AEROSOL SYSTEM FUNCTIONAL TEST QCDD FORM

Pin No. Date


Location Application Number
Project Name
Owner

QCDD Approved Drawing Ref. No.


Test Status Passed

TEST RESULT
MODE OF OPERATION DESCRIPTION YES N/A REMARKS
OPERATION 
1. Aerosol container filled with the required quantity as per approved drawing.
2. Amount of agent (in grams)
3. Quantity of agent (cylinder in number)
I. Test of the AEROSOL Discharge through
sensors (Detectors).
A. First Alarm test
1. Identify the zone to be activated.  
2. LED on sensor glowing RED.  
3. Zone number identified on the panel.  
4. System Alarm LED glowing.  
5. First Alarm Bell activated. (inside the protected
 
room)
6. Acknowledge operated and buzzer silenced.  
Signal Silence operated.  
First Alarm Bell silenced.  
7. Motorized Fire Damper closed.  
8. Air-conditioning/Fan shut down  
9. Interface with Main Fire Alarm Control Panel

Page 1 of 3
AEROSOL SYSTEM FUNCTIONAL TEST QCDD FORM

B. Second Alarm test.  


1. Identify the zone to be activated  
2. Device activated and send alarm signal to fire alarm
 
system.
3. LED on sensor glowing RED  
4. Zone number identified on the panel.  
5. System Alarm LED continues to glow.  
6. Second Alarm Horn/ Strobe activated. (outside)  
7. Illuminated sign “Evacuate Now, Gas Discharge”
 
has been activated.
8. acknowledge operated and buzzer silenced.  

A. Actuation of Manual Release.


1. Identify the release station to be activated. Release
 
station activated.
MANUAL 2. System Alarm LED glowing.  
OPERATION 3. Second Alarm Horn/ Strobe activated send alarm
signal to fire alarm system, motorized fire smoke  
damper to closed.
4. Illuminated sign “Don’t Enter System Discharged”
 
has been activated.
5. Air-conditioning shutdown.  
A. Activate the abort switch during the pre-
discharge time delay period and check for the
ABORT following results:
OPERATION 1. Illumination of “ABORT” indication on the
 
AEROSOL Control Panel.
2. Release of gas is held if abort switch is pressed.  

Page 2 of 3
AEROSOL SYSTEM FUNCTIONAL TEST QCDD FORM

B. Once released, wait for 30 seconds and


check for the following results:
1. Illumination of “RELEASE” indication on the
AEROSOL Control Panel; and activation of strobe  
light located outside the protected hazard.
2. Illuminated sign “Don’t Enter Gas Discharged” has
 
been activated.
3. Activation of alarm bell and strobe horn with
 
steady pulse

CERTIFICATION
The system as specified above has been installed and tested, in accordance with latest edition of NFPA, QCDD FSS and QCDD
approved drawings

________________________________ _______________________________________________
Contractor (QCDD Certificate No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)

CERTIFICATION
The undersigned accepted the testing report for the system as specified herein.

________________________________ _______________________________________________
Consultant (UPDA No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)

Page 3 of 3