TOPIC: Accessories
IDENT NO: 1--2620D
SUPERSEDES: 1--2620C
DATE: December 15, 2001
The tables in this Service Bulletin list “Alarm” and The temperature “shutdown” values shown in the tables
“Shutdown” setpoints by engine series for various are maximum permissible values which cannot be
engine operating parameters. These values can be exceeded regardless of application. The pressure
used as a guide when designing engine protection or “shutdown” values shown in the tables, are minimum
monitoring systems. permissible values which cannot be reduced regardless
of application.
The “Alarm” values shown are suggested values; they
can be changed to suit a specific application or Alarm and shutdown values shown are based on dry
measurement device. natural gas (900 Btu/cu. ft. SLHV). Refer to the following
Specification Sheets and Service Bulletins for changes
in operating temperatures when running on landfill or
digester gas fuels:
Do not allow an engine to operate in excess of
temperature shutdown limits or below pressure · Specification Sheets -- S7884--7 and S1015--29
shutdown limits. Engine shutdown limits are set to · Service Bulletins -- 9--2702A and 12--1880Y
ensure the engine will operate within its designed
parameters. Engine operation outside of the shut- By using controls that simultaneously shut off the fuel
down limits may cause severe engine damage, supply and ignition system upon reaching a “shutdown”
severe personal injury, or death. value, the potential for engine damage is reduced. -
WAUKESHA ENGINE
DRESSER, INC. Page 1 of 4
Waukesha WAUKESHA, WI 53188-4999
Service Bulletin No. 1--2620D
Normal
Up to 10° F (5.5° C) above design intercooler water 6 and 12 Cylinder Models
inlet temperature
Normal 50 -- 60 psi (345 -- 415 kPa)
20° F (11° C) above design intercooler water inlet
Alarm temperature Alarm 35 psi (241 kPa)
30° F (17° C) above design intercooler water inlet Shutdown 30 psi (207 kPa)
Shutdown temperature
16 Cylinder Models
INTAKE MANIFOLD TEMPERATURE -- AT27GL Normal 50 -- 60 psi (345 -- 415 kPa)
Up to 10° F (5.5° C) above design intercooler water Alarm 30 psi (207 kPa)
Normal inlet temperature
Shutdown 25 psi (172 kPa)
15° F (8.5° C) above design intercooler water inlet
Alarm temperature INTAKE MANIFOLD TEMPERATURE
20° F (11° C) above design intercooler water inlet
(GSI & GL ENGINES)
Shutdown temperature Up to 10° F (5.5° C) above design intercooler water
Normal inlet temperature
INTAKE MANIFOLD PRESSURE
15° F (8.5° C) above design intercooler water inlet
See SB 14--2748C (or current revision) Alarm temperature
MAIN BEARING TEMPERATURE 20° F (11° C) above design intercooler water inlet
Shutdown temperature
Shutdown 250° F (121° C)
OVERSPEED INTAKE MANIFOLD PRESSURE
Not to exceed 10% over governed speed or driven See SB 14--2755B (or current revision)
Shutdown machine limits MAIN BEARING TEMPERATURE
NOTE: Shutdown 250° F (121° C)
1 Waukesha Power Systems Code 1105, 1105A, or equivalent
pressure/temperature shutdown system is recommended when OVERSPEED
jacket water temperature exceeds 210° F (99° C).
2 AT25GL models may not attain this specification without oil Shutdown 10% over governed speed or driven machine limits
pressure feedback. Refer to SB 12--2810A (or current revision) for NOTE:
more information. 1 Waukesha Power Systems Code 1105, 1105A, or equivalent
shutdown system is recommended when jacket water temperature
exceeds 210° F (99° C).
2 Waukesha Power Systems Code 1106, 1106A, or equivalent
shutdown system is required for ebulliently cooled engines.
WAUKESHA ENGINE
Page 2 of 4 DRESSER, INC.
WAUKESHA, WI 53188-4999
Waukesha
Service Bulletin No. 1--2620D
Table 3. VGF
INTAKE MANIFOLD TEMPERATURE
JACKET WATER OUTLET TEMPERATURE With Standard Intercooler Water Temperatures
Standard Cooling System (176 BMEP Engines) 85 -- 130° F (29 -- 54° C)
(176 BMEP GL/GLD/GSID Engines)
180° F (82° C) for continuous rating
Normal 200° F (93° C) for intermittent rating Up to 10° F (5.5° C) above design intercooler water
Normal inlet temperature
Alarm 10° F (5.5° C) above normal/design temperature
15° F (8.5° C) above design intercooler water inlet
Shutdown 20° F (11° C) above normal/design temperature Alarm temperature
Elevated Temperature Solid Water Cooling System 20° F (11° C) above design intercooler water inlet
(176 BMEP Engines) Shutdown temperature
Normal 210 -- 265° F (99 -- 130° C) solid water With Elevated Intercooler Water Temperatures
Alarm 5° F (3° C) above normal/design temperature1 131 -- 176° F (55 -- 80° C)
(176 BMEP GL/GLD/GSID Engines)
Shutdown 10° F (5.5° C) above normal/design temperature1
Up to 10° F (5.5° C) above design intercooler water
Normal inlet temperature
Elevated Temperature Solid Water Cooling System
(200 BMEP Engines)
10° F (5.5° C) above design intercooler water inlet
Alarm temperature
Normal 210° F (99° C) solid water
Alarm 10° F (5.5° C) above normal/design temperature1 Shutdown
15° F (8.5° C) above design intercooler water inlet
temperature
Shutdown 15° F (8.5° C) above normal/design temperature1
With Elevated Intercooler Water Temperatures
LUBE OIL HEADER TEMPERATURE 158 -- 176° F (70 -- 80° C)
With a Jacket Water Temperature of 180° F (82° C) (200 BMEP GLD Engines Only)
and Intercooler Temperature of 85 -- 130° F Up to 10° F (5.5° C) above design intercooler water
(29 -- 54° C) (176 BMEP Engines Only) Normal inlet temperature
Normal 170 -- 195° F (76.5 -- 90.5° C) 10° F (5.5° C) above design intercooler water inlet
Alarm temperature
Alarm 200° F (93° C)
Shutdown 205° F (96° C) 15° F (8.5° C) above design intercooler water inlet
Shutdown temperature
With a Jacket Water Temperature of 265° F (129° C)
and Intercooler Temperature of 85 -- 130° F INTAKE MANIFOLD PRESSURE
(29 -- 54° C) (176 BMEP Engines Only ) See SB 14--2749D (or current revision)
Normal 170 -- 195° F (76.5 -- 90.5° C) MAIN BEARING TEMPERATURE
Alarm 200° F (93° C) Contact Waukesha Engine Sales Engineering
Shutdown 205° F (96° C) OVERSPEED
With a Jacket Water Temperature of 210° F (99° C) Not to exceed 15% over governed speed or drive
and Intercooler Temperature of 158 -- 176° F Shutdown machine limits
(70 -- 80° C) (200 BMEP GLD Engines Only)
NOTE:
Normal 190° F (88° C) 1 Waukesha Power Systems Code 1105, 1105A, or equivalent
pressure/temperature shutdown system is recommended when
Alarm 200° F (93° C)
jacket water temperature exceeds 210° F (99° C).
Shutdown 205° F (96° C)
LUBE OIL HEADER PRESSURE
F18/H24 Models
Normal 67 -- 83 psi (462 -- 572 kPa)
Alarm 40 psi (276 kPa)
Shutdown 35 psi (241 kPa)
L36/P48 Models
Normal 47 -- 63 psi (324 -- 434 kPa)
Alarm 40 psi (276 kPa)
Shutdown 35 psi (241 kPa)
WAUKESHA ENGINE
DRESSER, INC. Page 3 of 4
Waukesha WAUKESHA, WI 53188-4999
Service Bulletin No. 1--2620D
Not to exceed 15% over governed speed or drive Normal 160 -- 230° F (71 -- 110° C)
Shutdown machine limits Alarm 240° F (116° C)
Shutdown 250° F (121° C)
LUBE OIL HEADER PRESSURE
Normal 35 -- 45 psi (241 -- 310 kPa)
Alarm 15 psi (103 kPa)
Shutdown 10 psi (69 kPa)
INTAKE MANIFOLD TEMPERATURE
Not Applicable
INTAKE MANIFOLD PRESSURE
Not Applicable
OVERSPEED
Not to exceed 15% over governed speed or drive
Shutdown machine limits
WAUKESHA ENGINE
Page 4 of 4 DRESSER, INC.
WAUKESHA, WI 53188-4999