Logging - Chiller 1

Carrier: 19XR 8787

Which chiller are running?

Chiller 1 Chiller 2 Chiller 3 Chiller 4

Chiller 1 LOGGING

GENERAL
POWER METER READING (SUM MWH):

Enter text

% CURRENT LOAD (%):

Enter text
MOTOR KW:

Enter text

MOTOR KWH:

Enter text

COOLER
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

Enter text

CHILLED WATER OUT TEMPERATURE (Design = 4°C):

Enter text
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

Enter text

EVAPORATOR APPROACH (Reference= < 0.6 °C):

Enter text
CHW IN PRESSURE (PSI):

Enter text

CHW OUT PRESSURE (PSI):

Enter text
WATER PRESSURE DROP (Design= 8.1 PSI):

Enter text

CONDENSER

CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

Enter text
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

Enter text

CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

Enter text
CONDENSER APPROACH (Reference = < 0.6°C):

Enter text

COND. WATER IN PRESSURE (PSI):

Enter text
COND. WATER OUT PRESSURE (PSI):

Enter text

WATER PRESSURE DROP (Design = 8.7 PSI):

Enter text

COMPRESSOR
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

Enter text

OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

Enter text
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert =
85 °C):

Enter text

COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature


Alert = 79 °C):

Enter text
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature
override = 66 °C):

Enter text

REMARKS:

Enter text

Logging - Chiller 2

Carrier: 19XR 8787

Chiller 2 LOGGING

GENERAL
POWER METER READING (SUM MWH):

Enter text

% CURRENT LOAD (%):

Enter text
MOTOR KW:

Enter text

MOTOR KWH:

Enter text

COOLER
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

Enter text

CHILLED WATER OUT TEMPERATURE (Design = 4°C):

Enter text
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

Enter text

EVAPORATOR APPROACH (Reference= < 0.6 °C):

Enter text
CHW IN PRESSURE (PSI):

Enter text

CHW OUT PRESSURE (PSI):

Enter text
WATER PRESSURE DROP (Design= 8.1 PSI):

Enter text

CONDENSER

CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

Enter text
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

Enter text

CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

Enter text
CONDENSER APPROACH (Reference = < 0.6°C):

Enter text

COND. WATER IN PRESSURE (PSI):

Enter text
COND. WATER OUT PRESSURE (PSI):

Enter text

WATER PRESSURE DROP (Design = 8.7 PSI):

Enter text

COMPRESSOR
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

Enter text

OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

Enter text
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert =
85 °C):

Enter text

COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature


Alert = 79 °C):

Enter text
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature
override = 66 °C):

Enter text

REMARKS:

Enter text
Logging - Chiller 3

Carrier: 19XR 8787

Chiller 3 LOGGING

GENERAL

POWER METER READING (SUM MWH):

Enter text

% CURRENT LOAD (%):

Enter text
MOTOR KW:

Enter text

MOTOR KWH:

Enter text

COOLER
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

Enter text

CHILLED WATER OUT TEMPERATURE (Design = 4°C):

Enter text
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

Enter text

EVAPORATOR APPROACH (Reference= < 0.6 °C):

Enter text
CHW IN PRESSURE (PSI):

Enter text

CHW OUT PRESSURE (PSI):

Enter text
WATER PRESSURE DROP (Design= 8.1 PSI):

Enter text

CONDENSER

CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

Enter text
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

Enter text

CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

Enter text
CONDENSER APPROACH (Reference = < 0.6°C):

Enter text

COND. WATER IN PRESSURE (PSI):

Enter text
COND. WATER OUT PRESSURE (PSI):

Enter text

WATER PRESSURE DROP (Design = 8.7 PSI):

Enter text

COMPRESSOR
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

Enter text

OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

Enter text
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert =
85 °C):

Enter text

COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature


Alert = 79 °C):

Enter text
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature
override = 66 °C):

Enter text

REMARKS:

Enter text
Logging - Chiller 4

Carrier: 19XR 8787

Chiller 4 LOGGING

GENERAL

POWER METER READING (SUM MWH):

Enter text

% CURRENT LOAD (%):

Enter text
MOTOR KW:

Enter text

MOTOR KWH:

Enter text

COOLER
CHILLED WATER IN TEMPERATURE (Design = 14 - 15 °C):

Enter text

CHILLED WATER OUT TEMPERATURE (Design = 4°C):

Enter text
EVAPORATOR PRESSURE (Reference= >28 PSI/193 Kpa):

Enter text

EVAPORATOR APPROACH (Reference= < 0.6 °C):

Enter text
CHW IN PRESSURE (PSI):

Enter text

CHW OUT PRESSURE (PSI):

Enter text
WATER PRESSURE DROP (Design= 8.1 PSI):

Enter text

CONDENSER

CONDENSER WATER IN TEMPERATURE (Design = 30.5 °C):

Enter text
CONDENSER WATER OUT TEMPERATURE (Design = 35.7 °C):

Enter text

CONDENSER PRESSURE (Reference = < 124 PSI/ 855 Kpa):

Enter text
CONDENSER APPROACH (Reference = < 0.6°C):

Enter text

COND. WATER IN PRESSURE (PSI):

Enter text
COND. WATER OUT PRESSURE (PSI):

Enter text

WATER PRESSURE DROP (Design = 8.7 PSI):

Enter text

COMPRESSOR
OIL SUMP TEMPERATURE (Reference = 50 - 60 °C):

Enter text

OIL PUMP DELTA PRESSURE (Reference > 16 PSI/110 Kpa):

Enter text
COMPRESSOR DISCHARGE TEMPERATURE (Discharge Temperature Alert =
85 °C):

Enter text

COMPRESSOR THRUST BEARING TEMPERATURE (Bearing Temperature


Alert = 79 °C):

Enter text
COMPRESSOR MOTOR WINDING TEMPERATURE (Motor temperature
override = 66 °C):

Enter text

REMARKS

Enter text
PUMP Condition

PRIMARY CHILLED WATER PUMP CONDITION

Which primary chilled water pump are operating?

PCHWP 1 PCHWP 2 PCHWP 3 PCHWP 4

Any Abnormal noise?

YES NO N/A

Any leaking?

YES NO N/A

SECONDARY CHILLED WATER PUMP CONDITION

Which secondary chilled water pump are operating?

SCHWP-1 SCHWP-2 SCHWP-3 SCHWP-4 SCHWP-5

SCHWP-6 SCHWP-7 SCHWP-8 SCHWP-9 SCHWP-10

SCHWP-11 SCHWP-E1-2-1 SCHWP-E1-2-2 SCHWP-E1-2-3

Any Abnormal noise?

YES NO N/A

Any Leaking?

YES NO N/A
CONDENSER WATER PUMP CONDITION

Which condenser water pump are operating?

CWP-1 CWP-2 CWP-3 CWP-4

Any Abnormal noise?

YES NO N/A

Any Leaking?

YES NO N/A

REMARKS:

Enter text
Cooling Tower Condition

COOLING TOWER CONDITION

Which cooling tower are operating?

Cooling Tower 1 Cooling Tower 2 Cooling Tower 3 Cooling Tower 4

Any Abnormal noise?

YES NO N/A

Any leaking?

YES NO N/A

Water level High (H) or Low (L):

High Low Normal

Inlet motorised valve open or close:

OPEN CLOSE

Outlet motorised valve open or close:

OPEN CLOSE
PHASE 1 Ampere:

Enter text

PHASE 2 Ampere:

Enter text
PHASE 3 Ampere:

Enter text

Running frequency (hz):

Enter text
Energy consumption (KWH):

Enter text

REMARKS:

Enter text

SIGN OFF

Recorded by:

Verified by: