between Line current & Phase current =30
Phase current and line voltage phase angle difference =51
IBp = Irms GREATER THAN (0+120)
Phase angle different between Line voltage & line current @ R Phase
Phase angle = (81+120)
cos (201) = 0.93, , The cos factor value suitable for fourth transformer of the Table Si.No.- -4