• Aim:
Design a overall dimension of 25KVA, 11000/433V, 50Hz 3
phase delta/star core type transformer.
• Objective:
To draw the overall dimension on drawing sheet.
• Theory:
When dealing with overall dimensions in transformer problems
refer to the following details & diagram.
Overall dimensions of 3 Phase core type transformer
a= Width of largest stamping
d= diameter of circumscribing circle
D= distance between centers of adjacent limbs
H= overall height of transformer over yokes
W= length of yoke
Hw= Height of window
Hy= Height of yoke
Ww= Width of window
D = d + Ww, Dy = a
H = Hw + 2Hy, W = 2D + a
Width over two limbs = D + outer diameter of hv winding
Width over one limb = outer diameter of hv winding
For single phase shell type transformer refer fig.
Dy= b , Hy= a, W= 2Ww + 4a, H= Hw + 2a
• Diagram:
• Problem:
Design a 25 kVA, 11000/433V, 50 Hz, 3 phase, delta/star,
core type, oil immersed natural cooled distribution transformer. The
transformer is provided with tapping ± 2(1/2) ± 5% on the h.v.
winding. Maximum temperature rise not to exceed 45°C with mean
temperature rise of oil 35°C.
Hot rolled silicon steel grade 92 is used. The value of flux density B is
assumed as 1.0 W/m2
0.010135
Net iron area Ai = = 0.01035 m2 = 10.135*103 mm2
1.0
• Result:
Terms Calculated
H 528 mm
W 624 mm
Dy 114 mm
• Conclusion:
In this way we have design the 3 phase core type transformer
and drawn on sheet.