Professional Documents
Culture Documents
See
Photo
Fig. 092-9. Grounding of messenger wires (Rule 092C1).
under tension and electrically connected to the post for the mesh to be
grounded. In the example shown in Fig. 092-13, the grounding conductor feed
up to the barbwire strands is woven through the chain-link mesh for added
grounding continuity.
Fig. 092-11. Common grounding of messenger and guy on a crossing structure (Rule 092C3b).
minum or ACSR is used above grade, spliced to copper, which then runs below
grade. Some utilities utilize copper-coated steel. Copper substitutes have
become popular due to copper theft.
Never should the grounding conductor have a switching device unless all the
conductors to the equipment are disconnected at the same time. Other excep-
tions include high-voltage DC systems, testing under competent supervision,
and surge arrester operation. This rule provides an important note stating that
the normally grounded base of the surge arrester may be at line potential (fully
energized) following the operation of the disconnector.
093B. Connection of Grounding Conductors. The connection between the
grounding conductor (pole ground) and grounded conductor (neutral) must be
made considering the metals involved and exposure to the environment. The
connector must not corrode and must be rated for the type of metals it is con-
necting. Dissimilar metals connected together with an improper connector will
set up a battery action which will accelerate corrosion. Soldering is not accept-
able except on lead sheath cable, as fault currents will produce enough heat to
melt the solder. Suitable connection methods are shown in Fig. 093-1
Sec09_Marne_136262-6 1/24/02 12:52 PM Page 29
See
Photo
See
Photo
093C. Ampacity and Strength. This rule lists short-time ampacity requirements
for bare and insulated grounding conductors. A bare conductor can carry a larger
fault current than an insulated conductor of the same size because melting or dam-
aging the bare conductor is the limiting factor. The insulated grounding conductor
has the additional constraint of not damaging the insulation. See Fig. 093-2.
Short-time ampacity of both bare and insulated conductors can be obtained
from conductor manufacturers. The charts used to obtain this information are
typically referred to as short-circuit withstand charts.
Fig. 093-2. Short-time ampacity of bare and insulated grounding conductors (Rule 093C).
Sec09_Marne_136262-6 1/24/02 12:52 PM Page 31
Fig. 093-3. System grounding conductor for single-grounded systems (Rule 093C1).
Sec09_Marne_136262-6 1/24/02 12:53 PM Page 32
Fig. 093-4. System grounding conductors for multigrounded alternating current systems (Rule 093C2).
type of soil, moisture in the soil, length of rod, etc. Field measurements must
be taken to determine actual ground rod resistance.
The mechanical strength of grounding conductors must be suitable to the
conditions they are exposed to (i.e., lawn mowers, weed eaters, car bumpers,
etc.). Unguarded grounding conductors must have a tensile strength equal to
or greater than AWG No. 8 soft-drawn copper except for conductors noted in
Rule 093C3 (i.e., AWG No. 12 copper for instrument transformers).
093D. Guarding and Protection. Guards over grounding conductors are only
required for single-grounded systems that are exposed to the public. If the ground-
ing electrode is on a single-grounded system that is not exposed to the public (i.e.,
in a fenced substation), it does not have to be guarded. Grounding electrodes on
multigrounded systems are not required to be guarded even if they are exposed to
mechanical damages. A multigrounded system requires at least four grounds per
mile, and Rule 214 requires inspection of overhead lines. These two requirements
provide a method to assure safe grounding on multigrounded systems; therefore,
guards on multigrounded systems are not required. Even if guards are not
Sec09_Marne_136262-6 1/24/02 12:53 PM Page 34
See
Photo
Fig. 093-6. Requirements for grounding conductors with or without guards (Rules 093D2
and 093D3).
required, they can be installed. If guards are not required but they are installed,
they should be installed in a manner as if they were required.
Rules 239D and 360A also provide guarding requirements for various conduc-
tors. If guarding of the grounding conductor is required, guards must be suitable
for the damage to which they will be exposed. If guarding of the grounding con-
ductor is not required, a typical installation method is stapling the grounding con-
ductor to a wood pole. The requirements for grounding conductors with or
without guards are outlined in Fig. 093-6.
Rule 093D4 recognizes that an inductive choke is created when a conductor is
run through a metallic raceway. This can create hazardous voltage during light-
ning strike or fault conditions. The Code requires a nonmetallic guard (e.g., con-
duit) to avoid this condition. The strength of nonmetallic materials (i.e., plastics)
has increased to the point where they can be used for protection without cracking
or breaking. A U-shaped metallic raceway is acceptable, as it does not completely
enclose the grounding conductor. If a metallic guard similar to a steel pipe or rigid
metal conduit is used, it must be bonded to the grounding conductor at both ends,
as shown in Fig. 093-7.
093E. Underground. Grounding conductors laid underground require slack due
to the earth’s settling. Direct-buried joints or splices must be made with
Sec09_Marne_136262-6 1/24/02 12:53 PM Page 35
See
Photo
example of one common grounding conductor for the circuit and equipment is
shown in Fig. 093-9.