Professional Documents
Culture Documents
Fire Alarm Design
Fire Alarm Design
F i re D e t e c t i o n & A l a r m D e s i g n
1/3
one
F I R E D E T E C T I O N & A L A R M D E S I G N
S Y S T E M D E S I G N
S Y S T E M D E S I G N
S Y S T E M D E S I G N
Diagram 1.
Semi-flush mounting kits reduce sensor
profile and improve aesthetics.
Wall
7. 7.
5 m 5 m
m 5 m 5
7. 7.
10.6 m
Smoke Smoke
Detector S S Detector
Plan View
Wall
5. 5.
3 m 3 m
m 3 m 3
5. 5.
7.5 m
H H
Heat Detector Heat Detector
Diagram 2.
Obstacle
0.5m 0.5m
Min Min
End
View
If greater than
10% of ceiling
height treat as
wall
1/7
one
F I R E D E T E C T I O N & A L A R M D E S I G N
S Y S T E M D E S I G N
Corridors
Detectors in corridors may generally be
spaced more widely.
7. 7. Wall
5+ 5+
5m
1. 1. 4 This is NOT applicable to life safety
1.
5m 5m
5+
7.
applications unless all adjoining rooms
Smoke 17.9 m Smoke have smoke detection.
2m
Detector S S Detector
4 This is NOT applicable to corridors
7.
5m
5m
5+
1.
1.
1.
5m
5+
5+
flat horizontal ceilings).
7.
7.
1. 1.
1.
Detector H H Detector
5.
3+
5m
5m
1.
1.
1.
5m
3+
3+
5.
5.
S Y S T E M D E S I G N
Pitched Roofs
A row of sensors should be installed along
Roof
the apex of any pitched roof or ‘north-
light’ roof.
Smoke sensors should be not more than
600mm from the apex of the roof. 20º 600mm
Max
Horizontal spacing between sensors may
20º pitch allows spacing
be extended when used under pitched to be extended 20% for
roofs. The horizontal distance may be example from 7.5m to
9.0m
extended by up to 1% for each degree of
slope of the roof (relative to horizontal) up
to a maximum of 25%.
Heights
Maximum heights of detectors are
dependant on the fire brigade response
available:
Beam 25 40
* The height may be increased to 40m provided that the general height to which combustibles are stored in the
building does not exceed 5m and that the fire brigade can attend within 5 minutes.
NOTE: Generally the beam should not pass closer, to a wall or partition, than 500mm and not closer to an
obstruction, than 600mm. However, up to 3m of the beam may be closer than this. Always consult Gent 24 if in
doubt.
Where the beam detector is mounted in the apex of a pitched or ‘north-light’ roof the horizontal distance can be
1/9
increased by 1% for each degree of slope up to a maximum of 25% (eg 20º slope of roof 20% of 7.5m = 1.5m).
one
F I R E D E T E C T I O N & A L A R M D E S I G N
S Y S T E M D E S I G N
S Y S T E M D E S I G N
Life Protecting
The minimum sound levels must be
produced in all occupiable parts of the
building. Occupiable parts include
restricted areas such as service ducts
where people could be working on Typical ambient noise levels dB (A)
occasion. As audible alarms are essential
for the protection of life, a minimum of
two independent sounders must always Light Street
Noise
be provided to guard against the failure of
Average Office
one. A minimum of one sounder should Noise
be provided in each fire compartment. Stock Room
Noise
Property Protection
Light Assembly
In Type P systems the minimum sound Room Noise
S Y S T E M D E S I G N
S Y S T E M D E S I G N
Standby Period
In the event of a mains failure, the
minimum standby period is 24 hours in
normal conditions followed by 30 minutes
at full alarm load. In special circumstances,
such as the availability of a standby
generator, these periods can be reduced.
S Y S T E M D E S I G N
S Y S T E M D E S I G N
Stage 6. Zoning
Zoning Notes:
DESIGN TIP!
For several reasons a building must be 1. A fire compartment is an area bordered
split into a number of fire detection and by a fire-resisting structure usually at
alarm zones. least 30 minutes resistance. Remote indicator lamps
2. Zone limits can be relaxed only in can be used to reduce
The prime purpose of zoning is to identify
certain Type M systems. the need for small
the location of a fire or fault. The following
complex zones.
criteria govern the number and size of 3. To avoid misleading indication of the
They are also useful
zones: position of a fire, consideration should
for voids and locked
be given to the separate zoning of
4 The floor area of a single zone should cupboards.
manual call points, particularly those
not exceed 2000m2.
on staircase landings. This can be
4 No person in a zone should have to
achieved by indicating automatic
travel more than 30m to visually
detectors and manual call points
determine the position of a fire.
separately.
4 The zone should not cover more than
one storey unless the total building
area is less than 300m2. Stairwells, lift
shafts and flue-like openings should be
treated as separate zones.
4 It is permissible for a zone to cover a
whole number of fire compartments, or
for a fire compartment to contain a
whole number of zones, but a zone
cannot extend over parts of two or
more fire compartments.
4 For multiple-occupancy buildings the
occupancy boundaries should coincide
with zone boundaries.
4 If there is an area of special fire risk,
consideration should be given to
setting up a separate zone for rapid
identification of a fire in that risk area.
4 When addressable systems are ring
wired the units on the same ring should
not cover an area of more than
10,000m2.
1/15
one
F I R E D E T E C T I O N & A L A R M D E S I G N
E X A M P L E S
Canteen
Warehouse
E X A M P L E S
4 Minimum 65 dB required or 5 dB
greater than background noise.
4 75 dB required at bedheads.
WC WC WC
4 Sound level reduces by 6 dB for every
time the distance from the sounder is Stores Office WC
doubled i.e. Reception
100 dB - 1m
94 dB - 2m
88 dB - 4m
82 dB - 8m Office
Boiler
76 dB - 16m Room Assembly Area
4 Sound level is attenuated by 30 dB for
fire doors and 20 dB for internal doors.
Canteen
Fire Panel.
Remote LEDs.
WC WC WC
Office
Zone 1 Stores WC
Zone 2 Reception
Zone 3
Zone 4
Office
Boiler Assembly Area
Room
Canteen
Warehouse
1/17
one
F I R E D E T E C T I O N & A L A R M D E S I G N
FA L S E A L A R M S
False Alarms
C A B L E I N S TA L L AT I O N
Wiring
C A B L E I N S TA L L AT I O N
Installation of Cables