Professional Documents
Culture Documents
RTWA Tornillo - 70 A 125 TR
RTWA Tornillo - 70 A 125 TR
Trane Series R® Chiller – What makes the 70-125 ton Series R • Grooved pipe connections on both
chillers special? These chillers have evaporators and condensers (RTWA)
Model RTWA been designed to meet the satisfaction for ease of installation
The RTWA offers high reliability, ease
of installation, and energy efficiency
of growing customer needs. A need • Control power transformer (standard)
due to its advanced design, low speed/
such as “bolt together” construction • Suction and discharge refrigerant
for easy disassembly in limited access pressure readouts from UCM
direct-drive compressor and proven
Series R chiller performance.
installations or the need to isolate the • Factory installed insulation
charge using the standard isolation • “Deluxe” control package as standard
The major advantages of the RTWA valves. The 70-125 ton chillers have • Current readings taken directly from the
are: been “enhanced” over the previous Clear Language Display
• 99.5% reliable. reciprocating chiller offering. These • Factory installed condenser water
• High energy efficiency. enhancements include: temperature sensing kit option
• Low sound levels. • Evaporator water flow protection • Two line by 40 character Clear
• Compact size. • Bolt together construction Language Display
• Bolt-together construction. • Hot gas bypass eliminated (unlike • Liquid line valve, suction valve and
• Low maintenance. typical reciprocating) discharge valve standard
• Dual independent refrigerant circuits. • Refrigerant isolation valves standard
The Series R helical rotary chiller is an (both discharge and suction) on RTWA
industrial grade design built for the • Single point power on all units
commercial markets. It is ideal for • Low side relief valves
office buildings, hospitals, schools,
retailers and industrials.
Features Summary 53
The standard ARI rating condition
(54/44 F and 85 F/3.0 gpm) and IPLV are
ARI certified. All other ratings, Mechanical Specifications 54
including the following, are outside the
scope of the certification program and
are excluded:
• Glycol.
• 50 Hz.
• Condenserless models (RTUA). Water Chiller Systems Business Unit
3
Features
and
Benefits
Compact Size Optimum Efficiencies
• Designed with the retrofit and Unsurpassed Full Load Efficiency With
replacement market in mind.
• Fits through standard single-width Precise Rotor Tip Clearances — Higher
doors. energy efficiency in a Trane helical
rotary screw compressor is obtained by
• Bolt-together construction for easy unit reducing the rotor tip clearances. This
disassembly.
• Small footprint of Series R chiller
® reduces the leakage between high and
saves valuable equipment room space. low pressure cavities during
compression. Precise rotor tip
Simple Installation clearance is achieved with the latest
• Lightweight design simplifies rigging manufacturing and machining
requirements. Reduces cost and technology. Trane is the first helical
speeds installation time. rotary compressor manufacturer to
• Simplified piping; the only water piping electronically check compressor parts
required is for the evaporator and machining accuracy as part of the
condenser. standard production process.
• No oil cooler or purge system
connections. • Capacity control with unloader valves,
provides load matching such that the
• Simple power connection. need for hot gas bypass is eliminated.
• Standard unit mounted starter
eliminates additional jobsite labor • PID chilled water setpoint control
requirements. maintains chilled water supply to
• Extensive factory testing. within ± 1/2 degree F of setpoint.
• Full factory refrigerant and oil charge Optimized Compressor Parts Profiles
further reducing field labor, materials
— Rotors and load/unloader valves are
and installation cost.
unique designs, optimized for pressure
• Factory installed controls and options ranges in air conditioning applications.
are completely tested to maintain
The load/unloader valve has a unique
minimal start-up time and expenses.
profile that resulted from computer
Single-Source Reliability performance modeling in typical part
• RTUA compressor chillers can be load situations.
matched with RTCA air-cooled
Advanced Heat Transfer Surfaces —
condensers.
Condenser and evaporator tubes use
Adaptive Control™ Microprocessor the latest heat transfer technology for
• Optimizes efficiency increased efficiency.
• Prevents nuisance trip-outs
• Prevents unnecessary service calls and
unhappy tenants
Superior Microprocessor Control (for
further details see following pages)
• Over 90 diagnostic and operating
conditions
• Displays chiller temperatures and
pressures
• Trane Integrated Comfort™ system (ICS)
interface
4
Features
and
Benefits
Great Part Load Efficiency Figure F-2 — Trane Helical Rotary Screw Compressor
5
Features
and
Benefits
Figure F-5 — Compressor Parts: Reciprocating, Left, vs. Trane Helical Rotary Screw, Right
6
Features
and
Benefits
Superior Control Easy Chiller System Logging Easy Interface To The Building
The UCM displays data required to log Management System
Unit Control Module Controlling the 70-125 ton Series R
Trane’s Adaptive Control™ the chiller system. The clear language
display (CLD) eliminates diagnostic chillers with non-Trane building
microprocessor control system management systems is state-of-the-
enhances the Series R® chiller by codes. Information available with the
Adaptive Control microprocessor art yet simple.
providing the latest chiller control
technology. An improved easy-to-use includes: Chiller inputs include:
operator interface panel displays all • Entering and leaving chilled water • Chiller enable/disable
operating and safety diagnostics. temperatures • Circuit enable/disable
Adaptive Control microprocessor • Entering and leaving condenser water • Chilled water setpoint
features shut down the chiller only if temperatures (RTWA option) • Current limit setpoint
absolutely necessary. The Unit Control • Ambient air temperature (RTUA only) • Ice making enable
Module (UCM) anticipates potential • Evaporator and condenser refrigerant Chiller outputs include:
temperatures and pressures
problems and initiates corrective
• Compressor suction temperature • Compressor running indication
actions to prevent nuisance tripouts.
• Percent RLA for each compressor • Alarm indication (Ckt1/Ckt2)
• Percent line voltage • Maximum capacity
Unit Control Module • Compressor starts and running hours Trane Chiller Plant Manager™/ICS
Features • Active setpoints The Tracer® Chiller Plant Manager
Equal Compressor Sequencing — chilled water setpoint building management system provides
Trane maximizes compressor life by — current limit setpoint building automation and energy
equalizing both the number of starts — ice termination setpoint management functions through stand
and the operating hours on each — low ambient lockout setpoint alone control. The Chiller Plant
compressor. The UCM will start the • Over 90 diagnostic and operating Manager is capable of monitoring and
compressor with the least number of conditions controlling your entire chiller plant
starts and turn off the compressor with • Part Failure diagnostics system.
the most operating hours. — water temperature sensors Application software available:
— refrigerant temperature sensors
Conventional “auto” lead-lag control
— compressor contactors
• Time of day scheduling
will equalize starts, but running hours • Duty cycling
will typically be unequal. Equalizing Remote Display Panel • Demand limiting
both starts and running hours will Trane Series R chillers are available • Chiller sequencing
provide equal compressor wear. with a twisted wire pair connection to a • Process control language
remote display panel. Chiller operation • Boolean Processing
Internal “Built-in” Chiller can be controlled similarly to the • Zone Control
Flow Protection control interface on the chiller itself. • Reports and logs
The UCM automatically detects a no With a twisted wire pair, the unit can be • Custom messages
waterflow condition. An external flow turned on or off, the chilled water • Run time and maintenance
switch is not required, which lowers setpoint changed, and over 90 • Trend log
costs versus typical chillers. Also, operating and diagnostic conditions are • Totalizing
built-in flow protection eliminates displayed. Equally important, the • PID control loops
nuisance flow switch problems. remote display panel can monitor up to And of course, Trane’s Chiller Plant
four units. Manager panel can be used on a
standalone basis or tied into a
complete building automation system.
7
Model RTWA and RTUA
Number Packaged Chillers and
Description Compressor Chillers
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Digits 1,2 — Unit Model Digit 10,11 — Design Sequence Digit 17 — Compressor Type
RT = Rotary Chiller ** = (Factory Input) (Factory Assigned)
V = High volume or pressure ratio
Digit 3 — Unit Type Digit 12 — Evaporator Leaving Temperature W = Low volume or pressure ratio
W = Water-cooled packaged chiller 1 = Standard 40 to 65 F High Vi = If Digit 12 is 2 or if Digit 13 is E or F.
U = Compressor-chiller 2 = Low temp process (0-39 F) Low Vi = If Digit 12 is 1 or 3 and Digit 13 is
3 = Standard temp Ice making 20 to 65 F C or D.
Digit 4 — Development Sequence 4 = Low temp icemaking (0-39 F)
A = First Digit 18+ — Factory Installed or
Digit 13 — Condenser Configuration Factory Supplied Options
Digit 5,6,7 — Nominal Capacity C = Standard Efficiency D = Low ambient lockout sensor (1)
070 = 70 Tons D = High Efficiency Condenser F = Power disconnect
080 = 80 Tons E = Standard Efficiency, high temp Q= Rubber-in-shear isolators
090 = 90 Tons F = High Efficiency Condenser, high temp R = Remote display
100 = 100 Tons R = Remote Air-Cooled Condenser T = Condenser water temperature sensors(2)
110 = 110 Tons S = Special H = Unit sound attenuator
125 = 125 Tons Y = Condenser refrigerant sensors (3)
Digit 14 — Agency Listing
Digit 8 — Unit Voltage 0 = No Agency Listing Digits 18+ may be multiple independent add
A = 200/60/3 3 = C/UL Listed on options.
C = 230/60/3
D = 380/60/3 Digit 15 — Control Interface Notes:
4 = 460/60/3 C = Deluxe without communication 1) Either RTCA or non-RTCA condensers
5 = 575/60/3 D = Deluxe with communication 2) RTWA only
S = Special Customer Option 3) Use only with RTUA and non-RTCA
Digit 16 — Chilled Water Reset condensers
Digit 9 — Compressor Start Type 0 = No chilled water reset
Y = Y-Delta Closed Transition 1 = Based on return water temperature
X = X-Line (Across the Line) 2 = Based on outside air temperature
S = Special
Model RTCA
Number Air-Cooled Condenser
Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Digits 1,2 — Unit Model Digit 9 — Compressor Starter Type Digit 15 — Control Interface
RT = Rotary Chiller Y = Y-Delta Closed Transition C = Deluxe without Communication
X = X-Line (Across the Line) D = Deluxe with Communication
Digit 3 — Unit Type S = Special * = Not Applicable
C = Air Cooled Condenser * = Not Applicable
Digit 16 — Chilled Water Reset
Digit 4 — Development Sequence Digit 10, 11 — Design Sequence 0 = No Chilled Water Reset
A = First Sequence ** = Factory Input 1 = Based on Return Water Temperature
2 = Based on Outside Air Temperature
Digit 5, 6 & 7 — Nominal Capacity Digit 12 — Evaporator Leaving Temperature * = Not Applicable
070 = 70 tons 1 = Standard 40 to 65 F
080 = 80 tons 2 = Low 0 to 39 F Digit 17 — Miscellaneous Factory Installed
090 = 90 tons 3 = Ice-Making 20 to 65 F Options
100 = 100 tons S = Special A = Architectural Louvered Panels
110 = 110 tons * = Not Applicable D = Low Ambient Lockout Sensor
125 = 125 tons G = Low Ambient Operation
Digit 13 — Condenser Coil Fin Material K = Coil Protection
Digit 8 — Unit Voltage A = Aluminum M = Access Guard
A = 200/60/3 S = Special
C = 230/60/3 Field Installed Options
D = 380/60/3 Digit 14 — Agency Listing Q = Spring Isolators
4 = 460/60/3 0 = No Agency Listing N = Neoprene Isolators
5 = 575/60/3 1 = C/UL Listing 8 = Architectural Louvered Panels
S = Special 9 = Coil Protection
0 = Access Guard
8
General
Data
9
General
Data
10
Selection
Procedure
The 70-125 ton water-cooled Series R® General Data Tables Integrated Part Load Performance
chiller and compressor chiller General unit data is shown in the data The Integrated Part Load Value (IPLV) is
performance is rated in accordance section. General unit information a method of measuring total chiller
with ARI Standard 550/590-98 includes refrigerant charge (RTWA performance over a defined range of
Certification Program. The 70-125 ton only), oil charge, shipping weight and part load conditions. This method was
water-cooled chiller product line operating weight. Also evaporator and established by ARI and is included in
provides numerous individual unit condenser data, including water ARI Standard 550/590-98. IPLV serves
selections over a capacity range of storage capacities, and minimum and as a good method of comparing the
70-125 tons. maximum flow limits. If the maximum part load efficiency of various chillers
Performance flow limit is exceeded, tube erosion on an equal basis. The formula for
The performance examples, on the may result. Flow rates less than the calculating IPLV is defined as:
following pages provide performance specified minimum result in laminar IPLV = .01A + .42B + .45C + .12D
information at various tonnages, flow with a reduction in performance,
as well as potential for increased Where:
including capacity in tons, efficiency A = EER at 100% load point
and water pressure drops. All fouling and corrosion.
B = EER at 75% load point
capacities are net tons and are based Evaporator and Condenser Pressure C = EER at 50% load point
on fouling factors of 0.00010 for the Drop Curves D = EER at 25% load point
evaporator and 0.00025 for the Located in the data section, pressure
condenser (RTWA) watersides. Unit drop data is provided for both To approximate total energy
performance at nonstandard fouling evaporators and condensers requirements over a period of time, use
factors may vary from standard (RTWA only). of a computerized load and
performance. See Table P-21 for fouling performance program that considers
Part Load Performance air conditioning load, machine
factor adjustments. The 70-125 ton water-cooled Series R performance, cooling tower
Dimensional Drawings chiller and compressor chillers possess performance (RTWA), outside wet bulb
The dimensional drawings illustrate excellent part load performance temperature and ambient temperature
overall measurements of the unit. The characteristics. Air conditioning system (RTUA) is suggested. Contact the local
recommended service clearances loads usually are significantly less than Trane sales office for more information
indicate clearances required to easily full load design conditions. Therefore, on these computerized programs.
service the 70-125 ton water-cooled the chillers seldom operate at full load.
chiller and compressor chiller. All The 70-125 ton Series R chillers can
catalog dimensional drawings are provide significant operating savings.
subject to change. Current submittal Part load chiller operation is normally
drawings should be referred to for associated with reduced condenser
detailed dimensional information. water temperatures (RTWA only) and
Contact the local Trane sales office for reduced ambient temperatures (RTUA
submittal and template information. only). At part load operation, the heat
Electrical Data Tables rejected to the cooling tower is less
Electrical data is shown in the data than at full load operation. Also, part
section of the appropriate chiller family. load operation is typically associated
A voltage utilization range is tabulated with reduced outside wet bulb
for each voltage listed. The 70-125 ton temperatures, resulting in improved
Series R compressor motors are cooling tower performance (RTWA).
designed to operate satisfactorily over Part load operation associated with
a range of ± 10 percent of the standard reduced ambient temperatures results
design voltages of 200 volt, 230 volt, in improved compressor chiller
460 volt and 575 volt for 60 cycle, performance (RTUA).
3 phase motors.
To properly size field electrical wiring,
the electrical engineer or contractor on
a project needs to know the minimum
circuit ampacity (MCA) of the 70-125
ton Series R chillers. The National
Electrical Code (NEC), Article 440-33,
defines the method of calculating the
minimum circuit ampacity. These
values have been calculated and are
provided in the electrical data tables.
11
Selection
Procedure
The chiller capacity tables presented in Condenser flow rates can be To determine the condenser pressure
this catalog cover the most frequently determined by using the following drop we use the flow rate (GPM) and
encountered leaving water formulas: the condenser water pressure drop
temperatures. The tables reflect a 10 F GPM = curves, Figure P-2 and P-3. For a
(5.6 C) temperature drop through the 24 x (Tons + (.285 x Compressor kW)) standard length condenser, enter the
evaporator. For temperature drops Condenser Water Temperature Drop curve (in Figure P-3) at 220 GPM, the
other than 10 F (5.6 C), refer to pressure drop for a nominal 70 ton
Table P-21, and apply the appropriate or L/S = standard length condenser is 16.5 feet.
Performance Data Adjustment Factors. 1.5 x (Tons + Compressor kW)) 4
For chilled brine selections, refer to Condenser Water Temp. Drop (°C) For selections where the temperature
Figures PAF-1 and PAF-2 for Ethylene Condenser pressure drops can be drop is different than 10 F, the
Glycol and Propylene Glycol obtained from Figures P-2 and P-3. performance adjustment factors shown
Adjustment Factors. in Table P-21 should be applied at this
Selection Example point.
For example: Given: 5
Corrected Capacity = Capacity Required System Load = 73.5 Tons The final unit selection is:
(unadjusted) x Glycol Capacity
Adjustment Factor Leaving Chilled Water Temperature QTY (1) RTWA 70 Standard
(LCWT) = 44 F Cooling Capacity = 73.6 tons*
Corrected Flow Rate = Flow Rate
(unadjusted) x Glycol Flow Rate Temperature Drop = 10 F Design Entering/Leaving Chilled Water
Adjustment Factor (Both evap and condenser) Temperatures = 54/44 F
To select a Trane water-cooled Entering Condenser Water = 85 F Chilled Water Flow Rate = 177 GPM
Series R® chiller, the following Evaporator Fouling Factor = 0.00010 Evaporator Water Pressure Drop =
information is required: 1 15 Feet
1 From Table P-1 (RTWA 70 Standard
Design load in tons of refrigeration Performance Data), an RTWA 70 at the Entering/Leaving Condenser Water
2 given conditions will produce 73.6 tons Temperatures = 85/95
Design chilled water temperature drop with a compressor power input of 63.2 Condenser Water Flow Rate =
or GPM kW and a unit EER of 14.0. 220 GPM
3 2
Design leaving chilled water To calculate the required chilled water Condenser Water Pressure Drop =
temperature flow rate we use the formula given 16.5 Feet
4 below: Compressor Power Input = 63.2 kW
Design entering condenser water GPM = 73.6 x 24 = 177 GPM Unit EER = 14.0
temperature 10 F
Minimum Leaving Chilled Water
Evaporator flow rates can be To calculate the required condenser Temperature Setpoint
determined by using the following water flow rate we use the formula The minimum leaving chilled water
formulas: given below: temperature setpoint for water is 40 F.
GPM = GPM = For those applications requiring 0-39 F
Tons x 24 24 x (tons + (.285 x compressor kW)) fluid setpoints, a glycol solution must
Temperature Drop (Degrees F) Condenser water temperature drop be used. Contact the local Trane Sales
or L/S = = 220 Engineer for additional information.
kW (Capacity) x .239 3
Temperature Drop (Degrees C) To determine the evaporator pressure
NOTE: Flow rates must fall within the drop we use the flow rate (GPM) and
limits specified in Tables G-1 or G-2 the evaporator water pressure drop
(for GPM or for L/S). curves, Figure P-1. Entering the curve at
177 GPM, the pressure drop for a
Evaporator pressure drops can be nominal 70 ton evaporator is 15 feet.
obtained from Figure P-1.
Note: Use same procedure for RTUA compressor chillers; exclude condenser portion.
12
Selection
Procedure
Compressor Chiller — (RTUA with no Step 3a: Select a condenser that Step 4: In ACDS-DS-1 enter Chart 9-1 at
cataloged condensers) appears to meet the tonnage the appropriate condensing
Selection procedure when matching requirements. temperature and ambient temperature
RTUA with non-RTCA condensers. to determine increase in capacity due
When selecting a combination of
• Select CAUC-C80 (upflow air-cooled to subcooling.
condenser)
equipment or conditions which are not Percent increase in capacity due to
cataloged, it becomes necessary to Step 3b: Plot two gross heat rejection
points (ACDS-DS-1) divided by the subcooling for an ambient temperature
match the compressor and condenser of 95 F and a condensing temperature
performance. The following procedure appropriate N value (Table 13-1).
of 124 F is 9.5%.
can be used in selecting the correct By selecting points at 25 F and 35 F
condenser. initial temperature different (ITD = 875 * 1.0975 = 960 MBh
Example: condensing temp. - ambient temp.), the Step 5: From performance data charts,
following table is constructed determine kW of compressor-
Given: condenser at condensing temperatures
1 Cond. Cond. Gross Heat Rejection
of 124 F.
Total cooling load = 78 tons (936 MBh) ITD Temp. MBh
25 F 120 950 MBh = 960
2 kW = 86
35 F 130 1350
Leaving Chiller Water = 45 F
3 Divide gross heat rejection by the Values Of “N” (RTUA)
Design air temperature entering appropriate N value to get net capacity. Cond. Leaving Chilled Water Temperature
coil = 95 F (See table below.) Temp. 40 45 50
4 85 1.14 1.12 1.10
Leaving 95 1.16 1.14 1.13
Altitude = sea level Water Cond. GHP/N 105 1.19 1.17 1.15
5 Temp. Temp. N in MBh 115 1.24 1.21 1.18
Refrigerant = HCFC 22 45 F 120 F 1.24 766 125 1.19 1.26 1.22
45 F 130 F 1.29 1047 135 1.36 1.32 1.28
Select a compressor-chiller/condenser
145 1.46 1.39 1.35
combination to satisfy design Resultant capacity is 875 at a
requirements (assuming component condensing temperature of 124 F.
performance is not cataloged).
The procedure is outlined as follows:
Step 1: Select a compressor-chiller that Chart S-1 — Compressor-Chiller/Condenser Performance
appears to meet tonnage
requirements.
• Select RTUA 80 (2-40 ton circuits)
Step 2: Plot at least two gross
compressor-chiller capacities, less
subcooling at the design leaving water
temperature, and different condensing
temperatures as shown on Chart S-1.
• From performance data, the following
points are plotted for RTUA 80:
To subtract capacity increase due to
subcooling reduce catalog capacity by
five percent (for every 10 F of
subcooling).
Leaving
Water Cond MBh Deg MBh
Temp. Temp. w/Subclg. Subclg. Less Subclg
45 F 115 981 10 F 932
45 F 135 865 10 F 821
13
Application
Considerations
14
Performance
Data
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 264.4 57.6 4.6 251.9 63.7 4.0 238.3 70.3 3.4
8 281.3 58.4 4.8 267.9 64.4 4.2 253.4 71.1 3.6
10 298.4 59.1 5.0 284.2 65.2 4.4 268.8 71.8 3.7
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 269.5 54.4 5.0 257.5 60.3 4.3 244.3 66.7 3.7
8 286.8 55.1 5.2 274.1 60.9 4.5 260.1 67.3 3.9
10 304.7 55.7 5.5 291.1 61.5 4.7 276.2 67.9 4.1
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
15
Performance
Data
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 304.4 64.3 4.7 290.5 71.3 4.1 275.5 79.2 3.5
8 324.2 65.0 5.0 309.3 72.1 4.3 293.3 80.2 3.7
10 344.6 65.9 5.2 328.8 73.1 4.5 311.8 81.2 3.8
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 309.6 61.0 5.1 296.3 67.7 4.4 281.7 75.2 3.7
8 330.1 61.6 5.4 315.8 68.3 4.6 300.2 76.0 4.0
10 351.3 62.2 5.6 336.0 69.1 4.9 319.4 76.8 4.2
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
16
Performance
Data
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 351.1 74.8 4.7 335.6 82.2 4.1 318.7 90.6 3.5
8 373.4 75.9 4.9 356.9 83.3 4.3 339.0 91.7 3.7
10 396.5 77.0 5.1 378.9 84.5 4.5 360.1 92.9 3.9
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 357.2 71.4 5.0 342.2 78.5 4.4 325.7 86.5 3.8
8 380.2 72.4 5.3 364.2 79.4 4.6 346.8 87.5 4.0
10 404.0 73.4 5.5 387.0 80.5 4.8 368.6 88.5 4.2
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
17
Performance
Data
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 394.9 84.8 4.7 377.9 92.6 4.1 359.3 101.4 3.5
8 419.6 86.2 4.9 401.6 93.9 4.3 382.1 102.7 3.7
10 445.2 87.6 5.1 426.2 95.3 4.5 405.7 103.9 3.9
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 401.6 81.5 4.9 385.1 88.9 4.3 367.1 97.4 3.8
8 427.0 82.8 5.2 409.5 90.1 4.5 390.5 98.5 4.0
10 453.4 84.2 5.4 434.9 91.4 4.8 414.9 99.6 4.2
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
18
Performance
Data
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 424.7 91.9 4.6 406.5 100.4 4.0 386.7 109.9 3.5
8 451.4 93.4 4.8 432.1 101.8 4.2 411.3 111.3 3.7
10 479.1 95.0 5.0 458.8 103.2 4.4 436.9 112.6 3.9
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 431.7 88.4 4.9 414.1 96.5 4.3 397.8 105.7 3.8
8 459.1 89.8 5.1 440.4 97.8 4.5 420.1 106.9 3.9
10 487.6 91.3 5.3 467.8 99.2 4.7 446.5 108.2 4.1
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
19
Performance
Data
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 460.9 99.2 4.6 441.1 108.4 4.1 419.6 118.6 3.5
8 490.0 100.9 4.9 469.0 109.9 4.3 446.3 120.1 3.7
10 520.1 102.6 5.1 498.0 111.5 4.5 474.2 121.6 3.9
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
Metric
Entering Condenser Water Temperature (Degrees C)
LWT 25 30 35
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP
6 468.4 95.6 4.9 449.2 104.3 4.3 428.2 114.2 3.7
8 498.3 97.2 5.1 477.9 105.7 4.5 455.8 115.5 3.9
10 529.3 98.8 5.4 507.8 107.2 4.7 484.5 116.9 4.1
Notes:
1. Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the
condenser.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
20
Performance
Data
21
Performance
Data
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 251.4 74.5 3.4 235.6 80.0 2.9 219.3 86.1 2.5 202.8 92.9 2.2
8 268.1 76.0 3.5 251.6 81.5 3.1 234.8 87.7 2.7 217.6 94.6 2.3
10 283.4 78.1 3.6 268.2 83.1 3.2 250.7 89.4 2.8 232.9 96.4 2.4
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 287.4 86.2 3.3 269.8 92.6 2.9 251.7 99.4 2.5 233.2 107.3 2.2
8 307.0 88.4 3.5 288.5 94.8 3.0 269.6 101.9 2.6 250.2 109.6 2.3
10 325.1 91.4 3.6 307.9 97.1 3.2 288.0 104.2 2.8 267.8 112.0 2.4
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
22
Performance
Data
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 318.9 101.2 3.2 299.8 108.1 2.8 279.9 116.0 2.4 259.6 124.8 2.1
8 339.8 103.8 3.3 319.8 110.7 2.9 299.0 118.6 2.5 277.6 127.4 2.2
10 359.1 107.3 3.4 340.3 113.5 3.0 318.5 121.4 2.6 296.2 130.2 2.3
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 347.3 115.8 3.0 326.9 123.4 2.6 305.6 132.1 2.3 283.5 141.9 2.0
8 369.4 118.8 3.1 348.0 126.3 2.8 325.6 135.1 2.4 302.5 144.9 2.1
10 389.7 122.8 3.2 369.7 129.5 2.9 346.2 138.2 2.5 322.0 148.0 2.2
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
23
Performance
Data
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 374.2 124.9 3.0 352.2 133.1 2.7 329.2 142.6 2.3 305.4 153.3 2.0
8 398.1 128.2 3.1 375.0 136.4 2.7 350.9 145.9 2.4 326.0 156.6 2.1
10 420.0 132.6 3.2 398.5 139.8 2.8 373.2 149.3 2.5 347.1 160.0 2.2
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 405.8 135.2 3.0 381.8 144.1 2.6 356.7 154.4 2.3 330.7 166.0 2.0
8 431.7 138.8 3.1 406.5 147.7 2.8 380.2 158.1 2.4 353.0 169.7 2.1
10 455.5 143.7 3.2 432.0 151.6 2.8 404.3 161.8 2.5 375.8 173.4 2.2
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6 C.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
24
Performance
Data
25
Performance
Data
26
Performance
Data
27
Performance
Data
Figure P-4 — RTUA 35-Ton Circuit (MBH vs. LWTE) Figure P-5 — RTUA 35-Ton Circuit (kW vs. LWTE)
Figure P-6 — RTUA 40-Ton Circuit (MBH vs. LWTE) Figure P-7 — RTUA 40-Ton Circuit (kW vs. LWTE)
28
Performance
Data
Figure P-8 — RTUA 50-Ton Circuit (MBH vs. LWTE) Figure P-9 — RTUA 50-Ton Circuit (kW vs. LWTE)
Figure P-10 — RTUA 60-Ton Circuit (MBH vs. LWTE) Figure P-11 — RTUA 60-Ton Circuit (kW vs. LWTE)
29
Performance
Adjustment
Factors
Table PAF-1 — Pressure Drop Correction Factor
Fluid % Ethylene Glycol
Temp. F 0 10 20 30 40 50
0 NA NA NA NA 1.50 1.60
10 NA NA NA 1.38 1.46 1.55
20 NA NA 1.26 1.34 1.42 1.51
30 NA 1.15 1.22 1.30 1.38 1.47
40 1.00 1.12 1.19 1.26 1.34 1.42
50 1.00 1.09 1.16 1.23 1.31 1.39
60 1.00 1.05 1.09 1.12 1.16 1.21
Figure PAF-1 — Ethylene Glycol Performance Factors Figure PAF-2 — Propylene Glycol Performance Factors
30
Electrical RTWA
Data
31
Electrical RTUA and RTWA
Data
32
Electrical RTCA
Data
33
Jobsite RTWA
Connections
34
Jobsite RTUA and RTWA
Connections
35
Jobsite
Connections
NOTES:
1. DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY OTHERS.
CHECK SALES ORDER TO DETERMINE IF WIRING IS REQUIRED FOR
SPECIFIC OPTIONS.
2. ALL THREE PHASE MOTORS SUPPLIED WITH THE UNIT ARE PROTECTED
UNDER PRIMARY SINGLE PHASE FAILURE CONDITIONS.
3. CAUTION - DO NOT ENERGIZE UNIT UNTIL CHECK OUT AND START-UP WIRING
PROCEDURES HAVE BEEN COMPLETED. 8 ALL CUSTOMER CONTROL CIRCUIT WIRING MUST HAVE A MINIMUM RATING OF 150
4 THE FOLLOWING CAPABILITIES ARE OPTIONAL - THEY ARE VOLTS.
IMPLEMENTED AND WIRED AS REQUIRED FOR A SPECIFIC SYSTEM 9. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
APPLICATION. (NEC), STATE, AND LOCAL REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER
A ICE-MACHINE CONTROL (CANNOT BE USED WITH OPT. L) COUNTRIES APPLICABLE NATIONAL AND/OR LOCAL REQUIREMENTS SHALL APPLY.
B COMMUNICATIONS INTERFACE REQUIRED WIRING
D WYE-DELTA CLOSED TRANSITION STARTER 10 COPPER WIRE ONLY – SIZED PER N.E.C. – BASED ON NAMEPLATE MINIMUM CIRCUIT
AMPACITY (MCA). SEE CUSTOMER WIRE SELECTION TABLE.
E DELETED
11 2 WIRES, 115 VAC CIRCUIT. MINIMUM CONTACT RATING AT 115 VAC – 5.9 VA INRUSH.
H UNIT DISCONNECT, NON-FUSED
1.3 VA SEALED.
J CHILLED WATER RESET - RETURN WATER
12 DELETED
K CHILLED WATER RESET - OUTDOOR AIR
OPTIONAL WIRING:
L CHILLED WATER RESET - ZONE AIR (CANNOT BE USED WITH OPT. A)
14 3 WIRES. 115 VAC CIRCUIT. SEPARATE 115 VAC POWER SUPPLY IS REQUIRED. LOAD
O LOW AMBIENT LOCKOUT NOT TO EXCEED 1150 VA INRUSH, 115 VA SEALED.
S CHILLED WATER FLOW SWITCH (NOT REQUIRED FOR CHILLER 15 2 WIRES. 115 VAC CIRCUIT. MINIMUM CONTACT RATING AT 115 VAC - 6.9 VA INRUSH,
PROTECTION) 1.3 VA SEALED.
T REMOTE CLEAR LANGUAGE DISPLAY. 16 2 WIRES. 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN CONDUIT WITH HIGHER
(BUFFER FOR DISPLAY LOCATED IN UNIT CONTROL PANEL.) VOLTAGE CIRCUITS. SEE CUSTOMER WIRE SELECTION TABLE.
17 SHIELDED TWISTED PAIR, 30 VOLT OR LESS CIRCUIT. MAXIMUM LENGTH 5000 FEET.
5. AUXILIARY CONTROLS FOR A CUSTOMER SPECIFIED OR INSTALLED DO NOT RUN IN CONDUIT WITH HIGHER VOLTAGE CIRCUITS. SEE CUSTOMER WIRE
LATCHING TRIPOUT. THE CHILLER WILL RUN NORMALLY WHEN THE SELECTION TABLE. BELDON TYPE 8760 RECOMMENDED.
CONTACT IS CLOSED AND TRIP THE CHILLER OFF ON MANUALLY 18 CUSTOMER SUPPLIED CONTACTS MUST BE COMPATIBLE WITH DRY CIRCUIT 12 VDC,
RESETTABLE DIAGNOSTIC WHEN THE CONTACT OPENS. MANUAL RESET 45 mA RESISTIVE LOAD. SILVER OR GOLD PLATED CONTACTS ARE RECOMMENDED.
IS ACCOMPLISHED AT THE LOCAL OR REMOTE CLEAR LANGUAGE
19 CHILLER MODULE (1U1) RELAY OUTPUTS (K1, K2, K3) CAN BE PROGRAMMED TO
DISPLAY.
PERFORM ALTERNATE FUNCTIONS, FUNCTION #1 IS SHOWN. SEE INSTALLATION,
6 AUXILIARY CONTROLS FOR A CUSTOMER SPECIFIED OR INSTALLED OPERATION AND MAINTENANCE MANUAL FOR DETAILS.
REMOTE AUTO/STOP FUNCTION. THE CHILLER WILL RUN NORMALLY
WHEN THE CONTACT IS CLOSED AND STOP THE CHILLER WHEN THE
CONTACT IS OPEN. RE-CLOSURE OF THE CONTACT WILL PERMIT THE
CHILLER TO AUTOMATICALLY RETURN TO NORMAL OPERATION. TO BE
IN SERIES WITH WATER PUMP RELAY (5K21). NOTE: DO NOT USE
CHILLED WATER PUMP TO STOP THE CHILLER.
7 NORMALLY OPEN CONTACTS FOR REMOTE SHUTDOWN OR
REFRIGERANT CIRCUIT OPERATION. THE REFRIGERANT CIRCUIT WILL GO
THRU A NORMAL SHUTDOWN WHEN THE CONTACTS ARE CLOSED AND
WILL AUTOMATICALLY RESUME NORMAL START AND RUN MODES
WHEN CONTACTS ARE OPEN.
36
Jobsite
Connections
NOTES:
1. DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY OTHERS. CHECK SALES
ORDER TO DETERMINE IF WIRING IS REQUIRED FOR SPECIFIC OPTIONS.
2. ALL THREE PHASE MOTORS SUPPLIED WITH THE UNIT ARE PROTECTED UNDER
PRIMARY SINGLE PHASE FAILURE CONDITIONS.
WIRING
3. CAUTION - DO NOT ENERGIZE UNIT UNTIL CHECK OUT AND START-UP PROCEDURES
HAVE BEEN COMPLETED. 8 ALL CUSTOMER CONTROL CIRCUIT WIRING MUST HAVE A MINIMUM RATING OF 150 VOLTS.
4 THE FOLLOWING CAPABILITIES ARE OPTIONAL - THEY ARE IMPLEMENTED AND WIRED 9. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), STATE, AND
AS REQUIRED FOR A SPECIFIC SYSTEM APPLICATION. LOCAL REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER COUNTRIES APPLICABLE NATIONAL AND/OR
A ICE-MACHINE CONTROL (CANNOT BE USED WITH OPT. L) LOCAL REQUIREMENTS SHALL APPLY.
REQUIRED WIRING
B COMMUNICATIONS INTERFACE
D WYE-DELTA CLOSED TRANSITION STARTER 10 COPPER WIRE ONLY – SIZED PER N.E.C. – BASED ON NAMEPLATE MINIMUM CIRCUIT AMPACITY (MCA). SEE
CUSTOMER WIRE SELECTION TABLE.
E DELETED
11 2 WIRES, 115 VAC CIRCUIT. MINIMUM CONTACT RATING AT 115 VAC – 5.9 VA INRUSH. 1.3 VA SEALED.
H UNIT DISCONNECT, NON-FUSED
OPTIONAL WIRING:
J CHILLED WATER RESET - RETURN WATER
14 3 WIRES. 115 VAC CIRCUIT. SEPARATE 115 VAC POWER SUPPLY IS REQUIRED. LOAD NOT TO EXCEED 1150 VA
K CHILLED WATER RESET - OUTDOOR AIR INRUSH, 115 VA SEALED.
L CHILLED WATER RESET - ZONE AIR (CANNOT BE USED WITH OPT. A) 15 2 WIRES. 115 VAC CIRCUIT. MINIMUM CONTACT RATING AT 115 VAC - 6.9 VA INRUSH, 1.3 VA SEALED.
O LOW AMBIENT LOCKOUT 16 2 WIRES. 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN CONDUIT WITH HIGHER VOLTAGE CIRCUITS. SEE
S CHILLED WATER FLOW SWITCH (NOT REQUIRED FOR CHILLER CUSTOMER WIRE SELECTION TABLE.
PROTECTION) 17 SHIELDED TWISTED PAIR, 30 VOLT OR LESS CIRCUIT. MAXIMUM LENGTH 5000 FEET. DO NOT RUN IN CONDUIT
T REMOTE CLEAR LANGUAGE DISPLAY. WITH HIGHER VOLTAGE CIRCUITS. SEE CUSTOMER WIRE SELECTION TABLE. BELDON TYPE 8760
(BUFFER FOR DISPLAY LOCATED IN UNIT CONTROL PANEL.) RECOMMENDED.
5 AUXILIARY CONTROLS FOR A CUSTOMER SPECIFIED OR INSTALLED LATCHING 18 CUSTOMER SUPPLIED CONTACTS MUST BE COMPATIBLE WITH DRY CIRCUIT 12 VDC, 45 mA RESISTIVE LOAD.
TRIPOUT. THE CHILLER WILL RUN NORMALLY WHEN THE CONTACT IS CLOSED AND SILVER OR GOLD PLATED CONTACTS ARE RECOMMENDED.
TRIP THE CHILLER OFF ON MANUALLY RESETTABLE DIAGNOSTIC WHEN THE CONTACT 19 CHILLER MODULE (1U1) RELAY OUTPUTS (K1, K2, K3) CAN BE PROGRAMMED TO PERFORM ALTERNATE
OPENS. MANUAL RESET IS ACCOMPLISHED AT THE LOCAL OR REMOTE CLEAR FUNCTIONS, FUNCTION #1 IS SHOWN. SEE INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR
LANGUAGE DISPLAY. DETAILS.
6 AUXILIARY CONTROLS FOR A CUSTOMER SPECIFIED OR INSTALLED REMOTE AUTO/ 20 9 WIRES, 115 VAC CIRCUIT. USE #16 AWG MINIMUM.
STOP FUNCTION. THE CHILLER WILL RUN NORMALLY WHEN THE CONTACT IS CLOSED
AND STOP THE CHILLER WHEN THE CONTACT IS OPEN. RE-CLOSURE OF THE CONTACT 21 3 WIRES, 115 VAC CIRCUIT. MINIMUM CONTACT RATING AT 115 VAC - 180 VA INRUSH, 1150 VA SEALED.
WILL PERMIT THE CHILLER TO AUTOMATICALLY RETURN TO NORMAL OPERATION. TO 22 1 RUNS OF 8 CONDUCTOR #22 AWG 300V 80 C, 100% SHIELDED, RECOMMEND BELDON 9305 OR EQUIVALENT.
BE IN SERIES WITH WATER PUMP RELAY (5K21). NOTE: DO NOT USE THE CHILLED OR 3 RUNS OF 2 CONDUCTOR #18 AWG 300V 80 C, 100% SHIELDED, RECOMMENDED BELDEN 8780 OR
WATER PUMP TO STOP THE CHILLER. EQUIVALENT.
7 NORMALLY OPEN CONTACTS FOR REMOTE SHUTDOWN OR REFRIGERANT CIRCUIT 23 1 RUNS OF 8 CONDUCTOR #22 AWG 300V 80 C, 100% SHIELDED, RECOMMEND BELDON 9305 OR EQUIVALENT.
OPERATION. THE REFRIGERANT CIRCUIT WILL GO THRU A NORMAL SHUTDOWN WHEN OR 4 RUNS OF 2 CONDUCTOR #18 AWG 300V 80 C, 100% SHIELDED, RECOMMENDED BELDEN 8780 OR
THE CONTACTS ARE CLOSED AND WILL AUTOMATICALLY RESUME NORMAL START EQUIVALENT.
AND RUN MODES WHEN CONTACTS ARE OPEN.
37
Controls Microcomputer
Controls
The 70-125 ton water-cooled Series R® Additionally, the UCM optimizes total 3
chillers and compressor chillers chiller power consumption during Chilled Water Pump Control
employ the most advanced controls on normal operating conditions. During Unit controls provide an output to
the market today. The two line by 40 abnormal operating conditions, the control chilled water pump(s). One
character clear language display (CLD) UCM will continue to optimize chiller contact closure to the chiller is all that is
has a backlight for simple readout. performance by taking the corrective required to initiate the chilled water
Adaptive Control™ Microcomputer action necessary to avoid shutdown. system.
The microcomputer-based controller This keeps cooling capacity available Optional Features
optimizes controls around the chiller until the problem can be solved. 1
application and the specific Whenever possible, the chiller is Communication Interface
components used in the Series R allowed to perform its function; make Capability for communication with the
chiller. For instance, the compressor chilled water. In addition, following control device:
protection system is specifically microcomputer controls provide safety a
designed for the Series R unit. A protections such as under/over voltage Trane Tracer® Building Automation
leaving chilled water temperature (option), phase reversal, phase loss, Systems
control algorithm maintains accurate phase imbalance, low voltage and 2
temperature control, minimizes the overload protection. These, safety External Chilled Water Setpoint
drift from setpoint and provides better controls help the chiller to remain in Allows the external setting
building comfort. The microprocessor operation and all of the building independent of the front panel point by
control incorporates improved chiller occupants satisfied. one of three means:
start-up, load limiting, lead/lag, and Monitoring and Diagnostics a) a remote resistor input (fixed or
compressor run time equalization Since the microcomputer provides all adjustable), b) a 2-10 volt DC input, or
functions into standard chiller control functions, it can easily indicate c) a 4-20 mA input.
operation. Interface with building such parameters as leaving chilled 3
automation systems remains flexible water temperature. All of the External Current Limit Setpoint
and easy. monitoring and diagnostic information Allows the external setting
Simple Interface with Other Control is displayed directly on a clear independent of the front panel setpoint
Systems language microcomputer display. If a by one of three means: a) a remote
Microprocessor controls afford simple failure does occur, one of many clear resistor input (fixed or adjustable),
interface with other control systems, language display messages will b) a 2-10 volt DC input, or c) a 4-20 mA
such as time clocks, building indicate the problem. input.
automation systems and ice storage Simple Interface with Other Control 4
systems. Wiring to the chiller can be as Systems Remote Running and Alarm Indication
simple as two wires! This means you The microcomputer controls on 70-125 Contacts
can have the flexibility to meet job ton Series R chillers easily interface The chiller provides three single-pole
requirements while not having to learn with several external control systems. double-throw contact closures to
a complicated control system. These control systems include: Trane indicate that a failure has occurred, if
Integrated Comfort™ systems, other any compressors are running, or if the
Safety Controls compressors are running at maximum
A centralized microcomputer provides manufacturer’s building automation
systems, time clocks for standalone capacity. These contact closures may
a high level of machine protection. The be used to trigger jobsite supplied
safety controls are designed to avoid units, ice storage systems and control
from a remote display panel. Each alarm lights or alarm bells.
compressor and/or evaporator 5
operation failures, to minimize system description includes a list of
those features which can be used, and Ice Making Control
nuisance shutdowns. The Unit Control Provides interface with ice making
Module (UCM) directly senses the which external Trane device is required.
Wiring to the unit can be as simple as control systems
control variables that govern the 6
operation of the chiller: motor current two wires.
Chilled Water Temperature Reset
draw, evaporator temperature, Standard Features Reset can be based on return water
condenser temperature, etc. When any 1 temperature or outdoor air
one of the variables approaches a limit External Auto/Stop temperature.
condition where the chiller may be A jobsite provided contact closure will
shutdown to avoid damage, the UCM turn the chiller on and off. Note: Do The next section reviews the
takes corrective action to avoid not use the chilled water pump to stop recommended interface with the
shutdown and keep the chiller the chiller following control systems:
operating. Corrected action is 2 Integrated Comfort system interface
accomplished through combined External Interlock non-Trane building automation
actions of compressor unloader valve A jobsite supplied contact opening systems
modulation, electronic expansion valve wired to this input will turn the chiller Standalone chillers
modulation. off and will require a manual reset of Ice making systems
the chiller microcomputer. This closure Remote display
is typically triggered by a jobsite
supplied system such as a fire alarm.
38
Controls Microcomputer
Controls
Trane Integrated Comfort™ System Required Features: In addition, the signals may be
Interface (ICS) 1 — External Auto/Stop (standard) provided over the twisted wire pair
A single twisted pair of wires tie 2 — Chilled Waterflow Interlock from a Tracer system. The chiller
directly between the 70-125 ton (standard) provides outputs to turn water pumps
Series R® chiller and a Tracer® system. Additional Features That May Be Used: on and off.
A Tracer system provides elaborate 1— Remote Running and Alarm Required Features
control, monitoring and diagnostic Indication Contacts 1 — External Auto/Stop (standard)
capabilities. When the Series R chillers 2 — External Interlock (Standard) 2 — Ice making Control
are used in conjunction with a Trane 3 — Chilled Water Temperature Reset
Tracer system, the chiller can be Additional Features
monitored and controlled from a External Trane Devices Required: 1 — Remote running and failure
remote location. The Series R chiller NONE indication contacts
can be controlled to fit into the overall Note: All wiring outside the unit is 2 — Communications Interface
building automation strategy by using supplied at the jobsite. (For Tracer systems)
time of day scheduling, timed override, 3 — Chilled Water Temperature reset
duty cycling, demand limiting, and Interface with Non-Trane Building (Indoor zone reset not available
chiller sequencing. A building owner Automation Systems with ice making option).
can completely monitor the Series R The Series R chillers can interface with
non-Trane building automation External Trane Devices Required:
chiller from the Tracer system, because NONE
all of the monitoring information systems via hard wire connections.
indicated on the microcomputer can be Required Features: Remote Display
read off the Tracer system display. In 1 — External Auto/Stop (standard) The remote display panel option allows
addition, all the powerful diagnostic the operator to monitor chiller
Additional Features: operation from a location within the
information can be read back at the 1 — External Interlock (standard)
Tracer system. In addition, the Tracer building. Over 60 essential chiller
2 — External Demand Limit (setpoint) operating parameters can be
system can provide sequencing control (Requires Communications
for two to six chillers on the same transmitted between the unit control
Interface) module on the chiller and the remote
chilled water loop. Also, pump 3 — Remote Running and Alarm
sequencing control can be provided by display option via a bi-directional
Indication Contacts communications link. In addition to
the Tracer. The Tracer system can be 4 — External Chilled Water Setpoint
used in conjunction with the remote monitoring chiller operation, alarms
(Requires Communications and unit diagnostics can be read from
display panel option on the 70-125 ton Interface)
Series R chillers. Best of all, this the remote display. The chilled water
5 — Chilled Water Temperature Reset temperature setpoint can be adjusted
powerful capability is accomplished 6 — Chilled Waterflow Interlock
through a single twisted pair of wires. and the chiller can be turned on or off
(standard) from the remote display. Furthermore,
Required Features: External Trane devices required : up to four chillers can be monitored on
1— Communications Interface NONE one remote display panel.
Additional Features: Ice Making Systems Required Features:
1 — Chilled Water Temperature reset An ice making option may be ordered 1 — Communications Interface
2 — Ice making control with the 70-125 ton Series R chiller. The Additional Features:
External Trane Devices Required: chiller will have two operating modes, 1 — External Interlock (standard)
1— Tracer 100™ System or Tracer ice making and normal daytime 2 — Chilled Water Temperature
Chiller Plant Manager™ cooling. In the ice making mode, the Setpoint
Standalone Unit Series R chiller will operate at full 3 — Chilled Waterflow Interlock
Interface to standalone chillers is very compressor capacity until the return (standard)
simple; only a remote auto/stop for chilled fluid temperature entering the 4 — Remote running and failure
scheduling is required for chiller evaporator meets the ice making Indication contacts
operation. Signals from the chilled setpoint. This ice making setpoint is
manually adjusted on the chillers External Trane Devices Required:
water pump contactor auxiliary or a 1 — Remote Display Panel
flow switch are wired to the chilled microcomputer. Two input signals are
waterflow interlock. Signals from a required to the Series R chiller for the
timeclock or some other remote device ice making option. The first is an auto/
are wired to the external auto/stop stop signal for scheduling and the
input. Unit controls provide an output second is required to switch the unit in
to turn pumps on and off and should between the ice making mode and
remain on for a minimum of one normal daytime operation. The signals
minute to allow the chiller to complete are provided by a remote jobsite
its shutdown cycle. building automation device such
as a time clock or a manual switch.
Note: Do not use the chilled water
pump to stop the chiller.
39
Dimensional
Data
Figure D-1 — Water Cooled Series R® Standard Length Condensers 70-100 Ton
Figure D-2 — Water Cooled Series R® Standard Length Condensers 110-125 Ton
40
Dimensional
Data
Figure D-3 — Water Cooled Series R® Long Length Condensers 70-100 Ton
Figure D-4 — Water Cooled Series R® Long Length Condensers 110-125 Ton
41
Dimensional
Data
42
Dimensional
Data
43
Dimensional
Data
Figure D-7 — Series R® Air Cooled Condenser Rotary Liquid Chiller RTCA 70-125 Ton
44
Options
RTWA and RTUA Options Chilled Water Reset: This option RTCA Options
provides the control logic and field
Non-Fused Power Disconnect Switch: installed sensors for either load based Architectural Louvered Panels:
A non-fused molded case switch is (return water temperature) or Louvered panels cover the complete
provided for disconnecting main power temperature based (ambient or zone) condensing coil and the service area
through the control panel door. reset of leaving chilled water beneath the coils.
Isolators: Neoprene isolators are temperature. Coil Protection: Louvered panels cover
available for field installation beneath Remote Display: A menu driven, digital the condenser coils.
unit frame. display with two 40 character lines Access Guard: A wire mesh that covers
Low Leaving Fluid Temperature: The provides a full array of operating only the service area beneath the
unit controls can be factory set to condition and diagnostic readouts to a condenser coils.
handle low temperature brine remote location via a twisted wire pair.
Unit Isolation: Neoprene isolators are
applications (0 F to 39 F). Can control up to four units on one
offered for unit isolation from the
display.
Ice Making: The unit controls can be building structure.
factory set to handle ice making for Low Ambient Lockout: (RTUA only)
Low Ambient Operation: Allows the
thermal storage applications. A field-installed low ambient sensor
condenser to operate to -10 F.
(factory installed if ordered with mating
Long Condenser Shell: (RTWA only)
RTCA Series air-cooled condenser) and
All unit sizes are available with long
control logic can prevent starting below
condenser shell option for superior
desired operating temperatures.
operating efficiency.
Condenser Refrigerant Sensors:
High Temperature Condenser: (RTWA
Necessary option to obtain pressure
only) Available to handle high leaving
and temperature readouts when using
condenser water temperatures (110 F
RTUA with non-Trane condenser.
to 130 F)
Two-Way Water Regulating Valves:
Condenser Water Temperature
Provide head pressure control with
Sensors: (RTWA only) Factory installed
low entering condenser water
and tested condenser entering and
temperatures.
leaving water temperature sensors
with digital display.
Building Automation System
Communication Interface: Permits
either bi-direction communication to
the Trane Integrated Comfort™ system
or permits remote chilled water
setpoint and demand limiting by
accepting a 4-20 mA or 2-10 VDC
analog signal.
45
Typical
Wiring
Diagrams
Figure TW-1 — RTWA 70-125 Tons
NOTES:
1. DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY
OTHERS. PHANTOM LINES INDICATE ALTERNATE CIRCUITRY
OR AVAILABLE SALES OPTION. CHECK SALES ORDER TO
DETERMINE IF WIRING IS REQUIRED FOR SPECIFIC OPTIONS.
2. ALL THREE PHASE MOTORS SUPPLIED WITH THE UNIT ARE
PROTECTED UNDER PRIMARY SINGLE PHASE FAILURE
CONDITIONS.
3. CAUTION - DO NOT ENERGIZE UNIT UNTIL CHECK OUT AND
START-UP PROCEDURES HAVE BEEN COMPLETED.
4 SEE INSERT “A” FOR RESISTOR CONNECTIONS TO PROGRAM
AN EXTERNAL CHILLED WATER SETPOINT WHEN 4 - 20 mA OR
A 2 - 10 VDC SIGNAL IS NOT USED. SEE THE OPERATORS
MANUAL FOR RESISTOR VALUES.
5 SEE INSERT “B” FOR RESISTOR CONNECTIONS TO PROGRAM
AN EXTERNAL CURRENT LIMIT SETPOINT WHEN 4 - 20 mA OR
A 2 - 10 VDC SIGNAL IS NOT USED. SEE THE OPERATORS
MANUAL FOR RESISTOR VALUES.
6 SEE INSERT “C” FOR CONTACTS (IN PLACE OF THE ZONE TEMP.
SENSOR) FOR OPTIONAL ICE MACHINE CONTROL - OPTION
“A”.
7. THE FOLLOWING CAPABILITIES ARE OPTIONAL - THEY ARE
IMPLEMENTED AND WIRED AS REQUIRED FOR A SPECIFIC
SYSTEM APPLICATION.
A ICE-MACHINE CONTROL (CANNOT BE USED WITH OPT. L)
B COMMUNICATIONS INTERFACE
D WYE-DELTA CLOSED TRANSITION STARTER
E DELETED
H UNIT DISCONNECT, NON-FUSED
J CHILLED WATER RESET - RETURN WATER
K CHILLED WATER RESET - OUTDOOR AIR
L CHILLED WATER RESET - ZONE AIR (CANNOT BE USED WITH
OPT. A)
O LOW AMBIENT LOCKOUT
S CHILLED WATER FLOW SWITCH (NOT REQUIRED FOR
CHILLER PROTECTION)
T REMOTE CLEAR LANGUAGE DISPLAY
(BUFFER FOR DISPLAY LOCATED IN UNIT CONTROL PANEL)
WIRING AND CONTACT REQUIREMENTS:
20. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE (NEC), STATE, AND LOCAL
REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER
COUNTRIES APPLICABLE NATIONAL AND/OR LOCAL
REQUIREMENTS SHALL APPLY.
21 DELETED
23 CUSTOMER SUPPLIED CONTACTS MUST BE COMPATIBLE
WITH DRY CIRCUIT 12 VDC, 45 mA RESISTIVE LOAD. SILVER OR
GOLD PLATED CONTACTS ARE RECOMMENDED.
24 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN CONDUIT WITH
HIGHER VOLTAGE CIRCUITS. USE #14-18 AWG. SEE SELECTION
TABLE.
25 MINIMUM PILOT DUTY CONTACT RATING AT 115 VAC; 6.9 VA
INRUSH, 1.3 VA SEALED.
26 FIELD WIRED ELECTRICAL LOADING IS NOT TO EXCEED THE
FOLLOWING RATINGS:
TERMINALS DEVICE VOLTAGE SEALED VA INRUSH VA
1U1-TB4-2,1 1U1K1,NO 115 115 1150*
1U1-TB4-3 1U1K1,NC 115 115 1150*
1U1-TB4-5,4 1U1K2,NO 115 115 1150*
1U1-TB4-6,7 1U1K3,NC 115 115 1150*
1U1-TB4-8,9 1U1K2,NO 115 115 1150*
1U1-TB4-10,11 1U1K3,NC 115 115 1150*
*STANDARD PILOT DUTY RATING (35% POWER FACTOR).
27 IF EXTERNAL CIRCUIT LOCKOUT IS USED ON CKT 1 CUT
JUMPER W7 ON CIRCUIT #1 AND SPLICE 48A AND 488 TO THE
INDIVIDUAL CUT ENDS OF THE JUMPER. FOR CIRCUIT #2 CUT
JUMPER W4 AND SPLICE 48A AND 488 TO THE INDIVIDUAL
CUT ENDS OF THE JUMPER.
28 AS SHIPPED 380/415 VOLT UNIT TRANSFORMER 1T1 IS WIRED
FOR 415 VOLT OPERATION. IF UNIT IS TO BE OPERATED ON A
380 VOLT POWER SUPPLY, RE-CONNECT AS SHOWN IN INSET
“D”. REPROGRAM “UNIT LINE VOLTAGE” IN SERVICE SETTING
MENU OF CLEAR LANGUAGE DISPLAY FROM 415 TO 380.
29 K1, K2, K3 RELAY OUTPUTS CAN BE PROGRAMED TO
PERFORM ALTERNATE FUNCTIONS. SEE INSTALLATION,
OPERATION, AND MAINTENANCE MANUAL FOR DETAILS,
FUNCTION #1.
30 CHILLED WATER PUMP CONTROL FROM TRANE UNIT UCM
MODULE CHILLED WATER PUMP IS REQUIRED TO OPERATE A
MINIMUM OF ONE MINUTE AFTER A COMMAND TO
TERMINATE CHILLER OPERATION (UCM WILL PROVIDE TIME
DELAY CONTACTS). CHILLED WATER SYSTEM DEMAND
SWITCH (532) IS CONNECTED TO THE UCM EXTERNAL AUTO/
STOP INPUT.
46
Typical
Wiring
Diagrams
47
Typical
Wiring
Diagrams
Figure TW-2 — RTUA 70-125 with Trane RTCA Condensers
NOTES:
1. DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY
OTHERS. PHANTOM LINES INDICATE ALTERNATE CIRCUITRY
OR AVAILABLE SALES OPTION. CHECK SALES ORDER TO
DETERMINE IF WIRING IS REQUIRED FOR SPECIFIC OPTIONS.
2. ALL THREE PHASE MOTORS SUPPLIED WITH THE UNIT ARE
PROTECTED UNDER PRIMARY SINGLE PHASE FAILURE
CONDITIONS.
3. CAUTION - DO NOT ENERGIZE UNIT UNTIL CHECK OUT AND
START-UP PROCEDURES HAVE BEEN COMPLETED.
4 SEE INSERT “A” FOR RESISTOR CONNECTIONS TO PROGRAM
AN EXTERNAL CHILLED WATER SETPOINT WHEN 4 - 20 mA OR
A 2 - 10 VDC SIGNAL IS NOT USED. SEE THE OPERATORS
MANUAL FOR RESISTOR VALUES.
5 SEE INSERT “B” FOR RESISTOR CONNECTIONS TO PROGRAM
AN EXTERNAL CURRENT LIMIT SETPOINT WHEN 4 - 20 mA OR
A 2 - 10 VDC SIGNAL IS NOT USED. SEE THE OPERATORS
MANUAL FOR RESISTOR VALUES.
6 SEE INSERT “C” FOR CONTACTS (IN PLACE OF THE ZONE TEMP.
SENSOR) FOR OPTIONAL ICE MACHINE CONTROL - OPTION
“A”.
7. THE FOLLOWING CAPABILITIES ARE OPTIONAL - THEY ARE
IMPLEMENTED AND WIRED AS REQUIRED FOR A SPECIFIC
SYSTEM APPLICATION.
A ICE-MACHINE CONTROL
B COMMUNICATIONS INTERFACE
D WYE-DELTA CLOSED TRANSITION STARTER
E CONTROL POWER TRANSFORMER
H UNIT DISCONNECT, NON-FUSED
J CHILLED WATER RESET - RETURN WATER
K CHILLED WATER RESET - OUTDOOR AIR
O LOW AMBIENT LOCKOUT
S CHILLED WATER FLOW SWITCH (NOT REQUIRED FOR
CHILLER PROTECTION)
T REMOTE CLEAR LANGUAGE DISPLAY
(BUFFER FOR DISPLAY LOCATED IN UNIT CONTROL PANEL)
WIRING AND CONTACT REQUIREMENTS:
20. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE (NEC), STATE, AND LOCAL
REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER
COUNTRIES APPLICABLE NATIONAL AND/OR LOCAL
REQUIREMENTS SHALL APPLY.
23 CUSTOMER SUPPLIED CONTACTS MUST BE COMPATIBLE
WITH DRY CIRCUIT 12 VDC, 45 mA RESISTIVE LOAD. SILVER OR
GOLD PLATED CONTACTS ARE RECOMMENDED.
24 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN CONDUIT WITH
HIGHER VOLTAGE CIRCUITS. USE #14-18 AWG. SEE SELECTION
TABLE.
25 MINIMUM PILOT DUTY CONTACT RATING AT 115 VAC; 6.9 VA
INRUSH, 1.3 VA SEALED.
26 FIELD WIRED ELECTRICAL LOADING IS NOT TO EXCEED THE
FOLLOWING RATINGS:
TERMINALS DEVICE VOLTAGE SEALED VA INRUSH VA
1U1-TB4-1,2 1U1K1,NO 115 180 1150*
1U1-TB4-3 1U1K1,NC 115 180 1150*
1U1-TB4-5,4 1U1K2,NO 115 180 1150*
1U1-TB4-6,7 1U1K3,NC 115 180 1150*
1U1-TB4-8,9 1U1K2,NO 115 250 1150*
1U1-TB4-10,11 1U1K3,NC 115 180 1150*
*STANDARD PILOT DUTY RATING (35% POWER FACTOR).
27 IF EXTERNAL CIRCUIT LOCKOUT IS USED ON CKT 1 CUT
JUMPER W7 ON CIRCUIT #1 AND SPLICE 48A AND 488 TO THE
INDIVIDUAL CUT ENDS OF THE JUMPER. FOR CIRCUIT #2 CUT
JUMPER W4 AND SPLICE 48A AND 488 TO THE INDIVIDUAL
CUT ENDS OF THE JUMPER.
28 AS SHIPPED 380/415 VOLT UNIT TRANSFORMER 1T1 IS WIRED
FOR 415 VOLT OPERATION. IF UNIT IS TO BE OPERATED ON A
380 VOLT POWER SUPPLY, RE-CONNECT AS SHOWN IN INSET
“D”. REPROGRAM “UNIT LINE VOLTAGE” IN SERVICE SETTING
MENU OF CLEAR LANGUAGE DISPLAY FROM 415 TO 380.
29 K1, K2, K3 RELAY OUTPUTS CAN BE PROGRAMED TO
PERFORM ALTERNATE FUNCTIONS. SEE INSTALLATION,
OPERATION, AND MAINTENANCE MANUAL FOR DETAILS,
FUNCTION #1 IS SHOWN.
30 CHILLED WATER PUMP CONTROL FROM TRANE UNIT UCM
MODULE CHILLED WATER PUMP IS REQUIRED TO OPERATE A
MINIMUM OF ONE MINUTE AFTER A COMMAND TO
TERMINATE CHILLER OPERATION (UCM WILL PROVIDE TIME
DELAY CONTACTS). CHILLED WATER SYSTEM DEMAND
SWITCH (532) IS CONNECTED TO THE UCM EXTERNAL AUTO/
STOP INPUT.
31 RECOMMEND USING 1 RUN OF 8 CONDUCTORS #22 AND 300V
80 C, 100% SHIELDED WITH DRAIN WIRE (BELDON 8305 OR
EQUIVALENT). MAX. LENGTH FOR #22 IS 500 FT. USE 4 RUNS
OF 2 CONDUCTOR #18 AND 100% SHIELDED WITH DRAIN WIRE
FOR RUNS UP TO 1000 FT. (BELDON 8780 OR EQUIVALENT). DO
NOT RUN IN CONDUIT WITH HIGHER VOLTAGE CIRCUITS.
32 9 WIRES, 115 VAC CIRCUIT. USE #16 AWG MINIMUM.
48
Typical
Wiring
Diagrams
49
Typical
Wiring
Diagrams
Figure TW-3 — RTUA 70-125 with Non-Trane Condensers
NOTES:
1. DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY
OTHERS. PHANTOM LINES INDICATE ALTERNATE CIRCUITRY
OR AVAILABLE SALES OPTION. CHECK SALES ORDER TO
DETERMINE IF WIRING IS REQUIRED FOR SPECIFIC OPTIONS.
2. ALL THREE PHASE MOTORS SUPPLIED WITH THE UNIT ARE
PROTECTED UNDER PRIMARY SINGLE PHASE FAILURE
CONDITIONS.
3. CAUTION - DO NOT ENERGIZE UNIT UNTIL CHECK OUT AND
START-UP PROCEDURES HAVE BEEN COMPLETED.
4 SEE INSERT “A” FOR RESISTOR CONNECTIONS TO PROGRAM
AN EXTERNAL CHILLED WATER SETPOINT WHEN 4 - 20 mA OR
A 2 - 10 VDC SIGNAL IS NOT USED. SEE THE OPERATORS
MANUAL FOR RESISTOR VALUES.
5 SEE INSERT “B” FOR RESISTOR CONNECTIONS TO PROGRAM
AN EXTERNAL CURRENT LIMIT SETPOINT WHEN 4 - 20 mA OR
A 2 - 10 VDC SIGNAL IS NOT USED. SEE THE OPERATORS
MANUAL FOR RESISTOR VALUES.
6 SEE INSERT “C” FOR CONTACTS (IN PLACE OF THE ZONE TEMP.
SENSOR) FOR OPTIONAL ICE MACHINE CONTROL - OPTION
“A”.
7. THE FOLLOWING CAPABILITIES ARE OPTIONAL - THEY ARE
IMPLEMENTED AND WIRED AS REQUIRED FOR A SPECIFIC
SYSTEM APPLICATION.
A ICE-MACHINE CONTROL
B COMMUNICATIONS INTERFACE
D WYE-DELTA CLOSED TRANSITION STARTER
E CONTROL POWER TRANSFORMER
H UNIT DISCONNECT, NON-FUSED
J CHILLED WATER RESET - RETURN WATER
K CHILLED WATER RESET - OUTDOOR AIR
O LOW AMBIENT LOCKOUT
S CHILLED WATER FLOW SWITCH (NOT REQUIRED FOR
CHILLER PROTECTION)
T REMOTE CLEAR LANGUAGE DISPLAY
(BUFFER FOR DISPLAY LOCATED IN UNIT CONTROL PANEL)
WIRING AND CONTACT REQUIREMENTS:
20. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE (NEC), STATE, AND LOCAL
REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER
COUNTRIES APPLICABLE NATIONAL AND/OR LOCAL
REQUIREMENTS SHALL APPLY.
23 CUSTOMER SUPPLIED CONTACTS MUST BE COMPATIBLE
WITH DRY CIRCUIT 12 VDC, 45 mA RESISTIVE LOAD. SILVER OR
GOLD PLATED CONTACTS ARE RECOMMENDED.
24 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN CONDUIT WITH
HIGHER VOLTAGE CIRCUITS. USE #14-18 AWG. SEE SELECTION
TABLE.
25 MINIMUM PILOT DUTY CONTACT RATING AT 115 VAC; 6.9 VA
INRUSH, 1.3 VA SEALED.
26 FIELD WIRED ELECTRICAL LOADING IS NOT TO EXCEED THE
FOLLOWING RATINGS:
TERMINALS DEVICE VOLTAGE SEALED VA INRUSH VA
1U1-TB4-1,2 1U1K1,NO 115 180 1150*
1U1-TB4-3 1U1K1,NC 115 180 1150*
1U1-TB4-5,4 1U1K2,NO 115 180 1150*
1U1-TB4-6,7 1U1K3,NC 115 180 1150*
1U1-TB4-8,9 1U1K2,NO 115 250 1150*
1U1-TB4-10,11 1U1K3,NC 115 180 1150*
*STANDARD PILOT DUTY RATING (35% POWER FACTOR).
27 IF EXTERNAL CIRCUIT LOCKOUT IS USED ON CKT 1 CUT
JUMPER W7 ON CIRCUIT #1 AND SPLICE 48A AND 488 TO THE
INDIVIDUAL CUT ENDS OF THE JUMPER. FOR CIRCUIT #2 CUT
JUMPER W4 AND SPLICE 48A AND 488 TO THE INDIVIDUAL
CUT ENDS OF THE JUMPER.
28 AS SHIPPED 380/415 VOLT UNIT TRANSFORMER 1T1 IS WIRED
FOR 415 VOLT OPERATION. IF UNIT IS TO BE OPERATED ON A
380 VOLT POWER SUPPLY, RE-CONNECT AS SHOWN IN INSET
“D”. REPROGRAM “UNIT LINE VOLTAGE” IN SERVICE SETTING
MENU OF CLEAR LANGUAGE DISPLAY FROM 415 TO 380.
29 K1, K2, K3 RELAY OUTPUTS CAN BE PROGRAMED TO
PERFORM ALTERNATE FUNCTIONS. SEE INSTALLATION,
OPERATION, AND MAINTENANCE MANUAL FOR DETAILS,
FUNCTION #1 IS SHOWN.
30 CHILLED WATER PUMP CONTROL FROM TRANE UNIT UCM
MODULE CHILLED WATER PUMP IS REQUIRED TO OPERATE A
MINIMUM OF ONE MINUTE AFTER A COMMAND TO
TERMINATE CHILLER OPERATION (UCM WILL PROVIDE TIME
DELAY CONTACTS). CHILLED WATER SYSTEM DEMAND
SWITCH (532) IS CONNECTED TO THE UCM EXTERNAL AUTO/
STOP INPUT.
31 RECOMMEND USING 1 RUN OF 8 CONDUCTORS #22 AND 300V
80 C, 100% SHIELDED WITH DRAIN WIRE (BELDON 8305 OR
EQUIVALENT). MAX. LENGTH FOR #22 IS 500 FT. USE 4 RUNS
OF 2 CONDUCTOR #18 AND 100% SHIELDED WITH DRAIN WIRE
FOR RUNS UP TO 1000 FT. (BELDEN 8780 OR EQUIVALENT). DO
NOT RUN IN CONDUIT WITH HIGHER VOLTAGE CIRCUITS.
32 MAX. CIRCUIT RATING 115 VOLTS, 180 VA INRUSH, 1150 VA
SEALED.
33 SEE INSTALLATION MANUAL FOR SENSOR MOUNTING
INSTRUCTIONS.
50
Typical
Wiring
Diagrams
51
Typical
Wiring
Diagrams
Figure TW-4 — RTCA 70-125 Air-Cooled Condensers
NOTES:
CUSTOMER WIRE SELECTION TABLE 1. DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY
POWER WIRE SELECTION TO MAIN TERMINAL BLOCK (1TB1) OTHERS. PHANTOM LINES INDICATE ALTERNATE CIRCUITRY
UNIT SIZE UNIT VOLTAGE TERMINAL BLOCK SIZE CONNECTOR WIRE RANGE OR AVAILABLE SALES OPTION. CHECK SALES ORDER TO
DETERMINE IF WIRING IS REQUIRED FOR SPECIFIC OPTIONS.
70 - 125 200, 230 175 #14 TO 2/0 2. ALL THREE PHASE MOTORS SUPPLIED WITH THE UNIT ARE
346, 380, 400, 460, 575 PROTECTED UNDER PRIMARY SINGLE PHASE FAILURE
CONTROL WIRE SELECTION FOR 30 VOLT OR LESS CIRCUITS – SEE NOTE 24 CONDITIONS.
WIRE SIZE MAXIMUM LENGTH FOR SENSOR LEADS 3. CAUTION - DO NOT ENERGIZE UNIT UNTIL CHECK OUT AND
START-UP PROCEDURES HAVE BEEN COMPLETED.
14 AWG 5000 FT
WIRING AND CONTACT REQUIREMENTS:
18 AWG 2000 FT 10. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE
18 AWG 1000 FT NATIONAL ELECTRICAL CODE (NEC), STATE, AND LOCAL
FUSE REPLACEMENT SECTION REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER
COUNTRIES APPLICABLE NATIONAL AND/OR LOCAL
FUSE DESCRIPTION UNIT SIZE UNIT VOLTAGE FUSE TYPE FUSE SIZE REQUIREMENTS SHALL APPLY.
INVERTER/AUTO-TRANSFORMER FUSE ALL 575/460/380/60 CLASS CC (600 V) 6 AMP 11 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN CONDUIT WITH
(1F18-1F23) 380/415/346/50 HIGHER VOLTAGE CIRCUITS. USE #14-18 AWG. SEE SELECTION
200/230/60 CLASS CC (600V) 10 AMP TABLE.
12 RECOMMEND USING 3 RUNS OF 2 CONDUCTORS #18 AWG
600V 80 C, 100% SHIELDED WITH DRAIN WIRE (BELDON 8305
OR EQUIVALENT). DO NOT RUN IN CONDUIT WITH HIGHER
VOLTAGE CIRCUITS.
13 RECOMMEND USING 1 RUN OF 8 CONDUCTORS #22 AWG 300V
80 C, 100% SHIELDED WITH DRAIN WIRE (BELDON 8305 OR
EQUIVALENT). DO NOT RUN IN CONDUIT WITH HIGHER
VOLTAGE CIRCUITS.
52
Features
Summary
53
Mechanical RTWA and RTUA
Specifications
54
Mechanical RTCA
Specifications
55
Literature Order Number RLC-DS-4
File Number PL-RF-RLC-000-DS-4-1199
Supersedes RLC-DS-4 1094
The Trane Company Stocking Location La Crosse
3600 Pammel Creek Road
La Crosse, WI 54601-7599
www.trane.com
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change
An American Standard Company design and specifications without notice.