Technical data
All data is supplied subject to change without notice. Specifications
are typical at 24 V, +25°C and 50% RH unless otherwise stated.
IP rating IP52
MANAGEMENT
SYSTEMS
MANAGEMENT
SYSTEMS
PRODUCT
CERTIFICATION
© Apollo Fire Detectors Ltd 2019
Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010
Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2553/2019/Issue 3
Page 2 of 4
Table 2: Intelligent Input/Output Unit operating modes* Figure 1: Intelligent Input/Output Unit dimensional
drawing
Mode Description
2 Alarm delays
90 mm
5 Output with Feedback (N/C)
Failsafe
60 mm
In Failsafe mode the Intelligent Input/Output Unit will activate
the on-board relay output without being commanded by the
control panel on loss of loop or protocol loss. Failsafe mode
is selected via a DIL switch and indicated with an analogue
value of 17.
150 mm
Mechanical Construction
The Intelligent Input/Output Unit (see Figure 1) is available
in the new faceplate style enclosure. This can be mounted
with the supplied back-box for surface mounting or flush Table 3: Status Indications
mounted using a UK double gang, flush mounting back-box
Legend LED Status Description
of minimum depth 30mm.
RLY Continuous Red Relay Active
EMC Directive 2014/30/EU
RLY Continuous Yellow Relay Fault
The Intelligent Input/Output Unit complies with the essential
requirements of the EMC Directive 2014/30/EU, provided Poll/ISO Flashing Green Polling LED
that it is used as described in this datasheet.
Poll/ISO Continuous Yellow Isolator LED
A copy of the Declaration of Conformity is available from
I/P Continuous Yellow Input Fault
Apollo on request.
Conformity of the Intelligent Input/Output Unit with the EMC I/P Continuous Red Input Active
Directive, does not confer compliance with the directive on
any apparatus or systems connected to them.
Construction Products Regulation 305/2011/EU
The Intelligent Input/Output Unit complies with the essential
requirements of the Construction Products Regulation
305/2011/EU.
A copy of the Declaration of Performance is available from
Apollo on request.
Connectivity
Figures 2, 3 and 4 for unit connection information. Refer to the
Installation Guide 39215-159 for the installation instructions
on this product. Table 3 details the status indications of this
unit, from normal operation through to fault conditions.
PP2553/2019/Issue 3
Page 3 of 4
Figure 2: Intelligent Input/Output Unit standard resistive monitoring mode connectivity diagram
L- L+
INPUT/OUTPUT
NC COM NO
UNIT
L- L+
Relay contact
POLL / ISOL
0
1A at 30V
RLY Polarity
Sensitive
L+
1
IP-
1
2
4
8
16
32
64
128
FS
LED
IP+
L-
N/O IP
Contact
L- L+
Loop
20k EOL 1k
Figure 3: Intelligent Input/Output Unit normally open monitoring mode connectivity diagram
(compatible with CoreProtocol only)
L- L+
INPUT/OUTPUT
NC COM NO
UNIT
L- L+
Relay contact
POLL / ISOL
0
1A at 30V
RLY Polarity
Sensitive
L+
1
IP-
1
2
4
8
16
32
64
128
FS
LED
IP+
L-
N/O IP
Contact
L- L+
Loop
Figure 4: Intelligent Input/Output Unit normally closed monitoring mode connectivity diagram
(compatible with CoreProtocol only)
L- L+
INPUT/OUTPUT
NC COM NO
UNIT
L- L+
Relay contact
POLL / ISOL
0
1A at 30V
RLY Polarity
Sensitive
L+ L-
1
IP-
1
2
4
8
16
32
64
128
FS
LED
IP+
IP
N/C
Contact
L- L+
Loop
PP2553/2019/Issue 3