expansion and/or contraction which could result in stresses in excess of those permitted
by applicable ANSI/ASME codes. Each support assembly, including the spring supports,
shall be designed to support the hydrostatic test load.
Corrosion Control
All spring hanger components and spring supports, with the exception of the spring coil,
alloy or stainless steel shall be galvanized. Galvanizing shall be in accordance with
Project
Specificaiton DGS-1300-175
Spring coils shall be neoprene coated with a minimum thickness of 0,15 mm.
Galvanized spring hanger housings shall not be welded after the coil has been installed.
Retainers for the coil shall be of a bolted or split ring type construction to avoid burning
the
housing.