TEST RESULT
MODE OF OPERATION DESCRIPTION YES N/A REMARKS
OPERATION
1. Aerosol container filled with the required quantity as per approved drawing.
2. Amount of agent (in grams)
3. Quantity of agent (cylinder in number)
I. Test of the AEROSOL Discharge through
sensors (Detectors).
A. First Alarm test
1. Identify the zone to be activated.
2. LED on sensor glowing RED.
3. Zone number identified on the panel.
4. System Alarm LED glowing.
5. First Alarm Bell activated. (inside the protected
room)
6. Acknowledge operated and buzzer silenced.
Signal Silence operated.
First Alarm Bell silenced.
7. Motorized Fire Damper closed.
8. Air-conditioning/Fan shut down
9. Interface with Main Fire Alarm Control Panel
Page 1 of 3
AEROSOL SYSTEM FUNCTIONAL TEST QCDD FORM
Page 2 of 3
AEROSOL SYSTEM FUNCTIONAL TEST QCDD FORM
CERTIFICATION
The system as specified above has been installed and tested, in accordance with latest edition of NFPA, QCDD FSS and QCDD
approved drawings
________________________________ _______________________________________________
Contractor (QCDD Certificate No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)
CERTIFICATION
The undersigned accepted the testing report for the system as specified herein.
________________________________ _______________________________________________
Consultant (UPDA No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)
Page 3 of 3