Professional Documents
Culture Documents
The regulations have been updated to further harmonize with International and European standards. The process of European
harmonization had already begun with the previous amendments to the 16th Edition, most notably the changes in cable
insulation colours. The 17th Edition maintains harmonization with the International Standard (IEC 60364) and the related
European Harmonization Document (HD 384) from the European Committee for Electrotechnical Standardisation (CENELEC),
which results in:
l Renumbering
l Restructuring
l New regulations
The biggest change from the 16th to the 17th Edition The 17th Edition refers to various applications and
is increased use of Residual Current Devices. Previously, installations which require Additional Protection by the
RCDs have only been required to protect socket outlets means of the aforementioned RCD. The first of which is
for use outdoors, where disconnection times can not be found in Regulation 411.3.3, where Additional Protection is
achieved, and special locations. With the introduction of the required for:
17th Edition, this is set to change.
i. Socket outlets with a rated current not exceeding 20A,
The term ‘Additional Protection’ is used throughout the that are for use by Ordinary Persons* and intended for
publication. The use of RCDs are recognised as a means general use
of providing additional protection in the event of failure of ii. Mobile equipment with a current rating not exceeding
the provision for Basic Protection*, as an additional means 32A for use outdoors
of Fault Protection*, and to protect against carelessness by An exception to ‘i’ is permitted for:
users. If an RCD is used to provide Additional Protection it a. Socket outlets for use under the supervision of Skilled* or
must then meet the requirements of Regulation 415.1.1. Instructed* Persons
That is, the RCD must have a rated residual operating current b. A specific labelled or otherwise suitably identified socket
not exceeding 30mA, and an operating time not exceeding outlet provided for connection of a particular item of
40ms at 5x the rated current. equipment
50mm
* This term is explained in the glossary at the end of this brochure.
50mm
50mm
17th Edition MK Sentry Solutions
All circuits within a location containing a bath or shower will require Additional Protection
Section 701 concerns locations containing a bath or shower. a. Avoid hazards and minimise inconvenience in the event of
It is now a requirement under 701.411.3.3 that additional a fault
protection shall be provided for all circuits of the location b. Take account of danger that may arise from the failure of
by the use of one or more RCDs, again, with an operating a single circuit such as a lighting circuit
current not exceeding 30mA, reference Regulation 415.1.1. c. Reduce the possibility of unwanted tripping of RCDs due
to excessive protective conductor currents produced by
As well as items such as electric towel rails and electric equipment in normal operation
showers, this regulation also applies to lighting.
This means a single RCD cannot be used to protect the
Although all of the aforementioned areas require RCD whole installation, as in the event of a fault, power will be
protection, the requirements of Regulation 314.1, Division of lost to all circuits potentially causing hazards, inconvenience
Installation, need to be taken into account, when designing and danger. Therefore multiple devices should be installed
and installing the circuit protective arrangements. 314.1 to protect the outgoing circuits and should also be split
states that every installation shall be divided into circuits as across the RCDs, alternatively the suitable installation of
necessary to: RCBOs could be used to protect individual circuits. A split
arrangement would be ground floor and first floor lighting
circuits protected by separate RCDs. Another example would
be that the circuit which supplies the bathroom lighting
would be separately protected from that which supplies the
electric shower. A fault developing on the electric shower
circuit would then not affect the lighting circuit.
MK Sentry Consumer Units
Specific consumer unit configurations have been designed to provide flexible solutions in meeting
the requirements of the 17th Edition with regards to RCD protection for circuits, cables and
socket outlets. The new MK Sentry Consumer Units, available in insulated and metal versions,
allow for protected and unprotected ways with the circuits being split across up to 3 RCDs,
whilst a new labelling sheet allows for full identification of all circuits.
COMPACT SIZE
But wiring space
increased where
required most low profile and
Units can curved design
be stacked Blends
for larger unobtrusively into FLEXIBLE NEUTRAL BAR
installations the environment CONFIGURATION
Enables installer to select a wide
combination of protected and
Optional unprotected circuits
locking
colour coded
mechanism
Earth and Neutral
terminal LOCATED
AT TOP OF UNIT FOR
EASE OF WIRING
backed out
and captive ample 360º knock-outs
Combi-head for cable routing
screws Open cable entry at rear plus
Allows speedy optional rear knock-outs
installation
discreet
moulded in
logo
Opaque and No visible fixing
downward screws
opening lid
Hides unsightly
labels and devices
EASILY
removable
Flush mountable din-rail
OPTIONS Improves
For an even neater first fix
installation
Raised
din-rail Floating busbar system
For improved For maximum installation
cable routing flexibility including
acceptance of control
Fixing holes modules
Allow tripod fixing offset incomer
to cope with uneven Provides additional
surfaces. Hole locations wiring space
allow access for cordless making mains input
drills and power drivers connections easier
AMPLE wiring
space
Individual protection
for designated circuits
Example of use:
l 40A electric shower
l 6A first floor lighting
l 6A ground floor lighting
Main Switch
for isolation
RCD protecting up to
8 outgoing ways
10 outgoing ways
5 + 5 split as
standard
Allows for 2
unprotected, or 2
RCBO ways
Dimensions
Width height depth
378mm 230mm 110mm
MK Sentry Consumer Units
Unprotected Ways
The example shown is K5686s MAG 17ED with unprotected ways. Depending on the position of
the U link, multiple unprotected ways are possible on the K5681S, K5683S and the K5684S.
Dimensions
Width height depth
378mm 230mm 110mm
K5666S MAG 17ED
2 x 63A 30mA RCDs, allowing 10 outgoing ways with up to 5 circuits per RCD. This Consumer
Unit allows for 2 unprotected, or 2 RCBO ways.
10 outgoing ways
5 + 5 split as
standard
Allows for 2
unprotected, or 2
RCBO ways
Dimensions
Width height depth
378mm 230mm 110mm
MK Sentry Consumer Units
15 outgoing ways
Multiple protected
and unprotected
configurations
Dimensions
Width height depth
468mm 230mm 110mm
K5683S MAG 17ED
2 x 63A 30mA RCDs, allowing 15 outgoing ways. Multiple protected and unprotected
configurations are possible.
15 outgoing ways
Multiple protected
and unprotected
configurations
Dimensions
Width height depth
468mm 230mm 110mm
MK Sentry Consumer Units
15 outgoing ways
5 + 5 + 3 split as
standard
Unprotected ways
possible
Dimensions
Width height depth
468mm 230mm 110mm
MK Sentry MCBs, RCBOs & RCDs
As shown, within the MK Sentry range a number of split load configurations are available
which meet the requirements of the 17th Edition. An essential element of the regulations is
the minimised hazard and inconvenience, and as such more than one RCD or RCBO per board
will be required. The following overview shows the total number of ways available with each
board, and the maximum number of circuits for each RCD.
For maximum flexibility, unpopulated boards can also be used in conjunction with MK RCDs,
RCBOs, MCBs and Switch Disconnectors to provide 17th Edition solutions.
MK Sentry MCBs
MK Sentry MCBs (Miniature Circuit Breakers) are of the thermo-magnetic, current limiting type and are
available with either Type B or Type C operating characteristics. For the purpose of this brochure we have
only listed the Type B devices, the full range can be found in the MK Catalogue.
The operating dolly may be locked in either the ON or OFF position without affecting the ability of the
trip mechanism to operate. The contacts themselves are manufactured from carefully chosen materials,
selected specifically for their low electrical resistance and low propensity to weld under fault conditions.
When the green indicator is visible, a contact gap of 4mm has been achieved, therefore Sentry MCBs may
be used as a single pole isolating switch where appropriate. The Sentry MCB has a mid-trip fault indicator.
If there is a short circuit or current overload, the dolly moves to the mid-position to indicate a fault.
MK Sentry MCBs
List No. Description Current Rating
5903s MCB Single Pole Type B 3A
5906s MCB Single Pole Type B 6A
5910s MCB Single Pole Type B 10A
5916s MCB Single Pole Type B 16A
5920s MCB Single Pole Type B 20A
5932s MCB Single Pole Type B 32A
5940s MCB Single Pole Type B 40A
5945s MCB Single Pole Type B 45A
5950s MCB Single Pole Type B 50A
For the full range of MK Sentry MCBs refer to the main MK Catalogue.
MK Sentry RCBOs
MK Sentry RCBOs (Residual Current Breakers with Overcurrent Protection) are of the solid neutral type,
single pole, in one module format. The RCBOs are a combination of a Type B MCB and a 30mA RCD. This
enables both overcurrent protection and earth fault current protection to be provided by a single unit.
This combination allows earth fault protection to be restricted to a single circuit, thus ensuring that only
the circuit with the fault is interrupted.
The operating dolly on all MK Sentry RCBOs may be locked in either the ON or OFF position without
affecting the ability of the trip mechanism to operate.
MK Sentry RCBOs
List No. Description Current Rating tripping current
6932s RCBO WITH SOLID NEUTRAL TYPE B 6A 30mA
6933s RCBO WITH SOLID NEUTRAL TYPE B 10A 30mA
6934s RCBO WITH SOLID NEUTRAL TYPE B 16A 30mA
6935s RCBO WITH SOLID NEUTRAL TYPE B 20A 30mA
6936s RCBO WITH SOLID NEUTRAL TYPE B 32A 30mA
6937s RCBO WITH SOLID NEUTRAL TYPE B 40A 30mA
6938s RCBO WITH SOLID NEUTRAL TYPE B 45A 30mA
6939s RCBO WITH SOLID NEUTRAL TYPE B 50A 30mA
For the full range of MK Sentry RCBOs refer to the main MK Catalogue.
MK Sentry MCBs, RCBOs & RCDs
MK Sentry RCDs
The MK Sentry range of RCDs (Residual Current Devices) offer a comprehensive
selection of devices designed to meet most residential, commercial and light
industrial requirements. The range includes two and four pole, a.c., d.c. fault
current sensitive and time delayed models, and a selection of current ratings from
16A to 100A, in a variety of tripping sensitivities. For the purpose of this brochure
we have only listed the 30mA 230V devices, the full range can be found in the MK
Catalogue.
When in the OFF position a contact gap of 4mm is present, enabling Sentry RCDs
to be used as isolating switches where appropriate. When the green indicator is
visible, a contact gap of 4mm has been achieved.
The operating dolly may be locked in either the ON or the OFF position without
affecting the ability of the trip mechanism to operate, ie the RCD is ‘trip-free’. It is
not possible to hold the contacts closed when a fault condition exists.
To interpret the new regulations, it is necessary to understand the terminology used. Electrical
Contractors should familiarise themselves with the following terms. A complete glossary is published
at the end of the 17th Edition document, here we have highlighted those which are particularly
relevant to the content of this brochure.
Instructed Person
An individual who has been adequately advised or supervised
to enable him/her to avoid the danger which may occur when
using electricity.
Basic Protection
Protection against electric shock under fault-free conditions.
Note: For low voltage installations, systems and equipment, basic
protection generally corresponds to protection against direct
contact, that is ‘contact of persons or livestock with live parts’.
Fault Protection
Protection against electric shock under single-fault conditions.
Note: For low voltage installations, systems and equipment,
fault protection generally corresponds to protection against
indirect contact, mainly with regard to failure of basic insulation.
Indirect contact is ‘contact of persons or livestock with
exposed-conductive-parts which have become live under fault
conditions’.
17th Edition Find out more
To find out more about the 17th Edition of the IEE Wiring Regulations, and the MK product solutions
including the MK Sentry range of Consumer Units, you can attend the MK CPD ‘Socket in a Shower
– What’s that all about’, or listen to the MK Podcast, produced in association with the NICEIC and
Professional Electrician & Installer Magazine.
Socket in a Shower –
This CPD is aimed at Electrical Contractors, Specifiers What’s that all about?
and Consultants, and is a review of the main changes to Continuing Professional Development
through the MK CPD Technical Seminar Programme
BS 7671:2008 – the 17th Edition of the Wiring Regulations and
the impact upon the electrical industry.
BRAND EXTERNAL
TITLE DESCRIPTION
REPRESENTED APPROVAL
For more information on this CPD and to register your interest Socket in a
Shower – What’s
MK A review of the main changes to BS 7671:2008 – 17th
Edition of the IEE Wiring Regulations and the impact upon
Construction CPD
Service
that all about? the electrical world.
CONTENT
L Reasons for change
L Structure
L Numbering
L Major changes chronologically for Parts 1-7 including;
L Definitions
L Protection against electric shock
L Cables in walls
MK Electric has joined forces with the NICEIC and Professional L Bath & shower rooms
is an easy-listen, readily digestible podcast ‘radio show’ that Te l +4 4 (0)126 8 5630 0 0 We bsite w w w.mkele c tric.co.uk / w w w.ackermann.co.uk E- mail mk .cp d@hone y we ll.com
Fa x +4 4 (0)126 8 5634 83 Re giste r e d O f fice: Hone y we ll Hous e, A rlington Busine s s Park , Brack ne ll, B erk shire, RG12 1EB Re giste r e d No. 189291
Whilst every effort has been made to ensure the information in this brochure is correct, British Standards and the IEE Wiring Regulations may be subject to change. This MK Electric brochure to 17th
Edition - MK Sentry Solutions is not a substitute to the ‘Requirements for Electrical Installations – IEE Wiring Regulations Seventeenth Edition’.
MK Electric
T h e A r n o l d C e n t r e Pa y c o c k e R o a d B a s i l d o n E s s e x S S 1 4 3 E A U n i t e d K i n g d o m Technical Helpline Tel 01268 563720
Customer Service Tel 01268 563404 Literature Helpline Tel 0870 240 3385 E-mail mkorderenquiries@honeywell.com
Customer Service Fax 01268 563405 Literature Helpline Fax 0870 240 3386 Website www.mkelectric.co.uk
Registered Office : Honeywell House Arlington Business Park Bracknell Berkshire RG12 1EB Registered No. 189291 Ref: MK242
TM