You are on page 1of 7

ELECTRICAL DESIGN COMPUTATION

Ground Floor:

FACULTY OFFICE : 299 m2


Lights - 40 VA x 299 m2 = 10,465 VA
Msc. Power/C.o. - 25 VA x 299 m2 = 7,475 VA
Other power Outlet:
Ceiling fans - 2,000 VA = 2,000 VA
VA
Special power Outlets = 1,500 VA
Total connected Load = 21,440 VA
Ten Year Load Growth 30% = 6,432 VA
TOTAL LOAD = 27872 VA

OFFICE AREA : 485 m2


Lights - 40 VA x 485 m2 = 16,975 VA
Msc. Power/C.o. - 25 VA x 485 m2 = 7,475 VA
Other power Outlet: = 1,500 VA
Total connected Load = 21,440 VA
Ten Year Load Growth 30% = 6,432 VA
TOTAL LOAD = 27872 VA

OFFICE AREA: 485 m2


Lights - 40 VA x 485 m2 = 16,975 volt-amperes
Msc. Power/C.o. - 25 VA x 485 m2 = 12,125 volt-amperes
Air-Conditioning Unit - 85 VA x 485 m2 = 41,225 volt-amperes
Special power Outlets = 1,500 volt-amperes
------------------------------
Total connected Load = 71,825 volt-amperes
Ten Year Load Growth 30% = 21,548 volt-amperes
-----------------------------------
Maximum Demand – 85% = 79,367 volt-amperes

LOBBY & HALLWAY (Entrance) : 245 m2


Lights - 8 VA x 245 m2 = 6,125 volt-amperes
Msc. Power/C.o. - 15 VA x 245 m2 = 3,765 volt-amperes
Special power Outlets: Spot & Emergency light = 4,500 volt-amperes
Emergency light = 300 volt-amperes
------------------------------
Total connected Load = 14,690 volt-amperes
Ten Year Load Growth 10% = 1,469 volt-amperes
-----------------------------------
Maximum Demand – 80% = 12,927 volt-amperes

TOTAL CONNECTED LOAD = 107,955 VA


TOTAL TEN YEAR LOAD GROWTH = 29,449 VA
MAXIMUM DEMAND BEFORE LOAD GROWTH = 91,762 VA
MAXIMUM DEMAND LOAD GROWTH = 116,794 VA

Second Floor:

LIBRARY AREA : 648 m2


Lights - 24 VA x 648 m2 = 14,256 volt-amperes
Msc. Power/C.o. - 65 VA x 648 m2 = 42,120 volt-amperes
Special power Outlet: Ceiling fans = 6,000 volt-amperes
------------------------------
Total connected Load = 62,376 volt-amperes
Ten Year Load Growth 40% = 24,951 volt-amperes
-----------------------------------
Maximum Demand – 85% = 74,228 volt-amperes

MUSSEUM AREA : 124 m2


Lights - 33 VA x 124 m2 = 4,092 volt-amperes
Msc. Power/C.o. - 6 VA x 124 m2 = 744 volt-amperes
Air-Conditioning Unit - 75 VA x 21 m2 = 1,575 volt-amperes
------------------------------
Total connected Load = 6,411 volt-amperes
Ten Year Load Growth 40% = 2,564 volt-amperes
-----------------------------------
Maximum Demand – 90% = 8,078 volt-amperes

LOBBY & HALLWAY: 184 m2


Lights -8 VA x 184 m2 = 4,600 volt-amperes
Msc. Power/C.o. - 8 VA x 184 m2 = 2,760 volt-amperes
Special power Outlet: Emergency light = 350 volt-amperes
------------------------------
Total connected Load = 7,710 volt-amperes
Ten Year Load Growth 10% = 771 volt-amperes
-----------------------------------
Maximum Demand – 80% = 6,785 volt-amperes

THEATRE WORK AREA : 135 m2


Lights - 45 VA x 135 m2 = 1,625 volt-amperes
Msc. Power/C.o. - 45 VA x 135 m2 = 1,625 volt-amperes
------------------------------
Total connected Load = 3,250 volt-amperes
Ten Year Load Growth 20% = 650 volt-amperes
-----------------------------------
Maximum Demand – 85% = 3,315 volt-amperes
TOTAL CONNECTED LOAD = 79,747 volt-amperes
TOTAL TEN YEAR LOAD GROWTH = 28,936 volt-amperes

MAX. DEMAND BEFORE LOAD GROWTH = 69,936 volt-amperes


MAX. DEMAND LOAD GROWTH = 94,257 volt-amperes

Third Floor:

THEATRE STAGE AREA : 203 m2


Lights - 430 VA x 203 m2 = 87,290 volt-amperes
Msc. Power/C.o. - 10 VA x 203 m2 = 2,030 volt-amperes
Air-Conditioning Unit - 90 VA x 203 m2 = 18,270 volt-amperes
Special power Outlets = 12,000 volt-amperes
-------------------------------
Total connected Load = 119,590 volt-amperes
Ten Year Load Growth 30% = 35,877 volt-amperes
-----------------------------------
Maximum Demand – 90% = 139,920 volt-amperes

THEATRE GENERAL AREA : 758 m2


Lights - 22 VA x 758 m2 = 16,676 volt-amperes
Msc. Power/C.o. - 6 VA x 758 m2 = 4,548 volt-amperes
Air-Conditioning Unit - 90 VA x 758 m2 = 68,220 volt-amperes
Special power Outlets: Emergency light = 400 volt-amperes
------------------------------
Total connected Load = 89,844 volt-amperes
Ten Year Load Growth 30% = 26,953 volt-amperes
-----------------------------------
Maximum Demand – 85% = 99,278 volt-amperes

LOBBY & HALLWAY: 184 m2


Lights -25 VA x 184 m2 = 4,600 volt-amperes
Msc. Power/C.o. - 15 VA x 184 m2 = 2,760 volt-amperes
Special power Outlet: Emergency light = 150 volt-amperes
------------------------------
Total connected Load = 7,510 volt-amperes
Ten Year Load Growth 10% = 751 volt-amperes
-----------------------------------
Maximum Demand – 80% = 6,609 volt-amperes

RADIO & TV PROUCTION ROOM & EDITING ROOM AREA : 160 m2


Lights - 45 VA x 160 m2 = 7,200 volt-amperes
2
Msc. Power/C.o. - 45 VA x 160 m = 7,200 volt-amperes
Air-Conditioning Unit - 80 VA x 160 m2 = 12,800 volt-amperes
------------------------------
Total connected Load = 27,200 volt-amperes
Ten Year Load Growth 30% = 8,160 volt-amperes
-----------------------------------
Maximum Demand – 90% = 31,824 volt-amperes
TOTAL CONNECTED LOAD = 244,144 volt-amperes
TOTAL TEN YEAR LOAD GROWTH = 71,741 volt-amperes

MAX. DEMAND BEFORE LOAD GROWTH = 207,522 volt-amperes


MAX. DEMAND LOAD GROWTH = 268,502 volt-amperes

Fourth Floor:

THEATRE BALCONY AREA : 270 m2


Lights - 22 VA x 270 m2 = 5,940 volt-amperes
Msc. Power/C.o. - 10 VA x 270 m2 = 2,700 volt-amperes
------------------------------
Total connected Load = 8,640 volt-amperes
Ten Year Load Growth 30% = 2,592 volt-amperes
-----------------------------------
Maximum Demand – 85% = 9,547 volt-amperes

LOBBY & HALLWAY: 184 m2


Lights -25 VA x 184 m2 = 4,600 volt-amperes
Msc. Power/C.o. - 15 VA x 184 m2 = 2,760 volt-amperes
Special power Outlet: Emergency light = 400 volt-amperes
------------------------------
Total connected Load = 7,760 volt-amperes
Ten Year Load Growth 10% = 776 volt-ampere
-----------------------------------
Maximum Demand – 80% = 6,829 volt-amperes

EMC AREA : 142 m2


Lights - 22 VA x 142 m2 = 3,124 volt-amperes
Msc. Power/C.o. - 22 VA x 142 m2 = 3,124 volt-amperes
Air-Conditioning Unit - 52 VA x 142 m2 = 7,384 volt-amperes
Special power Outlets = 1,500 volt-amperes
------------------------------
Total connected Load = 15,132 volt-amperes
Ten Year Load Growth 30% = 4,540 volt-amperes
-----------------------------------
Maximum Demand – 85% = 16,721 volt-amperes

TOTAL CONNECTED LOAD = 31,532 volt-amperes


TOTAL TEN YEAR LOAD GROWTH = 7,908 volt-amperes

MAX. DEMAND BEFORE LOAD GROWTH = 26,802 volt-amperes


MAX. DEMAND LOAD GROWTH = 33,524 volt-amperes
Roof Deck:

THEATRE GENERAL AREA : 585 m2


Lights - 11 VA x 585 m2 = 6,435 volt-amperes
Msc. Power/C.o. - 6 VA x 585 m2 = 3,510 volt-amperes
Special power Outlets: Spot light = 6,000 volt-amperes
------------------------------
Total connected Load = 15,945 volt-amperes
Ten Year Load Growth 30% = 4,784 volt-amperes
-----------------------------------
Maximum Demand – 85% = 17,619 volt-amperes
THEATRE CONTROL ROOM AREA : 40 m2
Lights - 22 VA x 40 m2 = 880 volt-amperes
Msc. Power/C.o. - 10 VA x 40 m2 = 400 volt-amperes
Air-Conditioning Unit - 80 VA x 40 m2 = 3,200 volt-amperes
------------------------------
Total connected Load = 4,480 volt-amperes
Ten Year Load Growth 30% = 1,344 volt-amperes
-----------------------------------
Maximum Demand – 85% = 4,950 volt-amperes

OPEN AREA: 396 m2


Total connected Load = 3,200 volt-amperes
Ten Year Load Growth 10% = 320 volt-amperes
-----------------------------------
Maximum Demand – 85% = 2,992 volt-amperes

TOTAL CONNECTED LOAD = 23,625 volt-amperes


TOTAL TEN YEAR LOAD GROWTH = 6,448 volt-amperes

MAX. DEMAND BEFORE LOAD GROWTH = 20,081 volt-amperes


MAX. DEMAND LOAD GROWTH = 25,562 volt-amperes

OTHER LOADS:
Elevator = 25,000 volt-amperes
Elevator Control = 1,500 volt-amperes
Buster Water Pump 2 x 3 Hp = 4,500 volt-amperes
------------------------------
Total connected Load = 31,000 volt-amperes
Maximum Demand 85% = 26,350 volt-amperes
Ten Year Load Growth 20% = 6,200 volt-amperes
-----------------------------------
Max. Demand with Load Growth 90% = 33,480 volt-amperes

SUMMARY:

Total connected Loads = 517,823 volt-amperes

Total Ten Year Load Growth = 150,682 volt-amperes

Max. Demand before Load Growth 75% = 388,367 volt-amperes

Max. Demand with Load Growth 75%: = 501,379 volt-amperes

TRANSFORMER RATING COMPUTATION:

Total Connected Load = 517,823 volt-amperes


Maximum Demand : 75 % x 517,823 VA = 388,367 volt-amperes

388,367 VA
Line Current = ---------------------- = 975 Amperes
1.732 x 230 V

Size of Service Entrance (SE):


Use: 3 x 200 mm2 THW copper wire per line.
Use: 3 x 80 mm dia. RSC with 3 wires per conduit.
Total Ampacity per line (: 3 x 200 mm2 THW copper wire)
330 Amperes x 3 = 990 Amperes

Size of Main Circuit Breaker:


Use: Moulded Case, 1,000 Amperes x 600 volts x 3 -pole with
Adjustable Thermal and Magnetic Trip Units

Size of Transformer/s:
Primary Voltage Rating = 13,200 / 7, 620 Volts Wye, 3-Phase
Secondary Voltage = 120 /240 Volts, 3-Phase

388,367 VA
kVA Capacity = ------------------- = 388.37 kVA, 3-Phase
1,000

Use: 400 kVA, 3-Phase

388.37 kVA
Or; --------------------- = 129 kVA , 1-Phase x 3 Units
3

Use: 150 kVA, 1-Phase x 3 Units

Or consider the Ten Year Load Growth and use Sizes and Capacities of Transformers and
Service Entrance for the anticipated Load Increase as follows:

Total Ten Year Load Growth = 150,682 volt-amperes


Total Connected Load 517,823 VA + 150,682 VA = 668,505 volt-amperes
Maximum Demand : 80 % x 668,505 VA = 534,804 volt-amperes

534,804 VA
Line Current = ---------------------- = 1,342 Amperes
1.732 x 230 V

Size of Service Entrance (SE):


Use: 4 x 250 mm2 THW copper wire per line.
Use: 4 x 90mm dia. RSC with 3 wires per conduit.
Total Ampacity per line (: 4 x 250 mm2 THW copper wire)
375 Amperes x 4 = 1,500 Amperes
or

Use: 3 x 400 mm2 THW copper wire per line.


Use: 4 x 90mm dia. RSC with 3 wires per conduit.
Total Ampacity per line (: 3 x 400 mm2 THW copper wire)
485 Amperes x 3 = 1,455 Amperes

Size of Main Circuit Breaker:


Use: Moulded Case, 1,500 Amperes x 600 volts x 3 -pole with
Adjustable Thermal and Magnetic Trip Units

Size of Transformer/s:
Primary Voltage Rating = 13,200 / 7, 620 Volts Wye, 3-Phase
Secondary Voltage = 120 /240 Volts, 3-Phase

534,804 VA
kVA Capacity = ------------------- = 534.8 kVA, 3-Phase
1,000

Use: 600 kVA, 3-Phase

534.8 kVA
Or; --------------------- = 178 kVA , 1-Phase x 3 Units
3

Use: 200 kVA, 1-Phase x 3 Units