Ground Floor:
Second Floor:
Third Floor:
Fourth Floor:
OTHER LOADS:
Elevator = 25,000 volt-amperes
Elevator Control = 1,500 volt-amperes
Buster Water Pump 2 x 3 Hp = 4,500 volt-amperes
------------------------------
Total connected Load = 31,000 volt-amperes
Maximum Demand 85% = 26,350 volt-amperes
Ten Year Load Growth 20% = 6,200 volt-amperes
-----------------------------------
Max. Demand with Load Growth 90% = 33,480 volt-amperes
SUMMARY:
388,367 VA
Line Current = ---------------------- = 975 Amperes
1.732 x 230 V
Size of Transformer/s:
Primary Voltage Rating = 13,200 / 7, 620 Volts Wye, 3-Phase
Secondary Voltage = 120 /240 Volts, 3-Phase
388,367 VA
kVA Capacity = ------------------- = 388.37 kVA, 3-Phase
1,000
388.37 kVA
Or; --------------------- = 129 kVA , 1-Phase x 3 Units
3
Or consider the Ten Year Load Growth and use Sizes and Capacities of Transformers and
Service Entrance for the anticipated Load Increase as follows:
534,804 VA
Line Current = ---------------------- = 1,342 Amperes
1.732 x 230 V
Size of Transformer/s:
Primary Voltage Rating = 13,200 / 7, 620 Volts Wye, 3-Phase
Secondary Voltage = 120 /240 Volts, 3-Phase
534,804 VA
kVA Capacity = ------------------- = 534.8 kVA, 3-Phase
1,000
534.8 kVA
Or; --------------------- = 178 kVA , 1-Phase x 3 Units
3