You are on page 1of 8

Product data sheet RE17RBMU

Characteristics Modular timing relay, 8 A, 1 s..100 h, 1 CO, single


interval relay, 24...240 V AC
Product availability : Stock - Normally stocked in distribution facility

Price* : 52.00 USD

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Zelio Time
Product or component type Modular timing relay
Discrete output type Relay
Maximum Width 0.69 in (17.5 mm)
Device short name RE17R
Time delay type B
Time delay range 10...100 h
1...10 min
6...60 min
1...10 s
6...60 s
1...10 h
0.1...1 s
Nominal output current 8 A

Complementary
Contacts type and composition 1 C/O
Contacts material Cadmium free
Height 3.54 in (90 mm)
Maximum Depth 2.83 in (72 mm)
Control type Selector switch front panel
[Us] rated supply voltage 24...240 V AC 50/60 Hz
24 V DC
Voltage range 0.85...1.1 Us
Supply frequency 50...60 Hz +/- 5 %
Release of input voltage 10 V
Connections - terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end

*  Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Mar 4, 2021
1
Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Tightening torque 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale 25 °C IEC 61812-1
Control signal pulse width 100 ms with load in parallel typical
30 ms typical
Insulation resistance 100 MOhm 500 V DC IEC 60664-1
Reset time 120 ms on de-energisation typical
On-load factor 100 %
Power consumption in VA 0…32 VA 240 V AC
Maximum power consumption in W 0.6 W 24 V DC
Minimum switching current 10 mA 5 V DC
Maximum switching current 8 A AC/DC
Maximum switching voltage 250 V AC
Breaking capacity 2000 VA
Operating frequency 10 Hz
Electrical durability 100000 cycles resistive 8 A 250 V AC
Mechanical durability 10000000 cycles
Dielectric strength 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
[Uimp] rated impulse withstand voltage 5 kV 1.2/50 µs
Power on delay 100 ms
Marking CE
Creepage distance 4 kV/3 IEC 60664-1
Safety reliability data MTTFd = 296.8 years
B10d = 270000
Mounting position Any position in relation to normal vertical mounting plane
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Local signalling LED indicator on steady: relay energised, no timing in progress
LED indicator 80 % ON and 20 % OFF flashing: timing in progress
LED indicator 5 % ON and 95 % OFF pulsing: relay de-energised, no timing in progress (except
function Di-D, Li-L)
Net Weight 0.15 lb(US) (0.07 kg)
Time delay type B
Functionality Pulse signal
Compatibility code RE17

Environment
Immunity to microbreaks 20 ms
Standards 2006/95/EC
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
IEC 61812-1
EN 61000-6-1
2004/108/EC
Product certifications GL
CULus
CSA
Ambient air temperature for storage -22…140 °F (-30…60 °C)
Ambient air temperature for operation -4…140 °F (-20…60 °C)
IP degree of protection IP20 IEC 60529 terminal block)
IP40 IEC 60529 housing)
IP50 IEC 60529 front panel)

2
Vibration resistance 20 m/s² 10…150 Hz)IEC 60068-2-6
Shock resistance 15 gn 11 ms IEC 60068-2-27
Relative humidity 93 % without condensation IEC 60068-2-30
Electromagnetic compatibility Electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2
Electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2
Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3
Electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4
Electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4
1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5
1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5
Conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11
Voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11
Conducted and radiated emissionsclass B EN 55022

Ordering and shipping details


Category 22370 - RE, RM MISC TIMERS & COUNTERS
Discount Schedule CP2
GTIN 00785901395133
Nbr. of units in pkg. 1
Package weight(Lbs) 0.17 lb(US) (0.08 kg)
Returnability Yes
Country of origin ID

Packing Units
Unit Type of Package 1 PCE
Package 1 Height 3.15 in (8 cm)
Package 1 width 1.06 in (2.7 cm)
Package 1 Length 3.74 in (9.5 cm)
Unit Type of Package 2 S02
Number of Units in Package 2 40
Package 2 Weight 8.43 lb(US) (3.822 kg)
Package 2 Height 5.91 in (15 cm)
Package 2 width 11.81 in (30 cm)
Package 2 Length 15.75 in (40 cm)

Offer Sustainability
Sustainable offer status Green Premium product
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which
is known to the State of California to cause cancer and birth defects or other reproductive harm. For
more information go to www.P65Warnings.ca.gov
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information

3
Product data sheet RE17RBMU
Dimensions Drawings

Width 17.5 mm

4
Product data sheet RE17RBMU
Connections and Schema

Internal Wiring Diagram

5
Product data sheet RE17RBMU
Connections and Schema

Wiring Diagram

6
Product data sheet RE17RBMU
Technical Description

Function B : Interval Relay with Control Signal

Description
After power-up, pulsing or maintaining control contact C starts the timing T. The output R closes for the duration of the timing period T then
reverts to its initial state.

Function: 1 Output

7
Product data sheet RE17RBMU
Technical Description

Legend

Relay de-energised
Relay energised
Output open
Output closed

C Control contact

G Gate

R Relay or solid state output

R1/R2 2 timed outputs

R2 inst. The second output is instantaneous if the right position is selected

T Timing period

Ta - Adjustable On-delay

Tr - Adjustable Off-delay

U Supply